02je469, N47076S, R0, P2P Na

You might also like

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 20

Revision History

IBM Cloud Pak for Data Systems HA, (Lenovo 40 Enclosures) NA 4 to 6 Single Phase PDU's from Base +1 to Base +38 (Factory Racking)

Revision Date Rev Modifications to WD 02JE469


9/11/2019 R1 Prototype 40 Enclosure Solstice HA 6 PDU per Rack
09/12/2019 R2 Moved all Hub Switch connections to Rack 3, Changed cable lengths
09/24/2019 R3 Changed Management interswitch MGMT port connections, reversed fabsw a & b mgt connections.
12/09/2019 R4 Added Base +2 sheet with 4 Single Phase PDU's for minimum system requirement. Added Storage Gateway
12/18/2019 R5 Added 1U space between each D2 enclosure
01/10/2020 R6 Changed information on Gateway server and cable lengths
1/22/2020 R7 Added second Storage Gateway
1/28/2020 R8 Added Third Storage Gateway and readjusted Spine Fabric 100GigE Connections
02/14/2020 R9 Fixed Enclosure count on Management table for mgtsw7a, add North American Power Designation.
02/24/2020 R10 Added Base+ 1 to 2 and Base+ 4 Tabs
02/25/2020 R11 Expanded tabs to create Base+ 1, Base+ 2, and Base+ 4.
02/26/2020 R12 Moved Mgtsw2A from Rack 2 to Rack 1 (Multi Rack)
02/27/2020 R13 Changed 10Gig SFP+ part number from 46C3448 to 77P9336 and added 4 more connections at the Patch Panel
02/28/2020 R14 Adjusted plug placement on all PDU's, Corrected lengths on inter pod cableing
03/18/2020 R15 Added Label information sheets.
03/26/2020 R16 Added WD Part number
04/01/2020 R17 Changed Blank panels on racks 2,4,6,8
04/01/2020 R18 Changed 4U filler in rack 1 Multi to 2 x 1U and 1 x 2u fillers
05/14/2020 R19 Changed fiber cables on Base+ 4 enclosure 6 to 3 meter lengths. Replaced 10' Grey 00J1697 with 3m Blue 01AF040 cables, Release Per ECO# N47076S

Eop

Page 1
Rack 1 (Base+ 1)

Doc Part # 02JE469


ECO#N47076S

ICP4D (Lenovo Base +1) 4 Single Phase PDU's NA Version


Fillers: 1U=10, 2U=9, 4U=1
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch 1a and 1b Connections SFP28 Xcvrs with LC - LC Cables Edge-Core AS4610-54T 1G Ethernet Management Switch 1a Connections.
42 From To From To
Harness Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #3 S4 (10/25GigE) P2 Fabsw 1b 12 15R8846, 3M Fiber LC-LC Fabsw 1b MGMT P0 Mgtsw 1a 46 Cat6 7' Blue- 00J1691
39 Plug 3 D2 Enclosure #3 S4 (10/25GigE) P1 Fabsw 1a 12 15R8846, 3M Fiber LC-LC Fabsw 1a MGMT P0 Mgtsw 1a 47 Cat6 7' Blue- 00J1691
38 Plug 4 D2 Enclosure #3 Right 39M5510 C13/C14 4.3m D2 Enclosure #3 S3 (10/25GigE) P2 Fabsw 1b 11 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 4 P1 Mgtsw 1a 15 01AF040, 3m Blue
2U Blank Panel
37 Plug 5 D2 Enclosure #3 S3 (10/25GigE) P1 Fabsw 1a 11 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 3 P1 Mgtsw 1a 14 01AF040, 3m Blue
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #3 S2 (10/25GigE) P2 Fabsw 1b 10 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 2 P1 Mgtsw 1a 13 01AF040, 3m Blue
RPC4
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #3 S2 (10/25GigE) P1 Fabsw 1a 10 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 1 P1 Mgtsw 1a 12 01AF040, 3m Blue
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #3 S1 (10/25GigE) P2 Fabsw 1b 9 15R8846, 3M Fiber LC-LC D2 Enclosure #3 SMM P1 Mgtsw 1a 11 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #3 S1 (10/25GigE) P1 Fabsw 1a 9 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 4 P1 Mgtsw 1a 10 01AF040, 3m Blue
32 2U Blank Panel Plug 10 D2 Enclosure #2 S4 (10/25GigE) P2 Fabsw 1b 8 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 3 P1 Mgtsw 1a 9 01AF040, 3m Blue
31 Interface Patch Panel Plug 11 D2 Enclosure #2 S4 (10/25GigE) P1 Fabsw 1a 8 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 2 P1 Mgtsw 1a 8 01AF040, 3m Blue
30 1U Blank Panel Plug 12 D2 Enclosure #2 S3 (10/25GigE) P2 Fabsw 1b 7 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 1 P1 Mgtsw 1a 7 01AF040, 3m Blue
29 Management Swt 2A – Edge-Core w/Air Duct D2 Enclosure #2 S3 (10/25GigE) P1 Fabsw 1a 7 15R8846, 3M Fiber LC-LC D2 Enclosure #2 SMM P1 Mgtsw 1a 6 01AF040, 3m Blue
78P5153 Qty 64
28 Management Swt 1A – Edge-Core w/Air Duct D2 Enclosure #2 S2 (10/25GigE) P2 Fabsw 1b 6 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 4 P1 Mgtsw 1a 5 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #2 S2 (10/25GigE) P1 Fabsw 1a 6 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 3 P1 Mgtsw 1a 4 01AF040, 3m Blue
26 Fabric Switch 1B – Mellanox w/Air Duct D2 Enclosure #2 S1 (10/25GigE) P2 Fabsw 1b 5 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 2 P1 Mgtsw 1a 3 01AF040, 3m Blue
25 Fabric Switch 1A – Mellanox w/Air Duct Plug 1 D2 Enclosure #2 S1 (10/25GigE) P1 Fabsw 1a 5 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 1 P1 Mgtsw 1a 2 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #1 S4 (10/25GigE) P2 Fabsw 1b 4 15R8846, 3M Fiber LC-LC D2 Enclosure #1 SMM P1 Mgtsw 1a 1 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #1 S4 (10/25GigE) P1 Fabsw 1a 4 15R8846, 3M Fiber LC-LC
2U Blank Panel
22 Plug 4 D2 Enclosure #3 Left 39M5510 C13/C14 4.3m D2 Enclosure #1 S3 (10/25GigE) P2 Fabsw 1b 3 15R8846, 3M Fiber LC-LC
21 Plug 5 D2 Enclosure #1 S3 (10/25GigE) P1 Fabsw 1a 3 15R8846, 3M Fiber LC-LC Edge-Core AS4610-54T 1G Ethernet Management Switch 2a Connections.
2U Blank Panel
20 Plug 6 D2 Enclosure #1 S2 (10/25GigE) P2 Fabsw 1b 2 15R8846, 3M Fiber LC-LC From To
RPC3
19 1U Blank Panel Plug 7 D2 Enclosure #1 S2 (10/25GigE) P1 Fabsw 1a 2 15R8846, 3M Fiber LC-LC ID Component PCI Slot Port ID Component Port Harness Color
18 Plug 8 D2 Enclosure #1 S1 (10/25GigE) P2 Fabsw 1b 1 15R8846, 3M Fiber LC-LC Mgtsw 2a N/A MGMT Mgtsw 1a 38 00J1689, 3' Blue
2U Blank Panel
17 Plug 9 D2 Enclosure #1 S1 (10/25GigE) P1 Fabsw 1a 1 15R8846, 3M Fiber LC-LC Mgtsw 2a N/A 42 Mgtsw 1a 42 Up Link 01AF044, 0.6m Blue
16 1U Blank Panel Plug 10 Fabsw 1a N/A 44 Fabsw 1b 44 01FT735, 0.5M 25Gb/s SFP28 ISL Mgtsw 2a N/A 41 Mgtsw 1a 41 Up Link 01AF044, 0.6m Blue
15 Plug 11 Fabsw 1a N/A 43 Fabsw 1b 43 01FT735, 0.5M 25Gb/s SFP28 ISL
2U Blank Panel SFP DACs
14 Plug 12 Fabsw 1a N/A 42 Fabsw 1b 42 01FT735, 0.5M 25Gb/s SFP28 ISL
13 1U Blank Panel Fabsw 1a N/A 41 Fabsw 1b 41 01FT735, 0.5M 25Gb/s SFP28 ISL System Patch Panel RJ45 1GigE Connections
12 From To
2U Blank Panel
11 Right Side Power from Rear ID Component Port ID Component Type Connections Length/Type
10 1U Blank Panel Mgtsw 1a 48 Patch-panel 1GigE SCP-A Cat6 5' Blue- 00J1690
9 Plug 1 Mgtsw 1a Right 39M5509 C13/C14 2.8m D2 Enclosure #1 EIOM Node 4 P2 Patch-panel 1GigE ETH3 01AF040, 3m Blue
D2 Enclosure #3 SD530 Nodes 1-4 (+ 1)
8 Plug 2 D2 Enclosure #1 EIOM Node 3 P2 Patch-panel 1GigE ETH2 01AF040, 3m Blue
7 1U Blank Panel Plug 3 Fabsw 1b Right 39M5509 C13/C14 2.8m D2 Enclosure #1 EIOM Node 2 P2 Patch-panel 1GigE ETH1 01AF040, 3m Blue
6 Plug 4 D2 Enclosure #1 EIOM Node 1 P2 Patch-panel 1GigE ETH0 01AF040, 3m Blue
D2 Enclosure #2 SD530 Nodes 1-4 (Base)
5 Plug 5 Fabsw 1a Right 39M5509 C13/C14 2.8m
4 1U Blank Panel Plug 6
RPC2
3 Plug 7 Mgtsw 2a Right 39M5509 C13/C14 2.8m Patch Panel 10 GigE SFP+ Connections
D2 Enclosure #1 SD530 Nodes 1-4 (Base)
2 Plug 8 D2 Enclosure #2 Right 39M5510 C13/C14 4.3m From To
1 1U Blank Panel Plug 9 ID Component Transceiver Port ID Component Type Connections Length/Type
Plug 10 Fabsw 1b P48 Patch-panel 25/10GigE ETH11 15R8846, 3M Fiber LC-LC
Plug 11 Fabsw 1b P47 Patch-panel 25/10GigE ETH10 15R8846, 3M Fiber LC-LC
Plug 12 D2 Enclosure #1 Right 39M5510 C13/C14 4.3m Fabsw 1b P46 Patch-panel 25/10GigE ETH9 15R8846, 3M Fiber LC-LC
Rack 1 (Base+ 1) Fabsw 1b P45 Patch-panel 25/10GigE ETH8 15R8846, 3M Fiber LC-LC
77P9336
Fabsw 1a P48 Patch-panel 25/10GigE ETH7 15R8846, 3M Fiber LC-LC
Left Side Power from Rear Fabsw 1a P47 Patch-panel 25/10GigE ETH6 15R8846, 3M Fiber LC-LC
Fabsw 1a P46 Patch-panel 25/10GigE ETH5 15R8846, 3M Fiber LC-LC
Plug 1 Mgtsw 1a Left 39M5509 C13/C14 2.8m Fabsw 1a P45 Patch-panel 25/10GigE ETH4 15R8846, 3M Fiber LC-LC
Plug 2
Plug 3 Fabsw 1b Left 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 1a Left 39M5509 C13/C14 2.8m
Plug 6
RPC1
Plug 7 Mgtsw 2a Left 39M5509 C13/C14 2.8m
Plug 8 D2 Enclosure #2 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #1 Left 39M5510 C13/C14 4.3m

Page 2
Rack 1 (Base+ 2)
Doc Part # 02JE469
ECO#N47076S

ICP4D (Lenovo Base + 2) 4 Single Phase PDU's NA Version


Fillers: 1U=10, 2U=8, 4U=1
Left Right Right Side Power from Rear
42
41 Plug 1
4U Blank Panel
40 Plug 2
39 Plug 3
38 Plug 4 D2 Enclosure #3 Right 39M5510 C13/C14 4.3m
2U Blank Panel
37 Plug 5
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6
RPC4
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9
32 2U Blank Panel Plug 10 D2 Enclosure #4 Right 39M5510 C13/C14 4.3m
31 Interface Patch Panel Plug 11
30 1U Blank Panel Plug 12
29 Management Swt 2A – Edge-Core w/Air Duct
28 Management Swt 1A – Edge-Core w/Air Duct
27 1U Blank Panel Left Side Power from Rear
26 Fabric Switch 1B – Mellanox w/Air Duct
25 Fabric Switch 1A – Mellanox w/Air Duct Plug 1
24 1U Blank Panel Plug 2
23 Plug 3
2U Blank Panel
22 Plug 4 D2 Enclosure #3 Left 39M5510 C13/C14 4.3m
21 Plug 5
2U Blank Panel
20 Plug 6
RPC3
19 1U Blank Panel Plug 7
18 Plug 8
2U Blank Panel
17 Plug 9
16 1U Blank Panel Plug 10 D2 Enclosure #4 Left 39M5510 C13/C14 4.3m
15 Plug 11
2U Blank Panel
14 Plug 12
13 1U Blank Panel
12
D2 Enclosure #4 SD530 Nodes 1-4 (+ 2)
11 Right Side Power from Rear
10 1U Blank Panel
9 Plug 1 Mgtsw 1a Right 39M5509 C13/C14 2.8m
D2 Enclosure #3 SD530 Nodes 1-4 (+ 1)
8 Plug 2
7 1U Blank Panel Plug 3 Fabsw 1b Right 39M5509 C13/C14 2.8m
6 Plug 4
D2 Enclosure #2 SD530 Nodes 1-4 (Base)
5 Plug 5 Fabsw 1a Right 39M5509 C13/C14 2.8m
4 1U Blank Panel Plug 6
RPC2
3 Plug 7 Mgtsw 2a Right 39M5509 C13/C14 2.8m
D2 Enclosure #1 SD530 Nodes 1-4 (Base)
2 Plug 8 D2 Enclosure #2 Right 39M5510 C13/C14 4.3m
1 1U Blank Panel Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #1 Right 39M5510 C13/C14 4.3m
Rack 1 (Base+ 2)
Left Side Power from Rear

Plug 1 Mgtsw 1a Left 39M5509 C13/C14 2.8m


Plug 2
Plug 3 Fabsw 1b Left 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 1a Left 39M5509 C13/C14 2.8m
Plug 6
RPC1
Plug 7 Mgtsw 2a Left 39M5509 C13/C14 2.8m
Plug 8 D2 Enclosure #2 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #1 Left 39M5510 C13/C14 4.3m

Page 3
Rack 1 (Base+ 2)

Mellanox SN2410 25GigE Leaf Switch 1a and 1b Connections SFP28 Xcvrs with LC - LC Cables
From To
Harness Transceiver
ID Component PCI Slot Port ID Component Port
D2 Enclosure #4 S4 (10/25GigE) P2 Fabsw 1b 16 15R8846, 3M Fiber LC-LC
D2 Enclosure #4 S4 (10/25GigE) P1 Fabsw 1a 16 15R8846, 3M Fiber LC-LC
D2 Enclosure #4 S3 (10/25GigE) P2 Fabsw 1b 15 15R8846, 3M Fiber LC-LC
D2 Enclosure #4 S3 (10/25GigE) P1 Fabsw 1a 15 15R8846, 3M Fiber LC-LC
D2 Enclosure #4 S2 (10/25GigE) P2 Fabsw 1b 14 15R8846, 3M Fiber LC-LC
D2 Enclosure #4 S2 (10/25GigE) P1 Fabsw 1a 14 15R8846, 3M Fiber LC-LC
D2 Enclosure #4 S1 (10/25GigE) P2 Fabsw 1b 13 15R8846, 3M Fiber LC-LC
D2 Enclosure #4 S1 (10/25GigE) P1 Fabsw 1a 13 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 S4 (10/25GigE) P2 Fabsw 1b 12 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 S4 (10/25GigE) P1 Fabsw 1a 12 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 S3 (10/25GigE) P2 Fabsw 1b 11 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 S3 (10/25GigE) P1 Fabsw 1a 11 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 S2 (10/25GigE) P2 Fabsw 1b 10 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 S2 (10/25GigE) P1 Fabsw 1a 10 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 S1 (10/25GigE) P2 Fabsw 1b 9 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 S1 (10/25GigE) P1 Fabsw 1a 9 15R8846, 3M Fiber LC-LC
78P5153 Qty 80
D2 Enclosure #2 S4 (10/25GigE) P2 Fabsw 1b 8 15R8846, 3M Fiber LC-LC
D2 Enclosure #2 S4 (10/25GigE) P1 Fabsw 1a 8 15R8846, 3M Fiber LC-LC
D2 Enclosure #2 S3 (10/25GigE) P2 Fabsw 1b 7 15R8846, 3M Fiber LC-LC
D2 Enclosure #2 S3 (10/25GigE) P1 Fabsw 1a 7 15R8846, 3M Fiber LC-LC
D2 Enclosure #2 S2 (10/25GigE) P2 Fabsw 1b 6 15R8846, 3M Fiber LC-LC
D2 Enclosure #2 S2 (10/25GigE) P1 Fabsw 1a 6 15R8846, 3M Fiber LC-LC
D2 Enclosure #2 S1 (10/25GigE) P2 Fabsw 1b 5 15R8846, 3M Fiber LC-LC
D2 Enclosure #2 S1 (10/25GigE) P1 Fabsw 1a 5 15R8846, 3M Fiber LC-LC
D2 Enclosure #1 S4 (10/25GigE) P2 Fabsw 1b 4 15R8846, 3M Fiber LC-LC
D2 Enclosure #1 S4 (10/25GigE) P1 Fabsw 1a 4 15R8846, 3M Fiber LC-LC
D2 Enclosure #1 S3 (10/25GigE) P2 Fabsw 1b 3 15R8846, 3M Fiber LC-LC
D2 Enclosure #1 S3 (10/25GigE) P1 Fabsw 1a 3 15R8846, 3M Fiber LC-LC
D2 Enclosure #1 S2 (10/25GigE) P2 Fabsw 1b 2 15R8846, 3M Fiber LC-LC
D2 Enclosure #1 S2 (10/25GigE) P1 Fabsw 1a 2 15R8846, 3M Fiber LC-LC
D2 Enclosure #1 S1 (10/25GigE) P2 Fabsw 1b 1 15R8846, 3M Fiber LC-LC
D2 Enclosure #1 S1 (10/25GigE) P1 Fabsw 1a 1 15R8846, 3M Fiber LC-LC
Fabsw 1a N/A 44 Fabsw 1b 44 01FT735, 0.5M 25Gb/s SFP28 ISL
Fabsw 1a N/A 43 Fabsw 1b 43 01FT735, 0.5M 25Gb/s SFP28 ISL
SFP DACs
Fabsw 1a N/A 42 Fabsw 1b 42 01FT735, 0.5M 25Gb/s SFP28 ISL
Fabsw 1a N/A 41 Fabsw 1b 41 01FT735, 0.5M 25Gb/s SFP28 ISL

Page 4
Rack 1 (Base+ 2)

Edge-Core AS4610-54T 1G Ethernet Management Switch 1a Connections.


From To
ID Component PCI Slot Port ID Component Port Harness Color
Fabsw 1b MGMT P0 Mgtsw 1a 46 Cat6 7' Blue- 00J1691
Fabsw 1a MGMT P0 Mgtsw 1a 47 Cat6 7' Blue- 00J1691
D2 Enclosure #4 EIOM Node 4 P1 Mgtsw 1a 20 01AF040, 3m Blue
D2 Enclosure #4 EIOM Node 3 P1 Mgtsw 1a 19 01AF040, 3m Blue
D2 Enclosure #4 EIOM Node 2 P1 Mgtsw 1a 18 01AF040, 3m Blue
D2 Enclosure #4 EIOM Node 1 P1 Mgtsw 1a 17 01AF040, 3m Blue
D2 Enclosure #4 SMM P1 Mgtsw 1a 16 01AF040, 3m Blue
D2 Enclosure #3 EIOM Node 4 P1 Mgtsw 1a 15 01AF040, 3m Blue
D2 Enclosure #3 EIOM Node 3 P1 Mgtsw 1a 14 01AF040, 3m Blue
D2 Enclosure #3 EIOM Node 2 P1 Mgtsw 1a 13 01AF040, 3m Blue
D2 Enclosure #3 EIOM Node 1 P1 Mgtsw 1a 12 01AF040, 3m Blue
D2 Enclosure #3 SMM P1 Mgtsw 1a 11 01AF040, 3m Blue
D2 Enclosure #2 EIOM Node 4 P1 Mgtsw 1a 10 01AF040, 3m Blue
D2 Enclosure #2 EIOM Node 3 P1 Mgtsw 1a 9 01AF040, 3m Blue
D2 Enclosure #2 EIOM Node 2 P1 Mgtsw 1a 8 01AF040, 3m Blue
D2 Enclosure #2 EIOM Node 1 P1 Mgtsw 1a 7 01AF040, 3m Blue
D2 Enclosure #2 SMM P1 Mgtsw 1a 6 01AF040, 3m Blue
D2 Enclosure #1 EIOM Node 4 P1 Mgtsw 1a 5 01AF040, 3m Blue
D2 Enclosure #1 EIOM Node 3 P1 Mgtsw 1a 4 01AF040, 3m Blue
D2 Enclosure #1 EIOM Node 2 P1 Mgtsw 1a 3 01AF040, 3m Blue
D2 Enclosure #1 EIOM Node 1 P1 Mgtsw 1a 2 01AF040, 3m Blue
D2 Enclosure #1 SMM P1 Mgtsw 1a 1 01AF040, 3m Blue

Edge-Core AS4610-54T 1G Ethernet Management Switch 2a Connections.


From To
ID Component PCI Slot Port ID Component Port Harness Color
Mgtsw 2a N/A MGMT Mgtsw 1a 38 00J1689, 3' Blue
Mgtsw 2a N/A 42 Mgtsw 1a 42 Up Link 01AF044, 0.6m Blue
Mgtsw 2a N/A 41 Mgtsw 1a 41 Up Link 01AF044, 0.6m Blue

System Patch Panel RJ45 1GigE Connections


From To
ID Component Port ID Component Type Connections Length/Type
Mgtsw 1a 48 Patch-panel 1GigE SCP-A Cat6 5' Blue- 00J1690
D2 Enclosure #1 EIOM Node 4 P2 Patch-panel 1GigE ETH3 01AF040, 3m Blue
D2 Enclosure #1 EIOM Node 3 P2 Patch-panel 1GigE ETH2 01AF040, 3m Blue
D2 Enclosure #1 EIOM Node 2 P2 Patch-panel 1GigE ETH1 01AF040, 3m Blue
D2 Enclosure #1 EIOM Node 1 P2 Patch-panel 1GigE ETH0 01AF040, 3m Blue

Patch Panel 10 GigE SFP+ Connections


From To
ID Component Transceiver Port ID Component Type Connections Length/Type
Fabsw 1b P48 Patch-panel 25/10GigE ETH11 15R8846, 3M Fiber LC-LC
Fabsw 1b P47 Patch-panel 25/10GigE ETH10 15R8846, 3M Fiber LC-LC
Fabsw 1b P46 Patch-panel 25/10GigE ETH9 15R8846, 3M Fiber LC-LC
Fabsw 1b P45 Patch-panel 25/10GigE ETH8 15R8846, 3M Fiber LC-LC
77P9336
Fabsw 1a P48 Patch-panel 25/10GigE ETH7 15R8846, 3M Fiber LC-LC
Fabsw 1a P47 Patch-panel 25/10GigE ETH6 15R8846, 3M Fiber LC-LC
Fabsw 1a P46 Patch-panel 25/10GigE ETH5 15R8846, 3M Fiber LC-LC
Fabsw 1a P45 Patch-panel 25/10GigE ETH4 15R8846, 3M Fiber LC-LC

Page 5
Rack 1 (Base+ 4)
Doc Part # 02JE469
ECO#N47076S

ICP4D (Lenovo Base+ 4) 6 Single Phase PDU's NA Version


Fillers: 1U=10, 2U=6, 4U=1
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch 1a and 1b Connections SFP28 Xcvrs with LC - LC Cables Edge-Core AS4610-54T 1G Ethernet Management Switch 1a Connections.
42 From To From To
Cable Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #6 Right 39M5510 C13/C14 4.3m D2 Enclosure #6 S4 (10/25GigE) P2 Fabsw 1b 24 15R8846, 3M Fiber LC-LC Fabsw 1b MGMT P0 Mgtsw 1a 46 Cat6 7' Blue- 00J1691
39 Plug 3 D2 Enclosure #6 S4 (10/25GigE) P1 Fabsw 1a 24 15R8846, 3M Fiber LC-LC Fabsw 1a MGMT P0 Mgtsw 1a 47 Cat6 7' Blue- 00J1691
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #6 S3 (10/25GigE) P2 Fabsw 1b 23 15R8846, 3M Fiber LC-LC D2 Enclosure #5 EIOM Node 4 P1 Mgtsw 1a 25 01AF040, 3m Blue
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #6 S3 (10/25GigE) P1 Fabsw 1a 23 15R8846, 3M Fiber LC-LC D2 Enclosure #5 EIOM Node 3 P1 Mgtsw 1a 24 01AF040, 3m Blue
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #5 Right 39M5510 C13/C14 4.3m D2 Enclosure #6 S2 (10/25GigE) P2 Fabsw 1b 22 15R8846, 3M Fiber LC-LC D2 Enclosure #5 EIOM Node 2 P1 Mgtsw 1a 23 01AF040, 3m Blue
RPC6
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #6 S2 (10/25GigE) P1 Fabsw 1a 22 15R8846, 3M Fiber LC-LC D2 Enclosure #5 EIOM Node 1 P1 Mgtsw 1a 22 01AF040, 3m Blue
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #6 S1 (10/25GigE) P2 Fabsw 1b 21 15R8846, 3M Fiber LC-LC D2 Enclosure #5 SMM P1 Mgtsw 1a 21 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #6 S1 (10/25GigE) P1 Fabsw 1a 21 15R8846, 3M Fiber LC-LC D2 Enclosure #4 EIOM Node 4 P1 Mgtsw 1a 20 01AF040, 3m Blue
32 2U Blank Panel Plug 10 D2 Enclosure #5 S4 (10/25GigE) P2 Fabsw 1b 20 15R8846, 3M Fiber LC-LC D2 Enclosure #4 EIOM Node 3 P1 Mgtsw 1a 19 01AF040, 3m Blue
31 Interface Patch Panel Plug 11 D2 Enclosure #5 S4 (10/25GigE) P1 Fabsw 1a 20 15R8846, 3M Fiber LC-LC D2 Enclosure #4 EIOM Node 2 P1 Mgtsw 1a 18 01AF040, 3m Blue
30 1U Blank Panel Plug 12 D2 Enclosure #5 S3 (10/25GigE) P2 Fabsw 1b 19 15R8846, 3M Fiber LC-LC D2 Enclosure #4 EIOM Node 1 P1 Mgtsw 1a 17 01AF040, 3m Blue
29 Management Swt 2A – Edge-Core w/Air Duct D2 Enclosure #5 S3 (10/25GigE) P1 Fabsw 1a 19 15R8846, 3M Fiber LC-LC D2 Enclosure #4 SMM P1 Mgtsw 1a 16 01AF040, 3m Blue
28 Management Swt 1A – Edge-Core w/Air Duct D2 Enclosure #5 S2 (10/25GigE) P2 Fabsw 1b 18 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 4 P1 Mgtsw 1a 15 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #5 S2 (10/25GigE) P1 Fabsw 1a 18 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 3 P1 Mgtsw 1a 14 01AF040, 3m Blue
26 Fabric Switch 1B – Mellanox w/Air Duct D2 Enclosure #5 S1 (10/25GigE) P2 Fabsw 1b 17 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 2 P1 Mgtsw 1a 13 01AF040, 3m Blue
25 Fabric Switch 1A – Mellanox w/Air Duct Plug 1 D2 Enclosure #5 S1 (10/25GigE) P1 Fabsw 1a 17 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 1 P1 Mgtsw 1a 12 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #6 Left 39M5510 C13/C14 4.3m D2 Enclosure #4 S4 (10/25GigE) P2 Fabsw 1b 16 15R8846, 3M Fiber LC-LC D2 Enclosure #3 SMM P1 Mgtsw 1a 11 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #4 S4 (10/25GigE) P1 Fabsw 1a 16 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 4 P1 Mgtsw 1a 10 01AF040, 3m Blue
2U Blank Panel
22 Plug 4 D2 Enclosure #4 S3 (10/25GigE) P2 Fabsw 1b 15 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 3 P1 Mgtsw 1a 9 01AF040, 3m Blue
21 Plug 5 D2 Enclosure #4 S3 (10/25GigE) P1 Fabsw 1a 15 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 2 P1 Mgtsw 1a 8 01AF040, 3m Blue
2U Blank Panel
20 Plug 6 D2 Enclosure #5 Left 39M5510 C13/C14 4.3m D2 Enclosure #4 S2 (10/25GigE) P2 Fabsw 1b 14 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 1 P1 Mgtsw 1a 7 01AF040, 3m Blue
RPC5
19 1U Blank Panel Plug 7 D2 Enclosure #4 S2 (10/25GigE) P1 Fabsw 1a 14 15R8846, 3M Fiber LC-LC D2 Enclosure #2 SMM P1 Mgtsw 1a 6 01AF040, 3m Blue
18 Plug 8 D2 Enclosure #4 S1 (10/25GigE) P2 Fabsw 1b 13 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 4 P1 Mgtsw 1a 5 01AF040, 3m Blue
D2 Enclosure #6 SD530 Nodes 1-4 (+ 4)
17 Plug 9 D2 Enclosure #4 S1 (10/25GigE) P1 Fabsw 1a 13 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 3 P1 Mgtsw 1a 4 01AF040, 3m Blue
78P5153 Qty 96
16 1U Blank Panel Plug 10 D2 Enclosure #3 S4 (10/25GigE) P2 Fabsw 1b 12 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 2 P1 Mgtsw 1a 3 01AF040, 3m Blue
15 Plug 11 D2 Enclosure #3 S4 (10/25GigE) P1 Fabsw 1a 12 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 1 P1 Mgtsw 1a 2 01AF040, 3m Blue
D2 Enclosure #5 SD530 Nodes 1-4 (+ 3)
14 Plug 12 D2 Enclosure #3 S3 (10/25GigE) P2 Fabsw 1b 11 15R8846, 3M Fiber LC-LC D2 Enclosure #1 SMM P1 Mgtsw 1a 1 01AF040, 3m Blue
13 1U Blank Panel D2 Enclosure #3 S3 (10/25GigE) P1 Fabsw 1a 11 15R8846, 3M Fiber LC-LC
12 D2 Enclosure #3 S2 (10/25GigE) P2 Fabsw 1b 10 15R8846, 3M Fiber LC-LC
D2 Enclosure #4 SD530 Nodes 1-4 (+ 2)
11 Right Side Power from Rear D2 Enclosure #3 S2 (10/25GigE) P1 Fabsw 1a 10 15R8846, 3M Fiber LC-LC Edge-Core AS4610-54T 1G Ethernet Management Switch 2a Connections.
10 1U Blank Panel D2 Enclosure #3 S1 (10/25GigE) P2 Fabsw 1b 9 15R8846, 3M Fiber LC-LC From To
9 Plug 1 D2 Enclosure #3 S1 (10/25GigE) P1 Fabsw 1a 9 15R8846, 3M Fiber LC-LC ID Component PCI Slot Port ID Component Port Harness Color
D2 Enclosure #3 SD530 Nodes 1-4 (+ 1)
8 Plug 2 D2 Enclosure #2 S4 (10/25GigE) P2 Fabsw 1b 8 15R8846, 3M Fiber LC-LC D2 Enclosure #6 EIOM Node 4 P1 Mgtsw 2a 5 01AF040, 3m Blue
7 1U Blank Panel Plug 3 D2 Enclosure #2 S4 (10/25GigE) P1 Fabsw 1a 8 15R8846, 3M Fiber LC-LC D2 Enclosure #6 EIOM Node 3 P1 Mgtsw 2a 4 01AF040, 3m Blue
6 Plug 4 D2 Enclosure #3 Right 39M5510 C13/C14 4.3m D2 Enclosure #2 S3 (10/25GigE) P2 Fabsw 1b 7 15R8846, 3M Fiber LC-LC D2 Enclosure #6 EIOM Node 2 P1 Mgtsw 2a 3 01AF040, 3m Blue
D2 Enclosure #2 SD530 Nodes 1-4 (Base)
5 Plug 5 D2 Enclosure #2 S3 (10/25GigE) P1 Fabsw 1a 7 15R8846, 3M Fiber LC-LC D2 Enclosure #6 EIOM Node 1 P1 Mgtsw 2a 2 01AF040, 3m Blue
4 1U Blank Panel Plug 6 D2 Enclosure #2 S2 (10/25GigE) P2 Fabsw 1b 6 15R8846, 3M Fiber LC-LC D2 Enclosure #6 SMM P1 Mgtsw 2a 1 01AF040, 3m Blue
RPC4
3 Plug 7 D2 Enclosure #2 S2 (10/25GigE) P1 Fabsw 1a 6 15R8846, 3M Fiber LC-LC Mgtsw 2a N/A MGMT Mgtsw 1a 38 00J1689, 3' Blue
D2 Enclosure #1 SD530 Nodes 1-4 (Base)
2 Plug 8 D2 Enclosure #2 S1 (10/25GigE) P2 Fabsw 1b 5 15R8846, 3M Fiber LC-LC Mgtsw 2a N/A 42 Mgtsw 1a 42 Up Link 01AF044, 0.6m Blue
1 1U Blank Panel Plug 9 D2 Enclosure #2 S1 (10/25GigE) P1 Fabsw 1a 5 15R8846, 3M Fiber LC-LC Mgtsw 2a N/A 41 Mgtsw 1a 41 Up Link 01AF044, 0.6m Blue
Plug 10 D2 Enclosure #4 Right 39M5510 C13/C14 4.3m D2 Enclosure #1 S4 (10/25GigE) P2 Fabsw 1b 4 15R8846, 3M Fiber LC-LC
Plug 11 D2 Enclosure #1 S4 (10/25GigE) P1 Fabsw 1a 4 15R8846, 3M Fiber LC-LC
Plug 12 D2 Enclosure #1 S3 (10/25GigE) P2 Fabsw 1b 3 15R8846, 3M Fiber LC-LC System Patch Panel RJ45 1GigE Connections
Rack 1 (Base+ 4) D2 Enclosure #1 S3 (10/25GigE) P1 Fabsw 1a 3 15R8846, 3M Fiber LC-LC From To
D2 Enclosure #1 S2 (10/25GigE) P2 Fabsw 1b 2 15R8846, 3M Fiber LC-LC ID Component Port ID Component Type Connections Length/Type
Left Side Power from Rear D2 Enclosure #1 S2 (10/25GigE) P1 Fabsw 1a 2 15R8846, 3M Fiber LC-LC Mgtsw 1a 48 Patch-panel 1GigE SCP-A Cat6 5' Blue- 00J1690
D2 Enclosure #1 S1 (10/25GigE) P2 Fabsw 1b 1 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 4 P2 Patch-panel 1GigE ETH3 01AF040, 3m Blue
Plug 1 D2 Enclosure #1 S1 (10/25GigE) P1 Fabsw 1a 1 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 3 P2 Patch-panel 1GigE ETH2 01AF040, 3m Blue
Plug 2 Fabsw 1a N/A 44 Fabsw 1b 44 01FT735, 0.5M 25Gb/s SFP28 ISL D2 Enclosure #1 EIOM Node 2 P2 Patch-panel 1GigE ETH1 01AF040, 3m Blue
Plug 3 Fabsw 1a N/A 43 Fabsw 1b 43 01FT735, 0.5M 25Gb/s SFP28 ISL D2 Enclosure #1 EIOM Node 1 P2 Patch-panel 1GigE ETH0 01AF040, 3m Blue
SFP DACs
Plug 4 D2 Enclosure #3 Left 39M5510 C13/C14 4.3m Fabsw 1a N/A 42 Fabsw 1b 42 01FT735, 0.5M 25Gb/s SFP28 ISL
Plug 5 Fabsw 1a N/A 41 Fabsw 1b 41 01FT735, 0.5M 25Gb/s SFP28 ISL
Plug 6 Patch Panel 10 GigE SFP+ Connections
RPC3
Plug 7 From To
Plug 8 ID Component Transceiver Port ID Component Type Connections Length/Type
Plug 9 Fabsw 1b P48 Patch-panel 25/10GigE ETH11 15R8846, 3M Fiber LC-LC
Plug 10 D2 Enclosure #4 Left 39M5510 C13/C14 4.3m Fabsw 1b P47 Patch-panel 25/10GigE ETH10 15R8846, 3M Fiber LC-LC
Plug 11 Fabsw 1b P46 Patch-panel 25/10GigE ETH9 15R8846, 3M Fiber LC-LC
Plug 12 Fabsw 1b P45 Patch-panel 25/10GigE ETH8 15R8846, 3M Fiber LC-LC
77P9336
Fabsw 1a P48 Patch-panel 25/10GigE ETH7 15R8846, 3M Fiber LC-LC
Fabsw 1a P47 Patch-panel 25/10GigE ETH6 15R8846, 3M Fiber LC-LC
Right Side Power from Rear Fabsw 1a P46 Patch-panel 25/10GigE ETH5 15R8846, 3M Fiber LC-LC
Fabsw 1a P45 Patch-panel 25/10GigE ETH4 15R8846, 3M Fiber LC-LC
Plug 1 Mgtsw 1a Right 39M5509 C13/C14 2.8m
Plug 2
Plug 3 Fabsw 1b Right 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 1a Right 39M5509 C13/C14 2.8m
Plug 6
RPC2
Plug 7 Mgtsw 2a Right 39M5509 C13/C14 2.8m
Plug 8 D2 Enclosure #2 Right 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #1 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1 Mgtsw 1a Left 39M5509 C13/C14 2.8m


Plug 2
Plug 3 Fabsw 1b Left 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 1a Left 39M5509 C13/C14 2.8m
Plug 6
RPC1
Plug 7 Mgtsw 2a Left 39M5509 C13/C14 2.8m
Plug 8 D2 Enclosure #2 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #1 Left 39M5510 C13/C14 4.3m

Page 6
Rack 1 Enclosures 1 - 5 (Multi

Doc Part # 02JE469


ECO#N47076S

ICP4D (Lenovo Based) 6 Single Phase PDU's NA Version (Multi Rack)


Fillers: 1U=10, 2U=7, 4U=1
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch 1a and 1b Connections SFP28 Xcvrs with LC - LC Cables Edge-Core AS4610-54T 1G Ethernet Management Switch 1a Connections.
42 From To From To
Cable Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #5 S4 (10/25GigE) P2 Fabsw 1b 20 15R8846, 3M Fiber LC-LC Fabsw 1b MGMT P0 Mgtsw 1a 46 Cat6 7' Blue- 00J1691
39 Plug 3 D2 Enclosure #5 S4 (10/25GigE) P1 Fabsw 1a 20 15R8846, 3M Fiber LC-LC Fabsw 1a MGMT P0 Mgtsw 1a 47 Cat6 7' Blue- 00J1691
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #5 S3 (10/25GigE) P2 Fabsw 1b 19 15R8846, 3M Fiber LC-LC Strgw2 Integrated LOM P1 Mgtsw 1a 29 Cat6 7' Blue- 00J1691
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #5 S3 (10/25GigE) P1 Fabsw 1a 19 15R8846, 3M Fiber LC-LC Strgw2 BMC Mgmt Mgtsw 1a 28 Cat6 7' Blue- 00J1691
Optional Storage Gateway
SR650 # 1 and 2 ,
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #5 Right 39M5510 C13/C14 4.3m D2 Enclosure #5 S2 (10/25GigE) P2 Fabsw 1b 18 15R8846, 3M Fiber LC-LC Strgw1 Integrated LOM P1 Mgtsw 1a 27 Cat6 7' Blue- 00J1691
RPC6 Management Connections
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #5 S2 (10/25GigE) P1 Fabsw 1a 18 15R8846, 3M Fiber LC-LC Strgw1 BMC Mgmt Mgtsw 1a 26 Cat6 7' Blue- 00J1691
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #5 S1 (10/25GigE) P2 Fabsw 1b 17 15R8846, 3M Fiber LC-LC D2 Enclosure #5 EIOM Node 4 P1 Mgtsw 1a 25 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #5 S1 (10/25GigE) P1 Fabsw 1a 17 15R8846, 3M Fiber LC-LC D2 Enclosure #5 EIOM Node 3 P1 Mgtsw 1a 24 01AF040, 3m Blue
32 2U Blank Panel Plug 10 D2 Enclosure #4 S4 (10/25GigE) P2 Fabsw 1b 16 15R8846, 3M Fiber LC-LC D2 Enclosure #5 EIOM Node 2 P1 Mgtsw 1a 23 01AF040, 3m Blue
31 Interface Patch Panel Plug 11 D2 Enclosure #4 S4 (10/25GigE) P1 Fabsw 1a 16 15R8846, 3M Fiber LC-LC D2 Enclosure #5 EIOM Node 1 P1 Mgtsw 1a 22 01AF040, 3m Blue
30 1U Blank Panel Plug 12 D2 Enclosure #4 S3 (10/25GigE) P2 Fabsw 1b 15 15R8846, 3M Fiber LC-LC D2 Enclosure #5 SMM P1 Mgtsw 1a 21 01AF040, 3m Blue
29 Management Swt 2A – Edge-Core w/Air Duct D2 Enclosure #4 S3 (10/25GigE) P1 Fabsw 1a 15 15R8846, 3M Fiber LC-LC D2 Enclosure #4 EIOM Node 4 P1 Mgtsw 1a 20 01AF040, 3m Blue
28 Management Swt 1A – Edge-Core w/Air Duct D2 Enclosure #4 S2 (10/25GigE) P2 Fabsw 1b 14 15R8846, 3M Fiber LC-LC D2 Enclosure #4 EIOM Node 3 P1 Mgtsw 1a 19 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #4 S2 (10/25GigE) P1 Fabsw 1a 14 15R8846, 3M Fiber LC-LC D2 Enclosure #4 EIOM Node 2 P1 Mgtsw 1a 18 01AF040, 3m Blue
26 Fabric Switch 1B – Mellanox w/Air Duct D2 Enclosure #4 S1 (10/25GigE) P2 Fabsw 1b 13 15R8846, 3M Fiber LC-LC D2 Enclosure #4 EIOM Node 1 P1 Mgtsw 1a 17 01AF040, 3m Blue
25 Fabric Switch 1A – Mellanox w/Air Duct Plug 1 D2 Enclosure #4 S1 (10/25GigE) P1 Fabsw 1a 13 15R8846, 3M Fiber LC-LC D2 Enclosure #4 SMM P1 Mgtsw 1a 16 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #3 S4 (10/25GigE) P2 Fabsw 1b 12 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 4 P1 Mgtsw 1a 15 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #3 S4 (10/25GigE) P1 Fabsw 1a 12 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 3 P1 Mgtsw 1a 14 01AF040, 3m Blue
Storage Gateway 2 SR650 (Optional) or 2U Blank Panel
22 Plug 4 D2 Enclosure #3 S3 (10/25GigE) P2 Fabsw 1b 11 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 2 P1 Mgtsw 1a 13 01AF040, 3m Blue
21 Plug 5 D2 Enclosure #3 S3 (10/25GigE) P1 Fabsw 1a 11 15R8846, 3M Fiber LC-LC D2 Enclosure #3 EIOM Node 1 P1 Mgtsw 1a 12 01AF040, 3m Blue
Storage Gateway 1 SR650 (Optional) or 2U Blank Panel 78P5153 Qty 80
20 Plug 6 D2 Enclosure #5 Left 39M5510 C13/C14 4.3m D2 Enclosure #3 S2 (10/25GigE) P2 Fabsw 1b 10 15R8846, 3M Fiber LC-LC D2 Enclosure #3 SMM P1 Mgtsw 1a 11 01AF040, 3m Blue
RPC5
19 1U Blank Panel Plug 7 D2 Enclosure #3 S2 (10/25GigE) P1 Fabsw 1a 10 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 4 P1 Mgtsw 1a 10 01AF040, 3m Blue
18 Plug 8 D2 Enclosure #3 S1 (10/25GigE) P2 Fabsw 1b 9 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 3 P1 Mgtsw 1a 9 01AF040, 3m Blue
2U Blank Panel
17 Plug 9 D2 Enclosure #3 S1 (10/25GigE) P1 Fabsw 1a 9 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 2 P1 Mgtsw 1a 8 01AF040, 3m Blue
16 1U Blank Panel Plug 10 D2 Enclosure #2 S4 (10/25GigE) P2 Fabsw 1b 8 15R8846, 3M Fiber LC-LC D2 Enclosure #2 EIOM Node 1 P1 Mgtsw 1a 7 01AF040, 3m Blue
15 Plug 11 D2 Enclosure #2 S4 (10/25GigE) P1 Fabsw 1a 8 15R8846, 3M Fiber LC-LC D2 Enclosure #2 SMM P1 Mgtsw 1a 6 01AF040, 3m Blue
D2 Enclosure #5 SD530 Nodes 1-4 (+ 3)
14 Plug 12 D2 Enclosure #2 S3 (10/25GigE) P2 Fabsw 1b 7 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 4 P1 Mgtsw 1a 5 01AF040, 3m Blue
13 1U Blank Panel D2 Enclosure #2 S3 (10/25GigE) P1 Fabsw 1a 7 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 3 P1 Mgtsw 1a 4 01AF040, 3m Blue
12 D2 Enclosure #2 S2 (10/25GigE) P2 Fabsw 1b 6 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 2 P1 Mgtsw 1a 3 01AF040, 3m Blue
D2 Enclosure #4 SD530 Nodes 1-4 (+ 2)
11 Right Side Power from Rear D2 Enclosure #2 S2 (10/25GigE) P1 Fabsw 1a 6 15R8846, 3M Fiber LC-LC D2 Enclosure #1 EIOM Node 1 P1 Mgtsw 1a 2 01AF040, 3m Blue
10 1U Blank Panel D2 Enclosure #2 S1 (10/25GigE) P2 Fabsw 1b 5 15R8846, 3M Fiber LC-LC D2 Enclosure #1 SMM P1 Mgtsw 1a 1 01AF040, 3m Blue
9 Plug 1 D2 Enclosure #2 S1 (10/25GigE) P1 Fabsw 1a 5 15R8846, 3M Fiber LC-LC
D2 Enclosure #3 SD530 Nodes 1-4 (+ 1)
8 Plug 2 Strgw2 Right 39M5509 C13/C14 2.8m D2 Enclosure #1 S4 (10/25GigE) P2 Fabsw 1b 4 15R8846, 3M Fiber LC-LC
7 1U Blank Panel Plug 3 D2 Enclosure #1 S4 (10/25GigE) P1 Fabsw 1a 4 15R8846, 3M Fiber LC-LC Edge-Core AS4610-54T 1G Ethernet Management Switch 2a Connections.
6 Plug 4 D2 Enclosure #3 Right 39M5510 C13/C14 4.3m D2 Enclosure #1 S3 (10/25GigE) P2 Fabsw 1b 3 15R8846, 3M Fiber LC-LC From To
D2 Enclosure #2 SD530 Nodes 1-4 (Base)
5 Plug 5 D2 Enclosure #1 S3 (10/25GigE) P1 Fabsw 1a 3 15R8846, 3M Fiber LC-LC ID Component PCI Slot Port ID Component Port Harness Color
4 1U Blank Panel Plug 6 D2 Enclosure #1 S2 (10/25GigE) P2 Fabsw 1b 2 15R8846, 3M Fiber LC-LC Mgtsw 2a N/A MGMT Mgtsw 1a 38 00J1689, 3' Blue
RPC4
3 Plug 7 D2 Enclosure #1 S2 (10/25GigE) P1 Fabsw 1a 2 15R8846, 3M Fiber LC-LC Mgtsw 2a N/A 42 Mgtsw 1a 42 Up Link 01AF044, 0.6m Blue
D2 Enclosure #1 SD530 Nodes 1-4 (Base)
2 Plug 8 D2 Enclosure #1 S1 (10/25GigE) P2 Fabsw 1b 1 15R8846, 3M Fiber LC-LC Mgtsw 2a N/A 41 Mgtsw 1a 41 Up Link 01AF044, 0.6m Blue
1 1U Blank Panel Plug 9 D2 Enclosure #1 S1 (10/25GigE) P1 Fabsw 1a 1 15R8846, 3M Fiber LC-LC
Plug 10 D2 Enclosure #4 Right 39M5510 C13/C14 4.3m Fabsw 1a N/A 44 Fabsw 1b 44 01FT735, 0.5M 25Gb/s SFP28 ISL
Plug 11 Fabsw 1a N/A 43 Fabsw 1b 43 01FT735, 0.5M 25Gb/s SFP28 ISL
SFP DACs
Plug 12 Fabsw 1a N/A 42 Fabsw 1b 42 01FT735, 0.5M 25Gb/s SFP28 ISL
Rack 1 (Base+ 3) Fabsw 1a N/A 41 Fabsw 1b 41 01FT735, 0.5M 25Gb/s SFP28 ISL
Strgw2 S5 (100GigE) P2 Fabsw 1b 50
Left Side Power from Rear Strgw2 S5 (100GigE) P1 Fabsw 1a 50 Optional Storage Gateway SR650 # 1
01AF722, 3M 100Gb/s QSFP28 AOC QSFP 28 AOCs
Strgw1 S5 (100GigE) P2 Fabsw 1b 49 and 2, Fabric Connections
Plug 1 Strgw1 S5 (100GigE) P1 Fabsw 1a 49

Note: Storage Gateway (SR650) will reside with Spine Switch in Plug 2 Strgw2 Left 39M5509 C13/C14 2.8m
rack 3 when systems larger than 2 racks are ordered. Plug 3 System Patch Panel RJ45 1GigE Connections
Plug 4 D2 Enclosure #3 Left 39M5510 C13/C14 4.3m From To
Plug 5 ID Component Port ID Component Type Connections Length/Type
Plug 6 Mgtsw 1a 48 Patch-panel 1GigE SCP-A Cat6 5' Blue- 00J1690
RPC3
Plug 7 D2 Enclosure #1 EIOM Node 4 P2 Patch-panel 1GigE ETH3 01AF040, 3m Blue
Plug 8 D2 Enclosure #1 EIOM Node 3 P2 Patch-panel 1GigE ETH2 01AF040, 3m Blue
Plug 9 D2 Enclosure #1 EIOM Node 2 P2 Patch-panel 1GigE ETH1 01AF040, 3m Blue
Plug 10 D2 Enclosure #4 Left 39M5510 C13/C14 4.3m D2 Enclosure #1 EIOM Node 1 P2 Patch-panel 1GigE ETH0 01AF040, 3m Blue
Plug 11
Plug 12
Patch Panel 10 GigE SFP+ Connections
From To
Right Side Power from Rear ID Component Transceiver Port ID Component Type Connections Length/Type
Fabsw 1b P48 Patch-panel 25/10GigE ETH11 15R8846, 3M Fiber LC-LC
Plug 1 Mgtsw 1a Right 39M5509 C13/C14 2.8m Fabsw 1b P47 Patch-panel 25/10GigE ETH10 15R8846, 3M Fiber LC-LC
Plug 2 Fabsw 1b P46 Patch-panel 25/10GigE ETH9 15R8846, 3M Fiber LC-LC
Plug 3 Fabsw 1b Right 39M5509 C13/C14 2.8m Fabsw 1b P45 Patch-panel 25/10GigE ETH8 15R8846, 3M Fiber LC-LC
77P9336
Plug 4 Fabsw 1a P48 Patch-panel 25/10GigE ETH7 15R8846, 3M Fiber LC-LC
Plug 5 Fabsw 1a Right 39M5509 C13/C14 2.8m Fabsw 1a P47 Patch-panel 25/10GigE ETH6 15R8846, 3M Fiber LC-LC
Plug 6 Fabsw 1a P46 Patch-panel 25/10GigE ETH5 15R8846, 3M Fiber LC-LC
RPC2
Plug 7 Mgtsw 2a Right 39M5509 C13/C14 2.8m Fabsw 1a P45 Patch-panel 25/10GigE ETH4 15R8846, 3M Fiber LC-LC
Plug 8 D2 Enclosure #2 Right 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11 Strgw1 Right 39M5509 C13/C14 2.8m
Plug 12 D2 Enclosure #1 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1 Mgtsw 1a Left 39M5509 C13/C14 2.8m


Plug 2
Plug 3 Fabsw 1b Left 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 1a Left 39M5509 C13/C14 2.8m
Plug 6
RPC1
Plug 7 Mgtsw 2a Left 39M5509 C13/C14 2.8m
Plug 8 D2 Enclosure #2 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11 Strgw1 Left 39M5509 C13/C14 2.8m
Plug 12 D2 Enclosure #1 Left 39M5510 C13/C14 4.3m

Page 7
Rack 2 Enclosures 6 -10 (Multi

Doc Part # 02JE469


ECO#N47076S

ICP4D (Lenovo Based) 6 Single Phase PDU's NA Version (Multi Rack)


Fillers: 1U=10, 2U=3, 4U=4
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch 1a and 1b Connections SFP28 Xcvrs with LC - LC Cables Edge-Core AS4610-54T 1G Ethernet Management Switch 2a Connections.
42 From To From To
Harness Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #10 S4 (10/25GigE) P2 Fabsw 1b 40 45D4774, 5M Fiber LC-LC D2 Enclosure #10 EIOM Node 4 P1 Mgtsw 2a 25 02CL468, 5M Blue
39 Plug 3 D2 Enclosure #10 S4 (10/25GigE) P1 Fabsw 1a 40 45D4774, 5M Fiber LC-LC D2 Enclosure #10 EIOM Node 3 P1 Mgtsw 2a 24 02CL468, 5M Blue
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #10 S3 (10/25GigE) P2 Fabsw 1b 39 45D4774, 5M Fiber LC-LC D2 Enclosure #10 EIOM Node 2 P1 Mgtsw 2a 23 02CL468, 5M Blue
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #10 S3 (10/25GigE) P1 Fabsw 1a 39 45D4774, 5M Fiber LC-LC D2 Enclosure #10 EIOM Node 1 P1 Mgtsw 2a 22 02CL468, 5M Blue
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #10 Right 39M5510 C13/C14 4.3m D2 Enclosure #10 S2 (10/25GigE) P2 Fabsw 1b 38 45D4774, 5M Fiber LC-LC D2 Enclosure #10 SMM P1 Mgtsw 2a 21 02CL468, 5M Blue
RPC6
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #10 S2 (10/25GigE) P1 Fabsw 1a 38 45D4774, 5M Fiber LC-LC D2 Enclosure #9 EIOM Node 4 P1 Mgtsw 2a 20 02CL468, 5M Blue
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #10 S1 (10/25GigE) P2 Fabsw 1b 37 45D4774, 5M Fiber LC-LC D2 Enclosure #9 EIOM Node 3 P1 Mgtsw 2a 19 02CL468, 5M Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #10 S1 (10/25GigE) P1 Fabsw 1a 37 45D4774, 5M Fiber LC-LC D2 Enclosure #9 EIOM Node 2 P1 Mgtsw 2a 18 02CL468, 5M Blue
32 Plug 10 D2 Enclosure #9 S4 (10/25GigE) P2 Fabsw 1b 36 45D4774, 5M Fiber LC-LC D2 Enclosure #9 EIOM Node 1 P1 Mgtsw 2a 17 02CL468, 5M Blue
31 Plug 11 D2 Enclosure #9 S4 (10/25GigE) P1 Fabsw 1a 36 45D4774, 5M Fiber LC-LC D2 Enclosure #9 SMM P1 Mgtsw 2a 16 02CL468, 5M Blue
4U Blank Panel
30 Plug 12 D2 Enclosure #9 S3 (10/25GigE) P2 Fabsw 1b 35 45D4774, 5M Fiber LC-LC D2 Enclosure #8 EIOM Node 4 P1 Mgtsw 2a 15 02CL468, 5M Blue
29 D2 Enclosure #9 S3 (10/25GigE) P1 Fabsw 1a 35 45D4774, 5M Fiber LC-LC D2 Enclosure #8 EIOM Node 3 P1 Mgtsw 2a 14 02CL468, 5M Blue
28 1U Blank Panel D2 Enclosure #9 S2 (10/25GigE) P2 Fabsw 1b 34 45D4774, 5M Fiber LC-LC D2 Enclosure #8 EIOM Node 2 P1 Mgtsw 2a 13 02CL468, 5M Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #9 S2 (10/25GigE) P1 Fabsw 1a 34 45D4774, 5M Fiber LC-LC D2 Enclosure #8 EIOM Node 1 P1 Mgtsw 2a 12 02CL468, 5M Blue
26 1U Blank Panel D2 Enclosure #9 S1 (10/25GigE) P2 Fabsw 1b 33 45D4774, 5M Fiber LC-LC D2 Enclosure #8 SMM P1 Mgtsw 2a 11 02CL468, 5M Blue
25 1U Blank Panel Plug 1 D2 Enclosure #9 S1 (10/25GigE) P1 Fabsw 1a 33 45D4774, 5M Fiber LC-LC D2 Enclosure #7 EIOM Node 4 P1 Mgtsw 2a 10 02CL468, 5M Blue
24 1U Blank Panel Plug 2 D2 Enclosure #8 S4 (10/25GigE) P2 Fabsw 1b 32 45D4774, 5M Fiber LC-LC D2 Enclosure #7 EIOM Node 3 P1 Mgtsw 2a 9 02CL468, 5M Blue
23 Plug 3 D2 Enclosure #8 S4 (10/25GigE) P1 Fabsw 1a 32 45D4774, 5M Fiber LC-LC D2 Enclosure #7 EIOM Node 2 P1 Mgtsw 2a 8 02CL468, 5M Blue
22 Plug 4 D2 Enclosure #8 S3 (10/25GigE) P2 Fabsw 1b 31 45D4774, 5M Fiber LC-LC D2 Enclosure #7 EIOM Node 1 P1 Mgtsw 2a 7 02CL468, 5M Blue
4U Blank Panel
21 Plug 5 D2 Enclosure #8 S3 (10/25GigE) P1 Fabsw 1a 31 45D4774, 5M Fiber LC-LC D2 Enclosure #7 SMM P1 Mgtsw 2a 6 02CL468, 5M Blue
78P5153 Qty 80
20 Plug 6 D2 Enclosure #10 Left 39M5510 C13/C14 4.3m D2 Enclosure #8 S2 (10/25GigE) P2 Fabsw 1b 30 45D4774, 5M Fiber LC-LC D2 Enclosure #6 EIOM Node 4 P1 Mgtsw 2a 5 02CL468, 5M Blue
RPC5
19 Plug 7 D2 Enclosure #8 S2 (10/25GigE) P1 Fabsw 1a 30 45D4774, 5M Fiber LC-LC D2 Enclosure #6 EIOM Node 3 P1 Mgtsw 2a 4 02CL468, 5M Blue
18 Plug 8 D2 Enclosure #8 S1 (10/25GigE) P2 Fabsw 1b 29 45D4774, 5M Fiber LC-LC D2 Enclosure #6 EIOM Node 2 P1 Mgtsw 2a 3 02CL468, 5M Blue
4U Blank Panel
17 Plug 9 D2 Enclosure #8 S1 (10/25GigE) P1 Fabsw 1a 29 45D4774, 5M Fiber LC-LC D2 Enclosure #6 EIOM Node 1 P1 Mgtsw 2a 2 02CL468, 5M Blue
16 Plug 10 D2 Enclosure #7 S4 (10/25GigE) P2 Fabsw 1b 28 45D4774, 5M Fiber LC-LC D2 Enclosure #6 SMM P1 Mgtsw 2a 1 02CL468, 5M Blue
15 Plug 11 D2 Enclosure #7 S4 (10/25GigE) P1 Fabsw 1a 28 45D4774, 5M Fiber LC-LC
D2 Enclosure #10 SD530 Nodes 1-4 (+ 8)
14 Plug 12 D2 Enclosure #7 S3 (10/25GigE) P2 Fabsw 1b 27 45D4774, 5M Fiber LC-LC
13 1U Blank Panel D2 Enclosure #7 S3 (10/25GigE) P1 Fabsw 1a 27 45D4774, 5M Fiber LC-LC
12 D2 Enclosure #7 S2 (10/25GigE) P2 Fabsw 1b 26 45D4774, 5M Fiber LC-LC
D2 Enclosure #9 SD530 Nodes 1-4 (+ 7)
11 Right Side Power from Rear D2 Enclosure #7 S2 (10/25GigE) P1 Fabsw 1a 26 45D4774, 5M Fiber LC-LC
10 1U Blank Panel D2 Enclosure #7 S1 (10/25GigE) P2 Fabsw 1b 25 45D4774, 5M Fiber LC-LC
9 Plug 1 D2 Enclosure #7 S1 (10/25GigE) P1 Fabsw 1a 25 45D4774, 5M Fiber LC-LC
D2 Enclosure #8 SD530 Nodes 1-4 (+ 6)
8 Plug 2 D2 Enclosure #6 S4 (10/25GigE) P2 Fabsw 1b 24 45D4774, 5M Fiber LC-LC
7 1U Blank Panel Plug 3 D2 Enclosure #6 S4 (10/25GigE) P1 Fabsw 1a 24 45D4774, 5M Fiber LC-LC
6 Plug 4 D2 Enclosure #8 Right 39M5510 C13/C14 4.3m D2 Enclosure #6 S3 (10/25GigE) P2 Fabsw 1b 23 45D4774, 5M Fiber LC-LC
D2 Enclosure #7 SD530 Nodes 1-4 (+ 5)
5 Plug 5 D2 Enclosure #6 S3 (10/25GigE) P1 Fabsw 1a 23 45D4774, 5M Fiber LC-LC
4 1U Blank Panel Plug 6 D2 Enclosure #6 S2 (10/25GigE) P2 Fabsw 1b 22 45D4774, 5M Fiber LC-LC
RPC4
3 Plug 7 D2 Enclosure #6 S2 (10/25GigE) P1 Fabsw 1a 22 45D4774, 5M Fiber LC-LC
D2 Enclosure #6 SD530 Nodes 1-4 (+ 4)
2 Plug 8 D2 Enclosure #6 S1 (10/25GigE) P2 Fabsw 1b 21 45D4774, 5M Fiber LC-LC
1 1U Blank Panel Plug 9 D2 Enclosure #6 S1 (10/25GigE) P1 Fabsw 1a 21 45D4774, 5M Fiber LC-LC
Plug 10 D2 Enclosure #9 Right 39M5510 C13/C14 4.3m
Plug 11
Plug 12
Rack 2 (Base+ 8)
Left Side Power from Rear

Plug 1
Plug 2
Plug 3
Plug 4 D2 Enclosure #8 Left 39M5510 C13/C14 4.3m
Plug 5
Plug 6
RPC3
Plug 7
Plug 8
Plug 9
Plug 10 D2 Enclosure #9 Left 39M5510 C13/C14 4.3m
Plug 11
Plug 12

Right Side Power from Rear

Plug 1
Plug 2
Plug 3
Plug 4
Plug 5
Plug 6
RPC2
Plug 7
Plug 8 D2 Enclosure #7 Right 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #6 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1
Plug 2
Plug 3
Plug 4
Plug 5
Plug 6
RPC1
Plug 7
Plug 8 D2 Enclosure #7 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #6 Left 39M5510 C13/C14 4.3m

Page 8
Rack 3 Enclosures 11 - 15 (Mult
Doc Part # 02JE469
ECO#N47076S

ICP4D (Lenovo Based) 6 Single Phase PDU's NA Version (Multi Rack)


Fillers: 1U=8, 2U=5, 4U=2
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch 2a and 2b Connections SFP28 Xcvrs with LC - LC Cables Edge-Core AS4610-54T 1G Ethernet Management Switch 3a Connections.
42 From To Harness From To
Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #15 S4 (10/25GigE) P2 Fabsw 2b 20 15R8846, 3M Fiber LC-LC Fabsw 2b MGMT P0 Mgtsw 3a 46 Cat6 7' Blue- 00J1691
39 Plug 3 D2 Enclosure #15 S4 (10/25GigE) P1 Fabsw 2a 20 15R8846, 3M Fiber LC-LC Fabsw 2a MGMT P0 Mgtsw 3a 47 Cat6 7' Blue- 00J1691
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #15 S3 (10/25GigE) P2 Fabsw 2b 19 15R8846, 3M Fiber LC-LC Spinesw 1b MGMT P0 Mgtsw 3a 45 Cat6 7' Blue- 00J1691
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #15 S3 (10/25GigE) P1 Fabsw 2a 19 15R8846, 3M Fiber LC-LC Spinesw 1a MGMT P0 Mgtsw 3a 44 Cat6 7' Blue- 00J1691
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #15 Right 39M5510 C13/C14 4.3m D2 Enclosure #15 S2 (10/25GigE) P2 Fabsw 2b 18 15R8846, 3M Fiber LC-LC Strgw3 Integrated LOM P1 Mgtsw 3a 27 Cat6 7' Blue- 00J1691 Optional Third Storage Gateway SR650
RPC6
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #15 S2 (10/25GigE) P1 Fabsw 2a 18 15R8846, 3M Fiber LC-LC Strgw3 BMC Mgmt Mgtsw 3a 26 Cat6 7' Blue- 00J1691 Management Connections
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #15 S1 (10/25GigE) P2 Fabsw 2b 17 15R8846, 3M Fiber LC-LC D2 Enclosure #15 EIOM Node 4 P1 Mgtsw 3a 25 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #15 S1 (10/25GigE) P1 Fabsw 2a 17 15R8846, 3M Fiber LC-LC D2 Enclosure #15 EIOM Node 3 P1 Mgtsw 3a 24 01AF040, 3m Blue
32 Hub Swt – Edge-Core w/Air Duct Plug 10 D2 Enclosure #14 S4 (10/25GigE) P2 Fabsw 2b 16 15R8846, 3M Fiber LC-LC D2 Enclosure #15 EIOM Node 2 P1 Mgtsw 3a 23 01AF040, 3m Blue
31 Spine Switch B – Mellanox w/Air Duct Plug 11 D2 Enclosure #14 S4 (10/25GigE) P1 Fabsw 2a 16 15R8846, 3M Fiber LC-LC D2 Enclosure #15 EIOM Node 1 P1 Mgtsw 3a 22 01AF040, 3m Blue
30 Spine Switch A – Mellanox w/Air Duct Plug 12 D2 Enclosure #14 S3 (10/25GigE) P2 Fabsw 2b 15 15R8846, 3M Fiber LC-LC D2 Enclosure #15 SMM P1 Mgtsw 3a 21 01AF040, 3m Blue
29 1U Blank Panel D2 Enclosure #14 S3 (10/25GigE) P1 Fabsw 2a 15 15R8846, 3M Fiber LC-LC D2 Enclosure #14 EIOM Node 4 P1 Mgtsw 3a 20 01AF040, 3m Blue
28 Management Swt 3A – Edge-Core w/Air Duct D2 Enclosure #14 S2 (10/25GigE) P2 Fabsw 2b 14 15R8846, 3M Fiber LC-LC D2 Enclosure #14 EIOM Node 3 P1 Mgtsw 3a 19 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #14 S2 (10/25GigE) P1 Fabsw 2a 14 15R8846, 3M Fiber LC-LC D2 Enclosure #14 EIOM Node 2 P1 Mgtsw 3a 18 01AF040, 3m Blue
26 Fabric Switch 2B – Mellanox w/Air Duct D2 Enclosure #14 S1 (10/25GigE) P2 Fabsw 2b 13 15R8846, 3M Fiber LC-LC D2 Enclosure #14 EIOM Node 1 P1 Mgtsw 3a 17 01AF040, 3m Blue
25 Fabric Switch 2A – Mellanox w/Air Duct Plug 1 D2 Enclosure #14 S1 (10/25GigE) P1 Fabsw 2a 13 15R8846, 3M Fiber LC-LC D2 Enclosure #14 SMM P1 Mgtsw 3a 16 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #13 S4 (10/25GigE) P2 Fabsw 2b 12 15R8846, 3M Fiber LC-LC D2 Enclosure #13 EIOM Node 4 P1 Mgtsw 3a 15 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #13 S4 (10/25GigE) P1 Fabsw 2a 12 15R8846, 3M Fiber LC-LC D2 Enclosure #13 EIOM Node 3 P1 Mgtsw 3a 14 01AF040, 3m Blue
2U Blank Panel
22 Plug 4 D2 Enclosure #13 S3 (10/25GigE) P2 Fabsw 2b 11 15R8846, 3M Fiber LC-LC D2 Enclosure #13 EIOM Node 2 P1 Mgtsw 3a 13 01AF040, 3m Blue
21 Plug 5 D2 Enclosure #13 S3 (10/25GigE) P1 Fabsw 2a 11 15R8846, 3M Fiber LC-LC D2 Enclosure #13 EIOM Node 1 P1 Mgtsw 3a 12 01AF040, 3m Blue
Storage Gateway 3 SR650 (Optional) or 2U Blank Panel 78P5153 Qty 80
20 Plug 6 D2 Enclosure #15 Left 39M5510 C13/C14 4.3m D2 Enclosure #13 S2 (10/25GigE) P2 Fabsw 2b 10 15R8846, 3M Fiber LC-LC D2 Enclosure #13 SMM P1 Mgtsw 3a 11 01AF040, 3m Blue
RPC5
19 Plug 7 D2 Enclosure #13 S2 (10/25GigE) P1 Fabsw 2a 10 15R8846, 3M Fiber LC-LC D2 Enclosure #12 EIOM Node 4 P1 Mgtsw 3a 10 01AF040, 3m Blue
18 Plug 8 D2 Enclosure #13 S1 (10/25GigE) P2 Fabsw 2b 9 15R8846, 3M Fiber LC-LC D2 Enclosure #12 EIOM Node 3 P1 Mgtsw 3a 9 01AF040, 3m Blue
4U Blank Panel
17 Plug 9 D2 Enclosure #13 S1 (10/25GigE) P1 Fabsw 2a 9 15R8846, 3M Fiber LC-LC D2 Enclosure #12 EIOM Node 2 P1 Mgtsw 3a 8 01AF040, 3m Blue
16 Plug 10 D2 Enclosure #12 S4 (10/25GigE) P2 Fabsw 2b 8 15R8846, 3M Fiber LC-LC D2 Enclosure #12 EIOM Node 1 P1 Mgtsw 3a 7 01AF040, 3m Blue
15 Plug 11 D2 Enclosure #12 S4 (10/25GigE) P1 Fabsw 2a 8 15R8846, 3M Fiber LC-LC D2 Enclosure #12 SMM P1 Mgtsw 3a 6 01AF040, 3m Blue
D2 Enclosure #15 SD530 Nodes 1-4 (+ 13)
14 Plug 12 D2 Enclosure #12 S3 (10/25GigE) P2 Fabsw 2b 7 15R8846, 3M Fiber LC-LC D2 Enclosure #11 EIOM Node 4 P1 Mgtsw 3a 5 01AF040, 3m Blue
13 1U Blank Panel D2 Enclosure #12 S3 (10/25GigE) P1 Fabsw 2a 7 15R8846, 3M Fiber LC-LC D2 Enclosure #11 EIOM Node 3 P1 Mgtsw 3a 4 01AF040, 3m Blue
12 D2 Enclosure #12 S2 (10/25GigE) P2 Fabsw 2b 6 15R8846, 3M Fiber LC-LC D2 Enclosure #11 EIOM Node 2 P1 Mgtsw 3a 3 01AF040, 3m Blue
D2 Enclosure #14 SD530 Nodes 1-4 (+ 12)
11 Right Side Power from Rear D2 Enclosure #12 S2 (10/25GigE) P1 Fabsw 2a 6 15R8846, 3M Fiber LC-LC D2 Enclosure #11 EIOM Node 1 P1 Mgtsw 3a 2 01AF040, 3m Blue
10 1U Blank Panel D2 Enclosure #12 S1 (10/25GigE) P2 Fabsw 2b 5 15R8846, 3M Fiber LC-LC D2 Enclosure #11 SMM P1 Mgtsw 3a 1 01AF040, 3m Blue
9 Plug 1 D2 Enclosure #12 S1 (10/25GigE) P1 Fabsw 2a 5 15R8846, 3M Fiber LC-LC Mgtsw 3a N/A MGMT Mgtsw 1a 43 001KL849, 20M Blue 01AF041, 10M Blue (Optional)
D2 Enclosure #13 SD530 Nodes 1-4 (+ 11)
8 Plug 2 D2 Enclosure #11 S4 (10/25GigE) P2 Fabsw 2b 4 15R8846, 3M Fiber LC-LC
7 1U Blank Panel Plug 3 D2 Enclosure #11 S4 (10/25GigE) P1 Fabsw 2a 4 15R8846, 3M Fiber LC-LC
6 Plug 4 D2 Enclosure #13 Right 39M5510 C13/C14 4.3m D2 Enclosure #11 S3 (10/25GigE) P2 Fabsw 2b 3 15R8846, 3M Fiber LC-LC Edge-Core AS4610-54T 1G Ethernet Hub Switch Connections.
D2 Enclosure #12 SD530 Nodes 1-4 (+ 10)
5 Plug 5 D2 Enclosure #11 S3 (10/25GigE) P1 Fabsw 2a 3 15R8846, 3M Fiber LC-LC From To
Standard Cable Optional Cable
4 1U Blank Panel Plug 6 D2 Enclosure #11 S2 (10/25GigE) P2 Fabsw 2b 2 15R8846, 3M Fiber LC-LC ID Component PCI Slot Port ID Component Port Type
RPC4
3 Plug 7 Spinesw b Right 39M5509 C13/C14 2.8m D2 Enclosure #11 S2 (10/25GigE) P1 Fabsw 2a 2 15R8846, 3M Fiber LC-LC Mgtsw 7a N/A 40 Hubsw 41 Uplink 001KL849, 20M Blue 01AF041, 10M Blue
D2 Enclosure #11 SD530 Nodes 1-4 (+ 9)
2 Plug 8 D2 Enclosure #11 S1 (10/25GigE) P2 Fabsw 2b 1 15R8846, 3M Fiber LC-LC Mgtsw 7a N/A 39 Hubsw 42 Uplink 001KL849, 20M Blue 01AF041, 10M Blue
1 1U Blank Panel Plug 9 D2 Enclosure #11 S1 (10/25GigE) P1 Fabsw 2a 1 15R8846, 3M Fiber LC-LC Mgtsw 5a N/A 40 Hubsw 43 Uplink 001KL849, 20M Blue 01AF041, 10M Blue
Plug 10 D2 Enclosure #14 Right 39M5510 C13/C14 4.3m Fabsw 2a N/A 44 Fabsw 2b 44 01FT735, 0.5M 25Gb/s SFP28 DAC Mgtsw 5a N/A 39 Hubsw 44 Uplink 001KL849, 20M Blue 01AF041, 10M Blue
Plug 11 Spinesw a Right 39M5509 C13/C14 2.8m Fabsw 2a N/A 43 Fabsw 2b 43 01FT735, 0.5M 25Gb/s SFP28 DAC Mgtsw 3a N/A 40 Hubsw 45 Uplink 00J1690, 5' Blue
ISL's
Plug 12 Fabsw 2a N/A 42 Fabsw 2b 42 01FT735, 0.5M 25Gb/s SFP28 DAC Mgtsw 3a N/A 39 Hubsw 46 Uplink 00J1690, 5' Blue
Rack 3 (Base+ 13) Fabsw 2a N/A 41 Fabsw 2b 41 01FT735, 0.5M 25Gb/s SFP28 DAC Mgtsw 1a N/A 40 Hubsw 47 Uplink 001KL849, 20M Blue 01AF041, 10M Blue
Mgtsw 1a N/A 39 Hubsw 48 Uplink 001KL849, 20M Blue 01AF041, 10M Blue
Left Side Power from Rear Mgtsw 1a N/A 44 Hubsw MGMT 001KL849, 20M Blue 01AF041, 10M Blue
Note: Storage Gateway #3, (SR650) will reside with Spine Mellanox SN2700 100GigE Spine Switch Connections AOC and DAC QSFP28 Cables
Switch in rack 3.
Plug 1 From To
Rack Standard Cable Optional Cable
Plug 2 ID Component Port ID Component Port
Plug 3 Spinesw b P23 Fabsw 4b P56
Plug 4 D2 Enclosure #13 Left 39M5510 C13/C14 4.3m Spinesw a P23 Fabsw 4b P55
7
Plug 5 Spinesw b P24 Fabsw 4a P56
Plug 6 Spinesw a P24 Fabsw 4a P55 01FT725, 20M 01FT724, 10M 100Gb/s
RPC3
Plug 7 Spinesw b Left 39M5509 C13/C14 2.8m Spinesw b P25 Fabsw 3b P56 100Gb/s QSFP28 AOC QSFP28 AOC

Plug 8 Spinesw a P25 Fabsw 3b P55


5
Plug 9 Spinesw b P26 Fabsw 3a P56
Plug 10 D2 Enclosure #14 Left 39M5510 C13/C14 4.3m Spinesw a P26 Fabsw 3a P55
Plug 11 Spinesw a Left 39M5509 C13/C14 2.8m Spinesw b P27 Fabsw 2b P56
Plug 12 Spinesw a P27 Fabsw 2b P55 01FT722, 3M 100Gb/s
3
Spinesw b P28 Fabsw 2a P56 QSFP28 AOC

Spinesw a P28 Fabsw 2a P55


Right Side Power from Rear Spinesw b P29 Fabsw 1b P56
Spinesw a P29 Fabsw 1b P55 01FT725, 20M 01FT724, 10M 100Gb/s
1
Plug 1 Mgtsw 3a Right 39M5509 C13/C14 2.8m Spinesw b P30 Fabsw 1a P56 100Gb/s QSFP28 AOC QSFP28 AOC

Plug 2 Strgw3 Right 39M5509 C13/C14 2.8m Spinesw a P30 Fabsw 1a P55
Plug 3 Fabsw 2b Right 39M5509 C13/C14 2.8m Spinesw a P32 Spinesw b P32 01FT718, 0.5M
3 100Gb/s QSFP28 DAC
Plug 4 Spinesw a P31 Spinesw b P31 (ISL's)
Plug 5 Fabsw 2a Right 39M5509 C13/C14 2.8m Strgw3 Slot 5 (100GigE) P2 Spinesw b P1
3
01AF722, 3M 100Gb/s Optional Third Storage Gateway SR650
Plug 6 Strgw3 Slot 5 (100GigE) P1 Spinesw a P1 QSFP28 AOC Fabric Connections
RPC2
Plug 7
Plug 8 D2 Enclosure #12 Right 39M5510 C13/C14 4.3m
Plug 9 Hubsw Right 39M5509 C13/C14 2.8m
Plug 10
Plug 11
Plug 12 D2 Enclosure #11 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1 Mgtsw 3a Left 39M5509 C13/C14 2.8m


Plug 2 Strgw3 Left 39M5509 C13/C14 2.8m
Plug 3 Fabsw 2b Left 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 2a Left 39M5509 C13/C14 2.8m
Plug 6
RPC1
Plug 7
Plug 8 D2 Enclosure #12 Left 39M5510 C13/C14 4.3m
Plug 9 Hubsw Left 39M5509 C13/C14 2.8m
Plug 10
Plug 11
Plug 12 D2 Enclosure #11 Left 39M5510 C13/C14 4.3m

Page 9
Rack 4 Enclosures 16 - 20 (Mult
Doc Part # 02JE469
ECO#N47076S

ICP4D (Lenovo Based) 6 Single Phase PDU's NA Version (Multi Rack)


Fillers: 1U=9, 2U=3, 4U=4
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch 2a and 2b Connections SFP28 Xcvrs with LC - LC Cables Edge-Core AS4610-54T 1G Ethernet Management Switch Connections.
42 From To From To
Harness Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #20 S4 (10/25GigE) P2 Fabsw 2b 40 45D4774, 5M Fiber LC-LC D2 Enclosure #20 EIOM Node 4 P1 Mgtsw 4a 25 01AF040, 3m Blue
39 Plug 3 D2 Enclosure #20 S4 (10/25GigE) P1 Fabsw 2a 40 45D4774, 5M Fiber LC-LC D2 Enclosure #20 EIOM Node 3 P1 Mgtsw 4a 24 01AF040, 3m Blue
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #20 S3 (10/25GigE) P2 Fabsw 2b 39 45D4774, 5M Fiber LC-LC D2 Enclosure #20 EIOM Node 2 P1 Mgtsw 4a 23 01AF040, 3m Blue
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #20 S3 (10/25GigE) P1 Fabsw 2a 39 45D4774, 5M Fiber LC-LC D2 Enclosure #20 EIOM Node 1 P1 Mgtsw 4a 22 01AF040, 3m Blue
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #20 Right 39M5510 C13/C14 4.3m D2 Enclosure #20 S2 (10/25GigE) P2 Fabsw 2b 38 45D4774, 5M Fiber LC-LC D2 Enclosure #20 SMM P1 Mgtsw 4a 21 01AF040, 3m Blue
RPC6
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #20 S2 (10/25GigE) P1 Fabsw 2a 38 45D4774, 5M Fiber LC-LC D2 Enclosure #19 EIOM Node 4 P1 Mgtsw 4a 20 01AF040, 3m Blue
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #20 S1 (10/25GigE) P2 Fabsw 2b 37 45D4774, 5M Fiber LC-LC D2 Enclosure #19 EIOM Node 3 P1 Mgtsw 4a 19 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #20 S1 (10/25GigE) P1 Fabsw 2a 37 45D4774, 5M Fiber LC-LC D2 Enclosure #19 EIOM Node 2 P1 Mgtsw 4a 18 01AF040, 3m Blue
32 Plug 10 D2 Enclosure #19 S4 (10/25GigE) P2 Fabsw 2b 36 45D4774, 5M Fiber LC-LC D2 Enclosure #19 EIOM Node 1 P1 Mgtsw 4a 17 01AF040, 3m Blue
31 Plug 11 D2 Enclosure #19 S4 (10/25GigE) P1 Fabsw 2a 36 45D4774, 5M Fiber LC-LC D2 Enclosure #19 SMM P1 Mgtsw 4a 16 01AF040, 3m Blue
4U Blank Panel
30 Plug 12 D2 Enclosure #19 S3 (10/25GigE) P2 Fabsw 2b 35 45D4774, 5M Fiber LC-LC D2 Enclosure #18 EIOM Node 4 P1 Mgtsw 4a 15 01AF040, 3m Blue
29 D2 Enclosure #19 S3 (10/25GigE) P1 Fabsw 2a 35 45D4774, 5M Fiber LC-LC D2 Enclosure #18 EIOM Node 3 P1 Mgtsw 4a 14 01AF040, 3m Blue
28 Management Swt 4A – Edge-Core w/Air Duct D2 Enclosure #19 S2 (10/25GigE) P2 Fabsw 2b 34 45D4774, 5M Fiber LC-LC D2 Enclosure #18 EIOM Node 2 P1 Mgtsw 4a 13 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #19 S2 (10/25GigE) P1 Fabsw 2a 34 45D4774, 5M Fiber LC-LC D2 Enclosure #18 EIOM Node 1 P1 Mgtsw 4a 12 01AF040, 3m Blue
26 1U Blank Panel D2 Enclosure #19 S1 (10/25GigE) P2 Fabsw 2b 33 45D4774, 5M Fiber LC-LC D2 Enclosure #18 SMM P1 Mgtsw 4a 11 01AF040, 3m Blue
25 1U Blank Panel Plug 1 D2 Enclosure #19 S1 (10/25GigE) P1 Fabsw 2a 33 45D4774, 5M Fiber LC-LC D2 Enclosure #17 EIOM Node 4 P1 Mgtsw 4a 10 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #18 S4 (10/25GigE) P2 Fabsw 2b 32 45D4774, 5M Fiber LC-LC D2 Enclosure #17 EIOM Node 3 P1 Mgtsw 4a 9 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #18 S4 (10/25GigE) P1 Fabsw 2a 32 45D4774, 5M Fiber LC-LC D2 Enclosure #17 EIOM Node 2 P1 Mgtsw 4a 8 01AF040, 3m Blue
22 Plug 4 D2 Enclosure #18 S3 (10/25GigE) P2 Fabsw 2b 31 45D4774, 5M Fiber LC-LC D2 Enclosure #17 EIOM Node 1 P1 Mgtsw 4a 7 01AF040, 3m Blue
4U Blank Panel
21 Plug 5 D2 Enclosure #18 S3 (10/25GigE) P1 Fabsw 2a 31 45D4774, 5M Fiber LC-LC D2 Enclosure #17 SMM P1 Mgtsw 4a 6 01AF040, 3m Blue
78P5153 Qty 80
20 Plug 6 D2 Enclosure #20 Left 39M5510 C13/C14 4.3m D2 Enclosure #18 S2 (10/25GigE) P2 Fabsw 2b 30 45D4774, 5M Fiber LC-LC D2 Enclosure #16 EIOM Node 4 P1 Mgtsw 4a 5 01AF040, 3m Blue
RPC5
19 Plug 7 D2 Enclosure #18 S2 (10/25GigE) P1 Fabsw 2a 30 45D4774, 5M Fiber LC-LC D2 Enclosure #16 EIOM Node 3 P1 Mgtsw 4a 4 01AF040, 3m Blue
18 Plug 8 D2 Enclosure #18 S1 (10/25GigE) P2 Fabsw 2b 29 45D4774, 5M Fiber LC-LC D2 Enclosure #16 EIOM Node 2 P1 Mgtsw 4a 3 01AF040, 3m Blue
4U Blank Panel
17 Plug 9 D2 Enclosure #18 S1 (10/25GigE) P1 Fabsw 2a 29 45D4774, 5M Fiber LC-LC D2 Enclosure #16 EIOM Node 1 P1 Mgtsw 4a 2 01AF040, 3m Blue
16 Plug 10 D2 Enclosure #17 S4 (10/25GigE) P2 Fabsw 2b 28 45D4774, 5M Fiber LC-LC D2 Enclosure #16 SMM P1 Mgtsw 4a 1 01AF040, 3m Blue
15 Plug 11 D2 Enclosure #17 S4 (10/25GigE) P1 Fabsw 2a 28 45D4774, 5M Fiber LC-LC Mgtsw 4a N/A MGMT Mgtsw 3a 38 01AF040, 3m Blue
D2 Enclosure #20 SD530 Nodes 1-4 (+ 18)
14 Plug 12 D2 Enclosure #17 S3 (10/25GigE) P2 Fabsw 2b 27 45D4774, 5M Fiber LC-LC Mgtsw 4a N/A 42 Mgtsw 3a 42 Up Link 01AF040, 3m Blue
13 1U Blank Panel D2 Enclosure #17 S3 (10/25GigE) P1 Fabsw 2a 27 45D4774, 5M Fiber LC-LC Mgtsw 4a N/A 41 Mgtsw 3a 41 Up Link 01AF040, 3m Blue
12 D2 Enclosure #17 S2 (10/25GigE) P2 Fabsw 2b 26 45D4774, 5M Fiber LC-LC
D2 Enclosure #19 SD530 Nodes 1-4 (+ 17)
11 Right Side Power from Rear D2 Enclosure #17 S2 (10/25GigE) P1 Fabsw 2a 26 45D4774, 5M Fiber LC-LC
10 1U Blank Panel D2 Enclosure #17 S1 (10/25GigE) P2 Fabsw 2b 25 45D4774, 5M Fiber LC-LC
9 Plug 1 D2 Enclosure #17 S1 (10/25GigE) P1 Fabsw 2a 25 45D4774, 5M Fiber LC-LC
D2 Enclosure #18 SD530 Nodes 1-4 (+ 16)
8 Plug 2 D2 Enclosure #16 S4 (10/25GigE) P2 Fabsw 2b 24 45D4774, 5M Fiber LC-LC
7 1U Blank Panel Plug 3 D2 Enclosure #16 S4 (10/25GigE) P1 Fabsw 2a 24 45D4774, 5M Fiber LC-LC
6 Plug 4 D2 Enclosure #18 Right 39M5510 C13/C14 4.3m D2 Enclosure #16 S3 (10/25GigE) P2 Fabsw 2b 23 45D4774, 5M Fiber LC-LC
D2 Enclosure #17 SD530 Nodes 1-4 (+ 15)
5 Plug 5 D2 Enclosure #16 S3 (10/25GigE) P1 Fabsw 2a 23 45D4774, 5M Fiber LC-LC
4 1U Blank Panel Plug 6 D2 Enclosure #16 S2 (10/25GigE) P2 Fabsw 2b 22 45D4774, 5M Fiber LC-LC
RPC4
3 Plug 7 D2 Enclosure #16 S2 (10/25GigE) P1 Fabsw 2a 22 45D4774, 5M Fiber LC-LC
D2 Enclosure #16 SD530 Nodes 1-4 (+ 14)
2 Plug 8 D2 Enclosure #16 S1 (10/25GigE) P2 Fabsw 2b 21 45D4774, 5M Fiber LC-LC
1 1U Blank Panel Plug 9 D2 Enclosure #16 S1 (10/25GigE) P1 Fabsw 2a 21 45D4774, 5M Fiber LC-LC
Plug 10 D2 Enclosure #19 Right 39M5510 C13/C14 4.3m
Plug 11
Plug 12
Rack 4 (Base+ 18)
Left Side Power from Rear

Plug 1
Plug 2
Plug 3
Plug 4 D2 Enclosure #18 Left 39M5510 C13/C14 4.3m
Plug 5
Plug 6
RPC3
Plug 7
Plug 8
Plug 9
Plug 10 D2 Enclosure #19 Left 39M5510 C13/C14 4.3m
Plug 11
Plug 12

Right Side Power from Rear

Plug 1 Mgtsw 4a Right 39M5509 C13/C14 2.8m


Plug 2
Plug 3
Plug 4
Plug 5
Plug 6
RPC2
Plug 7
Plug 8 D2 Enclosure #17 Right 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #16 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1 Mgtsw 4a Left 39M5509 C13/C14 2.8m


Plug 2
Plug 3
Plug 4
Plug 5
Plug 6
RPC1
Plug 7
Plug 8 D2 Enclosure #17 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #16 Left 39M5510 C13/C14 4.3m

Page 10
Rack 5 Enclosures 21 - 25 (Mult
Doc Part # 02JE469
ECO#N47076S

ICP4D (Lenovo Based) 6 Single Phase PDU's NA Version (Multi Rack)


Fillers: 1U=7, 2U=3, 4U=4
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch Connections DAC SFP28 Cables Edge-Core AS4610-54T 1G Ethernet Management and Hub Switch Connections.
42 From To From To
Harness Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #25 S4 (10/25GigE) P2 Fabsw 3b 20 15R8846, 3M Fiber LC-LC Fabsw 3b MGMT P0 Mgtsw 5a 46 Cat6 7' Blue- 00J1691
39 Plug 3 D2 Enclosure #25 S4 (10/25GigE) P1 Fabsw 3a 20 15R8846, 3M Fiber LC-LC Fabsw 3a MGMT P0 Mgtsw 5a 47 Cat6 7' Blue- 00J1691
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #25 S3 (10/25GigE) P2 Fabsw 3b 19 15R8846, 3M Fiber LC-LC D2 Enclosure #25 EIOM Node 4 P1 Mgtsw 5a 25 01AF040, 3m Blue
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #25 S3 (10/25GigE) P1 Fabsw 3a 19 15R8846, 3M Fiber LC-LC D2 Enclosure #25 EIOM Node 3 P1 Mgtsw 5a 24 01AF040, 3m Blue
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #25 Right 39M5510 C13/C14 4.3m D2 Enclosure #25 S2 (10/25GigE) P2 Fabsw 3b 18 15R8846, 3M Fiber LC-LC D2 Enclosure #25 EIOM Node 2 P1 Mgtsw 5a 23 01AF040, 3m Blue
RPC6
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #25 S2 (10/25GigE) P1 Fabsw 3a 18 15R8846, 3M Fiber LC-LC D2 Enclosure #25 EIOM Node 1 P1 Mgtsw 5a 22 01AF040, 3m Blue
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #25 S1 (10/25GigE) P2 Fabsw 3b 17 15R8846, 3M Fiber LC-LC D2 Enclosure #25 SMM P1 Mgtsw 5a 21 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #25 S1 (10/25GigE) P1 Fabsw 3a 17 15R8846, 3M Fiber LC-LC D2 Enclosure #24 EIOM Node 4 P1 Mgtsw 5a 20 01AF040, 3m Blue
32 Plug 10 D2 Enclosure #24 S4 (10/25GigE) P2 Fabsw 3b 16 15R8846, 3M Fiber LC-LC D2 Enclosure #24 EIOM Node 3 P1 Mgtsw 5a 19 01AF040, 3m Blue
31 Plug 11 D2 Enclosure #24 S4 (10/25GigE) P1 Fabsw 3a 16 15R8846, 3M Fiber LC-LC D2 Enclosure #24 EIOM Node 2 P1 Mgtsw 5a 18 01AF040, 3m Blue
4U Blank Panel
30 Plug 12 D2 Enclosure #24 S3 (10/25GigE) P2 Fabsw 3b 15 15R8846, 3M Fiber LC-LC D2 Enclosure #24 EIOM Node 1 P1 Mgtsw 5a 17 01AF040, 3m Blue
29 D2 Enclosure #24 S3 (10/25GigE) P1 Fabsw 3a 15 15R8846, 3M Fiber LC-LC D2 Enclosure #24 SMM P1 Mgtsw 5a 16 01AF040, 3m Blue
28 Management Swt 5A – Edge-Core w/Air Duct D2 Enclosure #24 S2 (10/25GigE) P2 Fabsw 3b 14 15R8846, 3M Fiber LC-LC D2 Enclosure #23 EIOM Node 4 P1 Mgtsw 5a 15 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #24 S2 (10/25GigE) P1 Fabsw 3a 14 15R8846, 3M Fiber LC-LC D2 Enclosure #23 EIOM Node 3 P1 Mgtsw 5a 14 01AF040, 3m Blue
26 Fabric Switch 3B – Mellanox w/Air Duct D2 Enclosure #24 S1 (10/25GigE) P2 Fabsw 3b 13 15R8846, 3M Fiber LC-LC D2 Enclosure #23 EIOM Node 2 P1 Mgtsw 5a 13 01AF040, 3m Blue
25 Fabric Switch 3A – Mellanox w/Air Duct Plug 1 D2 Enclosure #24 S1 (10/25GigE) P1 Fabsw 3a 13 15R8846, 3M Fiber LC-LC D2 Enclosure #23 EIOM Node 1 P1 Mgtsw 5a 12 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #23 S4 (10/25GigE) P2 Fabsw 3b 12 15R8846, 3M Fiber LC-LC D2 Enclosure #23 SMM P1 Mgtsw 5a 11 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #23 S4 (10/25GigE) P1 Fabsw 3a 12 15R8846, 3M Fiber LC-LC D2 Enclosure #22 EIOM Node 4 P1 Mgtsw 5a 10 01AF040, 3m Blue
22 Plug 4 D2 Enclosure #23 S3 (10/25GigE) P2 Fabsw 3b 11 15R8846, 3M Fiber LC-LC D2 Enclosure #22 EIOM Node 3 P1 Mgtsw 5a 9 01AF040, 3m Blue
4U Blank Panel
21 Plug 5 D2 Enclosure #23 S3 (10/25GigE) P1 Fabsw 3a 11 15R8846, 3M Fiber LC-LC D2 Enclosure #22 EIOM Node 2 P1 Mgtsw 5a 8 01AF040, 3m Blue
78P5153 Qty 80
20 Plug 6 D2 Enclosure #25 Left 39M5510 C13/C14 4.3m D2 Enclosure #23 S2 (10/25GigE) P2 Fabsw 3b 10 15R8846, 3M Fiber LC-LC D2 Enclosure #22 EIOM Node 1 P1 Mgtsw 5a 7 01AF040, 3m Blue
RPC5
19 Plug 7 D2 Enclosure #23 S2 (10/25GigE) P1 Fabsw 3a 10 15R8846, 3M Fiber LC-LC D2 Enclosure #22 SMM P1 Mgtsw 5a 6 01AF040, 3m Blue
18 Plug 8 D2 Enclosure #23 S1 (10/25GigE) P2 Fabsw 3b 9 15R8846, 3M Fiber LC-LC D2 Enclosure #21 EIOM Node 4 P1 Mgtsw 5a 5 01AF040, 3m Blue
4U Blank Panel
17 Plug 9 D2 Enclosure #23 S1 (10/25GigE) P1 Fabsw 3a 9 15R8846, 3M Fiber LC-LC D2 Enclosure #21 EIOM Node 3 P1 Mgtsw 5a 4 01AF040, 3m Blue
16 Plug 10 D2 Enclosure #22 S4 (10/25GigE) P2 Fabsw 3b 8 15R8846, 3M Fiber LC-LC D2 Enclosure #21 EIOM Node 2 P1 Mgtsw 5a 3 01AF040, 3m Blue
15 Plug 11 D2 Enclosure #22 S4 (10/25GigE) P1 Fabsw 3a 8 15R8846, 3M Fiber LC-LC D2 Enclosure #21 EIOM Node 1 P1 Mgtsw 5a 2 01AF040, 3m Blue
D2 Enclosure #25 SD530 Nodes 1-4 (+ 23)
14 Plug 12 D2 Enclosure #22 S3 (10/25GigE) P2 Fabsw 3b 7 15R8846, 3M Fiber LC-LC D2 Enclosure #21 SMM P1 Mgtsw 5a 1 01AF040, 3m Blue
13 1U Blank Panel D2 Enclosure #22 S3 (10/25GigE) P1 Fabsw 3a 7 15R8846, 3M Fiber LC-LC Mgtsw 5a N/A MGMT Mgtsw 3a 43 001KL849, 20M Blue 01AF041, 10M Blue (Optional)
12 D2 Enclosure #22 S2 (10/25GigE) P2 Fabsw 3b 6 15R8846, 3M Fiber LC-LC
D2 Enclosure #24 SD530 Nodes 1-4 (+22)
11 Right Side Power from Rear D2 Enclosure #22 S2 (10/25GigE) P1 Fabsw 3a 6 15R8846, 3M Fiber LC-LC
10 1U Blank Panel D2 Enclosure #22 S1 (10/25GigE) P2 Fabsw 3b 5 15R8846, 3M Fiber LC-LC
9 Plug 1 D2 Enclosure #22 S1 (10/25GigE) P1 Fabsw 3a 5 15R8846, 3M Fiber LC-LC
D2 Enclosure #23 SD530 Nodes 1-4 (+ 21)
8 Plug 2 D2 Enclosure #21 S4 (10/25GigE) P2 Fabsw 3b 4 15R8846, 3M Fiber LC-LC
7 1U Blank Panel Plug 3 D2 Enclosure #21 S4 (10/25GigE) P1 Fabsw 3a 4 15R8846, 3M Fiber LC-LC
6 Plug 4 D2 Enclosure #23 Right 39M5510 C13/C14 4.3m D2 Enclosure #21 S3 (10/25GigE) P2 Fabsw 3b 3 15R8846, 3M Fiber LC-LC
D2 Enclosure #22 SD530 Nodes 1-4 (+ 20)
5 Plug 5 D2 Enclosure #21 S3 (10/25GigE) P1 Fabsw 3a 3 15R8846, 3M Fiber LC-LC
4 1U Blank Panel Plug 6 D2 Enclosure #21 S2 (10/25GigE) P2 Fabsw 3b 2 15R8846, 3M Fiber LC-LC
RPC4
3 Plug 7 D2 Enclosure #21 S2 (10/25GigE) P1 Fabsw 3a 2 15R8846, 3M Fiber LC-LC
D2 Enclosure #21 SD530 Nodes 1-4 (+ 19)
2 Plug 8 D2 Enclosure #21 S1 (10/25GigE) P2 Fabsw 3b 1 15R8846, 3M Fiber LC-LC
1 1U Blank Panel Plug 9 D2 Enclosure #21 S1 (10/25GigE) P1 Fabsw 3a 1 15R8846, 3M Fiber LC-LC
Plug 10 D2 Enclosure #24 Right 39M5510 C13/C14 4.3m Fabsw 3a N/A 44 Fabsw 3b 44 01FT735, 0.5M 25Gb/s SFP28 ISL
Plug 11 Fabsw 3a N/A 43 Fabsw 3b 43 01FT735, 0.5M 25Gb/s SFP28 ISL
SFP DACs
Plug 12 Fabsw 3a N/A 42 Fabsw 3b 42 01FT735, 0.5M 25Gb/s SFP28 ISL
Rack 5 (Base+ 23) Fabsw 3a N/A 41 Fabsw 3b 41 01FT735, 0.5M 25Gb/s SFP28 ISL

Left Side Power from Rear

Plug 1
Plug 2
Plug 3
Plug 4 D2 Enclosure #23 Left 39M5510 C13/C14 4.3m
Plug 5
Plug 6
RPC3
Plug 7
Plug 8
Plug 9
Plug 10 D2 Enclosure #24 Left 39M5510 C13/C14 4.3m
Plug 11
Plug 12

Right Side Power from Rear

Plug 1 Mgtsw 5a Right 39M5509 C13/C14 2.8m


Plug 2
Plug 3 Fabsw 3b Right 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 3a Right 39M5509 C13/C14 2.8m
Plug 6
RPC2
Plug 7
Plug 8 D2 Enclosure #22 Right 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #21 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1 Mgtsw 5a Left 39M5509 C13/C14 2.8m


Plug 2
Plug 3 Fabsw 3b Left 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 3a Left 39M5509 C13/C14 2.8m
Plug 6
RPC1
Plug 7
Plug 8 D2 Enclosure #22 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #21 Left 39M5510 C13/C14 4.3m

Page 11
Rack 6 Enclosures 26 - 30 (Mult
Doc Part # 02JE469
ECO#N47076S

ICP4D (Lenovo Based) 6 Single Phase PDU's NA Version (Multi Rack)


Fillers: 1U=9, 2U=3, 4U=4
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch Connections DAC SFP28 Cables Edge-Core AS4610-54T 1G Ethernet Management Switch Connections.
42 From To From To
Harness Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #30 S4 (10/25GigE) P2 Fabsw 3b 40 45D4774, 5M Fiber LC-LC D2 Enclosure #30 EIOM Node 4 P1 Mgtsw 6a 25 01AF040, 3m Blue
39 Plug 3 D2 Enclosure #30 S4 (10/25GigE) P1 Fabsw 3a 40 45D4774, 5M Fiber LC-LC D2 Enclosure #30 EIOM Node 3 P1 Mgtsw 6a 24 01AF040, 3m Blue
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #30 S3 (10/25GigE) P2 Fabsw 3b 39 45D4774, 5M Fiber LC-LC D2 Enclosure #30 EIOM Node 2 P1 Mgtsw 6a 23 01AF040, 3m Blue
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #30 S3 (10/25GigE) P1 Fabsw 3a 39 45D4774, 5M Fiber LC-LC D2 Enclosure #30 EIOM Node 1 P1 Mgtsw 6a 22 01AF040, 3m Blue
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #30 Right 39M5510 C13/C14 4.3m D2 Enclosure #30 S2 (10/25GigE) P2 Fabsw 3b 38 45D4774, 5M Fiber LC-LC D2 Enclosure #30 SMM P1 Mgtsw 6a 21 01AF040, 3m Blue
RPC6
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #30 S2 (10/25GigE) P1 Fabsw 3a 38 45D4774, 5M Fiber LC-LC D2 Enclosure #29 EIOM Node 4 P1 Mgtsw 6a 20 01AF040, 3m Blue
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #30 S1 (10/25GigE) P2 Fabsw 3b 37 45D4774, 5M Fiber LC-LC D2 Enclosure #29 EIOM Node 3 P1 Mgtsw 6a 19 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #30 S1 (10/25GigE) P1 Fabsw 3a 37 45D4774, 5M Fiber LC-LC D2 Enclosure #29 EIOM Node 2 P1 Mgtsw 6a 18 01AF040, 3m Blue
32 Plug 10 D2 Enclosure #29 S4 (10/25GigE) P2 Fabsw 3b 36 45D4774, 5M Fiber LC-LC D2 Enclosure #29 EIOM Node 1 P1 Mgtsw 6a 17 01AF040, 3m Blue
31 Plug 11 D2 Enclosure #29 S4 (10/25GigE) P1 Fabsw 3a 36 45D4774, 5M Fiber LC-LC D2 Enclosure #29 SMM P1 Mgtsw 6a 16 01AF040, 3m Blue
4U Blank Panel
30 Plug 12 D2 Enclosure #29 S3 (10/25GigE) P2 Fabsw 3b 35 45D4774, 5M Fiber LC-LC D2 Enclosure #28 EIOM Node 4 P1 Mgtsw 6a 15 01AF040, 3m Blue
29 D2 Enclosure #29 S3 (10/25GigE) P1 Fabsw 3a 35 45D4774, 5M Fiber LC-LC D2 Enclosure #28 EIOM Node 3 P1 Mgtsw 6a 14 01AF040, 3m Blue
28 Management Swt 6A – Edge-Core w/Air Duct D2 Enclosure #29 S2 (10/25GigE) P2 Fabsw 3b 34 45D4774, 5M Fiber LC-LC D2 Enclosure #28 EIOM Node 2 P1 Mgtsw 6a 13 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #29 S2 (10/25GigE) P1 Fabsw 3a 34 45D4774, 5M Fiber LC-LC D2 Enclosure #28 EIOM Node 1 P1 Mgtsw 6a 12 01AF040, 3m Blue
26 1U Blank Panel D2 Enclosure #29 S1 (10/25GigE) P2 Fabsw 3b 33 45D4774, 5M Fiber LC-LC D2 Enclosure #28 SMM P1 Mgtsw 6a 11 01AF040, 3m Blue
25 1U Blank Panel Plug 1 D2 Enclosure #29 S1 (10/25GigE) P1 Fabsw 3a 33 45D4774, 5M Fiber LC-LC D2 Enclosure #27 EIOM Node 4 P1 Mgtsw 6a 10 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #28 S4 (10/25GigE) P2 Fabsw 3b 32 45D4774, 5M Fiber LC-LC D2 Enclosure #27 EIOM Node 3 P1 Mgtsw 6a 9 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #28 S4 (10/25GigE) P1 Fabsw 3a 32 45D4774, 5M Fiber LC-LC D2 Enclosure #27 EIOM Node 2 P1 Mgtsw 6a 8 01AF040, 3m Blue
22 Plug 4 D2 Enclosure #28 S3 (10/25GigE) P2 Fabsw 3b 31 45D4774, 5M Fiber LC-LC D2 Enclosure #27 EIOM Node 1 P1 Mgtsw 6a 7 01AF040, 3m Blue
4U Blank Panel
21 Plug 5 D2 Enclosure #28 S3 (10/25GigE) P1 Fabsw 3a 31 45D4774, 5M Fiber LC-LC D2 Enclosure #27 SMM P1 Mgtsw 6a 6 01AF040, 3m Blue
78P5153 Qty 80
20 Plug 6 D2 Enclosure #30 Left 39M5510 C13/C14 4.3m D2 Enclosure #28 S2 (10/25GigE) P2 Fabsw 3b 30 45D4774, 5M Fiber LC-LC D2 Enclosure #26 EIOM Node 4 P1 Mgtsw 6a 5 01AF040, 3m Blue
RPC5
19 Plug 7 D2 Enclosure #28 S2 (10/25GigE) P1 Fabsw 3a 30 45D4774, 5M Fiber LC-LC D2 Enclosure #26 EIOM Node 3 P1 Mgtsw 6a 4 01AF040, 3m Blue
18 Plug 8 D2 Enclosure #28 S1 (10/25GigE) P2 Fabsw 3b 29 45D4774, 5M Fiber LC-LC D2 Enclosure #26 EIOM Node 2 P1 Mgtsw 6a 3 01AF040, 3m Blue
4U Blank Panel
17 Plug 9 D2 Enclosure #28 S1 (10/25GigE) P1 Fabsw 3a 29 45D4774, 5M Fiber LC-LC D2 Enclosure #26 EIOM Node 1 P1 Mgtsw 6a 2 01AF040, 3m Blue
16 Plug 10 D2 Enclosure #27 S4 (10/25GigE) P2 Fabsw 3b 28 45D4774, 5M Fiber LC-LC D2 Enclosure #26 SMM P1 Mgtsw 6a 1 01AF040, 3m Blue
15 Plug 11 D2 Enclosure #27 S4 (10/25GigE) P1 Fabsw 3a 28 45D4774, 5M Fiber LC-LC Mgtsw 6a N/A MGMT Mgtsw 5a 38 01AF040, 3m Blue
D2 Enclosure #30 SD530 Nodes 1-4 (+ 28)
14 Plug 12 D2 Enclosure #27 S3 (10/25GigE) P2 Fabsw 3b 27 45D4774, 5M Fiber LC-LC Mgtsw 6a N/A 42 Mgtsw 5a 42 Up Link 01AF040, 3m Blue
13 1U Blank Panel D2 Enclosure #27 S3 (10/25GigE) P1 Fabsw 3a 27 45D4774, 5M Fiber LC-LC Mgtsw 6a N/A 41 Mgtsw 5a 41 Up Link 01AF040, 3m Blue
12 D2 Enclosure #27 S2 (10/25GigE) P2 Fabsw 3b 26 45D4774, 5M Fiber LC-LC
D2 Enclosure #29 SD530 Nodes 1-4 (+ 27)
11 Right Side Power from Rear D2 Enclosure #27 S2 (10/25GigE) P1 Fabsw 3a 26 45D4774, 5M Fiber LC-LC
10 1U Blank Panel D2 Enclosure #27 S1 (10/25GigE) P2 Fabsw 3b 25 45D4774, 5M Fiber LC-LC
9 Plug 1 D2 Enclosure #27 S1 (10/25GigE) P1 Fabsw 3a 25 45D4774, 5M Fiber LC-LC
D2 Enclosure #28 SD530 Nodes 1-4 (+ 26)
8 Plug 2 D2 Enclosure #26 S4 (10/25GigE) P2 Fabsw 3b 24 45D4774, 5M Fiber LC-LC
7 1U Blank Panel Plug 3 D2 Enclosure #26 S4 (10/25GigE) P1 Fabsw 3a 24 45D4774, 5M Fiber LC-LC
6 Plug 4 D2 Enclosure #28 Right 39M5510 C13/C14 4.3m D2 Enclosure #26 S3 (10/25GigE) P2 Fabsw 3b 23 45D4774, 5M Fiber LC-LC
D2 Enclosure #27 SD530 Nodes 1-4 (+ 25)
5 Plug 5 D2 Enclosure #26 S3 (10/25GigE) P1 Fabsw 3a 23 45D4774, 5M Fiber LC-LC
4 1U Blank Panel Plug 6 D2 Enclosure #26 S2 (10/25GigE) P2 Fabsw 3b 22 45D4774, 5M Fiber LC-LC
RPC4
3 Plug 7 D2 Enclosure #26 S2 (10/25GigE) P1 Fabsw 3a 22 45D4774, 5M Fiber LC-LC
D2 Enclosure #26 SD530 Nodes 1-4 (+ 24)
2 Plug 8 D2 Enclosure #26 S1 (10/25GigE) P2 Fabsw 3b 21 45D4774, 5M Fiber LC-LC
1 1U Blank Panel Plug 9 D2 Enclosure #26 S1 (10/25GigE) P1 Fabsw 3a 21 45D4774, 5M Fiber LC-LC
Plug 10 D2 Enclosure #29 Right 39M5510 C13/C14 4.3m
Plug 11
Plug 12
Rack 6 (Base+ 28)
Left Side Power from Rear

Plug 1
Plug 2
Plug 3
Plug 4 D2 Enclosure #28 Left 39M5510 C13/C14 4.3m
Plug 5
Plug 6
RPC3
Plug 7
Plug 8
Plug 9
Plug 10 D2 Enclosure #29 Left 39M5510 C13/C14 4.3m
Plug 11
Plug 12

Right Side Power from Rear

Plug 1 Mgtsw 6a Right 39M5509 C13/C14 2.8m


Plug 2
Plug 3
Plug 4
Plug 5
Plug 6
RPC2
Plug 7
Plug 8 D2 Enclosure #27 Right 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #26 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1 Mgtsw 6a Left 39M5509 C13/C14 2.8m


Plug 2
Plug 3
Plug 4
Plug 5
Plug 6
RPC1
Plug 7
Plug 8 D2 Enclosure #27 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #26 Left 39M5510 C13/C14 4.3m

Page 12
Rack 7 Enclosures 31 -35 (Multi
Doc Part # 02JE469
ECO#N47076S

ICP4D (Lenovo Based) 6 Single Phase PDU's NA Version (Multi Rack)


Fillers: 1U=7, 2U=3, 4U=4
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch Connections DAC SFP28 Cables Edge-Core AS4610-54T 1G Ethernet Management and Hub Switch Connections.
42 From To From To
Harness Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #35 S4 (10/25GigE) P2 Fabsw 4b 20 15R8846, 3M Fiber LC-LC Fabsw 4b MGMT P0 Mgtsw 7a 46 Cat6 7' Blue- 00J1691
39 Plug 3 D2 Enclosure #35 S4 (10/25GigE) P1 Fabsw 4a 20 15R8846, 3M Fiber LC-LC Fabsw 4a MGMT P0 Mgtsw 7a 47 Cat6 7' Blue- 00J1691
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #35 S3 (10/25GigE) P2 Fabsw 4b 19 15R8846, 3M Fiber LC-LC D2 Enclosure #35 EIOM Node 4 P1 Mgtsw 7a 25 01AF040, 3m Blue
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #35 S3 (10/25GigE) P1 Fabsw 4a 19 15R8846, 3M Fiber LC-LC D2 Enclosure #35 EIOM Node 3 P1 Mgtsw 7a 24 01AF040, 3m Blue
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #35 Right 39M5510 C13/C14 4.3m D2 Enclosure #35 S2 (10/25GigE) P2 Fabsw 4b 18 15R8846, 3M Fiber LC-LC D2 Enclosure #35 EIOM Node 2 P1 Mgtsw 7a 23 01AF040, 3m Blue
RPC6
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #35 S2 (10/25GigE) P1 Fabsw 4a 18 15R8846, 3M Fiber LC-LC D2 Enclosure #35 EIOM Node 1 P1 Mgtsw 7a 22 01AF040, 3m Blue
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #35 S1 (10/25GigE) P2 Fabsw 4b 17 15R8846, 3M Fiber LC-LC D2 Enclosure #35 SMM P1 Mgtsw 7a 21 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #35 S1 (10/25GigE) P1 Fabsw 4a 17 15R8846, 3M Fiber LC-LC D2 Enclosure #34 EIOM Node 4 P1 Mgtsw 7a 20 01AF040, 3m Blue
32 Plug 10 D2 Enclosure #34 S4 (10/25GigE) P2 Fabsw 4b 16 15R8846, 3M Fiber LC-LC D2 Enclosure #34 EIOM Node 3 P1 Mgtsw 7a 19 01AF040, 3m Blue
31 Plug 11 D2 Enclosure #34 S4 (10/25GigE) P1 Fabsw 4a 16 15R8846, 3M Fiber LC-LC D2 Enclosure #34 EIOM Node 2 P1 Mgtsw 7a 18 01AF040, 3m Blue
4U Blank Panel
30 Plug 12 D2 Enclosure #34 S3 (10/25GigE) P2 Fabsw 4b 15 15R8846, 3M Fiber LC-LC D2 Enclosure #34 EIOM Node 1 P1 Mgtsw 7a 17 01AF040, 3m Blue
29 D2 Enclosure #34 S3 (10/25GigE) P1 Fabsw 4a 15 15R8846, 3M Fiber LC-LC D2 Enclosure #34 SMM P1 Mgtsw 7a 16 01AF040, 3m Blue
28 Management Swt 7A – Edge-Core w/Air Duct D2 Enclosure #34 S2 (10/25GigE) P2 Fabsw 4b 14 15R8846, 3M Fiber LC-LC D2 Enclosure #33 EIOM Node 4 P1 Mgtsw 7a 15 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #34 S2 (10/25GigE) P1 Fabsw 4a 14 15R8846, 3M Fiber LC-LC D2 Enclosure #33 EIOM Node 3 P1 Mgtsw 7a 14 01AF040, 3m Blue
26 Fabric Switch 4B – Mellanox w/Air Duct D2 Enclosure #34 S1 (10/25GigE) P2 Fabsw 4b 13 15R8846, 3M Fiber LC-LC D2 Enclosure #33 EIOM Node 2 P1 Mgtsw 7a 13 01AF040, 3m Blue
25 Fabric Switch 4A – Mellanox w/Air Duct Plug 1 D2 Enclosure #34 S1 (10/25GigE) P1 Fabsw 4a 13 15R8846, 3M Fiber LC-LC D2 Enclosure #33 EIOM Node 1 P1 Mgtsw 7a 12 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #33 S4 (10/25GigE) P2 Fabsw 4b 12 15R8846, 3M Fiber LC-LC D2 Enclosure #33 SMM P1 Mgtsw 7a 11 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #33 S4 (10/25GigE) P1 Fabsw 4a 12 15R8846, 3M Fiber LC-LC D2 Enclosure #32 EIOM Node 4 P1 Mgtsw 7a 10 01AF040, 3m Blue
22 Plug 4 D2 Enclosure #33 S3 (10/25GigE) P2 Fabsw 4b 11 15R8846, 3M Fiber LC-LC D2 Enclosure #32 EIOM Node 3 P1 Mgtsw 7a 9 01AF040, 3m Blue
4U Blank Panel
21 Plug 5 D2 Enclosure #33 S3 (10/25GigE) P1 Fabsw 4a 11 15R8846, 3M Fiber LC-LC D2 Enclosure #32 EIOM Node 2 P1 Mgtsw 7a 8 01AF040, 3m Blue
78P5153 Qty 80
20 Plug 6 D2 Enclosure #35 Left 39M5510 C13/C14 4.3m D2 Enclosure #33 S2 (10/25GigE) P2 Fabsw 4b 10 15R8846, 3M Fiber LC-LC D2 Enclosure #32 EIOM Node 1 P1 Mgtsw 7a 7 01AF040, 3m Blue
RPC5
19 Plug 7 D2 Enclosure #33 S2 (10/25GigE) P1 Fabsw 4a 10 15R8846, 3M Fiber LC-LC D2 Enclosure #32 SMM P1 Mgtsw 7a 6 01AF040, 3m Blue
18 Plug 8 D2 Enclosure #33 S1 (10/25GigE) P2 Fabsw 4b 9 15R8846, 3M Fiber LC-LC D2 Enclosure #31 EIOM Node 4 P1 Mgtsw 7a 5 01AF040, 3m Blue
4U Blank Panel
17 Plug 9 D2 Enclosure #33 S1 (10/25GigE) P1 Fabsw 4a 9 15R8846, 3M Fiber LC-LC D2 Enclosure #31 EIOM Node 3 P1 Mgtsw 7a 4 01AF040, 3m Blue
16 Plug 10 D2 Enclosure #32 S4 (10/25GigE) P2 Fabsw 4b 8 15R8846, 3M Fiber LC-LC D2 Enclosure #31 EIOM Node 2 P1 Mgtsw 7a 3 01AF040, 3m Blue
15 Plug 11 D2 Enclosure #32 S4 (10/25GigE) P1 Fabsw 4a 8 15R8846, 3M Fiber LC-LC D2 Enclosure #31 EIOM Node 1 P1 Mgtsw 7a 2 01AF040, 3m Blue
D2 Enclosure #35 SD530 Nodes 1-4 (+ 33)
14 Plug 12 D2 Enclosure #32 S3 (10/25GigE) P2 Fabsw 4b 7 15R8846, 3M Fiber LC-LC D2 Enclosure #31 SMM P1 Mgtsw 7a 1 01AF040, 3m Blue
13 1U Blank Panel D2 Enclosure #32 S3 (10/25GigE) P1 Fabsw 4a 7 15R8846, 3M Fiber LC-LC Mgtsw 7a N/A MGMT Mgtsw 5a 43 001KL849, 20M Blue 01AF041, 10M Blue (Optional)
12 D2 Enclosure #32 S2 (10/25GigE) P2 Fabsw 4b 6 15R8846, 3M Fiber LC-LC
D2 Enclosure #34 SD530 Nodes 1-4 (+ 32)
11 Right Side Power from Rear D2 Enclosure #32 S2 (10/25GigE) P1 Fabsw 4a 6 15R8846, 3M Fiber LC-LC
10 1U Blank Panel D2 Enclosure #32 S1 (10/25GigE) P2 Fabsw 4b 5 15R8846, 3M Fiber LC-LC
9 Plug 1 D2 Enclosure #32 S1 (10/25GigE) P1 Fabsw 4a 5 15R8846, 3M Fiber LC-LC
D2 Enclosure #33 SD530 Nodes 1-4 (+ 31)
8 Plug 2 D2 Enclosure #31 S4 (10/25GigE) P2 Fabsw 4b 4 15R8846, 3M Fiber LC-LC
7 1U Blank Panel Plug 3 D2 Enclosure #31 S4 (10/25GigE) P1 Fabsw 4a 4 15R8846, 3M Fiber LC-LC
6 Plug 4 D2 Enclosure #33 Right 39M5510 C13/C14 4.3m D2 Enclosure #31 S3 (10/25GigE) P2 Fabsw 4b 3 15R8846, 3M Fiber LC-LC
D2 Enclosure #32 SD530 Nodes 1-4 (+ 30)
5 Plug 5 D2 Enclosure #31 S3 (10/25GigE) P1 Fabsw 4a 3 15R8846, 3M Fiber LC-LC
4 1U Blank Panel Plug 6 D2 Enclosure #31 S2 (10/25GigE) P2 Fabsw 4b 2 15R8846, 3M Fiber LC-LC
RPC4
3 Plug 7 D2 Enclosure #31 S2 (10/25GigE) P1 Fabsw 4a 2 15R8846, 3M Fiber LC-LC
D2 Enclosure #31 SD530 Nodes 1-4 (+ 29)
2 Plug 8 D2 Enclosure #31 S1 (10/25GigE) P2 Fabsw 4b 1 15R8846, 3M Fiber LC-LC
1 1U Blank Panel Plug 9 D2 Enclosure #31 S1 (10/25GigE) P1 Fabsw 4a 1 15R8846, 3M Fiber LC-LC
Plug 10 D2 Enclosure #34 Right 39M5510 C13/C14 4.3m Fabsw 4a N/A 44 Fabsw 4b 44 01FT735, 0.5M 25Gb/s SFP28 ISL
Plug 11 Fabsw 4a N/A 43 Fabsw 4b 43 01FT735, 0.5M 25Gb/s SFP28 ISL
SFP DACs
Plug 12 Fabsw 4a N/A 42 Fabsw 4b 42 01FT735, 0.5M 25Gb/s SFP28 ISL
Rack 7 (Base+ 33) Fabsw 4a N/A 41 Fabsw 4b 41 01FT735, 0.5M 25Gb/s SFP28 ISL

Left Side Power from Rear

Plug 1
Plug 2
Plug 3
Plug 4 D2 Enclosure #33 Left 39M5510 C13/C14 4.3m
Plug 5
Plug 6
RPC3
Plug 7
Plug 8
Plug 9
Plug 10 D2 Enclosure #34 Left 39M5510 C13/C14 4.3m
Plug 11
Plug 12

Right Side Power from Rear

Plug 1 Mgtsw 7a Right 39M5509 C13/C14 2.8m


Plug 2
Plug 3 Fabsw 4b Left 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 4a Right 39M5509 C13/C14 2.8m
Plug 6
RPC2
Plug 7
Plug 8 D2 Enclosure #32 Right 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #31 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1 Mgtsw 7a Left 39M5509 C13/C14 2.8m


Plug 2
Plug 3 Fabsw 4b Left 39M5509 C13/C14 2.8m
Plug 4
Plug 5 Fabsw 4a Left 39M5509 C13/C14 2.8m
Plug 6
RPC1
Plug 7
Plug 8 D2 Enclosure #32 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #31 Left 39M5510 C13/C14 4.3m

Page 13
Rack 8 Enclosures 36 - 40 (Mult
Doc Part # 02JE469
ECO#N47076S

ICP4D (Lenovo Based) 6 Single Phase PDU's NA Version (Multi Rack)


Fillers: 1U=9, 2U=3, 4U=4
Left Right Right Side Power from Rear Mellanox SN2410 25GigE Leaf Switch Connections DAC SFP28 Cables Edge-Core AS4610-54T 1G Ethernet Management Switch Connections.
42 From To From To
Harness Transceiver
41 Plug 1 ID Component PCI Slot Port ID Component Port ID Component PCI Slot Port ID Component Port Harness Color
4U Blank Panel
40 Plug 2 D2 Enclosure #40 S4 (10/25GigE) P2 Fabsw 4b 40 45D4774, 5M Fiber LC-LC D2 Enclosure #40 EIOM Node 4 P1 Mgtsw 8a 25 01AF040, 3m Blue
39 Plug 3 D2 Enclosure #40 S4 (10/25GigE) P1 Fabsw 4a 40 45D4774, 5M Fiber LC-LC D2 Enclosure #40 EIOM Node 3 P1 Mgtsw 8a 24 01AF040, 3m Blue
38 net R6-1 R6-2 R6-3 R6-4 R6-5 R6-6 R6-7 R6-8 R6-9 R6-10 R6-11 R6-12 in Plug 4 D2 Enclosure #40 S3 (10/25GigE) P2 Fabsw 4b 39 45D4774, 5M Fiber LC-LC D2 Enclosure #40 EIOM Node 2 P1 Mgtsw 8a 23 01AF040, 3m Blue
37 in R5-12 R5-11 R5-10 R5-9 R5-8 R5-7 R5-6 R5-5 R5-4 R5-3 R5-2 R5-1 net Plug 5 D2 Enclosure #40 S3 (10/25GigE) P1 Fabsw 4a 39 45D4774, 5M Fiber LC-LC D2 Enclosure #40 EIOM Node 1 P1 Mgtsw 8a 22 01AF040, 3m Blue
36 net R4-1 R4-2 R4-3 R4-4 R4-5 R4-6 R4-7 R4-8 R4-9 R4-10 R4-11 R4-12 in Plug 6 D2 Enclosure #40 Right 39M5510 C13/C14 4.3m D2 Enclosure #40 S2 (10/25GigE) P2 Fabsw 4b 38 45D4774, 5M Fiber LC-LC D2 Enclosure #40 SMM P1 Mgtsw 8a 21 01AF040, 3m Blue
RPC6
35 in R3-12 R3-11 R3-10 R3-9 R3-8 R3-7 R3-6 R3-5 R3-4 R3-3 R3-2 R3-1 net Plug 7 D2 Enclosure #40 S2 (10/25GigE) P1 Fabsw 4a 38 45D4774, 5M Fiber LC-LC D2 Enclosure #39 EIOM Node 4 P1 Mgtsw 8a 20 01AF040, 3m Blue
34 net R2-1 R2-2 R2-3 R2-4 R2-5 R2-6 R2-7 R2-8 R2-9 R2-10 R2-11 R2-12 in Plug 8 D2 Enclosure #40 S1 (10/25GigE) P2 Fabsw 4b 37 45D4774, 5M Fiber LC-LC D2 Enclosure #39 EIOM Node 3 P1 Mgtsw 8a 19 01AF040, 3m Blue
33 in R1-12 R1-11 R1-10 R1-9 R1-8 R1-7 R1-6 R1-5 R1-4 R1-3 R1-2 R1-1 net Plug 9 D2 Enclosure #40 S1 (10/25GigE) P1 Fabsw 4a 37 45D4774, 5M Fiber LC-LC D2 Enclosure #39 EIOM Node 2 P1 Mgtsw 8a 18 01AF040, 3m Blue
32 Plug 10 D2 Enclosure #39 S4 (10/25GigE) P2 Fabsw 4b 36 45D4774, 5M Fiber LC-LC D2 Enclosure #39 EIOM Node 1 P1 Mgtsw 8a 17 01AF040, 3m Blue
31 Plug 11 D2 Enclosure #39 S4 (10/25GigE) P1 Fabsw 4a 36 45D4774, 5M Fiber LC-LC D2 Enclosure #39 SMM P1 Mgtsw 8a 16 01AF040, 3m Blue
4U Blank Panel
30 Plug 12 D2 Enclosure #39 S3 (10/25GigE) P2 Fabsw 4b 35 45D4774, 5M Fiber LC-LC D2 Enclosure #38 EIOM Node 4 P1 Mgtsw 8a 15 01AF040, 3m Blue
29 D2 Enclosure #39 S3 (10/25GigE) P1 Fabsw 4a 35 45D4774, 5M Fiber LC-LC D2 Enclosure #38 EIOM Node 3 P1 Mgtsw 8a 14 01AF040, 3m Blue
28 Management Swt 8A – Edge-Core w/Air Duct D2 Enclosure #39 S2 (10/25GigE) P2 Fabsw 4b 34 45D4774, 5M Fiber LC-LC D2 Enclosure #38 EIOM Node 2 P1 Mgtsw 8a 13 01AF040, 3m Blue
27 1U Blank Panel Left Side Power from Rear D2 Enclosure #39 S2 (10/25GigE) P1 Fabsw 4a 34 45D4774, 5M Fiber LC-LC D2 Enclosure #38 EIOM Node 1 P1 Mgtsw 8a 12 01AF040, 3m Blue
26 1U Blank Panel D2 Enclosure #39 S1 (10/25GigE) P2 Fabsw 4b 33 45D4774, 5M Fiber LC-LC D2 Enclosure #38 SMM P1 Mgtsw 8a 11 01AF040, 3m Blue
25 1U Blank Panel Plug 1 D2 Enclosure #39 S1 (10/25GigE) P1 Fabsw 4a 33 45D4774, 5M Fiber LC-LC D2 Enclosure #37 EIOM Node 4 P1 Mgtsw 8a 10 01AF040, 3m Blue
24 1U Blank Panel Plug 2 D2 Enclosure #38 S4 (10/25GigE) P2 Fabsw 4b 32 45D4774, 5M Fiber LC-LC D2 Enclosure #37 EIOM Node 3 P1 Mgtsw 8a 9 01AF040, 3m Blue
23 Plug 3 D2 Enclosure #38 S4 (10/25GigE) P1 Fabsw 4a 32 45D4774, 5M Fiber LC-LC D2 Enclosure #37 EIOM Node 2 P1 Mgtsw 8a 8 01AF040, 3m Blue
22 Plug 4 D2 Enclosure #38 S3 (10/25GigE) P2 Fabsw 4b 31 45D4774, 5M Fiber LC-LC D2 Enclosure #37 EIOM Node 1 P1 Mgtsw 8a 7 01AF040, 3m Blue
4U Blank Panel
21 Plug 5 D2 Enclosure #38 S3 (10/25GigE) P1 Fabsw 4a 31 45D4774, 5M Fiber LC-LC D2 Enclosure #37 SMM P1 Mgtsw 8a 6 01AF040, 3m Blue
78P5153 Qty 80
20 Plug 6 D2 Enclosure #40 Left 39M5510 C13/C14 4.3m D2 Enclosure #38 S2 (10/25GigE) P2 Fabsw 4b 30 45D4774, 5M Fiber LC-LC D2 Enclosure #36 EIOM Node 4 P1 Mgtsw 8a 5 01AF040, 3m Blue
RPC5
19 Plug 7 D2 Enclosure #38 S2 (10/25GigE) P1 Fabsw 4a 30 45D4774, 5M Fiber LC-LC D2 Enclosure #36 EIOM Node 3 P1 Mgtsw 8a 4 01AF040, 3m Blue
18 Plug 8 D2 Enclosure #38 S1 (10/25GigE) P2 Fabsw 4b 29 45D4774, 5M Fiber LC-LC D2 Enclosure #36 EIOM Node 2 P1 Mgtsw 8a 3 01AF040, 3m Blue
4U Blank Panel
17 Plug 9 D2 Enclosure #38 S1 (10/25GigE) P1 Fabsw 4a 29 45D4774, 5M Fiber LC-LC D2 Enclosure #36 EIOM Node 1 P1 Mgtsw 8a 2 01AF040, 3m Blue
16 Plug 10 D2 Enclosure #37 S4 (10/25GigE) P2 Fabsw 4b 28 45D4774, 5M Fiber LC-LC D2 Enclosure #36 SMM P1 Mgtsw 8a 1 01AF040, 3m Blue
15 Plug 11 D2 Enclosure #37 S4 (10/25GigE) P1 Fabsw 4a 28 45D4774, 5M Fiber LC-LC Mgtsw 8a N/A MGMT Mgtsw 7a 38 01AF040, 3m Blue
D2 Enclosure #40 SD530 Nodes 1-4 (+ 38)
14 Plug 12 D2 Enclosure #37 S3 (10/25GigE) P2 Fabsw 4b 27 45D4774, 5M Fiber LC-LC Mgtsw 8a N/A 42 Mgtsw 7a 42 Up Link 01AF040, 3m Blue
13 1U Blank Panel D2 Enclosure #37 S3 (10/25GigE) P1 Fabsw 4a 27 45D4774, 5M Fiber LC-LC Mgtsw 8a N/A 41 Mgtsw 7a 41 Up Link 01AF040, 3m Blue
12 D2 Enclosure #37 S2 (10/25GigE) P2 Fabsw 4b 26 45D4774, 5M Fiber LC-LC
D2 Enclosure #39 SD530 Nodes 1-4 (+ 37)
11 Right Side Power from Rear D2 Enclosure #37 S2 (10/25GigE) P1 Fabsw 4a 26 45D4774, 5M Fiber LC-LC
10 1U Blank Panel D2 Enclosure #37 S1 (10/25GigE) P2 Fabsw 4b 25 45D4774, 5M Fiber LC-LC
9 Plug 1 D2 Enclosure #37 S1 (10/25GigE) P1 Fabsw 4a 25 45D4774, 5M Fiber LC-LC
D2 Enclosure #38 SD530 Nodes 1-4 (+ 36)
8 Plug 2 D2 Enclosure #36 S4 (10/25GigE) P2 Fabsw 4b 24 45D4774, 5M Fiber LC-LC
7 1U Blank Panel Plug 3 D2 Enclosure #36 S4 (10/25GigE) P1 Fabsw 4a 24 45D4774, 5M Fiber LC-LC
6 Plug 4 D2 Enclosure #38 Right 39M5510 C13/C14 4.3m D2 Enclosure #36 S3 (10/25GigE) P2 Fabsw 4b 23 45D4774, 5M Fiber LC-LC
D2 Enclosure #37 SD530 Nodes 1-4 (+ 35)
5 Plug 5 D2 Enclosure #36 S3 (10/25GigE) P1 Fabsw 4a 23 45D4774, 5M Fiber LC-LC
4 1U Blank Panel Plug 6 D2 Enclosure #36 S2 (10/25GigE) P2 Fabsw 4b 22 45D4774, 5M Fiber LC-LC
RPC4
3 Plug 7 D2 Enclosure #36 S2 (10/25GigE) P1 Fabsw 4a 22 45D4774, 5M Fiber LC-LC
D2 Enclosure #36 SD530 Nodes 1-4 (+ 34)
2 Plug 8 D2 Enclosure #36 S1 (10/25GigE) P2 Fabsw 4b 21 45D4774, 5M Fiber LC-LC
1 1U Blank Panel Plug 9 D2 Enclosure #36 S1 (10/25GigE) P1 Fabsw 4a 21 45D4774, 5M Fiber LC-LC
Plug 10 D2 Enclosure #39 Right 39M5510 C13/C14 4.3m
Plug 11
Plug 12
Rack 8 (Base+ 38)
Left Side Power from Rear

Plug 1
Plug 2
Plug 3
Plug 4 D2 Enclosure #38 Left 39M5510 C13/C14 4.3m
Plug 5
Plug 6
RPC3
Plug 7
Plug 8
Plug 9
Plug 10 D2 Enclosure #39 Left 39M5510 C13/C14 4.3m
Plug 11
Plug 12

Right Side Power from Rear

Plug 1 Mgtsw 8a Right 39M5509 C13/C14 2.8m


Plug 2
Plug 3
Plug 4
Plug 5
Plug 6
RPC2
Plug 7
Plug 8 D2 Enclosure #37 Right 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #36 Right 39M5510 C13/C14 4.3m

Left Side Power from Rear

Plug 1 Mgtsw 8a Left 39M5509 C13/C14 2.8m


Plug 2
Plug 3
Plug 4
Plug 5
Plug 6
RPC1
Plug 7
Plug 8 D2 Enclosure #37 Left 39M5510 C13/C14 4.3m
Plug 9
Plug 10
Plug 11
Plug 12 D2 Enclosure #36 Left 39M5510 C13/C14 4.3m

Page 14
Power Labeling Rack 1- 8

Doc Part # 02JE469


ECO#N47076S
Multi Rack Multi Rack Multi Rack Multi Rack
Rack 1 RPC Power Connection Labeling Enclosures 1 – 5 Rack 2 RPC Power Connection Labeling Enclosures 6 – 10 Rack 3 RPC Power Connection Labeling Enclosures 11 – 15 Rack 4 RPC Power Connection Labeling Enclosures 16 – 20
Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text

RPC6_P6 to ENC#5_RP ENC#5_RP to RPC6_P6 RPC6_P6 to ENC#10_RP ENC#10_RP to RPC6_P6 RPC6_P6 to ENC#15_RP ENC#15_RP to RPC6_P6 RPC6_P6 to ENC#20_RP ENC#20_RP to RPC6_P6
RPC5_P6 to ENC#5_LP ENC#5_LP to RPC5_P6 RPC5_P6 to ENC#10_LP ENC#10_LP to RPC5_P6 RPC5_P6 to ENC#15_LP ENC#15_LP to RPC5_P6 RPC5_P6 to ENC#20_LP ENC#20_LP to RPC5_P6
RPC4_P2 to STRGW2_RP STRGW2_RP to RPC4_P2 RPC4_P4 to ENC#8_RP ENC#8_RP to RPC4_P4 RPC4_P4 to ENC#13_RP ENC#13_RP to RPC4_P4 RPC4_P4 to ENC#18_RP ENC#18_RP to RPC4_P4
RPC4_P4 to ENC#3_RP ENC#3_RP to RPC4_P4 RPC4_P10 to ENC#9_RP ENC#9_RP to RPC4_P10 RPC4_P7 to SPINESWB_RP SPINESWB_RP to RPC4_P7 RPC4_P10 to ENC#19_RP ENC#19_RP to RPC4_P10
RPC4_P10 to ENC#4_RP ENC#4_RP to RPC4_P10 RPC3_P4 to ENC#8_LP ENC#8_LP to RPC3_P4 RPC4_P10 to ENC#14_RP ENC#14_RP to RPC4_P10 RPC3_P4 to ENC#18_LP ENC#18_LP to RPC3_P4
RPC3_P2 to STRGW2_LP STRGW2_LP to RPC3_P2 RPC3_P10 to ENC#9_LP ENC#9_LP to RPC3_P10 RPC4_P11 to SPINESWA_RP SPINESWA_RP to RPC4_P11 RPC3_P10 to ENC#19_LP ENC#19_LP to RPC3_P10
RPC3_P4 to ENC#3_LP ENC#3_LP to RPC3_P4 RPC2_P8 to ENC#7_RP ENC#7_RP to RPC2_P8 RPC3_P4 to ENC#13_LP ENC#13_LP to RPC3_P4 RPC2_P1 to MGTSW4A_RP MGTSW4A_RP to RPC2_P1
RPC3_P10 to ENC#4_LP ENC#4_LP to RPC3_P10 RPC2_P12 to ENC#6_RP ENC#6_RP to RPC2_P12 RPC3_P7 to SPINESWB_LP SPINESWB_LP to RPC3_P7 RPC2_P8 to ENC#17_RP ENC#17_RP to RPC2_P8
RPC2_P1 to MGTSW1A_RP MGTSW1A_RP to RPC2_P1 RPC1_P8 to ENC#7_LP ENC#7_LP to RPC1_P8 RPC3_P10 to ENC#14_LP ENC#14_LP to RPC3_P10 RPC2_P12 to ENC#16_RP ENC#16_RP to RPC2_P12
RPC2_P3 to FABSW1B_RP FABSW1B_RP to RPC2_P3 RPC1_P12 to ENC#6_LP ENC#6_LP to RPC1_P12 RPC3_P11 to SPINESWA_LP SPINESWA_LP to RPC3_P11 RPC1_P1 to MGTSW4A_LP MGTSW4A_LP to RPC1_P1
RPC2_P5 to FABSW1A_RP FABSW1A_RP to RPC2_P5 RPC2_P1 to MGTSW3A_RP MGTSW3A_RP to RPC2_P1 RPC1_P8 to ENC#17_LP ENC#17_LP to RPC1_P8
RPC2_P7 to MGTSW2A_RP MGTSW2A_RP to RPC2_P7 RPC2_P2 to STRGW3_RP STRGW3_RP to RPC2_P2 RPC1_P12 to ENC#16_LP ENC#16_LP to RPC1_P12
RPC2_P8 to ENC#2_RP ENC#2_RP to RPC2_P8 RPC2_P3 to FABSW2B_RP FABSW2B_RP to RPC2_P3
RPC2_P11 to STRGW1_RP STRGW1_RP to RPC2_11 RPC2_P5 to FABSW2A_RP FABSW2A_RP to RPC2_P5
RPC2_P12 to ENC#1_RP ENC#1_RP to RPC2_P12 RPC2_P8 to ENC#12_RP ENC#12_RP to RPC2_P8
RPC1_P1 to MGTSW1A_LP MGTSW1A_LP to RPC1_P1 RPC2_P9 to HUBSW_RP HUBSW_RP to RPC2_P9
RPC1_P3 to FABSW1B_LP FABSW1B_LP to RPC1_P3 RPC2_P12 to ENC#11_RP ENC#11_RP to RPC2_P12
RPC1_P5 to FABSW1A_LP FABSW1A_LP to RPC1_P5 RPC1_P1 to MGTSW3A_LP MGTSW3A_LP to RPC1_P1
RPC1_P7 to MGTSW2A_LP MGTSW2A_LP to RPC1_P7 RPC1_P2 to STRGW3_LP STRGW3_LP to RPC1_P2
RPC1_P8 to ENC#2_LP ENC#2_LP to RPC1_P8 RPC1_P3 to FABSW2B_LP FABSW2B_LP to RPC1_P3
RPC1_P11 to STRGW1_LP STRGW1_LP to RPC1_P11 RPC1_P5 to FABSW2A_LP FABSW2A_LP to RPC1_P5
RPC1_P12 to ENC#1_LP ENC#1_LP to RPC1_P12 RPC1_P8 to ENC#12_LP ENC#12_LP to RPC1_P8
RPC1_P9 to HUBSW_LP HUBSW_LP to RPC1_P9
RPC1_P12 to ENC#11_LP ENC#11_LP to RPC1_P12

Multi Rack Multi Rack Multi Rack Multi Rack


Rack 5 RPC Power Connection Labeling Enclosures 21 – 25 Rack 6 RPC Power Connection Labeling Enclosures 26 – 30 Rack 7 RPC Power Connection Labeling Enclosures 31 – 35 Rack 8 RPC Power Connection Labeling Enclosures 36 – 40
Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text

RPC6_P6 to ENC#25_RP ENC#25_RP to RPC6_P6 RPC6_P6 to ENC#30_RP ENC#30_RP to RPC6_P6 RPC6_P6 to ENC#35_RP ENC#35_RP to RPC6_P6 RPC6_P6 to ENC#40_RP ENC#40_RP to RPC6_P6
RPC5_P6 to ENC#25_LP ENC#25_LP to RPC5_P6 RPC5_P6 to ENC#30_LP ENC#30_LP to RPC5_P6 RPC5_P6 to ENC#35_LP ENC#25_LP to RPC5_P6 RPC5_P6 to ENC#40_LP ENC#40_LP to RPC5_P6
RPC4_P4 to ENC#23_RP ENC#23_RP to RPC4_P4 RPC4_P4 to ENC#28_RP ENC#28_RP to RPC4_P4 RPC4_P4 to ENC#33_RP ENC#33_RP to RPC4_P4 RPC4_P4 to ENC#38_RP ENC#38_RP to RPC4_P4
RPC4_P10 to ENC#24_RP ENC#24_RP to RPC4_P10 RPC4_P10 to ENC#29_RP ENC#29_RP to RPC4_P10 RPC4_P10 to ENC#34_RP ENC#34_RP to RPC4_P10 RPC4_P10 to ENC#39_RP ENC#39_RP to RPC4_P10
RPC3_P4 to ENC#23_LP ENC#23_LP to RPC3_P4 RPC3_P4 to ENC#28_LP ENC#28_LP to RPC3_P4 RPC3_P4 to ENC#33_LP ENC#33_LP to RPC3_P4 RPC3_P4 to ENC#38_LP ENC#38_LP to RPC3_P4
RPC3_P10 to ENC#24_LP ENC#24_LP to RPC3_P10 RPC3_P10 to ENC#29_LP ENC#29_LP to RPC3_P10 RPC3_P10 to ENC#34_LP ENC#34_LP to RPC3_P10 RPC3_P10 to ENC#39_LP ENC#39_LP to RPC3_P10
RPC2_P1 to MGTSW5A_RP MGTSW5A_RP to RPC2_P1 RPC2_P1 to MGTSW6A_RP MGTSW6A_RP to RPC2_P1 RPC2_P1 to MGTSW7A_RP MGTSW7A_RP to RPC2_P1 RPC2_P1 to MGTSW8A_RP MGTSW8A_RP to RPC2_P1
RPC2_P3 to FABSW3B_RP FABSW3B_RP to RPC2_P3 RPC2_P8 to ENC#27_RP ENC#27_RP to RPC2_P8 RPC2_P3 to FABSW4B_RP FABSW4B_RP to RPC2_P3 RPC2_P8 to ENC#37_RP ENC#37_RP to RPC2_P8
RPC2_P5 to FABSW3A_RP FABSW3A_RP to RPC2_P5 RPC2_P12 to ENC#26_RP ENC#26_RP to RPC2_P12 RPC2_P5 to FABSW4A_RP FABSW4A_RP to RPC2_P5 RPC2_P12 to ENC#36_RP ENC#36_RP to RPC2_P12
RPC2_P8 to ENC#22_RP ENC#22_RP to RPC2_P8 RPC1_P1 to MGTSW6A_LP MGTSW6A_LP to RPC1_P1 RPC2_P8 to ENC#32_RP ENC#32_RP to RPC2_P8 RPC1_P1 to MGTSW8A_LP MGTSW8A_LP to RPC1_P1
RPC2_P12 to ENC#21_RP ENC#21_RP to RPC2_P12 RPC1_P8 to ENC#27_LP ENC#27_LP to RPC1_P8 RPC2_P12 to ENC#31_RP ENC#31_RP to RPC2_P12 RPC1_P8 to ENC#37_LP ENC#37_LP to RPC1_P8
RPC1_P1 to MGTSW5A_LP MGTSW5A_LP to RPC1_P1 RPC1_P12 to ENC#26_LP ENC#26_LP to RPC1_P12 RPC1_P1 to MGTSW7A_LP MGTSW7A_LP to RPC1_P1 RPC1_P12 to ENC#36_LP ENC#36_LP to RPC1_P12
RPC1_P3 to FABSW3B_LP FABSW3B_LP to RPC1_P3 RPC1_P3 to FABSW4B_LP FABSW4B_LP to RPC1_P3
RPC1_P5 to FABSW3A_LP FABSW3A_LP to RPC1_P5 RPC1_P5 to FABSW4A_LP FABSW4A_LP to RPC1_P5
RPC1_P8 to ENC#22_LP ENC#22_LP to RPC1_P8 RPC1_P8 to ENC#32_LP ENC#32_LP to RPC1_P8
RPC1_P12 to ENC#21_LP ENC#21_LP to RPC1_P12 RPC1_P12 to ENC#31_LP ENC#31_LP to RPC1_P12

Base+ 1, 2 and 4
Rack 1 RPC Power Connection Labeling Enclosures 1 – 6
Side A Permanent Label Text Side B Permanent Label Text

RPC6_P2 to ENC#6_RP ENC#6_RP to RPC6_P2


RPC6_P6 to ENC#5_RP ENC#5_RP to RPC6_P6
RPC5_P2 to ENC#6_LP ENC#6_LP to RPC5_P2
RPC5_P6 to ENC#5_LP ENC#5_LP to RPC5_P6
RPC4_P4 to ENC#3_RP ENC#3_RP to RPC4_P4
RPC4_P10 to ENC#4_RP ENC#4_RP to RPC4_P10
RPC3_P4 to ENC#3_LP ENC#3_LP to RPC3_P4
RPC3_P10 to ENC#4_LP ENC#4_LP to RPC3_P10
RPC2_P1 to MGTSW1A_RP MGTSW1A_RP to RPC2_P1
RPC2_P3 to FABSW1B_RP FABSW1B_RP to RPC2_P3
RPC2_P5 to FABSW1A_RP FABSW1A_RP to RPC2_P5
RPC2_P7 to MGTSW2A_RP MGTSW2A_RP to RPC2_P7
RPC2_P8 to ENC#2_RP ENC#2_RP to RPC2_P8
RPC2_P12 to ENC#1_RP ENC#1_RP to RPC2_P12
RPC1_P1 to MGTSW1A_LP MGTSW1A_LP to RPC1_P1
RPC1_P3 to FABSW1B_LP FABSW1B_LP to RPC1_P3
RPC1_P5 to FABSW1A_LP FABSW1A_LP to RPC1_P5
RPC1_P7 to MGTSW2A_LP MGTSW2A_LP to RPC1_P7
RPC1_P8 to ENC#2_LP ENC#2_LP to RPC1_P8
RPC1_P12 to ENC#1_LP ENC#1_LP to RPC1_P12

Page 15
Fabric Switch Labeling 1A, 1B,

Doc Part # 02JE469


ECO#N47076S

Fabric Cable labeling Enclosures 1 - 5 Fabric Cable labeling Enclosures 6 - 10 Fabric Cable labeling Enclosures 11 - 15 Fabric Cable labeling Enclosures 16 - 20
Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text

ENC#5-S4_P2 to FABSW1B_P20 FABSW1B_P20 to ENC#5-S4_P2 ENC#10-S4_P2 to FABSW1B_P40 FABSW1B_P40 to ENC#10-S4_P2 ENC#15-S4_P2 to FABSW2B_P20 FABSW2B_P20 to ENC#15-S4_P2 ENC#20-S4_P2 to FABSW2B_P40 FABSW2B_P40 to ENC#20-S4_P2
ENC#5-S4_P1 to FABSW1A_P20 FABSW1A_P20 to ENC#5-S4_P1 ENC#10-S4_P1 to FABSW1A_P40 FABSW1A_P40 to ENC#10-S4_P1 ENC#15-S4_P1 to FABSW2A_P20 FABSW2A_P20 to ENC#15-S4_P1 ENC#20-S4_P1 to FABSW2A_P40 FABSW2A_P40 to ENC#20-S4_P1
ENC#5-S3_P2 to FABSW1B_P19 FABSW1B_P19 to ENC#5-S3_P2 ENC#10-S3_P2 to FABSW1B_P39 FABSW1B_P39 to ENC#10-S3_P2 ENC#15-S3_P2 to FABSW2B_P19 FABSW2B_P19 to ENC#15-S3_P2 ENC#20-S3_P2 to FABSW2B_P39 FABSW2B_P39 to ENC#20-S3_P2
ENC#5-S3_P1 to FABSW1A_P19 FABSW1A_P19 to ENC#5-S3_P1 ENC#10-S3_P1 to FABSW1A_P39 FABSW1A_P39 to ENC#10-S3_P1 ENC#15-S3_P1 to FABSW2A_P19 FABSW2A_P19 to ENC#15-S3_P1 ENC#20-S3_P1 to FABSW2A_P39 FABSW2A_P39 to ENC#20-S3_P1
ENC#5-S2_P2 to FABSW1B_P18 FABSW1B_P18 to ENC#5-S2_P2 ENC#10-S2_P2 to FABSW1B_P38 FABSW1B_P38 to ENC#10-S2_P2 ENC#15-S2_P2 to FABSW2B_P18 FABSW2B_P18 to ENC#15-S2_P2 ENC#20-S2_P2 to FABSW2B_P38 FABSW2B_P38 to ENC#20-S2_P2
ENC#5-S2_P1 to FABSW1A_P18 FABSW1A_P18 to ENC#5-S2_P1 ENC#10-S2_P1 to FABSW1A_P38 FABSW1A_P38 to ENC#10-S2_P1 ENC#15-S2_P1 to FABSW2A_P18 FABSW2A_P18 to ENC#15-S2_P1 ENC#20-S2_P1 to FABSW2A_P38 FABSW2A_P38 to ENC#20-S2_P1
ENC#5-S1_P2 to FABSW1B_P17 FABSW1B_P17 to ENC#5-S1_P2 ENC#10-S1_P2 to FABSW1B_P37 FABSW1B_P37 to ENC#10-S1_P2 ENC#15-S1_P2 to FABSW2B_P17 FABSW2B_P17 to ENC#15-S1_P2 ENC#20-S1_P2 to FABSW2B_P37 FABSW2B_P37 to ENC#20-S1_P2
ENC#5-S1_P1 to FABSW1A_P17 FABSW1A_P17 to ENC#5-S1_P1 ENC#10-S1_P1 to FABSW1A_P37 FABSW1A_P37 to ENC#10-S1_P1 ENC#15-S1_P1 to FABSW2A_P17 FABSW2A_P17 to ENC#15-S1_P1 ENC#20-S1_P1 to FABSW2A_P37 FABSW2A_P37 to ENC#20-S1_P1
ENC#4-S4_P2 to FABSW1B_P16 FABSW1B_P16 to ENC#4-S4_P2 ENC#9-S4_P2 to FABSW1B_P36 FABSW1B_P36 to ENC#9-S4_P2 ENC#14-S4_P2 to FABSW2B_P16 FABSW2B_P16 to ENC#14-S4_P2 ENC#19-S4_P2 to FABSW2B_P36 FABSW2B_P36 to ENC#19-S4_P2
ENC#4-S4_P1 to FABSW1A_P16 FABSW1A_P16 to ENC#4-S4_P1 ENC#9-S4_P1 to FABSW1A_P36 FABSW1A_P36 to ENC#9-S4_P1 ENC#14-S4_P1 to FABSW2A_P16 FABSW2A_P16 to ENC#14-S4_P1 ENC#19-S4_P1 to FABSW2A_P36 FABSW2A_P36 to ENC#19-S4_P1
ENC#4-S3_P2 to FABSW1B_P15 FABSW1B_P15 to ENC#4-S3_P2 ENC#9-S3_P2 to FABSW1B_P35 FABSW1B_P35 to ENC#9-S3_P2 ENC#14-S3_P2 to FABSW2B_P15 FABSW2B_P15 to ENC#14-S3_P2 ENC#19-S3_P2 to FABSW2B_P35 FABSW2B_P35 to ENC#19-S3_P2
ENC#4-S3_P1 to FABSW1A_P15 FABSW1A_P15 to ENC#4-S3_P1 ENC#9-S3_P1 to FABSW1A_P35 FABSW1A_P35 to ENC#9-S3_P1 ENC#14-S3_P1 to FABSW2A_P15 FABSW2A_P15 to ENC#14-S3_P1 ENC#19-S3_P1 to FABSW2A_P35 FABSW2A_P35 to ENC#19-S3_P1
ENC#4-S2_P2 to FABSW1B_P14 FABSW1B_P14 to ENC#4-S2_P2 ENC#9-S2_P2 to FABSW1B_P34 FABSW1B_P34 to ENC#9-S2_P2 ENC#14-S2_P2 to FABSW2B_P14 FABSW2B_P14 to ENC#14-S2_P2 ENC#19-S2_P2 to FABSW2B_P34 FABSW2B_P34 to ENC#19-S2_P2
ENC#4-S2_P1 to FABSW1A_P14 FABSW1A_P14 to ENC#4-S2_P1 ENC#9-S2_P1 to FABSW1A_P34 FABSW1A_P34 to ENC#9-S2_P1 ENC#14-S2_P1 to FABSW2A_P14 FABSW2A_P14 to ENC#14-S2_P1 ENC#19-S2_P1 to FABSW2A_P34 FABSW2A_P34 to ENC#19-S2_P1
ENC#4-S1_P2 to FABSW1B_P13 FABSW1B_P13 to ENC#4-S1_P2 ENC#9-S1_P2 to FABSW1B_P33 FABSW1B_P33 to ENC#9-S1_P2 ENC#14-S1_P2 to FABSW2B_P13 FABSW2B_P13 to ENC#14-S1_P2 ENC#19-S1_P2 to FABSW2B_P33 FABSW2B_P33 to ENC#19-S1_P2
ENC#4-S1_P1 to FABSW1A_P13 FABSW1A_P13 to ENC#4-S1_P1 ENC#9-S1_P1 to FABSW1A_P33 FABSW1A_P33 to ENC#9-S1_P1 ENC#14-S1_P1 to FABSW2A_P13 FABSW2A_P13 to ENC#14-S1_P1 ENC#19-S1_P1 to FABSW2A_P33 FABSW2A_P33 to ENC#19-S1_P1
ENC#3-S4_P2 to FABSW1B_P12 FABSW1B_P12 to ENC#3-S4_P2 ENC#8-S4_P2 to FABSW1B_P32 FABSW1B_P32 to ENC#8-S4_P2 ENC#13-S4_P2 to FABSW2B_P12 FABSW2B_P12 to ENC#13-S4_P2 ENC#18-S4_P2 to FABSW2B_P32 FABSW2B_P32 to ENC#18-S4_P2
ENC#3-S4_P1 to FABSW1A_P12 FABSW1A_P12 to ENC#3-S4_P1 ENC#8-S4_P1 to FABSW1A_P32 FABSW1A_P32 to ENC#8-S4_P1 ENC#13-S4_P1 to FABSW2A_P12 FABSW2A_P12 to ENC#13-S4_P1 ENC#18-S4_P1 to FABSW2A_P32 FABSW2A_P32 to ENC#18-S4_P1
ENC#3-S3_P2 to FABSW1B_P11 FABSW1B_P11 to ENC#3-S3_P2 ENC#8-S3_P2 to FABSW1B_P31 FABSW1B_P31 to ENC#8-S3_P2 ENC#13-S3_P2 to FABSW2B_P11 FABSW2B_P11 to ENC#13-S3_P2 ENC#18-S3_P2 to FABSW2B_P31 FABSW2B_P31 to ENC#18-S3_P2
ENC#3-S3_P1 to FABSW1A_P11 FABSW1A_P11 to ENC#3-S3_P1 ENC#8-S3_P1 to FABSW1A_P31 FABSW1A_P31 to ENC#8-S3_P1 ENC#13-S3_P1 to FABSW2A_P11 FABSW2A_P11 to ENC#13-S3_P1 ENC#18-S3_P1 to FABSW2A_P31 FABSW2A_P31 to ENC#18-S3_P1
ENC#3-S2_P2 to FABSW1B_P10 FABSW1B_P10 to ENC#3-S2_P2 ENC#8-S2_P2 to FABSW1B_P30 FABSW1B_P30 to ENC#8-S2_P2 ENC#13-S2_P2 to FABSW2B_P10 FABSW2B_P10 to ENC#13-S2_P2 ENC#18-S2_P2 to FABSW2B_P30 FABSW2B_P30 to ENC#18-S2_P2
ENC#3-S2_P1 to FABSW1A_P10 FABSW1A_P10 to ENC#3-S2_P1 ENC#8-S2_P1 to FABSW1A_P30 FABSW1A_P30 to ENC#8-S2_P1 ENC#13-S2_P1 to FABSW2A_P10 FABSW2A_P10 to ENC#13-S2_P1 ENC#18-S2_P1 to FABSW2A_P30 FABSW2A_P30 to ENC#18-S2_P1
ENC#3-S1_P2 to FABSW1B_P9 FABSW1B_P9 to ENC#3-S1_P2 ENC#8-S1_P2 to FABSW1B_P29 FABSW1B_P29 to ENC#8-S1_P2 ENC#13-S1_P2 to FABSW2B_P9 FABSW2B_P9 to ENC#13-S1_P2 ENC#18-S1_P2 to FABSW2B_P29 FABSW2B_P29 to ENC#18-S1_P2
ENC#3-S1_P1 to FABSW1A_P9 FABSW1A_P9 to ENC#3-S1_P1 ENC#8-S1_P1 to FABSW1A_P29 FABSW1A_P29 to ENC#8-S1_P1 ENC#13-S1_P1 to FABSW2A_P9 FABSW2A_P9 to ENC#13-S1_P1 ENC#18-S1_P1 to FABSW2A_P29 FABSW2A_P29 to ENC#18-S1_P1
ENC#2-S4_P2 to FABSW1B_P8 FABSW1B_P8 to ENC#2-S4_P2 ENC#7-S4_P2 to FABSW1B_P28 FABSW1B_P28 to ENC#7-S4_P2 ENC#12-S4_P2 to FABSW2B_P8 FABSW2B_P8 to ENC#12-S4_P2 ENC#17-S4_P2 to FABSW2B_P28 FABSW2B_P28 to ENC#17-S4_P2
ENC#2-S4_P1 to FABSW1A_P8 FABSW1A_P8 to ENC#2-S4_P1 ENC#7-S4_P1 to FABSW1A_P28 FABSW1A_P28 to ENC#7-S4_P1 ENC#12-S4_P1 to FABSW2A_P8 FABSW2A_P8 to ENC#12-S4_P1 ENC#17-S4_P1 to FABSW2A_P28 FABSW2A_P28 to ENC#17-S4_P1
ENC#2-S3_P2 to FABSW1B_P7 FABSW1B_P7 to ENC#2-S3_P2 ENC#7-S3_P2 to FABSW1B_P27 FABSW1B_P27 to ENC#7-S3_P2 ENC#12-S3_P2 to FABSW2B_P7 FABSW2B_P7 to ENC#12-S3_P2 ENC#17-S3_P2 to FABSW2B_P27 FABSW2B_P27 to ENC#17-S3_P2
ENC#2-S3_P1 to FABSW1A_P7 FABSW1A_P7 to ENC#2-S3_P1 ENC#7-S3_P1 to FABSW1A_P27 FABSW1A_P27 to ENC#7-S3_P1 ENC#12-S3_P1 to FABSW2A_P7 FABSW2A_P7 to ENC#12-S3_P1 ENC#17-S3_P1 to FABSW2A_P27 FABSW2A_P27 to ENC#17-S3_P1
ENC#2-S2_P2 to FABSW1B_P6 FABSW1B_P6 to ENC#2-S2_P2 ENC#7-S2_P2 to FABSW1B_P26 FABSW1B_P26 to ENC#7-S2_P2 ENC#12-S2_P2 to FABSW2B_P6 FABSW2B_P6 to ENC#12-S2_P2 ENC#17-S2_P2 to FABSW2B_P26 FABSW2B_P26 to ENC#17-S2_P2
ENC#2-S2_P1 to FABSW1A_P6 FABSW1A_P6 to ENC#2-S2_P1 ENC#7-S2_P1 to FABSW1A_P26 FABSW1A_P26 to ENC#7-S2_P1 ENC#12-S2_P1 to FABSW2A_P6 FABSW2A_P6 to ENC#12-S2_P1 ENC#17-S2_P1 to FABSW2A_P26 FABSW2A_P26 to ENC#17-S2_P1
ENC#2-S1_P2 to FABSW1B_P5 FABSW1B_P5 to ENC#2-S1_P2 ENC#7-S1_P2 to FABSW1B_P25 FABSW1B_P25 to ENC#7-S1_P2 ENC#12-S1_P2 to FABSW2B_P5 FABSW2B_P5 to ENC#12-S1_P2 ENC#17-S1_P2 to FABSW2B_P25 FABSW2B_P25 to ENC#17-S1_P2
ENC#2-S1_P1 to FABSW1A_P5 FABSW1A_P5 to ENC#2-S1_P1 ENC#7-S1_P1 to FABSW1A_P25 FABSW1A_P25 to ENC#7-S1_P1 ENC#12-S1_P1 to FABSW2A_P5 FABSW2A_P5 to ENC#12-S1_P1 ENC#17-S1_P1 to FABSW2A_P25 FABSW2A_P25 to ENC#17-S1_P1
ENC#1-S4_P2 to FABSW1B_P4 FABSW1B_P4 to ENC#1-S4_P2 ENC#6-S4_P2 to FABSW1B_P24 FABSW1B_P24 to ENC#6-S4_P2 ENC#11-S4_P2 to FABSW2B_P4 FABSW2B_P4 to ENC#11-S4_P2 ENC#16-S4_P2 to FABSW2B_P24 FABSW2B_P24 to ENC#16-S4_P2
ENC#1-S4_P1 to FABSW1A_P4 FABSW1A_P4 to ENC#1-S4_P1 ENC#6-S4_P1 to FABSW1A_P24 FABSW1A_P24 to ENC#6-S4_P1 ENC#11-S4_P1 to FABSW2A_P4 FABSW2A_P4 to ENC#11-S4_P1 ENC#16-S4_P1 to FABSW2A_P24 FABSW2A_P24 to ENC#16-S4_P1
ENC#1-S3_P2 to FABSW1B_P3 FABSW1B_P3 to ENC#1-S3_P2 ENC#6-S3_P2 to FABSW1B_P23 FABSW1B_P23 to ENC#6-S3_P2 ENC#11-S3_P2 to FABSW2B_P3 FABSW2B_P3 to ENC#11-S3_P2 ENC#16-S3_P2 to FABSW2B_P23 FABSW2B_P23 to ENC#16-S3_P2
ENC#1-S3_P1 to FABSW1A_P3 FABSW1A_P3 to ENC#1-S3_P1 ENC#6-S3_P1 to FABSW1A_P23 FABSW1A_P23 to ENC#6-S3_P1 ENC#11-S3_P1 to FABSW2A_P3 FABSW2A_P3 to ENC#11-S3_P1 ENC#16-S3_P1 to FABSW2A_P23 FABSW2A_P23 to ENC#16-S3_P1
ENC#1-S2_P2 to FABSW1B_P2 FABSW1B_P2 to ENC#1-S2_P2 ENC#6-S2_P2 to FABSW1B_P22 FABSW1B_P22 to ENC#6-S2_P2 ENC#11-S2_P2 to FABSW2B_P2 FABSW2B_P2 to ENC#11-S2_P2 ENC#16-S2_P2 to FABSW2B_P22 FABSW2B_P22 to ENC#16-S2_P2
ENC#1-S2_P1 to FABSW1A_P2 FABSW1A_P2 to ENC#1-S2_P1 ENC#6-S2_P1 to FABSW1A_P22 FABSW1A_P22 to ENC#6-S2_P1 ENC#11-S2_P1 to FABSW2A_P2 FABSW2A_P2 to ENC#11-S2_P1 ENC#16-S2_P1 to FABSW2A_P22 FABSW2A_P22 to ENC#16-S2_P1
ENC#1-S1_P2 to FABSW1B_P1 FABSW1B_P1 to ENC#1-S1_P2 ENC#6-S1_P2 to FABSW1B_P21 FABSW1B_P21 to ENC#6-S1_P2 ENC#11-S1_P2 to FABSW2B_P1 FABSW2B_P1 to ENC#11-S1_P2 ENC#16-S1_P2 to FABSW2B_P21 FABSW2B_P21 to ENC#16-S1_P2
ENC#1-S1_P1 to FABSW1A_P1 FABSW1A_P1 to ENC#1-S1_P1 ENC#6-S1_P1 to FABSW1A_P21 FABSW1A_P21 to ENC#6-S1_P1 ENC#11-S1_P1 to FABSW2A_P1 FABSW2A_P1 to ENC#11-S1_P1 ENC#16-S1_P1 to FABSW2A_P21 FABSW2A_P21 to ENC#16-S1_P1
FABSW1A_P44 to FABSW1B_P44 FABSW1B_P44 to FABSW1A_P44 FABSW2A_P44 to FABSW2B_P44 FABSW2B_P44 to FABSW2A_P44
FABSW1A_P43 to FABSW1B_P43 FABSW1B_P43 to FABSW1A_P43 FABSW2A_P43 to FABSW2B_P43 FABSW2B_P43 to FABSW2A_P43
FABSW1A_P42 to FABSW1B_P42 FABSW1B_P42 to FABSW1A_P42 FABSW2A_P42 to FABSW2B_P42 FABSW2B_P42 to FABSW2A_P42
FABSW1A_P41 to FABSW1B_P41 FABSW1B_P41 to FABSW1A_P41 FABSW2A_P41 to FABSW2B_P41 FABSW2B_P41 to FABSW2A_P41

Page 16
Fabric Switch Labeling 3A, 3B,

Doc Part # 02JE469


ECO#N47076S

Fabric Cable labeling Enclosures 21 - 25 Fabric Cable labeling Enclosures 26 - 30 Fabric Cable labeling Enclosures 31 - 35 Fabric Cable labeling Enclosures 36 - 40
Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text

ENC#25-S4_P2 to FABSW3B_P20 FABSW3B_P20 to ENC#25-S4_P2 ENC#30-S4_P2 to FABSW3B_P40 FABSW3B_P40 to ENC#30-S4_P2 ENC#35-S4_P2 to FABSW4B_P20 FABSW4B_P20 to ENC#35-S4_P2 ENC#40-S4_P2 to FABSW4B_P40 FABSW4B_P40 to ENC#40-S4_P2
ENC#25-S4_P1 to FABSW3A_P20 FABSW3A_P20 to ENC#25-S4_P1 ENC#30-S4_P1 to FABSW3A_P40 FABSW3A_P40 to ENC#30-S4_P1 ENC#35-S4_P1 to FABSW4A_P20 FABSW4A_P20 to ENC#35-S4_P1 ENC#40-S4_P1 to FABSW4A_P40 FABSW4A_P40 to ENC#40-S4_P1
ENC#25-S3_P2 to FABSW3B_P19 FABSW3B_P19 to ENC#25-S3_P2 ENC#30-S3_P2 to FABSW3B_P39 FABSW3B_P39 to ENC#30-S3_P2 ENC#35-S3_P2 to FABSW4B_P19 FABSW4B_P19 to ENC#35-S3_P2 ENC#40-S3_P2 to FABSW4B_P39 FABSW4B_P39 to ENC#40-S3_P2
ENC#25-S3_P1 to FABSW3A_P19 FABSW3A_P19 to ENC#25-S3_P1 ENC#30-S3_P1 to FABSW3A_P39 FABSW3A_P39 to ENC#30-S3_P1 ENC#35-S3_P1 to FABSW4A_P19 FABSW4A_P19 to ENC#35-S3_P1 ENC#40-S3_P1 to FABSW4A_P39 FABSW4A_P39 to ENC#40-S3_P1
ENC#25-S2_P2 to FABSW3B_P18 FABSW3B_P18 to ENC#25-S2_P2 ENC#30-S2_P2 to FABSW3B_P38 FABSW3B_P38 to ENC#30-S2_P2 ENC#35-S2_P2 to FABSW4B_P18 FABSW4B_P18 to ENC#35-S2_P2 ENC#40-S2_P2 to FABSW4B_P38 FABSW4B_P38 to ENC#40-S2_P2
ENC#25-S2_P1 to FABSW3A_P18 FABSW3A_P18 to ENC#25-S2_P1 ENC#30-S2_P1 to FABSW3A_P38 FABSW3A_P38 to ENC#30-S2_P1 ENC#35-S2_P1 to FABSW4A_P18 FABSW4A_P18 to ENC#35-S2_P1 ENC#40-S2_P1 to FABSW4A_P38 FABSW4A_P38 to ENC#40-S2_P1
ENC#25-S1_P2 to FABSW3B_P17 FABSW3B_P17 to ENC#25-S1_P2 ENC#30-S1_P2 to FABSW3B_P37 FABSW3B_P37 to ENC#30-S1_P2 ENC#35-S1_P2 to FABSW4B_P17 FABSW4B_P17 to ENC#35-S1_P2 ENC#40-S1_P2 to FABSW4B_P37 FABSW4B_P37 to ENC#40-S1_P2
ENC#25-S1_P1 to FABSW3A_P17 FABSW3A_P17 to ENC#25-S1_P1 ENC#30-S1_P1 to FABSW3A_P37 FABSW3A_P37 to ENC#30-S1_P1 ENC#35-S1_P1 to FABSW4A_P17 FABSW4A_P17 to ENC#35-S1_P1 ENC#40-S1_P1 to FABSW4A_P37 FABSW4A_P37 to ENC#40-S1_P1
ENC#24-S4_P2 to FABSW3B_P16 FABSW3B_P16 to ENC#24-S4_P2 ENC#29-S4_P2 to FABSW3B_P36 FABSW3B_P36 to ENC#29-S4_P2 ENC#34-S4_P2 to FABSW4B_P16 FABSW4B_P16 to ENC#34-S4_P2 ENC#39-S4_P2 to FABSW4B_P36 FABSW4B_P36 to ENC#39-S4_P2
ENC#24-S4_P1 to FABSW3A_P16 FABSW3A_P16 to ENC#24-S4_P1 ENC#29-S4_P1 to FABSW3A_P36 FABSW3A_P36 to ENC#29-S4_P1 ENC#34-S4_P1 to FABSW4A_P16 FABSW4A_P16 to ENC#34-S4_P1 ENC#39-S4_P1 to FABSW4A_P36 FABSW4A_P36 to ENC#39-S4_P1
ENC#24-S3_P2 to FABSW3B_P15 FABSW3B_P15 to ENC#24-S3_P2 ENC#29-S3_P2 to FABSW3B_P35 FABSW3B_P35 to ENC#29-S3_P2 ENC#34-S3_P2 to FABSW4B_P15 FABSW4B_P15 to ENC#34-S3_P2 ENC#39-S3_P2 to FABSW4B_P35 FABSW4B_P35 to ENC#39-S3_P2
ENC#24-S3_P1 to FABSW3A_P15 FABSW3A_P15 to ENC#24-S3_P1 ENC#29-S3_P1 to FABSW3A_P35 FABSW3A_P35 to ENC#29-S3_P1 ENC#34-S3_P1 to FABSW4A_P15 FABSW4A_P15 to ENC#34-S3_P1 ENC#39-S3_P1 to FABSW4A_P35 FABSW4A_P35 to ENC#39-S3_P1
ENC#24-S2_P2 to FABSW3B_P14 FABSW3B_P14 to ENC#24-S2_P2 ENC#29-S2_P2 to FABSW3B_P34 FABSW3B_P34 to ENC#29-S2_P2 ENC#34-S2_P2 to FABSW4B_P14 FABSW4B_P14 to ENC#34-S2_P2 ENC#39-S2_P2 to FABSW4B_P34 FABSW4B_P34 to ENC#39-S2_P2
ENC#24-S2_P1 to FABSW3A_P14 FABSW3A_P14 to ENC#24-S2_P1 ENC#29-S2_P1 to FABSW3A_P34 FABSW3A_P34 to ENC#29-S2_P1 ENC#34-S2_P1 to FABSW4A_P14 FABSW4A_P14 to ENC#34-S2_P1 ENC#39-S2_P1 to FABSW4A_P34 FABSW4A_P34 to ENC#39-S2_P1
ENC#24-S1_P2 to FABSW3B_P13 FABSW3B_P13 to ENC#24-S1_P2 ENC#29-S1_P2 to FABSW3B_P33 FABSW3B_P33 to ENC#29-S1_P2 ENC#34-S1_P2 to FABSW4B_P13 FABSW4B_P13 to ENC#34-S1_P2 ENC#39-S1_P2 to FABSW4B_P33 FABSW4B_P33 to ENC#39-S1_P2
ENC#24-S1_P1 to FABSW3A_P13 FABSW3A_P13 to ENC#24-S1_P1 ENC#29-S1_P1 to FABSW3A_P33 FABSW3A_P33 to ENC#29-S1_P1 ENC#34-S1_P1 to FABSW4A_P13 FABSW4A_P13 to ENC#34-S1_P1 ENC#39-S1_P1 to FABSW4A_P33 FABSW4A_P33 to ENC#39-S1_P1
ENC#23-S4_P2 to FABSW3B_P12 FABSW3B_P12 to ENC#23-S4_P2 ENC#28-S4_P2 to FABSW3B_P32 FABSW3B_P32 to ENC#28-S4_P2 ENC#33-S4_P2 to FABSW4B_P12 FABSW4B_P12 to ENC#33-S4_P2 ENC#38-S4_P2 to FABSW4B_P32 FABSW4B_P32 to ENC#38-S4_P2
ENC#23-S4_P1 to FABSW3A_P12 FABSW3A_P12 to ENC#23-S4_P1 ENC#28-S4_P1 to FABSW3A_P32 FABSW3A_P32 to ENC#28-S4_P1 ENC#33-S4_P1 to FABSW4A_P12 FABSW4A_P12 to ENC#33-S4_P1 ENC#38-S4_P1 to FABSW4A_P32 FABSW4A_P32 to ENC#38-S4_P1
ENC#23-S3_P2 to FABSW3B_P11 FABSW3B_P11 to ENC#23-S3_P2 ENC#28-S3_P2 to FABSW3B_P31 FABSW3B_P31 to ENC#28-S3_P2 ENC#33-S3_P2 to FABSW4B_P11 FABSW4B_P11 to ENC#33-S3_P2 ENC#38-S3_P2 to FABSW4B_P31 FABSW4B_P31 to ENC#38-S3_P2
ENC#23-S3_P1 to FABSW3A_P11 FABSW3A_P11 to ENC#23-S3_P1 ENC#28-S3_P1 to FABSW3A_P31 FABSW3A_P31 to ENC#28-S3_P1 ENC#33-S3_P1 to FABSW4A_P11 FABSW4A_P11 to ENC#33-S3_P1 ENC#38-S3_P1 to FABSW4A_P31 FABSW4A_P31 to ENC#38-S3_P1
ENC#23-S2_P2 to FABSW3B_P10 FABSW3B_P10 to ENC#23-S2_P2 ENC#28-S2_P2 to FABSW3B_P30 FABSW3B_P30 to ENC#28-S2_P2 ENC#33-S2_P2 to FABSW4B_P10 FABSW4B_P10 to ENC#33-S2_P2 ENC#38-S2_P2 to FABSW4B_P30 FABSW4B_P30 to ENC#38-S2_P2
ENC#23-S2_P1 to FABSW3A_P10 FABSW3A_P10 to ENC#23-S2_P1 ENC#28-S2_P1 to FABSW3A_P30 FABSW3A_P30 to ENC#28-S2_P1 ENC#33-S2_P1 to FABSW4A_P10 FABSW4A_P10 to ENC#33-S2_P1 ENC#38-S2_P1 to FABSW4A_P30 FABSW4A_P30 to ENC#38-S2_P1
ENC#23-S1_P2 to FABSW3B_P9 FABSW3B_P9 to ENC#23-S1_P2 ENC#28-S1_P2 to FABSW3B_P29 FABSW3B_P29 to ENC#28-S1_P2 ENC#33-S1_P2 to FABSW4B_P9 FABSW4B_P9 to ENC#33-S1_P2 ENC#38-S1_P2 to FABSW4B_P29 FABSW4B_P29 to ENC#38-S1_P2
ENC#23-S1_P1 to FABSW3A_P9 FABSW3A_P9 to ENC#23-S1_P1 ENC#28-S1_P1 to FABSW3A_P29 FABSW3A_P29 to ENC#28-S1_P1 ENC#33-S1_P1 to FABSW4A_P9 FABSW4A_P9 to ENC#33-S1_P1 ENC#38-S1_P1 to FABSW4A_P29 FABSW4A_P29 to ENC#38-S1_P1
ENC#22-S4_P2 to FABSW3B_P8 FABSW3B_P8 to ENC#22-S4_P2 ENC#27-S4_P2 to FABSW3B_P28 FABSW3B_P28 to ENC#27-S4_P2 ENC#32-S4_P2 to FABSW4B_P8 FABSW4B_P8 to ENC#32-S4_P2 ENC#37-S4_P2 to FABSW4B_P28 FABSW4B_P28 to ENC#37-S4_P2
ENC#22-S4_P1 to FABSW3A_P8 FABSW3A_P8 to ENC#22-S4_P1 ENC#27-S4_P1 to FABSW3A_P28 FABSW3A_P28 to ENC#27-S4_P1 ENC#32-S4_P1 to FABSW4A_P8 FABSW4A_P8 to ENC#32-S4_P1 ENC#37-S4_P1 to FABSW4A_P28 FABSW4A_P28 to ENC#37-S4_P1
ENC#22-S3_P2 to FABSW3B_P7 FABSW3B_P7 to ENC#22-S3_P2 ENC#27-S3_P2 to FABSW3B_P27 FABSW3B_P27 to ENC#27-S3_P2 ENC#32-S3_P2 to FABSW4B_P7 FABSW4B_P7 to ENC#32-S3_P2 ENC#37-S3_P2 to FABSW4B_P27 FABSW4B_P27 to ENC#37-S3_P2
ENC#22-S3_P1 to FABSW3A_P7 FABSW3A_P7 to ENC#22-S3_P1 ENC#27-S3_P1 to FABSW3A_P27 FABSW3A_P27 to ENC#27-S3_P1 ENC#32-S3_P1 to FABSW4A_P7 FABSW4A_P7 to ENC#32-S3_P1 ENC#37-S3_P1 to FABSW4A_P27 FABSW4A_P27 to ENC#37-S3_P1
ENC#22-S2_P2 to FABSW3B_P6 FABSW3B_P6 to ENC#22-S2_P2 ENC#27-S2_P2 to FABSW3B_P26 FABSW3B_P26 to ENC#27-S2_P2 ENC#32-S2_P2 to FABSW4B_P6 FABSW4B_P6 to ENC#32-S2_P2 ENC#37-S2_P2 to FABSW4B_P26 FABSW4B_P26 to ENC#37-S2_P2
ENC#22-S2_P1 to FABSW3A_P6 FABSW3A_P6 to ENC#22-S2_P1 ENC#27-S2_P1 to FABSW3A_P26 FABSW3A_P26 to ENC#27-S2_P1 ENC#32-S2_P1 to FABSW4A_P6 FABSW4A_P6 to ENC#32-S2_P1 ENC#37-S2_P1 to FABSW4A_P26 FABSW4A_P26 to ENC#37-S2_P1
ENC#22-S1_P2 to FABSW3B_P5 FABSW3B_P5 to ENC#22-S1_P2 ENC#27-S1_P2 to FABSW3B_P25 FABSW3B_P25 to ENC#27-S1_P2 ENC#32-S1_P2 to FABSW4B_P5 FABSW4B_P5 to ENC#32-S1_P2 ENC#37-S1_P2 to FABSW4B_P25 FABSW4B_P25 to ENC#37-S1_P2
ENC#22-S1_P1 to FABSW3A_P5 FABSW3A_P5 to ENC#22-S1_P1 ENC#27-S1_P1 to FABSW3A_P25 FABSW3A_P25 to ENC#27-S1_P1 ENC#32-S1_P1 to FABSW4A_P5 FABSW4A_P5 to ENC#32-S1_P1 ENC#37-S1_P1 to FABSW4A_P25 FABSW4A_P25 to ENC#37-S1_P1
ENC#21-S4_P2 to FABSW3B_P4 FABSW3B_P4 to ENC#21-S4_P2 ENC#26-S4_P2 to FABSW3B_P24 FABSW3B_P24 to ENC#26-S4_P2 ENC#31-S4_P2 to FABSW4B_P4 FABSW4B_P4 to ENC#31-S4_P2 ENC#36-S4_P2 to FABSW4B_P24 FABSW4B_P24 to ENC#36-S4_P2
ENC#21-S4_P1 to FABSW3A_P4 FABSW3A_P4 to ENC#21-S4_P1 ENC#26-S4_P1 to FABSW3A_P24 FABSW3A_P24 to ENC#26-S4_P1 ENC#31-S4_P1 to FABSW4A_P4 FABSW4A_P4 to ENC#31-S4_P1 ENC#36-S4_P1 to FABSW4A_P24 FABSW4A_P24 to ENC#36-S4_P1
ENC#21-S3_P2 to FABSW3B_P3 FABSW3B_P3 to ENC#21-S3_P2 ENC#26-S3_P2 to FABSW3B_P23 FABSW3B_P23 to ENC#26-S3_P2 ENC#31-S3_P2 to FABSW4B_P3 FABSW4B_P3 to ENC#31-S3_P2 ENC#36-S3_P2 to FABSW4B_P23 FABSW4B_P23 to ENC#36-S3_P2
ENC#21-S3_P1 to FABSW3A_P3 FABSW3A_P3 to ENC#21-S3_P1 ENC#26-S3_P1 to FABSW3A_P23 FABSW3A_P23 to ENC#26-S3_P1 ENC#31-S3_P1 to FABSW4A_P3 FABSW4A_P3 to ENC#31-S3_P1 ENC#36-S3_P1 to FABSW4A_P23 FABSW4A_P23 to ENC#36-S3_P1
ENC#21-S2_P2 to FABSW3B_P2 FABSW3B_P2 to ENC#21-S2_P2 ENC#26-S2_P2 to FABSW3B_P22 FABSW3B_P22 to ENC#26-S2_P2 ENC#31-S2_P2 to FABSW4B_P2 FABSW4B_P2 to ENC#31-S2_P2 ENC#36-S2_P2 to FABSW4B_P22 FABSW4B_P22 to ENC#36-S2_P2
ENC#21-S2_P1 to FABSW3A_P2 FABSW3A_P2 to ENC#21-S2_P1 ENC#26-S2_P1 to FABSW3A_P22 FABSW3A_P22 to ENC#26-S2_P1 ENC#31-S2_P1 to FABSW4A_P2 FABSW4A_P2 to ENC#31-S2_P1 ENC#36-S2_P1 to FABSW4A_P22 FABSW4A_P22 to ENC#36-S2_P1
ENC#21-S1_P2 to FABSW3B_P1 FABSW3B_P1 to ENC#21-S1_P2 ENC#26-S1_P2 to FABSW3B_P21 FABSW3B_P21 to ENC#26-S1_P2 ENC#31-S1_P2 to FABSW4B_P1 FABSW4B_P1 to ENC#31-S1_P2 ENC#36-S1_P2 to FABSW4B_P21 FABSW4B_P21 to ENC#36-S1_P2
ENC#21-S1_P1 to FABSW3A_P1 FABSW3A_P1 to ENC#21-S1_P1 ENC#26-S1_P1 to FABSW3A_P21 FABSW3A_P21 to ENC#26-S1_P1 ENC#31-S1_P1 to FABSW4A_P1 FABSW4A_P1 to ENC#31-S1_P1 ENC#36-S1_P1 to FABSW4A_P21 FABSW4A_P21 to ENC#36-S1_P1
FABSW3A_P44 to FABSW3B_P44 FABSW3B_P44 to FABSW3A_P44 FABSW4A_P44 to FABSW4B_P44 FABSW4B_P44 to FABSW4A_P44
FABSW3A_P43 to FABSW3B_P43 FABSW3B_P43 to FABSW3A_P43 FABSW4A_P43 to FABSW4B_P43 FABSW4B_P43 to FABSW4A_P43
FABSW3A_P42 to FABSW3B_P42 FABSW3B_P42 to FABSW3A_P42 FABSW4A_P42 to FABSW4B_P42 FABSW4B_P42 to FABSW4A_P42
FABSW3A_P41 to FABSW3B_P41 FABSW3B_P41 to FABSW3A_P41 FABSW4A_P41 to FABSW4B_P41 FABSW4B_P41 to FABSW4A_P41

Page 17
Management Switch Labeling 1A -

Doc Part # 02JE469


ECO#N47076S
Management Switch 1A Management Switch 2A Management Switch 3A Management Switch 4A
Management Cable labeling Enclosures 1 - 5 Management Cable labeling Enclosures 6 - 10 Management Cable labeling Enclosures 11 - 15 Management Cable labeling Enclosures 16 - 20
Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text

FABSW1B-MGMT_P0 to MGTSW1A_P46 MGTSW1A_P46 to FABSW1B-MGMT_P0 MGTSW2A_MGMT to MGTSW1A_P38 MGTSW1A_P38 to MGTSW2A_MGMT MGTSW3A_MGMT to MGTSW1A_P43 MGTSW1A_P43 to MGTSW3A_MGMT MGTSW4A_MGMT to MGTSW3A_P38 MGTSW3A_P38 to MGTSW4A_MGMT
FABSW1A-MGMT_P0 to MGTSW1A_P47 MGTSW1A_P47 to FABSW1A-MGMT_P0 MGTSW2A_P42 to MGTSW1A_P42 MGTSW1A_P42 to MGTSW2A_P42 FABSW2B-MGMT_P0 to MGTSW3A_P46 MGTSW3A_P46 to FABSW2B-MGMT_P0 MGTSW4A_P42 to MGTSW3A_P42 MGTSW3A_P42 to MGTSW4A_P42
ENC#5-EIOM-N4_P1 to MGTSW1A_P25 MGTSW1A_P25 to ENC#5-EIOM-N4_P1 MGTSW2A_P41 to MGTSW1A_P41 MGTSW1A_P41 to MGTSW2A_P41 FABSW2A-MGMT_P0 to MGTSW3A_P47 MGTSW3A_P47 to FABSW2A-MGMT_P0 MGTSW4A_P41 to MGTSW3A_P41 MGTSW3A_P41 to MGTSW4A_P41
ENC#5-EIOM-N3_P1 to MGTSW1A_P24 MGTSW1A_P24 to ENC#5-EIOM-N3_P1 ENC#10-EIOM-N4_P1 to MGTSW2A_P25 MGTSW2A_P25 to ENC#10-EIOM-N4_P1 ENC#15-EIOM-N4_P1 to MGTSW3A_P25 MGTSW3A_P25 to ENC#15-EIOM-N4_P1 ENC#120-EIOM-N4_P1 to MGTSW4A_P25 MGTSW4A_P25 to ENC#120-EIOM-N4_P1
ENC#5-EIOM-N2_P1 to MGTSW1A_P23 MGTSW1A_P23 to ENC#5-EIOM-N2_P1 ENC#10-EIOM-N3_P1 to MGTSW2A_P24 MGTSW2A_P24 to ENC#10-EIOM-N3_P1 ENC#15-EIOM-N3_P1 to MGTSW3A_P24 MGTSW3A_P24 to ENC#15-EIOM-N3_P1 ENC#120-EIOM-N3_P1 to MGTSW4A_P24 MGTSW4A_P24 to ENC#120-EIOM-N3_P1
ENC#5-EIOM-N1_P1 to MGTSW1A_P22 MGTSW1A_P22 to ENC#5-EIOM-N1_P1 ENC#10-EIOM-N2_P1 to MGTSW2A_P23 MGTSW2A_P23 to ENC#10-EIOM-N2_P1 ENC#15-EIOM-N2_P1 to MGTSW3A_P23 MGTSW3A_P23 to ENC#15-EIOM-N2_P1 ENC#120-EIOM-N2_P1 to MGTSW4A_P23 MGTSW4A_P23 to ENC#120-EIOM-N2_P1
ENC#5-SMM_P1 to MGTSW1A_P21 MGTSW1A_P21 to ENC#5-SMM_P1 ENC#10-EIOM-N1_P1 to MGTSW2A_P22 MGTSW2A_P22 to ENC#10-EIOM-N1_P1 ENC#15-EIOM-N1_P1 to MGTSW3A_P22 MGTSW3A_P22 to ENC#15-EIOM-N1_P1 ENC#120-EIOM-N1_P1 to MGTSW4A_P22 MGTSW4A_P22 to ENC#120-EIOM-N1_P1
ENC#4-EIOM-N4_P1 to MGTSW1A_P20 MGTSW1A_P20 to ENC#4-EIOM-N4_P1 ENC#10-SMM_P1 to MGTSW2A_P21 MGTSW2A_P21 to ENC#10-SMM_P1 ENC#15-SMM_P1 to MGTSW3A_P21 MGTSW3A_P21 to ENC#15-SMM_P1 ENC#120-SMM_P1 to MGTSW4A_P21 MGTSW4A_P21 to ENC#120-SMM_P1
ENC#4-EIOM-N3_P1 to MGTSW1A_P19 MGTSW1A_P19 to ENC#4-EIOM-N3_P1 ENC#9-EIOM-N4_P1 to MGTSW2A_P20 MGTSW2A_P20 to ENC#9-EIOM-N4_P1 ENC#14-EIOM-N4_P1 to MGTSW3A_P20 MGTSW3A_P20 to ENC#14-EIOM-N4_P1 ENC#19-EIOM-N4_P1 to MGTSW4A_P20 MGTSW4A_P20 to ENC#19-EIOM-N4_P1
ENC#4-EIOM-N2_P1 to MGTSW1A_P18 MGTSW1A_P18 to ENC#4-EIOM-N2_P1 ENC#9-EIOM-N3_P1 to MGTSW2A_P19 MGTSW2A_P19 to ENC#9-EIOM-N3_P1 ENC#14-EIOM-N3_P1 to MGTSW3A_P19 MGTSW3A_P19 to ENC#14-EIOM-N3_P1 ENC#19-EIOM-N3_P1 to MGTSW4A_P19 MGTSW4A_P19 to ENC#19-EIOM-N3_P1
ENC#4-EIOM-N1_P1 to MGTSW1A_P17 MGTSW1A_P17 to ENC#4-EIOM-N1_P1 ENC#9-EIOM-N2_P1 to MGTSW2A_P18 MGTSW2A_P18 to ENC#9-EIOM-N2_P1 ENC#14-EIOM-N2_P1 to MGTSW3A_P18 MGTSW3A_P18 to ENC#14-EIOM-N2_P1 ENC#19-EIOM-N2_P1 to MGTSW4A_P18 MGTSW4A_P18 to ENC#19-EIOM-N2_P1
ENC#4-SMM_P1 to MGTSW1A_P16 MGTSW1A_P16 to ENC#4-SMM_P1 ENC#9-EIOM-N1_P1 to MGTSW2A_P17 MGTSW2A_P17 to ENC#9-EIOM-N1_P1 ENC#14-EIOM-N1_P1 to MGTSW3A_P17 MGTSW3A_P17 to ENC#14-EIOM-N1_P1 ENC#19-EIOM-N1_P1 to MGTSW4A_P17 MGTSW4A_P17 to ENC#19-EIOM-N1_P1
ENC#3-EIOM-N4_P1 to MGTSW1A_P15 MGTSW1A_P15 to ENC#3-EIOM-N4_P1 ENC#9-SMM_P1 to MGTSW2A_P16 MGTSW2A_P16 to ENC#9-SMM_P1 ENC#14-SMM_P1 to MGTSW3A_P16 MGTSW3A_P16 to ENC#14-SMM_P1 ENC#19-SMM_P1 to MGTSW4A_P16 MGTSW4A_P16 to ENC#19-SMM_P1
ENC#3-EIOM-N3_P1 to MGTSW1A_P14 MGTSW1A_P14 to ENC#3-EIOM-N3_P1 ENC#8-EIOM-N4_P1 to MGTSW2A_P15 MGTSW2A_P15 to ENC#8-EIOM-N4_P1 ENC#13-EIOM-N4_P1 to MGTSW3A_P15 MGTSW3A_P15 to ENC#13-EIOM-N4_P1 ENC#18-EIOM-N4_P1 to MGTSW4A_P15 MGTSW4A_P15 to ENC#18-EIOM-N4_P1
ENC#3-EIOM-N2_P1 to MGTSW1A_P13 MGTSW1A_P13 to ENC#3-EIOM-N2_P1 ENC#8-EIOM-N3_P1 to MGTSW2A_P14 MGTSW2A_P14 to ENC#8-EIOM-N3_P1 ENC#13-EIOM-N3_P1 to MGTSW3A_P14 MGTSW3A_P14 to ENC#13-EIOM-N3_P1 ENC#18-EIOM-N3_P1 to MGTSW4A_P14 MGTSW4A_P14 to ENC#18-EIOM-N3_P1
ENC#3-EIOM-N1_P1 to MGTSW1A_P12 MGTSW1A_P12 to ENC#3-EIOM-N1_P1 ENC#8-EIOM-N2_P1 to MGTSW2A_P13 MGTSW2A_P13 to ENC#8-EIOM-N2_P1 ENC#13-EIOM-N2_P1 to MGTSW3A_P13 MGTSW3A_P13 to ENC#13-EIOM-N2_P1 ENC#18-EIOM-N2_P1 to MGTSW4A_P13 MGTSW4A_P13 to ENC#18-EIOM-N2_P1
ENC#3-SMM_P1 to MGTSW1A_P11 MGTSW1A_P11 to ENC#3-SMM_P1 ENC#8-EIOM-N1_P1 to MGTSW2A_P12 MGTSW2A_P12 to ENC#8-EIOM-N1_P1 ENC#13-EIOM-N1_P1 to MGTSW3A_P12 MGTSW3A_P12 to ENC#13-EIOM-N1_P1 ENC#18-EIOM-N1_P1 to MGTSW4A_P12 MGTSW4A_P12 to ENC#18-EIOM-N1_P1
ENC#2-EIOM-N4_P1 to MGTSW1A_P10 MGTSW1A_P10 to ENC#2-EIOM-N4_P1 ENC#8-SMM_P1 to MGTSW2A_P11 MGTSW2A_P11 to ENC#8-SMM_P1 ENC#13-SMM_P1 to MGTSW3A_P11 MGTSW3A_P11 to ENC#13-SMM_P1 ENC#18-SMM_P1 to MGTSW4A_P11 MGTSW4A_P11 to ENC#18-SMM_P1
ENC#2-EIOM-N3_P1 to MGTSW1A_P9 MGTSW1A_P9 to ENC#2-EIOM-N3_P1 ENC#7-EIOM-N4_P1 to MGTSW2A_P10 MGTSW2A_P10 to ENC#7-EIOM-N4_P1 ENC#12-EIOM-N4_P1 to MGTSW3A_P10 MGTSW3A_P10 to ENC#12-EIOM-N4_P1 ENC#17-EIOM-N4_P1 to MGTSW4A_P10 MGTSW4A_P10 to ENC#17-EIOM-N4_P1
ENC#2-EIOM-N2_P1 to MGTSW1A_P8 MGTSW1A_P8 to ENC#2-EIOM-N2_P1 ENC#7-EIOM-N3_P1 to MGTSW2A_P9 MGTSW2A_P9 to ENC#7-EIOM-N3_P1 ENC#12-EIOM-N3_P1 to MGTSW3A_P9 MGTSW3A_P9 to ENC#12-EIOM-N3_P1 ENC#17-EIOM-N3_P1 to MGTSW4A_P9 MGTSW4A_P9 to ENC#17-EIOM-N3_P1
ENC#2-EIOM-N1_P1 to MGTSW1A_P7 MGTSW1A_P7 to ENC#2-EIOM-N1_P1 ENC#7-EIOM-N2_P1 to MGTSW2A_P8 MGTSW2A_P8 to ENC#7-EIOM-N2_P1 ENC#12-EIOM-N2_P1 to MGTSW3A_P8 MGTSW3A_P8 to ENC#12-EIOM-N2_P1 ENC#17-EIOM-N2_P1 to MGTSW4A_P8 MGTSW4A_P8 to ENC#17-EIOM-N2_P1
ENC#2-SMM_P1 to MGTSW1A_P6 MGTSW1A_P6 to ENC#2-SMM_P1 ENC#7-EIOM-N1_P1 to MGTSW2A_P7 MGTSW2A_P7 to ENC#7-EIOM-N1_P1 ENC#12-EIOM-N1_P1 to MGTSW3A_P7 MGTSW3A_P7 to ENC#12-EIOM-N1_P1 ENC#17-EIOM-N1_P1 to MGTSW4A_P7 MGTSW4A_P7 to ENC#17-EIOM-N1_P1
ENC#1-EIOM-N4_P1 to MGTSW1A_P5 MGTSW1A_P5 to ENC#1-EIOM-N4_P1 ENC#7-SMM_P1 to MGTSW2A_P6 MGTSW2A_P6 to ENC#7-SMM_P1 ENC#12-SMM_P1 to MGTSW3A_P6 MGTSW3A_P6 to ENC#12-SMM_P1 ENC#17-SMM_P1 to MGTSW4A_P6 MGTSW4A_P6 to ENC#17-SMM_P1
ENC#1-EIOM-N3_P1 to MGTSW1A_P4 MGTSW1A_P4 to ENC#1-EIOM-N3_P1 ENC#6-EIOM-N4_P1 to MGTSW2A_P5 MGTSW2A_P5 to ENC#6-EIOM-N4_P1 ENC#11-EIOM-N4_P1 to MGTSW3A_P5 MGTSW3A_P5 to ENC#11-EIOM-N4_P1 ENC#16-EIOM-N4_P1 to MGTSW4A_P5 MGTSW4A_P5 to ENC#16-EIOM-N4_P1
ENC#1-EIOM-N2_P1 to MGTSW1A_P3 MGTSW1A_P3 to ENC#1-EIOM-N2_P1 ENC#6-EIOM-N3_P1 to MGTSW2A_P4 MGTSW2A_P4 to ENC#6-EIOM-N3_P1 ENC#11-EIOM-N3_P1 to MGTSW3A_P4 MGTSW3A_P4 to ENC#11-EIOM-N3_P1 ENC#16-EIOM-N3_P1 to MGTSW4A_P4 MGTSW4A_P4 to ENC#16-EIOM-N3_P1
ENC#1-EIOM-N1_P1 to MGTSW1A_P2 MGTSW1A_P2 to ENC#1-EIOM-N1_P1 ENC#6-EIOM-N2_P1 to MGTSW2A_P3 MGTSW2A_P3 to ENC#6-EIOM-N2_P1 ENC#11-EIOM-N2_P1 to MGTSW3A_P3 MGTSW3A_P3 to ENC#11-EIOM-N2_P1 ENC#16-EIOM-N2_P1 to MGTSW4A_P3 MGTSW4A_P3 to ENC#16-EIOM-N2_P1
ENC#1-SMM_P1 to MGTSW1A_P1 MGTSW1A_P1 to ENC#1-SMM_P1 ENC#6-EIOM-N1_P1 to MGTSW2A_P2 MGTSW2A_P2 to ENC#6-EIOM-N1_P1 ENC#11-EIOM-N1_P1 to MGTSW3A_P2 MGTSW3A_P2 to ENC#11-EIOM-N1_P1 ENC#16-EIOM-N1_P1 to MGTSW4A_P2 MGTSW4A_P2 to ENC#16-EIOM-N1_P1
ENC#6-SMM_P1 to MGTSW2A_P1 MGTSW2A_P1 to ENC#6-SMM_P1 ENC#11-SMM_P1 to MGTSW3A_P1 MGTSW3A_P1 to ENC#11-SMM_P1 ENC#16-SMM_P1 to MGTSW4A_P1 MGTSW4A_P1 to ENC#16-SMM_P1

Management Switch 5A Management Switch 6A Management Switch 7A Management Switch 8A


Management Cable labeling Enclosures 21 - 25 Management Cable labeling Enclosures 26 - 30 Management Cable labeling Enclosures 31 - 35 Management Cable labeling Enclosures 36 - 40
Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text

MGTSW5A_MGMT to MGTSW3A_P43 MGTSW3A_P43 to MGTSW5A_MGMT MGTSW6A_MGMT to MGTSW5A_P38 MGTSW5A_P38 to MGTSW6A_MGMT MGTSW7A_MGMT to MGTSW5A_P43 MGTSW5A_P43 to MGTSW7A_MGMT MGTSW8A_MGMT to MGTSW7A_P38 MGTSW7A_P38 to MGTSW8A_MGMT
FABSW3B-MGMT_P0 to MGTSW5A_P46 MGTSW5A_P46 to FABSW3B-MGMT_P0 MGTSW6A_P42 to MGTSW5A_P42 MGTSW5A_P42 to MGTSW6A_P42 FABSW4B-MGMT_P0 to MGTSW7A_P46 MGTSW7A_P46 to FABSW4B-MGMT_P0 MGTSW8A_P42 to MGTSW7A_P42 MGTSW7A_P42 to MGTSW8A_P42
FABSW3A-MGMT_P0 to MGTSW5A_P47 MGTSW5A_P47 to FABSW3A-MGMT_P0 MGTSW6A_P41 to MGTSW5A_P41 MGTSW5A_P41 to MGTSW6A_P41 FABSW4A-MGMT_P0 to MGTSW7A_P47 MGTSW7A_P47 to FABSW4A-MGMT_P0 MGTSW8A_P41 to MGTSW7A_P41 MGTSW7A_P41 to MGTSW8A_P41
ENC#25-EIOM-N4_P1 to MGTSW5A_P25 MGTSW5A_P25 to ENC#25-EIOM-N4_P1 ENC#30-EIOM-N4_P1 to MGTSW6A_P25 MGTSW6A_P25 to ENC#30-EIOM-N4_P1 ENC#35-EIOM-N4_P1 to MGTSW7A_P25 MGTSW7A_P25 to ENC#35-EIOM-N4_P1 ENC#40-EIOM-N4_P1 to MGTSW8A_P25 MGTSW8A_P25 to ENC#40-EIOM-N4_P1
ENC#25-EIOM-N3_P1 to MGTSW5A_P24 MGTSW5A_P24 to ENC#25-EIOM-N3_P1 ENC#30-EIOM-N3_P1 to MGTSW6A_P24 MGTSW6A_P24 to ENC#30-EIOM-N3_P1 ENC#35-EIOM-N3_P1 to MGTSW7A_P24 MGTSW7A_P24 to ENC#35-EIOM-N3_P1 ENC#40-EIOM-N3_P1 to MGTSW8A_P24 MGTSW8A_P24 to ENC#40-EIOM-N3_P1
ENC#25-EIOM-N2_P1 to MGTSW5A_P23 MGTSW5A_P23 to ENC#25-EIOM-N2_P1 ENC#30-EIOM-N2_P1 to MGTSW6A_P23 MGTSW6A_P23 to ENC#30-EIOM-N2_P1 ENC#35-EIOM-N2_P1 to MGTSW7A_P23 MGTSW7A_P23 to ENC#35-EIOM-N2_P1 ENC#40-EIOM-N2_P1 to MGTSW8A_P23 MGTSW8A_P23 to ENC#40-EIOM-N2_P1
ENC#25-EIOM-N1_P1 to MGTSW5A_P22 MGTSW5A_P22 to ENC#25-EIOM-N1_P1 ENC#30-EIOM-N1_P1 to MGTSW6A_P22 MGTSW6A_P22 to ENC#30-EIOM-N1_P1 ENC#35-EIOM-N1_P1 to MGTSW7A_P22 MGTSW7A_P22 to ENC#35-EIOM-N1_P1 ENC#40-EIOM-N1_P1 to MGTSW8A_P22 MGTSW8A_P22 to ENC#40-EIOM-N1_P1
ENC#25-SMM_P1 to MGTSW5A_P21 MGTSW5A_P21 to ENC#25-SMM_P1 ENC#30-SMM_P1 to MGTSW6A_P21 MGTSW6A_P21 to ENC#30-SMM_P1 ENC#35_SMM_P1 to MGTSW7A_P21 MGTSW7A_P21 to ENC#35_SMM_P1 ENC#40_SMM_P1 to MGTSW8A_P21 MGTSW8A_P21 to ENC#40_SMM_P1
ENC#24-EIOM-N4_P1 to MGTSW5A_P20 MGTSW5A_P20 to ENC#24-EIOM-N4_P1 ENC#29-EIOM-N4_P1 to MGTSW6A_P20 MGTSW6A_P20 to ENC#29-EIOM-N4_P1 ENC#34-EIOM-N4_P1 to MGTSW7A_P20 MGTSW7A_P20 to ENC#34-EIOM-N4_P1 ENC#39-EIOM-N4_P1 to MGTSW8A_P20 MGTSW8A_P20 to ENC#39-EIOM-N4_P1
ENC#24-EIOM-N3_P1 to MGTSW5A_P19 MGTSW5A_P19 to ENC#24-EIOM-N3_P1 ENC#29-EIOM-N3_P1 to MGTSW6A_P19 MGTSW6A_P19 to ENC#29-EIOM-N3_P1 ENC#34-EIOM-N3_P1 to MGTSW7A_P19 MGTSW7A_P19 to ENC#34-EIOM-N3_P1 ENC#39-EIOM-N3_P1 to MGTSW8A_P19 MGTSW8A_P19 to ENC#39-EIOM-N3_P1
ENC#24-EIOM-N2_P1 to MGTSW5A_P18 MGTSW5A_P18 to ENC#24-EIOM-N2_P1 ENC#29-EIOM-N2_P1 to MGTSW6A_P18 MGTSW6A_P18 to ENC#29-EIOM-N2_P1 ENC#34-EIOM-N2_P1 to MGTSW7A_P18 MGTSW7A_P18 to ENC#34-EIOM-N2_P1 ENC#39-EIOM-N2_P1 to MGTSW8A_P18 MGTSW8A_P18 to ENC#39-EIOM-N2_P1
ENC#24-EIOM-N1_P1 to MGTSW5A_P17 MGTSW5A_P17 to ENC#24-EIOM-N1_P1 ENC#29-EIOM-N1_P1 to MGTSW6A_P17 MGTSW6A_P17 to ENC#29-EIOM-N1_P1 ENC#34-EIOM-N1_P1 to MGTSW7A_P17 MGTSW7A_P17 to ENC#34-EIOM-N1_P1 ENC#39-EIOM-N1_P1 to MGTSW8A_P17 MGTSW8A_P17 to ENC#39-EIOM-N1_P1
ENC#24-SMM_P1 to MGTSW5A_P16 MGTSW5A_P16 to ENC#24-SMM_P1 ENC#29-SMM_P1 to MGTSW6A_P16 MGTSW6A_P16 to ENC#29-SMM_P1 ENC#34_SMM_P1 to MGTSW7A_P16 MGTSW7A_P16 to ENC#34_SMM_P1 ENC#39_SMM_P1 to MGTSW8A_P16 MGTSW8A_P16 to ENC#39_SMM_P1
ENC#23-EIOM-N4_P1 to MGTSW5A_P15 MGTSW5A_P15 to ENC#23-EIOM-N4_P1 ENC#28-EIOM-N4_P1 to MGTSW6A_P15 MGTSW6A_P15 to ENC#28-EIOM-N4_P1 ENC#33-EIOM-N4_P1 to MGTSW7A_P15 MGTSW7A_P15 to ENC#33-EIOM-N4_P1 ENC#38-EIOM-N4_P1 to MGTSW8A_P15 MGTSW8A_P15 to ENC#38-EIOM-N4_P1
ENC#23-EIOM-N3_P1 to MGTSW5A_P14 MGTSW5A_P14 to ENC#23-EIOM-N3_P1 ENC#28-EIOM-N3_P1 to MGTSW6A_P14 MGTSW6A_P14 to ENC#28-EIOM-N3_P1 ENC#33-EIOM-N3_P1 to MGTSW7A_P14 MGTSW7A_P14 to ENC#33-EIOM-N3_P1 ENC#38-EIOM-N3_P1 to MGTSW8A_P14 MGTSW8A_P14 to ENC#38-EIOM-N3_P1
ENC#23-EIOM-N2_P1 to MGTSW5A_P13 MGTSW5A_P13 to ENC#23-EIOM-N2_P1 ENC#28-EIOM-N2_P1 to MGTSW6A_P13 MGTSW6A_P13 to ENC#28-EIOM-N2_P1 ENC#33-EIOM-N2_P1 to MGTSW7A_P13 MGTSW7A_P13 to ENC#33-EIOM-N2_P1 ENC#38-EIOM-N2_P1 to MGTSW8A_P13 MGTSW8A_P13 to ENC#38-EIOM-N2_P1
ENC#23-EIOM-N1_P1 to MGTSW5A_P12 MGTSW5A_P12 to ENC#23-EIOM-N1_P1 ENC#28-EIOM-N1_P1 to MGTSW6A_P12 MGTSW6A_P12 to ENC#28-EIOM-N1_P1 ENC#33-EIOM-N1_P1 to MGTSW7A_P12 MGTSW7A_P12 to ENC#33-EIOM-N1_P1 ENC#38-EIOM-N1_P1 to MGTSW8A_P12 MGTSW8A_P12 to ENC#38-EIOM-N1_P1
ENC#23-SMM_P1 to MGTSW5A_P11 MGTSW5A_P11 to ENC#23-SMM_P1 ENC#28-SMM_P1 to MGTSW6A_P11 MGTSW6A_P11 to ENC#28-SMM_P1 ENC#33_SMM_P1 to MGTSW7A_P11 MGTSW7A_P11 to ENC#33_SMM_P1 ENC#38_SMM_P1 to MGTSW8A_P11 MGTSW8A_P11 to ENC#38_SMM_P1
ENC#22-EIOM-N4_P1 to MGTSW5A_P10 MGTSW5A_P10 to ENC#22-EIOM-N4_P1 ENC#27-EIOM-N4_P1 to MGTSW6A_P10 MGTSW6A_P10 to ENC#27-EIOM-N4_P1 ENC#32-EIOM-N4_P1 to MGTSW7A_P10 MGTSW7A_P10 to ENC#32-EIOM-N4_P1 ENC#37-EIOM-N4_P1 to MGTSW8A_P10 MGTSW8A_P10 to ENC#37-EIOM-N4_P1
ENC#22-EIOM-N3_P1 to MGTSW5A_P9 MGTSW5A_P9 to ENC#22-EIOM-N3_P1 ENC#27-EIOM-N3_P1 to MGTSW6A_P9 MGTSW6A_P9 to ENC#27-EIOM-N3_P1 ENC#32-EIOM-N3_P1 to MGTSW7A_P9 MGTSW7A_P9 to ENC#32-EIOM-N3_P1 ENC#37-EIOM-N3_P1 to MGTSW8A_P9 MGTSW8A_P9 to ENC#37-EIOM-N3_P1
ENC#22-EIOM-N2_P1 to MGTSW5A_P8 MGTSW5A_P8 to ENC#22-EIOM-N2_P1 ENC#27-EIOM-N2_P1 to MGTSW6A_P8 MGTSW6A_P8 to ENC#27-EIOM-N2_P1 ENC#32-EIOM-N2_P1 to MGTSW7A_P8 MGTSW7A_P8 to ENC#32-EIOM-N2_P1 ENC#37-EIOM-N2_P1 to MGTSW8A_P8 MGTSW8A_P8 to ENC#37-EIOM-N2_P1
ENC#22-EIOM-N1_P1 to MGTSW5A_P7 MGTSW5A_P7 to ENC#22-EIOM-N1_P1 ENC#27-EIOM-N1_P1 to MGTSW6A_P7 MGTSW6A_P7 to ENC#27-EIOM-N1_P1 ENC#32-EIOM-N1_P1 to MGTSW7A_P7 MGTSW7A_P7 to ENC#32-EIOM-N1_P1 ENC#37-EIOM-N1_P1 to MGTSW8A_P7 MGTSW8A_P7 to ENC#37-EIOM-N1_P1
ENC#22-SMM_P1 to MGTSW5A_P6 MGTSW5A_P6 to ENC#22-SMM_P1 ENC#27-SMM_P1 to MGTSW6A_P6 MGTSW6A_P6 to ENC#27-SMM_P1 ENC#32_SMM_P1 to MGTSW7A_P6 MGTSW7A_P6 to ENC#32_SMM_P1 ENC#37_SMM_P1 to MGTSW8A_P6 MGTSW8A_P6 to ENC#37_SMM_P1
ENC#21-EIOM-N4_P1 to MGTSW5A_P5 MGTSW5A_P5 to ENC#21-EIOM-N4_P1 ENC#26-EIOM-N4_P1 to MGTSW6A_P5 MGTSW6A_P5 to ENC#26-EIOM-N4_P1 ENC#31-EIOM-N4_P1 to MGTSW7A_P5 MGTSW7A_P5 to ENC#31-EIOM-N4_P1 ENC#36-EIOM-N4_P1 to MGTSW8A_P5 MGTSW8A_P5 to ENC#36-EIOM-N4_P1
ENC#21-EIOM-N3_P1 to MGTSW5A_P4 MGTSW5A_P4 to ENC#21-EIOM-N3_P1 ENC#26-EIOM-N3_P1 to MGTSW6A_P4 MGTSW6A_P4 to ENC#26-EIOM-N3_P1 ENC#31-EIOM-N3_P1 to MGTSW7A_P4 MGTSW7A_P4 to ENC#31-EIOM-N3_P1 ENC#36-EIOM-N3_P1 to MGTSW8A_P4 MGTSW8A_P4 to ENC#36-EIOM-N3_P1
ENC#21-EIOM-N2_P1 to MGTSW5A_P3 MGTSW5A_P3 to ENC#21-EIOM-N2_P1 ENC#26-EIOM-N2_P1 to MGTSW6A_P3 MGTSW6A_P3 to ENC#26-EIOM-N2_P1 ENC#31-EIOM-N2_P1 to MGTSW7A_P3 MGTSW7A_P3 to ENC#31-EIOM-N2_P1 ENC#36-EIOM-N2_P1 to MGTSW8A_P3 MGTSW8A_P3 to ENC#36-EIOM-N2_P1
ENC#21-EIOM-N1_P1 to MGTSW5A_P2 MGTSW5A_P2 to ENC#21-EIOM-N1_P1 ENC#26-EIOM-N1_P1 to MGTSW6A_P2 MGTSW6A_P2 to ENC#26-EIOM-N1_P1 ENC#31-EIOM-N1_P1 to MGTSW7A_P2 MGTSW7A_P2 to ENC#31-EIOM-N1_P1 ENC#36-EIOM-N1_P1 to MGTSW8A_P2 MGTSW8A_P2 to ENC#36-EIOM-N1_P1
ENC#21-SMM_P1 to MGTSW5A_P1 MGTSW5A_P1 to ENC#21-SMM_P1 ENC#26-SMM_P1 to MGTSW6A_P1 MGTSW6A_P1 to ENC#26-SMM_P1 ENC#31_SMM_P1 to MGTSW7A_P1 MGTSW7A_P1 to ENC#31_SMM_P1 ENC#36_SMM_P1 to MGTSW8A_P1 MGTSW8A_P1 to ENC#36_SMM_P1

Page 18
Spine A and B, Hub, Patch Panel

Doc Part # 02JE469


ECO#N47076S
Storage Gateway 1 and 2 to Fabric Switch 1A and 1B and Management Switch 1A Spine Switch A and B to Fabric Leaf Switch 1A and B – 4A and B
Fabric and Management Cable labeling Storage Gateway 1 and 2 Leaf and Spine Cable labeling
Side A Permanent Label Text Side B Permanent Label Text Side A Permanent Label Text Side B Permanent Label Text

STRGW2-LOM_P1 to MGTSW1A_P29 MGTSW1A_P29 to STRGW2-LOM_P1 SPINESWB_P23 to FABSW4B_P56 FABSW4B_P56 to SPINESWB_P23


STRGW2-BMC_MGMT to MGTSW1A_P28 MGTSW1A_P28 to STRGW2-BMC_MGMT SPINESWA_P23 to FABSW4B_P55 FABSW4B_P55 to SPINESWA_P23
STRGW1-LOM_P1 to MGTSW1A_P27 MGTSW1A_P27 to STRGW1-LOM_P1 SPINESWB_P24 to FABSW4A_P56 FABSW4A_P56 to SPINESWB_P24
STRGW1-BMC_MGMT to MGTSW1A_P26 MGTSW1A_P26 to STRGW1-BMC_MGMT SPINESWA_P24 to FABSW4A_P55 FABSW4A_P55 to SPINESWA_P24
STRGW2-S5_P2 to FABSW1B_P50 FABSW1B_P50 to STRGW2-S5_P2 SPINESWB_P25 to FABSW3B_P56 FABSW3B_P56 to SPINESWB_P25
STRGW2-S5_P1 to FABSW1A_P50 FABSW1A_P50 to STRGW2-S5_P1 SPINESWA_P25 to FABSW3B_P55 FABSW3B_P55 to SPINESWA_P25
STRGW1-S5_P2 to FABSW1B_P49 FABSW1B_P49 to STRGW1-S5_P2 SPINESWB_P26 to FABSW3A_P56 FABSW3A_P56 to SPINESWB_P26
STRGW1-S5_P1 to FABSW1A_P49 FABSW1A_P49 to STRGW1-S5_P1 SPINESWA_P26 to FABSW3A_P55 FABSW3A_P55 to SPINESWA_P26
SPINESWB_P27 to FABSW2B_P56 FABSW2B_P56 to SPINESWB_P27
SPINESWA_P27 to FABSW2B_P55 FABSW2B_P55 to SPINESWA_P27
SPINESWB_P28 to FABSW2A_P56 FABSW2A_P56 to SPINESWB_P28
Storage Gateway 3 to Spine Switch A and B and Management Switch 3A SPINESWA_P28 to FABSW2A_P55 FABSW2A_P55 to SPINESWA_P28
Spine and Management Cable labeling Storage Gateway 3 SPINESWB_P29 to FABSW1B_P56 FABSW1B_P56 to SPINESWB_P29
Side A Permanent Label Text Side B Permanent Label Text SPINESWA_P29 to FABSW1B_P55 FABSW1B_P55 to SPINESWA_P29
SPINESWB_P30 to FABSW1A_P56 FABSW1A_P56 to SPINESWB_P30
SPINESWB-MGMT_P0 to MGTSW3A_P45 MGTSW3A_P45 to SPINESWB-MGMT_P0 SPINESWA_P30 to FABSW1A_P55 FABSW1A_P55 to SPINESWA_P30
SPINESWA-MGMT_P0 to MGTSW3A_P44 MGTSW3A_P44 to SPINESWA-MGMT_P0 SPINESWA_P32 to SPINESWB_P32 SPINESWB_P32 to SPINESWA_P32
STRGW3-LOM_P1 to MGTSW3A_P27 MGTSW3A_P27 to STRGW3-LOM_P1 SPINESWA_P31 to SPINESWB_P31 SPINESWB_P31 to SPINESWA_P31
STRGW3-BMC_MGMT to MGTSW3A_P26 MGTSW3A_P26 to STRGW3-BMC_MGMT
STRGW3-S5_P2 to SPINESWB_P1 SPINESWB_P1 to STRGW3-S5_P2
STRGW3-S5_P1 to SPINESWA_P1 SPINESWA_P1 to STRGW3-S5_P1
Patch Panel to Management, Fabric and Node Cable Labeling
Side A Permanent Label Text Side B Permanent Label Text

MGTSW1A_P48 to PP_SCP-A PP_SCP-A to MGTSW1A_P48


ENC#1-1G-N4_P2 to PP_ETH3 PP_ETH3 to ENC#1-1G-N4_P2
Hub Switch to Management Switch 1A, 3A, 5A, and 7A ENC#1-1G-N3_P2 to PP_ETH2 PP_ETH2 to ENC#1-1G-N3_P2
Cable labeling for Hub to Management Switches ENC#1-1G-N2_P2 to PP_ETH1 PP_ETH1 to ENC#1-1G-N2_P2
Side A Permanent Label Text Side B Permanent Label Text ENC#1-1G-N1_P2 to PP_ETH0 PP_ETH0 to ENC#1-1G-N1_P2
FABSW1B_P48 to PP_ETH11 PP_ETH11 to FABSW1B_P48
MGTSW7A_P40 to HUBSW_P41 HUBSW_P41 to MGTSW7A_P40 FABSW1B_P47 to PP_ETH10 PP_ETH10 to FABSW1B_P47
MGTSW7A_P39 to HUBSW_P42 HUBSW_P42 to MGTSW7A_P39 FABSW1B_P46 to PP_ETH9 PP_ETH9 to FABSW1B_P46
MGTSW5A_P40 to HUBSW_P43 HUBSW_P43 to MGTSW5A_P40 FABSW1B_P45 to PP_ETH8 PP_ETH8 to FABSW1B_P45
MGTSW5A_P39 to HUBSW_P44 HUBSW_P44 to MGTSW5A_P39 FABSW1A_P48 to PP_ETH7 PP_ETH7 to FABSW1A_P48
MGTSW3A_P40 to HUBSW_P45 HUBSW_P45 to MGTSW3A_P40 FABSW1A_P47 to PP_ETH6 PP_ETH6 to FABSW1A_P47
MGTSW3A_P39 to HUBSW_P46 HUBSW_P46 to MGTSW3A_P39 FABSW1A_P46 to PP_ETH5 PP_ETH5 to FABSW1A_P46
MGTSW1A_P40 to HUBSW_P47 HUBSW_P47 to MGTSW1A_P40 FABSW1A_P45 to PP_ETH4 PP_ETH4 to FABSW1A_P45
MGTSW1A_P39 to HUBSW_P48 HUBSW_P48 to MGTSW1A_P39
MGTSW1A_P44 to HUBSW_MGMT HUBSW_MGMT to MGTSW1A_P44

Page 19
Components

Doc Part # 02JE469


ECO#N47076S

Port 1 Port 47

Hub and
MGMT
Management
Port
Switch
Port 2 Port 48

Port 1 Port 31 4 6 M 4 0 0 4 S w itc h e d P D U

Spine

6
D E

Switch C
B
F
1
A 2

5
LA N
Port 2 Port 32

Fiber LC Duplex
Connections E th e rn e t L A N C ir c u it
M anagem ent B re a k e r
CAT5e RJ-45
CAT5e RJ-45
A C M a in
Connections P o rt
Connections In p u t
e th 0 e th 1 e th 2 e th 3 e th 4 /5 e th 6 /7 e th 8/9 e th 1 0 /1 1 SYSTEM PATCH PANEL
FCA1 FCA2 FCB1 FCB2

1 0 / 2 5 G ig E
c6 c6 c6 c6 c6 c6
F ib re C h a n n e l
1 G ig E SCP - A SCP- B

Patch Panel Layout

Page 20