ERGON ENERGY

SPECIALIST PLANT SERVICES


POWER TRANSFORMER LOAD LOSS AND IMPEDANCE
Project No Works Order No
Manufacturer Serial No
Plant
Number
Rating KVA Voltage Ratio (SPN)

LOAD LOSS AND IMPEDANCE CALCULATIONS Input Data in yellow cells


Calculated results in green cells

HV Winding Resistance

HV Resistances: Av.Temp Resist.@ Test Temp.


A 0.32570 Ohms 29.5 °C 0.32878 Ohms
B 0.32630 Ohms 29.5 °C 0.32938 Ohms
C 0.32620 Ohms 29.5 °C 0.32928 Ohms
Average Resist.@ Test Temp.
0.32915 Ohms

LV Winding Resistance

LV Resistances: Av.Temp Resist.@ Test Temp.


a 0.003271 Ohms 29.5 °C 0.00330 Ohms
b 0.003271 Ohms 29.5 °C 0.00330 Ohms
c 0.003270 Ohms 29.5 °C 0.00330 Ohms
Average Resist.@ Test Temp.
0.00330 Ohms

Transformer Details:

Rating: 353000 KVA


Tap No. HV Voltage: 231000 Volts 882.27 Amps
LV Voltage: 19000 Volts 10726.56 Amps

Meter Readings:

Voltage Current
Volts A Volts B Volts C Amps A Amps B Amps C
19000.0 19000.0 19000.0 882.0 882.0 882.0

Av.Volts= 19000.0 Volts Av. Amps= 882.00 Amps

Power Test Temperature


Watts A Watts B Watts C Top Rad. Bot.Rad.
770.0 770.0 770.0 32.0 32.0

Total Watts= 2310 Watts Av.Temp= 32.0 °C

Check this is the latest Process Zone version befor Page 1 of 2 Form SP0504C06 Ver 2
Ergon Energy Corporation Limited ABN 50 087 646 062
Ergon Energy Queensland Pty Ltd ABN 11 121 177 802
ERGON ENERGY
SPECIALIST PLANT SERVICES
POWER TRANSFORMER LOAD LOSS AND IMPEDANCE
Project No 0 Works Order N 0
Manufacturer 0 Serial No 0
Plant
Number
Rating 0 KVA Voltage Ratio 0 (SPN)

Load Loss and Impedances Calculations:

1.5 HV I²R at Rated Current at Load Loss Temp.: 384315 Watts


1.5 LV I²R at Rated Current at Load Loss Temp.: 569815 Watts
Total I²R at Rated Current at Load Loss Temp.: 954130 Watts
Measured Load Loss at Test Current at Load Loss Temp.: 2310 Watts
Calc. Load Loss at Rated Current at Test Temp.: 2311 Watts
Eddies and Strays at Test Temp.: -951819 Watts
Eddies and Strays at 75 °C : -819792 Watts
Total I²R at 75 °C : 1107792 Watts

Total Load Loss at 75 °C 287999 Watts

Average Impedance Volts at Test Current : 32909.0 Volts


Average Impedance Volts at Rated Current : 32919.1 Volts
Impedance Voltage % at Test Temp.: 14.251 %
Resistance Voltage % at Test Temp.: 0.001 %
Reactance Voltage % : 14.251 %
Resistance Voltage % at 75 °C : 0.082 %

Impedance Voltage % at 75 °C : 14.251 %

TESTED BY: __________ __ DATE: ___/___/___

SUPERVISOR: __________ __ DATE: ___/___/___

ENGINEER: __________ __ DATE: ___/___/___

Check this is the latest Process Zone version befor Page 2 of 2 Form SP0504C06 Ver 2