Image For Illustrative Purposes Only..: Generating Set Model (Pm550)

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

TM

PZ550
PM550
3 PHASE/1500RPM
3PHASE/1500RPM

Image for illustrative purposes only..


GENERATING SET MODEL (PM550) ALTERNATOR DATA
Output Ratings Prime Standby Make Stamford
380-415 V, 3 ph, 50 Hz, 1500 rpm 500 KVA 550 KVA Model HCI 534D/544D
400 KW 440 KW No. of bearings 1
Insulation class H
Total Harmonic Content <2%
Wires 12
ENGINE / TECHNICAL DATA Ingress Protection IP23
Ratings at 0.8 Power Factor Excitation System SHUNT
Winding Pitch 2/3 (n° 6)
Engine Make Perkins AVR Model R250
Engine Model 2506A-E15TAG2 Overspeed 2250 mn-1
Governing Type Electronic Voltage Regulation (steady) ± 0.5%
Short Circuit Capacity -
Number of Cylinders 6
Cylinder Arrangement Vertical in line CONTROL PANEL
Bore and Stroke mm 137 x 171 Make Deep Sea
Displacement / Cubic Capacity litres 15.2 Model 7120
Induction System Turbocharged and air to air charge cooled
The DSE7120 is an Auto Start Control Module for
Cycle 4 stroke
single genset applications. It includes a backlit
Combustion System Direct Injection
LCD display which clearly shows the status of the
Compression Ratio 16:1 engine all the times. This module can either be
Rotation Anti-clockwise, viewed on flywheel programmed using the front panel or by using the
Cooling System Water - cooled DSE configuration suite PC software.
Frequency and Engine Speed 50Hz & 1500rpm 60Hz & 1800rpm Metering and Alarm indications:
Prime Standby Prime Standby • Generator frequency
• Underspeed, Overspeed
Gross Engine Power kW (hp) 451 (605) 495 (664) 458 (615) 514 (689)
• Generator volts (L-L, L-N)
Fuel Consumption @ 50% load L/hr 53 - 53 - • Generator current
@ 75% load L/hr 76 - 78 - • Engine oil pressure
@ 100% load L/hr 100 111 102 116 • Engine coolant temperature
• Fuel level (Warning or shutdown) - Optional
Total Lubrication System Capacity litres 62 62 62 62
• Hours run counter
Total Coolant Capacity litres 58 58 58 58 • Battery volts
Boost Pressure Ratio 3.40 3.60 3.00 3.25 • Fail to start/stop
Exhaust Temperature: °C n/a 550 n/a 550 • Emergency stop
• Failed to reach loading voltage/frequency
Radiator Cooling Air Flow (Min): m3/sec 11 11 13.7 13.7
• Charge fail
Combustion Air Flow: m3/min 35.8 36.6 34.3 38 • Loss of magnetic pick-up signal - Optional
Exhaust Gas Flow: m3/min 94 98 96 105.3 • Low DC voltage
Fuel Tank Capacity: litres 705 705 705 705 • CAN diagnostics and CAN fail/error
STANDARD SPECIFICATIONS PM550

1. ENGINE 7. ALTERNATOR 913..FACTORYWARRANTYTEST

Perkins four stroke heavy duty high 7.1 INSULATION SYSTEM • The Generating set is load tested before dispatch
performance industrial type diesel engine. • The insulation system is Class H. • All protective devices control functions and
• All windings are impregnated in either a site load conditions are simulated. The generator
triple dip thermosetting liquid, oil and acid and it’s systems are checked before dispatch.
2. ENGINE FILTRATION SYSTEM resisting polyester varnish or vacuum pressure
impregnated with a special polyester resin. 10.13. EQUIPMENTWARRANTY FINISHING
• Cartridge type dry air filter.
• Heavy coat of antitracking varnishadditional
• Two Cartridge type fuel filters.
protection against moisture or condensation.
• Full flow lube oil filter. All mild steel components are fully degreased and
All filters have replaceable elements. 7.2 AUTOMATIC VOLTAGE REGULATOR (AVR) painted with powder coated paint to ensure
The fully sealed Automatic Voltage maximum scuff resistance and durability.
3 . Regulator maintains the Voltage Regulation
3 . COOLINGRADIATOR at ±0.5%. Nominal adjustment by means of 1113.. DOCUMENTATIONWARRANTY
Radiator and cooling fan, complete with safety guards, a trim pot incorporated on the AVR.
designed to cool the engine at high ambient temperatures
Operation & Maintenance manual, Circuit wiring diagrams
(consult your dealer for de-ration factors) 7.3 MOTOR STARTING
and Commissioning / Fault Finding instruction leaflets are
An overload capacity equivalent to 300% of
accompanied with the Generator.
the Full Load impedance at zero Power
4. EXHAUST SYSTEM Factor can be sustained for 10 seconds,
when AREP or PMG option is fitted. 123.2..QUALITYWARRANTYSTANDARDS
Heavy duty Industrial Exhaust Silencer
813..MOUNTINGWARRANTYARRANGEMENT
The equipment meets the following standards:
Silencer noise reduction level 15 (dB)
8.1 BASE FRAME BS4999, BS5000, BS5514 IEC 60034,
Maximum allowable back pressure 6.8 The complete Generating Set is mounted as a whole
(kPa) VDE0530, NEMA MG 1.22 and ISO 8528.
on a heavy duty fabricated steel Baseframe.

8.2 COUPLING 1313.. WARRANTY


55..CIRCUTBREAKER TYPE The Engine and Alternator are directly coupled by
means of an SAE flange. The Engine flywheel is All of the Generating Sets
ABB 3 pole MCCB. (4 pole is optional) flexibly coupled to the Alternator rotor. arecovered under a
warranty policy for a period of 24 months.
8.3 ANTI-VIBRATION MOUNTING PADS Warranty of the equipment is in line with
6.6.FUEL SYSTEM Anti-Vibration pads are affixed between the Engine / manufacturers warranty terms & conditions.
Alternator feet and the Baseframe thus ensuring (check warranty statement for more details, as it may vary for different countries)
The baseframe design is incorporated with an
integral fuel tank with a capacity of approx. 8 complete vibration isolation of the rotating assembly.
In line with continuous product development, we reserve
hours running at Full Load. The tank is supplied 8.4 SAFETY GUARDS the right to change specifications without notice.
complete with fill cap breather, fuel feed and The Fan & Fan Drive along with the Battery
return lines to the Engine and drain plug. Charging Alternator are Safety Guard
protected for personnel protection.

STANDARD REFERENCE CONDITIONS


H
Prime Power
These ratings are applicable for supplying continuous electrical power (at variable load)
in lieu of commercially purchased power. 10% overload power is available for 1 hour in
12 hours continuous operation.
Standby Power L
These ratings are applicable for supplying continuous electrical power (at variable load)
in the event of a utility power failure. No overload is permitted on these ratings.
DIMENSIONS AND WEIGHT

Length cm Width cm Height cm Weight* kg (wet)


336 117 203 3810