EMAAR GIGA KARACHI LIMITED


DESIGN CONSULTANCY SERVICES FOR INFRASTRUCTURE OF PEARL & REEF TOWER, CRESCENT BAY
BILL OF QUANTITIES
Code-01 EXTERNAL DEVELOPMENT
Item Description Unit Qty. Unit Total
No. Rate Amount
(Rupees) (Rupees)
(1) (2) (3) (4) (5) (6)
P. PLUMBING WORKS

EXTERNAL SEWAGE PIPES & FITTINGS


Ref. Spec. 1100, 5213, 5217 & 5233
01-1P Excavation of trenches in all kinds of subsurfaces material
including dewatering, disposal of surplus/rejected
excavated material to designated places as directed by the
Engineer.
a) 0 to 1.5 meters Cu. M 2800

b) 1.5 to 3.0 meters Cu. M 1400

c) 3.0 to 4.5 meters Cu. M 250

01-2P Fill and backfill with selected material obtained from


required excavation including compaction. Cu. M 2239

01-3P Fill and backfill with selected material obtained from outside
sources including compaction. Cu. M 959

01-4P Bedding with fine sand obtained from approved outside


source as directed by the Engineer. Cu. M 1200

01-5P Providing and laying Class 'B' concrete encasement using


Portland cement as shown on drawings/specifications
and/or directed by the Engineer.
Cu. M 52

01-6P Providing and laying uPVC Spirally wounded pipe of


following diameters conforming to ASTM 1093, F-1741, F-
1697, DIN 16961, DIN 8061, AS1145, AS 1254 and as
specified and/or as directed by the Engineer.

a) 300 mm. RM. 1010

b) 750 mm. RM. 10

01-7P Providing and laying Polyethlene (PE-100) pipe and fittings


conforming to ISO-4427, DIN-8074/75 and PS-3580: 1984
PN-10 of following diameter as shown on
drawings/specifications and/or directed by the Engineer.

a) 200 mm. (Outer Dia 250mm) RM. 500


01-P : 2 of 13

Code-01 EXTERNAL DEVELOPMENT


Item Description Unit Qty. Unit Total
No. Rate Amount
(Rupees) (Rupees)
(1) (2) (3) (4) (5) (6)

SEWAGE TREATMENT PLANT


Ref. Spec. 5540
01-8P Providing design, supply, construction, installation, testing
and commissioning of Package Type Sewage Treatment
Plant of 40,000 gallons/day capacity and necessary
components as mentioned in the specifications and
construction of structures including Under Ground Water
Tanks, Control Room etc. required for operation of plant
with all relevent works (civil, mechanical, electrical,
instrumentation and piping works) all on EPC Basis. The
plant shall also include the pumping arrangement to
dispose off the treated water at outfall chambers.

Job 1

STORM WATER DRAINAGE


Ref. Spec. 1100, 5217 & 5233
01-9P Excavation of trenches in all kinds of subsurfaces material
including dewatering, disposal of surplus/rejected
excavated material to designated places as directed by the
Engineer.

a) 0 to 1.5 meters Cu. M 1050

01-10P Fill and backfill with selected material obtained from


250
required excavation including compaction. Cu. M

01-11P Fill and backfill with selected material obtained from outside
110
sources including compaction. Cu. M

01-12P Bedding with fine sand obtained from approved outside


source as directed by the Engineer. 650
Cu. M

01-13P Providing and laying Class 'B' concrete encasement using


Portland cement as shown on drawings/specifications
and/or directed by the Engineer.
Cu. M 34

01-14P Providing and laying uPVC Spirally wounded pipe of


following diameters conforming to ASTM 1093, F-1741, F-
1697, DIN 16961, DIN 8061, AS1145, AS 1254 and as
specified and/or as directed by the Engineer.

a) 500 mm. RM. 350

b) 650 mm. RM. 100

c) 700 mm. RM. 165

01-15P Providing and fixing Cast iron grating with frame of


following sizes and duty complete in all respects as
specified and shown on the drawing and/or as directed by
the Engineer.
a) 600 X 600 mm (Medium duty) No. 5
01-P : 3 of 13

Code-01 EXTERNAL DEVELOPMENT


Item Description Unit Qty. Unit Total
No. Rate Amount
(Rupees) (Rupees)
(1) (2) (3) (4) (5) (6)
b) 1000 X 1000 mm (Medium duty) No. 2

01-16P Providing RCC grating of following sizes complete in all


respects as specified and shown on the drawing and/or as
directed by the Engineer.

a) 600 X 600 mm No. 41

EXTERNAL WATER SUPPLY


Ref. Spec. 1100, 5213, 5220 & 5233
01-17P Excavation of trenches in all kinds of subsurfaces material
including dewatering, disposal of surplus/rejected
excavated material to designated places as directed by the
Engineer.
a) 0 to 1.5 meters Cu. M 1050

b) 1.5 to 3.0 meters Cu. M 800

c) 3.0 to 4.5 meters Cu. M 200

01-18P Fill and backfill with selected material obtained from


required excavation including compaction. Cu. M 1127

01-19P Fill and backfill with selected material obtained from outside
sources including compaction. Cu. M 483

01-20P Bedding with fine sand obtained from approved outside


source as directed by the Engineer. Cu. M 400

01-21P Providing and laying Class 'B' concrete encasement using


Portland cement as shown on drawings/specifications
and/or directed by the Engineer.
Cu. M 40

01-22P Providing and laying Polyethlene (PE-100) pipe and fittings


conforming to ISO-4427, DIN-8074/75 and PS-3580: 1984
PN-10 of following diameter as specidfied (for potable
water supply)

a) 200 mm (Outer dia 250mm) RM. 130

b) 250 mm (Outer dia 280mm) RM. 560

01-23P Providing and installing Cast iron gate valve of following


diameter as specified on drawings/specifications and/or
directed by the Engineer.

a) 250 mm No. 3

01-24P Providing and laying Class "B" Concrete thurst block as


shown on the drawing with required anchor bars complete
in all respect as shown on drawings/specifications and/or
directed by the Engineer.

Cu.M 3
01-P : 4 of 13

Code-01 EXTERNAL DEVELOPMENT


Item Description Unit Qty. Unit Total
No. Rate Amount
(Rupees) (Rupees)
(1) (2) (3) (4) (5) (6)
01-25P Providing and installing Coupling with chain and cover cap
for Water Tankers inlet connection as shown on the
drawing and as directed by the Engineer complete in all
respect.
No. 4

01-26P Providing and installing Cast iron check (non-return) valve


of following diameter as specified complete in all respect as
shown on drawings/specifications and/or directed by the
Engineer.
a) 75mm No. 4

01-27P Providing and installing Cast iron covers (medium duty) of


following dimension as specified complete in all respect as
shown on drawings/specifications and/or directed by the
Engineer.
a) 600 x 600mm No. 3

EXTERNAL FIRE FIGHTING


Ref. Spec. 1100, 5213, 5150, 5220, 5233 & 5280

01-28P Excavation of trenches in all kinds of subsurfaces material


including dewatering, disposal of surplus/rejected
excavated material to designated places as directed by the
Engineer.
a) 0 to 1.5 meters Cu. M 2200

01-29P Fill and backfill with selected material obtained from


required excavation including compaction. Cu. M 949

01-30P Fill and backfill with selected material obtained from outside
sources including compaction. Cu. M 407

01-31P Bedding with fine sand obtained from approved outside


source as directed by the Engineer. Cu. M 800

01-32P Providing and laying Class 'B' concrete encasement using


Portland cement as shown on drawings/specifications
and/or directed by the Engineer.
Cu. M 44

01-33P Providing and laying Polyethlene (PE-100) pipe and fittings


conforming to ISO-4427, DIN-8074/75 and PS-3580: 1984
PN-16 of following diameter as specidfied (for fire water
supply)

a) 150 mm (Outer Dia 180mm) RM. 630

b) 200 mm (Outer Dia 250mm) RM. 600

c) 225 mm (Outer Dia 280mm) RM. 50


01-P : 5 of 13

Code-01 EXTERNAL DEVELOPMENT


Item Description Unit Qty. Unit Total
No. Rate Amount
(Rupees) (Rupees)
(1) (2) (3) (4) (5) (6)
01-34P Providing and laying Fire Hydrant (above ground) pillar
type with 150mm dia inlet and one 100mm dia & two 65mm
dia outlet connections including all accessories as shown
on the drawing and as specified.
No. 20

01-35P Providing and installing Cast iron gate valve (PN-16)


following diameters as specified & shown on drawings
and/or directed by the Engineer.
a) 150 mm diameter
No. 20

01-36P Providing and laying Class "B" Concrete thurst block as


shown on the drawing with required anchor bars complete
in all respect as shown on drawings/specifications and/or
directed by the Engineer.
Cu. M 4

01-37P Providing and installing Air release valve (Double Acting) of


50mm dia in chamber as shown on drawings/specifications
and/or directed by the Engineer.
No. 1

01-38P Providing and installing Portable fire extinguisher for Pump


Room and Guard Rooms of following types with hanging
arrangement as specified and/or directed by the Engineer.

a) Dry Chemical Powder Type (5 Kg) No. 4

b) Carbon Dioxide type (6 Kg) No. 4

c) Foam type (9 litre) No. 1

01-39P Providing and installing Cast iron covers of following


dimension as shown on drawings/specifications and/or
directed by the Engineer.

a) 600 x 600mm No. 21

01-40P Providing & installing plastic dust/garbage bin 240 liters


with door (code-201) size 28.3(L)X22.8(W)X39.3(H) (in
inches) by Bin House (I.S.Traders) or approved equivalent
complete in all respects and/or as directed by the Engineer.
No. 12

TOTAL COST OF CODE-01 (EXTERNAL DEVELOPMENT WORKS)


(Carried over to summary)
02-P : 6 of 13

EMAAR GIGA KARACHI LIMITED


DESIGN CONSULTANCY SERVICES FOR INFRASTRUCTURE OF PEARL & REEF TOWER, CRESCENT BAY

BILL OF QUANTITIES
Code-02 UGWT & PUMP ROOM
Item Description Unit Qty. Unit Total
No. Rate Amount
(Rupees) (Rupees)
(1) (2) (3) (4) (5) (6)
P. PLUMBING WORKS

UNDERGROUND WATER TANK

02-1P PUMPING MACHINERY


Ref. Spec. 5240, 5233, 5214 & 5220

a) Fire Water Pumps (NFPA 20 Compliance Three Pumps set)


Providing and installing Centrifugal fire water main pumps UL
Listed / FM Approved (2 in number, one Electric Motor Driven
and one Diesel Engine Driven) of the following capacity and
head including control panel, valves, pressure
switches/transducers, flexible connector & other accessories
required for installation and operation complete in all respect as
specified and/or as directed by the Engineer.

Q = 1000 USGPM
H = 9.0 bars

Providing and installing Centrifugal fire water jockey pump and


motor, UL Listed / FM Approved, of the following capacity and
head including control panel (as specified in electrical
specification), valves, pressure switches/transducers, flexible
connector & other accessories required for installation and
operation with Surge release valve and pressure relief valve as
shown on drawing and as specified and/or as directed by the
Engineer.

Q = 50 USGPM
H = 10.0 bars Set 1

02-2P Providing and installing Water level indicator in underground tank


with display in pump room with all accessories required for
installation and operation complete in all respect as shown on
drawing and as specified and/or as directed by the Engineer.
No. 1

02-3P Providing and installing Girder, Chain and pulley block


arrangement for 3.0 ton lifting capacity with all accessories
required for installation and operation complete in all respects as
shown on drawing and as specified and/or as directed by the
Engineer.
No. 1
02-P : 7 of 13

Code-02 UGWT & PUMP ROOM


Item Description Unit Qty. Unit Total
No. Rate Amount
(Rupees) (Rupees)
(1) (2) (3) (4) (5) (6)
02-4P Providing and installing Submersible pump and motor (drainage)
of following flow and head with lifting arrangement, level switches
for for controlling, control panel including all accessories
required for installation, mantenance and operation as shown on
drawing and as specified and/or as directed by the Engineer.

Flow = 50 US GPM
Head = 1.0 bar No. 1

02-5P Providing and installing Galvanized mild steel U turned vent


pipes (BS 1387/EN 10255, medium quality) with wire mash of
following dia as shown on drawing and as specified and/or as
directed by the Engineer.
a) 100mm No. 9

02-6P Providing and installing Mild Steel ladder rungs (20mm dia) as
specified and shown on the drawing (epoxy coated) and as
specified and/or as directed by the Engineer.
No. 45

02-7P Providing and installing Cast iron cover & frame conforming to
BS EN 124 of following sizes and duty as shown on the drawing
and as specified and/or as directed by the Engineer.

a) 750 X 750 mm (light duty) No. 5

02-8P Providing and installing Cast iron grating with frame of following
sizes and duty as shown on the drawing and as specified and/or
as directed by the Engineer.

a) 750 X 750 mm (Medium duty) No. 2

TOTAL COST OF CODE-02 (POTABLE WATER AND FIRE WATER TANK)


(Carried over to summary)
03-P : 8 of 13

EMAAR GIGA KARACHI LIMITED


DESIGN CONSULTANCY SERVICES FOR INFRASTRUCTURE OF PEARL & REEF TOWER, CRESCENT BAY

BILL OF QUANTITIES
Code-03 IRRIGATION WATER TANK
Item Description Unit Qty. Unit Total
No. Rate Amount
(Rupees) (Rupees)
(1) (2) (3) (4) (5) (6)
P. PLUMBING WORKS

IRRIGATION WATER TANK


Ref. Spec. 5214, 5220, 5280, 5233 & 5240
03-1P Providing and fixing Seamless mild steel pipe conforming to ASTM
A-53/106 Schedule 40 and fitting conforming to ASTM A234 of
following diameter complete in all respect as per drawing,
specification and/or as directed by the Engineer.

b) 100 mm. (wall thickness 6.4 mm)


RM. 15

03-2P Providing and installing Submersible pump and motor (for


wastewater) of following flow and head with lifting arrangement,
pressure switches for controlling, level switch for dry running
protection, weather protected control panel (with required canopy)
including all accessories required for installation, mantenance and
operation as shown on drawing and as specified and/or as directed
by the Engineer.

Flow = 50 US GPM
Head = 9.0 meters No. 1

03-3P Providing and installing Galvanized Iron Guard rail/Pipe railing


(50mm dia) conforming to BS 1387 (EN 10255) (Medium Duty) near
irrigation filling point as shown on the drawing with required civil
work complete in all respect as specified and/or as directed by the
Engineer.
No. 3

03-4P Providing and installing Cast iron gate valve (PN-10) of following
diameter as shown on drawings, specification and/or as directed by
the Engineer.
a) 100mm No. 1

03-5P Providing and installing Galvanized mild steel U turned vent pipes
(BS 1387/EN 10255, medium quality) with wire mash of following
dia as shown on drawings, specification and/or as directed by the
Engineer.
a) 75mm No. 2

03-6P Providing and installing Cast iron cover & frame conforming to BS
EN 124 of following sizes and duty as shown on drawings,
specification and/or as directed by the Engineer.

a) 750 X 750 mm (light duty) No. 1

03-7P Providing and installing Mild Steel ladder rungs (20mm dia) as
specified and shown on the drawing (epoxy coated) as shown on
drawings, specification and/or as directed by the Engineer. No. 10

TOTAL COST OF CODE-01 (IRRIGATION WATER TANK )


(Carried over to summary)
SPECIFICATION COMPLIANCE DEVIATION
CAST IRON GATE VALVES
SECTION - 5220

Cast iron gate valves shall have flanged ends and


wheel handle and shall conform to B.S.5163
"Specifications for Double Flanged Cast Iron Wedge
Gate Valves for Waterworks purposes". Flanges
shall be drilled to B.S. 4504 Part 1. Valves shall be COMPLY NO
rated for a working/service pressure of 10 bars for
potable water system and 16 bars for firefighting
system. Valves shall close in clockwise direction.
The valve parts shall be of the following materials.

-        Valve body shall be of cast iron.


-        Flanges shall be of cast iron.
-        Shaft shall be of stainless steel.
-        Disc shall be of cast iron with bronze trim.
-        Seat shall be of cast iron with bronze trim.
-        Disc and shaft seal shall be of rubber (O-ring
type).
-        Wheel handle shall be of cast iron.
Valve parts in contact with water shall be of
corrosion resistant material, free from toxic
substances and shall not foster microbiological
growth or impart taste, odour, turbidity or colour to
the water.Inside surfaces of valves shall be
enameled and outside surfaces shall be epoxy
coated.
4. CAST IRON CHECK VALVES

Cast iron check valves shall be of non-slam, swing


type with flanged ends and shall conform to B.S.
5153, "Specifications for Cast Iron Check Valves for
General Purposes". Flanges shall be drilled to B.S.
4504 Part 1. Valves shall be rated for a COMPLY NO
working/service pressure of 10 bars for potable
water system and 16 bars for firefighting system.
The direction of flow shall be permanently marked
on the body of the valve.

-        Valve body shall be of cast iron.


-        Flanges shall be of cast iron.
-        Shaft and spring shall be of stainless steel.
-        Disc and seat shall be of cast iron with bronze
trim.
-        Disc and shaft seal shall be of rubber (O-ring
type).
-        Wheel handle shall be of cast iron.
Valve parts in contact with water shall be of
corrosion resistant material, free from toxic
substances and shall not foster microbiological
growth or impart taste, odour, turbidity or colour to
the water.
Inside surfaces of valves shall be enameled and
outside surfaces shall be epoxy coated.
5.BRONZE GATE VALVES

Bronze gate valves shall conform to B.S.


5154, “Specifications for Copper Alloy Globe, Globe
Stop, Check and Gate Valves for General
Purposes". Valves shall be rated for a
working/service pressure of 10 bars for potable
water system and 16 bars for firefighting system. COMPLY NO
Valve ends shall be screwed or flanged as shown on
the drawings. Threads shall be to B.S. 21 and
flanges shall be drilled to B.S. 4504 Part 1. Valves
shall close in clockwise direction. Open and shut
indicators shall be marked on the wheel handle.

6. BRONZE CHECK VALVES

Bronze check valves shall conform to B.S. 5154,


“Specifications for Copper Alloy Globe, Globe Stop,
Check and Gate Valves for General Purposes".
Valves shall be rated for a working/service pressure
of 10 bars for potable water system and 16 bars for COMPLY NO
firefighting system. Valve ends shall be screwed or
flanged as shown on the drawings. Threads shall be
to B.S. 21 and flanges shall be drilled to B.S. 4504
Part 1. The direction of flow shall be permanently
marked on the valve body.
S
COMPLIANCE SHEET
SPECIFICATION COMPLIANCE DEVIATION
S.N HDPE PIPES & FITTINGS
SECTION - 5213
2.1 Pipes and fittings shall be new and unused. comply No

Where manufacturers of pipes and fittings are


2.2 specified, they shall be of the same manufacturers comply No
unless otherwise approved by the Engineer.

Where more than one similar items of pipes and


2.3 fittings are specified, they shall be of the same comply No
manufacturer.
The Contractor shall submit to the Engineer for
2.4 approval the following information regarding the comply No
specified/proposed items of pipes and fittings.
i)Name and address of the manufacturers
ii)Country of origin, make and model
iii) Dimensions and wall thicknesses of pipes and
fittings
iv) Material and thicknesses of coating and linning
(v)           MTC - mill test certificate from the
manufacturers
(vi)          Method of jointing, testing and
commissioning
(vii)         Manufacturer has the following
Accreditations:
-       ISO 9001, 14001 and 4427

-       Third Party International Inspection Certificate.

-       Manufacturer’s Submittal of QA/QC Document.

Approval by the Engineer shall not be construed as


2.5 authorizing any deviation(s) from the specifications Comply NO
unless they are specifically brought to notice of the
Engineer.

Approval by the Engineer shall not relieve the


2.6 Contractor from any of his contractual responsibility NO
regarding satisfactory performance and other
requirements of the works.
3 SPECIAL REQUIREMENTS
Pipes and fittings shall be suitable for the intended Comply NO
3.1
use.
Every pipe shall be tested at the manufacturer's
works to specified hydraulic test pressure. The test
3.2 Comply NO
pressure shall be maintained for sufficiently long
time for proof and inspection.
Each pipe and fitting shall be permanently marked or
3.3 Comply NO
engraved giving the following information:-

i               Manufacturers Name or Trademark


ii              Manufacturing date
iii             Manufacturing number
iv             Nominal diameter in mm
v              Class or pressure rating
vi             Manufacturers Inspection mark
Standards according to which the pipes and fittings
have been manufactured.
viii           Heat number should be embossed on all
pipes, fittings and flanges

Unless otherwise specified, diameters of pipes and


fittings shall be nominal. Actual inside and outside
3.4 Comply No
diameters and tolerances in diameters of pipes and
fittings shall be according to the specified standards.

Unless otherwise specified, service ratings of pipes


3.5 and fittings shall not be less than the maximum Comply No
pressure to which they will be subjected to.

Unless otherwise specified, wall thicknesses of the


pipes shall be according to the class, schedule or
duty of the pipes. The wall thicknesses shall be
3.6 Comply No
measured at locations excluding the jointing ends.
The tolerances in wall thicknesses shall be
according to the specified standards.

Wall thicknesses of fittings shall not be less than


those of corresponding pipes to which they are Comply No
joined together.

Pipes and fittings ends shall be matching and


3.7 compatible with each other and with the ends of Comply No
valves and appurtenances to which they are joined.

Unless otherwise approved by the Engineer, pipes


and fittings, jointing materials etc. shall be of the
3.8 Comply No
same manufacturers as those of the pipes and
fittings.