SERVICE ENTRANCE

1 SINGLE LINE DIAGRAM N


NORMAL SOURCE
E 5 SCALE: NTS

NE
W
N
W Ronnie Tuddao
E
ALTERNATE SOURCE

SW

SE
2 - 14mm sq THW
1 - 5.50mm sq THW grounding THIS
encased in 32mm dia. PVC
G P7 P8 S I T E
S
M
kwhr
meter
2 - 14mm sq THW 2 - 14mm sq THW 2 - 14mm sq THW
1 - 8.0mm sq THW grounding 1 - 8.0mm sq THW grounding 1 - 8.0mm sq THW grounding
conductor conductor conductor
Manual Transfer Switch encased in 32mm dia. PVC encased in 32mm dia. PVC encased in 32mm dia. PVC
2 - 32mm sq THW 100AT, 100AF, 240v, 2P

1 - 14mm sq THW grounding


conductor
encased in 32mm dia. PVC

P5 P1 P2

2 - 14mm sq THW 2 - 14mm sq THW 2 - 14mm sq THW 2 - 14mm sq THW


1 - 8.0mm sq THW grounding 1 - 8.0mm sq THW grounding 1 - 8.0mm sq THW grounding 1 - 8.0mm sq THW grounding
conductor conductor conductor conductor
encased in 32mm dia. PVC encased in 32mm dia. PVC encased in 32mm dia. PVC encased in 32mm dia. PVC

2 - 32mm sq THW
1 - 14mm sq THW grounding
conductor
encased in 32mm dia. PVC
3 VICINITY MAP
E 5 SCALE: NTS

2 GENERAL NOTES AND SPECIFICATIONS:


E 5 SCALE: NTS

1. All electrical materials, equipment and wiring methods shall be done in accordance to plans and specifications herein
contained and shall be in conformity with the provisions of the latest edition of the Philippine Electrical Code, the
wiring method allowed in the PEC context shall be used to encased/protect wires for branch circuits. Service entrance conduit
requirements of the local government unit concerned and the electric utility company.
2. All electrical materials shall be new, and of the make, type, and description specified by the electrical engineer. All
electrical installations, circuits, controls, and equipment shall be in proper operating condition before the work
3. Conduits smaller than 20 mm sq trade size are not to be installed in the plant. Rigid non-metal conduit and/or appropriate

4. All conductors used within the plant which are larger than 3.50 mm sq shall be stranded. No conductor smaller than
2.00 mm sq shall be used except for fixture wiring. Branch circuits conductors shall have an insulation of THW or THWN.
Conductors used for feeders and service entrance shall be THW or THWN in RNM conduit.
5. All electrical installations shall be done under the direct supervision of a duly licensed electrical engineer.
ENGINEER (P.E.E) ENGINEER (R.E.E) CADD BY: CHECKED BY: DATE DESCRIPTIONS PROJECT TITLE: SHEET CONTENTS: OWNER: SHEET NO.:

31
JUN JUN P. ANCHETA 2-Storey Commercial Building SINGLE LINE DIAGRAM
R.A. 9266 SEC. 33 DRAWINGS AND SPECIFICATIONS AND OTHER CONTRACT DOCUMENTS DULY E5 31
SIGNED, STAMPED OR SEALED, AS INSTRUMENTS OF SERVICE, ARE THE INTELLECTUAL PROPERTY AND
GENERAL NOTES & SPECIFICATION
DOCUMENTS OF THE ARCHITECT, WHETHER THE OBJECT FOR WHICH THEY ARE MADE IS EXECUTED OR NOT. VICINITY MAP Mr. LEOVIGILDO A. ESPITA
IT SHALL BE UNLAWFUL FOR ANY PERSON TO DUPLICATE OR TO MAKE COPIES OF SAID DOCUMENTS FOR USE
IN THE REPETITION OF AND FOR OTHER PROJECTS OR BUILDINGS, WHETHER EXECUTED PARTLY OR IN
PRC NO. : PTR NO. : PRC NO. : PTR NO. : DATE LOCATION: JOB NO.:
WHOLE, WITHOUT THE WRITTEN CONSENT OF ARCHITECT OR AUTHOR OF SAID DOCUMENTS.
TIN NO. : PLACE ISSUED : TIN NO. : PLACE ISSUED : ADDRESS :
Bulanao, Tabuk City, Kalinga 2019