ECTICon 2015 7206957

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Evaluation of Transformer Loading and Energy Loss

For Increasing Energy Efficiency in Distribution System


Suresh Krishnamoorthy, Dr. Devishree Jayabal
Faculty of Electrical and Electronics Engineering
Coimbatore Institute of Technology-CIT, Coimbatore, Tamil Nadu - 641014, India
e-mail: sureshdhaya@rediffmail.com
.
Abstract – Estimating loading per cent of a distribution (core) loss is predominant and the losses are estimated via loss
transformer and energy loss during power transformation for factor and working hours for the loss estimation is suggested
a continuous process industry having High Tension (HT) to [3]. Errors in energy consumption and loss calculation are
Low Tension (LT) power conversion in its distribution is an happened with the instantaneous measured data if operational
imperative for the betterment of energy efficiency. This is done conditions or standard utilization of industry is not ensured
by measuring and analysing active and apparent power at [4]. Energy wastage identification through energy and power
utilization and compensated reactive power at transformer audit for energy conservation and loss reduction after
end at standard industry operating condition. Thereby implementation leads to demand reduction [5]. Designing an
transformer loading level and operating efficiency is derived industrial power system with energy efficiency through load
with the help of actual load test results. Transformer loading estimation and selection of rating of service equipment during
level estimation with transformer secondary current planning and commissioning stages is a challenging task and
(conventional method) and estimation by power flow is extended to expansion [6]. Energy losses are calculated
(proposed method) are compared with standard and energy using generalized models of transformer considering the
loss of the transformer is expressed as percent of total energy. voltage variation that influences no load and load losses with
A case study in an industry is also given as an implementation limitation of minimum loss present with actual loading [7].
of suggested the methodology for the scope of increasing Computing the energy consumption and line losses with the
energy efficiency. standard industry production is important to reduce the cost of
the energy contribution to decrease individual energy
Keywords: Power Control Centre (PCC), Distribution
consumption without decreasing individual welfare and
Transformer, Active power (kW), Apparent power (kVA),
productivity. It is obvious that it also contributes to increase
Reactive power (kVAr), power factor (pf) , Energy Losses, Energy
the overall energy efficiency of the national economy.
Efficiency.
In all the above references, loss calculation and/or,
1. INTRODUCTION improvement of energy efficiency is analyzed with
1.1 Need of the Study transformer secondary current. Reactive power compensated
In industries electrical power transportation from at transformer end, reactive power inductive and reactive
supply to load is done through a transformer with level power capacitive is not taken into account for evaluation. In
change from High Tension (HT-11/22kV) to Low Tension this method a step by step procedure is suggested to
(LT- 440V) voltage at 50 Hz. Aim of the energy calculating the transformer loading level based on the power
management technique is to utilise the input power more flow to the loads and the reactive power compensated at
effectively as active power with decreasing energy transformer end.
wastages. For an industry, transformer is main power 2. METHODOLOGY
handling service equipment in the LT distribution. Avoiding A new procedure is suggested to estimate the transformer
excess line losses in distribution is one of the important loading level, comparing with the standards for loss,
areas to increase the energy efficiency. Computing the estimating the loss as a percent of total industry energy and
loading of transformer and estimating the losses of suggestion to increase the energy efficiency of the transformer
transformer are the main objective of the paper to express and industry.
the industry energy efficiency.
2.1 Estimation of Transformer loading and loss
1.2. Literature Survey a) Measurement of apparent power, active power and
LT distribution transformer losses are calculated based reactive power compensated at load end feeder cables
on fixed core loss (no load loss) for the period of energizing connected to a particular transformer
and copper loss (load loss) as a factor of ratio of minimum b) Calculation of total reactive power (inductive) at
and maximum load [1]. As a case study it is evaluated that transformer to be compensated.
transformer operation is at efficient level at 50 percent c) Measurement of reactive power compensated at
loading with good voltage profile and over loading leads to transformer end.
power factor (pf) reduction, voltage sag and more losses [2]. d) Calculate the remaining reactive power at transformer end
Energy losses of LT distribution system is having direct after compensation
proportional relation with increase in load with no load

978-1-4799-7961-5/15/$31.00 ©2015 IEEE


e) Compute the apparent power of the trransformer which
is actual load and express as per centc of its rated
capacity.
f) Calculate the losses from actual loadd test results and
derive its operating efficiency and enerrgy wastage as a
percent of total energy consumption of the
t industry.

2.2. Standards for Transformer losses

Losses and efficiency of the transfoormers not only


depend on the design, but also, on the efffective operating
load. Transformer losses consist of two paarts: No-load loss
and Load loss. Fig.1. Transformer loading vs Looss.
2.2.1. No-load loss (core loss)
2.4. Power Flow in Industry LT Distribution.
It is the self power consumed to keep up the magnetic
field in the transformer's core. Core loosses are caused Electrical distribution of HT
T/LT conversion in an industry
mainly by two factors: hysteresis and edddy current losses. having conventional method off reactive power compensation
Hysteresis loss is that energy loss consumption
c by and the power flow from HT souurce to load is shown in Fig.2.
magnetic field reversal in the core duringg the positive and
negative o the alternating current or vooltage. Also self
induced current at core is the reason for the eddy current
loss. Also as a third factor, negligible am
mount of no load
copper loss compared to core loss is accouunted.

2.2.2. Load loss (copper- I2R loss)


It is associated with full load currrent flow in the
transformer windings. Copper loss is poower lost in the
primary and secondary windings of a traansformer due to
the ohm resistance of the windings. Coopper loss varies
with the square of the load current. Hence
H efficiency
varies for an industrial distribution trransformer with
different level of loading. Efficiency decrease with
increase in load for a distribution transfoormer (500 kVA
capacity) is tabulated in Table.1 [10].

Table: 1 Transformer Load and effficiency


Percent Load 125 100 75 50 25
Efficiency at
98.52 98.76 98.97 9
99.14 99.10
unity pf
Efficiency at
98.15 98.45 98.72 9
98.93 98.87
0.8 pf
Fig.2. Power flow and loss distriibution in LT network
2.3. Optimum loading and energy wastagee
2.5 Energy Efficiency:
Efficient loading of a distribution transformer is
As the distribution traansformer gives maximum
between 50 percent – 60 percent at 0.95 – 0.99 PF where
efficiency between 50 percent – 60 percent load levels, for
core loss and copper loss are equal. Maxim mum efficiency of
an industry to be energy efficient, the losses at transformer
the transformer is 98.5 percent to have a standard loss of
during power transportation shhould be less than 1.5 percent
1.5 percent of total energy [9]. If the trannsformer is fully
of total energy [9].
loaded additional energy loss varies betweeen 0.4 percent –
1.9 percent. This results the total loss off the transformer
will be 1.9 percent – 2.4 percent dependinng on the layout 3. ESTIMATION OF TRANSFOR
RMER LOADING AND LOSSES.
and complexity of the distribution system m which turns the
system inefficiency. The relation between the
t losses and the 3.1 Conventional method
loading of a distribution transformer is show
wn in Fig.1. Secondary current of the transformer = A1 Amps
Rated secondary current of the trransformer = A2 Amps
Transformer loading level (in peercent)
A1
Percent load = x 100 (1)
A2
3.2 Proposed method 4.1.2 Field Study and data analysis
Measurements Secondary current of transformer at PCC and power flow
Transformer rated Capacity = kVA1 to each feeder is measured through recording of voltage,
Existing Reactive Power at PCC = kVAr1 active (kW) , apparent power (kVA) at feeder end and the
(in general, it is inductive) reactive power compensated at both feeder and transformer
Reactive power compensated with = kVAr2 end. The electrical parameters of each feeder are measured at
capacitors at PCC actual industry standard running condition during power study
Reactive power at PCC = kVAr3 is given in Table.3 and Table.4.
after compensation
Measured full load Active power = kW Table: 3 Feeder end active and apparent power
(Adding active power of all feeder values)
Measured full load Apparent power = kVA2 Full
(Adding apparent of all feeder values) Stopped Load Full Active Apparent
Apparent Power at PCC = kVA3 Feeder Load in HP Factor Power kW Power kW
after reactive power compensation Feeder 1 101.3 0.54 103 184
Feeder 2 0.0 0.56 120 136
3.3 Transformer loading (Proposed Method) Feeder 3 130.0 0.76 193 272
Feeder 4 0.0 0.73 71 96
kVAr 1(inductive ) = ( kVA 2 ) 2 − ( kW ) 2 (2) Total 487 688
kVAr3 = kVAr1 – kVAr2 (3)
Table:4 Reactive Power Compensation
(Negative value of kVAr3 indicates excess reactive power
Compensation Effective
compensated at PCC panel) At Rated kVAr kVAr ** Voltage
2 2
kVA 3 = (kVAr3 ) + (kW ) (4) Transformer 300 284
Feeder 1 0 0 415 V
Transformer loading level (in percent) Feeder 2 0 0
kVA3 Feeder 3 0 0
Percent load = x 100 (5) Feeder 4 0 0
kVA1
** Effective value of the capacitor bank is calculated
4. RESULTS AND DISCUSSIONS WITH A CASE STUDY from the percent reduction from the ratio of measured
4.1 Details of the Industry Considered: capacitor current to the rated current.
A continuous yarn manufacturing industry has been
4.2 Results
selected for the energy study. The industry considered is
high tension (HT) power consumer from the utility With the data obtained from study and interpretation,
supplier having HT /LT electrical distribution network. analysis is done with conventional method (secondary current)
4.1.1 Transformer Details and proposed method (power flow analysis) to estimate the
loading percent of transformer and the result is given in
The industry is having a distribution transformer for its
Table.5.
power consuming loads. It is without on-load tap correction
Table: 5 Transformer loading comparison
(OLTC) facility for voltage correction. The rating of
transformer and the connected load details identified and Percent
recorded during the field study are given in Table.2. Loading estimation by Measured Rated Loading
Conventional Method
Table: 2 Transformer rating and connected load 733.5 A 722 A 101.6 %
Secondary current
Transformer Capacity 500 kVA Proposed Method 527.2 500
105.4 % *
Primary. Voltage Rating 11000 V Apparent Power kVA kVA
Secondary Voltage Rating. 400 V * Excess loading level indentified = 4%
Primary current rating. 26 A
4.2.2 Interpretation
Secondary current rating.. 722 A
No of Feeders Connected 4 From the analysis and interpretation, it is clear that
Connected Load in feeders in Horse Power (HP) loading analysis through power flow shows a significance
difference at higher side than the secondary current analysis
Feeder 1 255 method. Loading comparison of a distribution transformer
Feeder 2 285 with two methods in percent is shown in Figure.3.
Feeder 3 341
Feeder 4 131
107 105.4
REFERENCES
Loadin g in percent

105 [1] W.Wysocki and Marcin Szlosek, “Compensation of


103 101.6 Reactive Power as a method for reducing losses”,
Proceedings of International Conference on Electrical
101 Power Quality and Utilisation (EPQU)”, IEEE, pp1-5, Oct
99 2011.
Secondary Current Power Flow [2] Xiaodong Liang, Jeffrey Lim and Obinna Ilochonwu,
Method Method “Power System Optimisation for Industrial Facilities
Using Power Studies”, IEEE Transactions on Industry
Transformer Loading Estimation Applications, Vol 48, No 3, pp-1095 -1106, May/June,2012.
[3] BoYang, Reigh Walling, Lavelle Freeman, et.al,
“Improving Energy Efficiency through Loss Identification”,
Fig.3. Transformer loading comparison in Transmission and Distribution Conference and
4.2.3 Estimation of Transformer losses Expotion,IEEE , pp-1-6,April 2010.
[4] James A. Bright and Wei-Jen Lee,” Integrated
From the case study it is revealed that the transformer Monitoring, Protection and Control Systems for Industrial
loading is maximum and above 100 percent. Estimated and Commercial Power Systems”, IEEE Transactions on
energy loss through power flow study is higher and hence Industry Applications, Vol-36, No1, pp-11-15,
the efficiency loss of the transformer is 0.5 percent more of January/February, 2000.
energy handled by the transformer [10]. By keeping the [5] P.Loganthurai, Dr. V. Rajasekaran and S.Subbulakshmi,
loading of the transformer between 50 – 60 percent, the “A New Proposal to Implement Energy Management
industry is said to be 0.5 percent more energy efficient. This Technique in Industries”, Proceedings of International
energy loss can be conserved through capacity Conference on Computing Electronics and Electrical
augmentation of the transformer as an energy conservation Technologies [ICCEET] ,pp-495-500, March,2012.
measure. [6] Chun Lien Su, “Load Estimation in Industrial Power
System for Expansion and Planning”, IEEE Transactions
5. CONCLUSIONS on Industry Applications, Vol 47, No 6, pp-2311 -
2323, November/December 2011.
Transformer loading and loss estimation is done based
[7] Cornel Toader, Mircea Scutariu and Catalin Dumitriu,
on power measurements and compensated reactive power.
“The Analysis of Optimal Energy Losses in TwoWinding
This approach gives real estimation compared to the
Transformers”, Proceedings of 10th Mediterranean Electro
secondary current estimation. Also additional increase in
Technical Conference, Melecon, Vol-III, pp-29-31
energy efficiency is computed through calculating the
May,2000.
inductive and capacitive reactive powers at transformer end
[8] C.Palanichamy, C.Natarajan, Sundar Babu,et al,“Budget
along with load end active power and apparent power gives
Constrained Energy Conservation – A Experience with a
exact value of transformer end power factor and also tells
Textile Industry”, IEEE Transaction on Energy
about whether it is lagging or leading to avoid penalty if it
Conversion Vol-16, No-4, pp 340-345, December, 2001.
exceeds the utility supplier set limit. Optimum loading of
[9] Bureau of Energy Efficiency, Ministry of Power,
distribution transformer is between 50 – 60 percent with
Government of India, “Energy Efficiency in Electrical
efficiency 98.5 percent at unity power factor. Every 10
Utilities”, Book-3, pp-5, 15-18, 2005.www.beeindia..in,
percent increase in load on transformer from 50 percent,
[10] Indo Tech Transformers, ‘‘Distribution Transformer Test
results 0.1 percent excess raise in transformer losses. In
Certificate’, Manufacturer Specification No: IS 2026/
order to operate at high efficiency with standard loss, over
1977/QA/DTP 8.2.4/R/07, pp-1-2, September, 2008.
loading of industrial distribution transformer should be
avoided.
As the Transformer loss is one of the major portions of
line losses in LT distribution, it is derived for the industry
as the percent of total input energy. Result of this approach
gives raise to increase the energy efficiency for the better
energy management of the industry. Industries in India
coming under HT tariff structure having high energy cost
for the product. Facing acute power crisis and high energy
cost, energy conservation and reducing energy wastage is
imperative and can be attained through periodic power and
energy studies and adopting better energy management
techniques at correct instant [8].Hence improvement in
industry energy efficiency of the industry with the
advantage of above suggested approach can be quantified
with a complete study of entire distribution system starting
from transformer, feeder and till utility.

You might also like