Cm-Pbe, Cm-Pfe, Cm-Pfe.2, Cm-Pve: Operating and Installation Instructions

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Warnung! Gefährliche Spannung!

Installation nur durch elektro­


Printed in Germany - Doc.no. 1SVC 550 510 M0001 A (12/15)

technische Fachkraft.
Warning! Hazardous voltage! Installation by person with electrotechnical
expertise only.
Avertissement! Tension électrique dangereuse! Installation uniquement
par des personnes qualifiées en électrotechnique.
¡Advertencia! ¡Tensión peligrosa! La instalación deberá ser realizada
únicamente por electricistas especializados.
Avvertenza! Tensione pericolosa! Far installare solo da un elettricista
specializzato.
Varning! Farlig spänning! Installation får endast utföras av en elektriker.
Oсторожно! Опасное напряжение! Монтаж должен выполняться
только специалистом-электриком.
警告!危险电压!仅可由电气专业人员安装。

CM-PBE, CM-PFE, CM-PFE.2, CM-PVE

Operating and installation instructions


Three-phase monitoring relays, CM range
Note: All statements serve exclusively to describe the product and have
not to be understood as assured characteristics with legal force. Further
information and data is obtainable from the catalogues and data sheets of
this product, from the local ABB sales organisations as well as on the ABB
homepage www.abb.com. Subject to change without prior notice.
2CDC 253 005 F0015
2CDC 253 004 F0015

CM/CT-E range
2CDC 252 048 F0009

0.6...0.8 Nm
5.31...7.08 lb.in
Ø 4.5 mm / 0.177 in / PZ 1
10 mm
0.39 in
2 x 0.75...1.5 mm²
2 x 18...16 AWG
2CDC 252 048 F0009

10 mm
0.39 in
2 x 1.0...1.5 mm²
2 x 18...16 AWG
10 mm
0.39 in
2 x 0.75...1.5 mm²
2 x 18...16 AWG

ABB STOTZ-KONTAKT GmbH, Eppelheimer Straße 82, 69123 Heidelberg / Germany


www.abb.com/lowvoltage
Technical data:
Ta: -20 ... +60 °C (-4 ... +140 °F)
IP 20
Pollution degree 3

CM-PFE.2:
If both, ambient temperature > 50 °C and rated operational currents > 2 A,
lateral spacing to other units has to be min. 10 mm (0.394 in).

CM-PBE

L1, L2, L3, N

2CDC 252 045 F0203


Measuring value
L1, L2, L3, N L1, L2, N L1, L2, L3, N L2, L3, N L1, L2, L3, N L1, L2 L1, L2, L3, N
L3
with
L3 L1 N
neutral
t t <t t <t
s v s s v

13-14
R: yellow LED
ts = Start-up delay fixed 500 ms
tv = Tripping delay fixed 150 ms

L1, L2, L3

2CDC 252 046 F0203


Measuring value
L1, L2, L3 L1, L2 L1, L2, L3 L1, L2 L1, L2, L3 L1, L2 L1, L2, L3

without L3 L3 L3

neutral t
s
t
v
<t
s
t
s
<t
v

13-14
R: yellow LED
ts = Start-up delay fixed 500 ms
tv = Tripping delay fixed 150 ms

CM-PFE, CM-PFE.2

L1, L2, L3
2CDC 252 061 F0208

Measuring value
L1, L2, L3 L1, L3, L2 L1, L2, L3 L1, L2 L1, L2, L3

t t t t L3 t
s v s v s

11-14
11-12

R: yellow LED
ts = Start-up delay fixed 500 ms
tv = Tripping delay fixed 500 ms

CM-PVE

L1, L2, L3, N


2CDC 252 047 F0203

Umax
Umax - 5 %

Measuring value
Umin + 5 %
Umin
with ts tv <ts ts <tv tv ts
neutral 13-14

R: yellow LED
ts = Start-up delay fixed 500 ms
tv = Tripping delay fixed 500 ms

L1, L2, L3
2CDC 252 048 F0203

Umax
Umax - 5 %

Measuring value
Umin + 5 %
Umin
without ts tv <ts ts <tv tv ts
neutral 13-14

R: yellow LED
ts = Start-up delay fixed 500 ms
tv = Tripping delay fixed 500 ms