Protection Examples
Protection Examples
Chapter 10
1
Differential Relay Protection of Single Phase Transformer
Iop
Step 1: Phasing
Step 2: CT ratios
and taps 3
Example
Transformer differential protection
4
Transformer differential protection
5
Transformer differential protection
Transformer Str 200M VA Vtr_p 345kV Vtr_s 69kV xtr 12%
1. Describe the objectives of the protection. Determine the fault location when t he CB operation is
desired and fault locations when t he CB must be blocked.
Differencial prot ect ion blocks CB2 in case of Fault 1; The fault is cleard by CB1
Differencial prot ect ion t riggers CB2 and CB3 in case of Fault 2. The fault is cleard by CB2
and CB3
Differencial prot ect ion t riggers CB2 and CB2 in case of Fault 3. The fault is cleard by CB2
and CB3
Differencial prot ect ion blocks CB3 in case of Fault 4. The fault is cleard by CB4
1. Calculate the load currents and maximum and minimum short circuit currents for t he
selected four fault location
Str Str
Load currents IL_p 334.696A IL_s 1.673 kA
3 Vtr_p 3 Vtr_s
2 2
( 345kV) ( 69kV)
Base impedances Zbase_345 1.19 k Zbase_69 47.61
Sbase Sbase
Str Str
Ibase_345 334.696A Ibase_69 1.673 kA
3 Vtr_p 3 Vtr_s
7
Transformer differential protection
Network and transformer impedances
Vnet1 Xnet1
Xnet1 19.919 xnet1 1.673 %
3 Inet1_short Zbase_345
Vnet2 Xnet2
Xnet2 7.967 xnet2 16.735%
3 Inet2_short Zbase_69
2
Vtr_s Xtr
Xtr xtr 2.857 xtr_1 6 %
Str Zbase_69
8
Transformer differential protection
Fault 1 Three-phase short circut current through CB2 from net1 and tr
1.05
IF1.CB2 4.618 IF1_min_p IF1.CB2Ibase_345 1.546kA
xnet2 xtr_1
1.05
IF2.CB2 62.744 IF2_max_p IF2.CB2Ibase_345 21 kA
xnet1
1.05
IF3.CB3 6.274 IF3_min_s IF3.CB3Ibase_69 10.5 kA
xnet2
1.05
IF4_CB3 13.683 IF4_max_s IF4_CB3Ibase_69 22.899 kA
xnet1 xtr_1
9
Transformer differential protection
1. Select t he current transformers and calculate the error current at the maximum and
minimum short circuit current. Calculate the mismatch. Is it acceptable?
345 3000
Selected CT at the secondary side is CT_s 550A 2.75 kA CTs
69 5
10
Transformer differential protection
Fault 1 Relay operation
IF1_min_p IF1_min_s
IrelayF1_pr 14.053A IrelayF1_sec 12.882 A
CT_p CTs
K1 0.25
Iopp_cal Irestrain if IrestrainK1 1A 1A IrestrainK1
Iopp_cal Irestrain_F1 6.734A
11
Transformer differential protection
Fault 1 Neglect CT sat urat iom
IF1_min_p IF1_min_s
IrelayF1_pr 14.053A IrelayF1_sec 12.882 A
CT_p CTs
Relay operation
Irestrain_F1 IrelayF1_pr IrelayF1_sec 26.934A
K1 0.25
Iopp_cal Irestrain if IrestrainK1 1A 1A IrestrainK1
Iopp_cal Irestrain_F1 6.734A
12
Transformer differential protection
Fault 2 same CT
345
IF2_max_p 21 kA IF2_max_s IF2_max_p 105 kA
69
IF2_max_p IF2_max_s
IrelayF2_pr 190.909 A IrelayF2_sec 175 A
CT_p CTs
K1 0.25
Iopp_cal_F2 Irestrain_F2 if Irestrain_F2K1 1A 1A Irestrain_F2K1
Iopp_cal Irestrain_F2 91.477A
13
Transformer differential protection
Fault 3 same CT
345
IF3_min_se IF3_min_s 52.5kA
IF3_min_s 10.5 kA 69
IF3_min_s IF3_min_se
IrelayF3_pr 95.455A IrelayF3_sec 87.5 A
CT_p CTs
Relay operation
Irestrain_F3 IrelayF3_pr IrelayF3_sec 182.955A
K1 0.25
Iopp_cal_F3 Irestrain_F3 if Irestrain_F3K1 1A 1A Irestrain_F3K1
Iopp_cal Irestrain_F3 45.739A
The relay will operate, the current is larger than the calculated one
14
Transformer differential protection
Fault 4 same CT
345
IF4_max_sec IF4_max_s 114.495kA
IF4_max_s 22.899 kA 69
IF4_max_s IF4_max_sec
IrelayF4_pr 208.173 A IrelayF4_sec 190.825 A
CT_p CTs
Relay operation
Irestrain_F4 IrelayF4_pr IrelayF4_sec 398.998A
K1 0.25
Iopp_cal_F4 Irestrain_F4 if Irestrain_F4K1 1A 1A Irestrain_F4K1
Iopp_cal Irestrain_F4 99.75 A
The relay will not operate, the current is smaler than the calculated one
15
Example
Transmission Line Overcurrent Protection
16
Transmission Line Overcurrent Protection
Overcurrent prot ect ion.
Design over current prot ection for t he net work below.
1. Calculate the short circuit currents at Bus 1, Bus 2 and Bus 3
2. Describe t he objectives of prot ection
3. Select current t ransformers
4. Calculat e CT saturat ion
5. Calculate relay operat ion.
6. Mark relays wit h direct ional prot ection
17
Transmission Line Overcurrent Protection
18
Transmission Line Overcurrent Protection
19
Transmission Line Overcurrent Protection
B1
CB1 B2 B3
Network1
L12 L23
Network2
CB2 CB3 CB4 CB5 CB6
6
Syst em data M 10
20
Transmission Line Overcurrent Protection
TD 5.95
t Ishort
7 I 2
0.18
short
1
Is
21
Transmission Line Overcurrent Protection
2 Short circuit calculation
Base values
2
Sbase 100M VA Vbase 69kV Vbase
Zbase_69 47.61
Sbase
Sbase
Ibase_69 836.74A
3 Vbase
Vn1 Xnet1
Xnet1 6.64 xn1 xn1 13.946%
3 Ishort1 Zbase_69
Vn2 Xnet2
Xnet2 5.691 xn2 xn2 11.953%
3 Ishort2 Zbase_69
22
Transmission Line Overcurrent Protection
23
Transmission Line Overcurrent Protection
1.05
iBus2_min 2.029 IBus2_min iBus2_minIbase_69
x n1 XL12
IBus2_min 1.698 kA
1.05
iBus2_max 2.826 IBus2_max iBus2_maxIbase_69
x n2 XL23
IBus2_max 2.364kA
24
Transmission Line Overcurrent Protection
25
Transmission Line Overcurrent Protection
Current transformer selection
EBus1 IBus1_max_CT R500 Rrelay 56.52V No saturation
ICT1 0.09A
ICT1
ErrorCT1 0.15 % very good no saturation
ICT1 IBus1_max_CT
26
27
Transmission Line Overcurrent Protection
CT select ion for CB3 and CB4
IBus2_min
IL 500A 848.82A
2
600
CTCB3
5
Sat urat ion calculat ion
IBus2_max
IBus2_max 2.364kA IBus2_max_CT 19.704 A
CTCB3
EBus2 IBus2_max_CT R600 R relay 19.625 V No saturat ion
ICT3 0.08A
ICT3
ErrorCT3 0.404% very good no saturation
ICT3 IBus2_max_CT
28
Transmission Line Overcurrent Protection
CT select ion for CB5 and CB 6
IBus3_min
IL 500A 570.818A
2
500
CTCB5
5
Sat urat ion calculat ion
IBus3_max
IBus3_max 7 kA IBus3_max_CT 70 A
CTCB5
EBus3 IBus3_max_CT R 500 Rrelay 65.94V Close to saturation
ICT5 0.2A
ICT5
ErrorCT5 0.285 % acceptable
ICT5 IBus3_max_CT
29
Transmission Line Overcurrent Protection
Emperical rule: Relay tap value, currrent set value should be between the load current and the half
of the minimum fault current
IL load current
TD tap value
Is current setting
IBus1_min
IFmin 1.25 IL 14.65A
1.25 IL 40Is 15.625A 2 40
2 40
TD 1
Moderately invers relay operat ion time
TD 5.95
tCB2 Ishort
7 2
0.18
Ishort
I 1
s1 30
Transmission Line Overcurrent Protection
Fault in L12
B1
CB1 B2 B3
Network1
L12 L23
Network2
CB2 CB3 CB4 CB5 CB6
IBus1_max 6 kA IBus1_max_CT 60 A
IBus2_min
IBus2_min 1.698 kA IBus2_min_CT 16.976 A
CTCB1
tCB2 IBus1_max_CT 0.05
tCB2 IBus2_min_CT 0.477
31
Transmission Line Overcurrent Protection
IBus1_min 1.172 kA
CB3 must operate IBus2_max 2.364kA
TD 1
32
Transmission Line Overcurrent Protection
CB3 Operat ion t ime
IBus1_min 1.172 kA
CB3 must operat e IBus2_max 2.364kA
TD 1
TD 5.95
tCB3 Ishort
7
2
0.18
Ishort
I 1
s2
IBus2_max IBus1_min
tCB3 0.148 tCB3 0.924
CTCB3 CTCB3
33