Recovery Time for ISO Class 8 cleanrooms

GOOD VALIDATION PRACTICE (cGVP) HVAC VALIDATION

mc02622 Jun '16

According to the revised draft working document from WHO for HVAC of non-sterile facilities (QAS/15 639/Rev.1), the recovery test for ISO
14644 Class 8 clean rooms should be performed using the particle decay method as per ISO 14644-3 clause B.12.3.2. Is anyone familiar with
this method and can provide any kind of guidance?

created last reply 2 13.2k 2 1


Jun '16 Jun '16 replies views users like

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
JaredCroft Jun '16

The WHO draft guidance is a bit confusing. Section 5.5.1 states that HEPA are not required to obtain non-sterile operation. Then goes on to
explain how to do HEPA testing throughout the rest of the document. Please bear in mind that WHO is actively searching for feedback and
comments. In ISO 14644-2, recovery tests are listed as “optional” for all areas. I personally would apply a risked based approach to this. Do you
have HEPA filters? Are there low air returns? What is the nature of operations (high particle generation?)
I’m a little surprised that WHO is asking for a recovery test for ISO 8 areas (especially when they state that HEPAs are not needed for ISO 8)

That being said. If a recovery test is requested. The ISO guideline is available for purchase, with the full equation. Unfortunately, the ISO is a
copywritten document, and I cannot reproduce it (my apologies).

Steering you slightly here. Overall ISO (and WHO) first recommends doing the 100:1 test, where you start out with 100x the allowable
concentration, Then turn the air handler on, and see how long it takes to get the air to within the allowable concentration. Using this method,
there is no “correction equation” to correlate the “slope” method with the 100:1 method. The slope method is only used when the 100:1 method
cannot be performed for some reason.

The 100x concentration can easily be obtained using an aerosol. In my experience a company called TSS was able to come and “fog” the room
to obtain 100x the allowable concentration.

Overall, if you still need to do the recovery tests listed in ISO14644-3 B.12.3.2, It is listed very well, the calculations are not too difficult, and the
testing method is straight forward.

mc02622 Jun '16

Thank you very much for your respond.

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
1

Reply

Suggested Topics

Topic Replies Activity

Batch size deviation required stabiity 0 May '20


GOOD MANUFACTUR…

Migrating of Data from Non-Validated System to Validated System 1 6d


COMPUTER SYSTEM …

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD
Topic Replies Activity

Thermocouple placements 0 Dec '20

Traceability of Design Outputs to Design Inputs a Key Task for MDSAP [Video] 0 10d
GOOD VALIDATION P…

Are Your Personnel Adhering to CFR 211.28 to Avoid Contamination? [Video] 0 10d
GOOD MANUFACTUR…

Want to read more? Browse other topics in HVAC VALIDATION or view latest topics.

Create PDF in your applications with the Pdfcrowd HTML to PDF API PDFCROWD

You might also like