Professional Documents
Culture Documents
002 Case Study On Voltage Sag Severity Analysis in An Ind CKT
002 Case Study On Voltage Sag Severity Analysis in An Ind CKT
1, JANUARY/FEBRUARY 2017 15
Abstract—This paper presents the results of a power quality [3]. This is due to the widespread use of equipment sensitive
study carried out in an industrial distribution system. The main to this disturbance [4], even if they are of very short duration
objective of this study was to quantify the negative impact caused (1–6 cycles) [3]. Consequently, voltage sags have become an im-
by voltage sags in industrial processes and its relationship to gen-
erated interruptions. A series of measurements of power quality portant problem for network operators and end users. Multiple
variations were taken at the substation that feeds the circuit and studies are needed to analyze the relationship between voltage
at the point-of-common coupling of each industrial user. The new sags and the generation of interruptions in industrial processes
standard IEEE Std 1564-2014 “Guide for Voltage Sag Indices” was and also the destruction of equipment [3]–[6]. This problem was
used to determine the indicators to assess the severity of voltage detected in an industrial distribution system when the network
sags and also the calculation method. Sag severity was selected as
it allows the calculation of the probability of voltage sags to gen- operator (OR) of the city of Manizales (Colombia) conducted a
erate interruptions in industrial processes or electrical equipment. study of power quality in an industrial circuit. First, research car-
Thus, an analysis of the quality of the supply voltage can be done. ried out in 25 industrial users revealed that 60% of these compa-
Severity was initially calculated at the substation that feeds the in- nies reported the occurrence of voltage variations. Also, around
dustrial circuit and later, at the point-of-common coupling of each 80% of these companies reported using equipment sensitive to
user. Subsequently, the relationship between user interruptions
and severity values was determined. Finally, recommendations of such disturbances. Therefore, the need to quantify the quality
good engineering practices in industrial processes were done. of voltage supply arose. A series of measurements was taken at
the substation that feeds the industrial distribution system and
Index Terms—Distortion measurement, IEEE Std 1564, power
distribution, power quality, voltage fluctuations.
at the point-of-common coupling (PCC) of each industrial user.
First, the duration and retained voltage of each voltage sag
I. INTRODUCTION was recorded. These two parameters were selected given the
possibility of combining them into a single indicator known as
HE need to prevent and reduce the effects of disturbances
T on electrical systems has acquired great importance in re-
cent years [1]. Among all possible disturbances, voltage sags
voltage sag severity. Voltage sag severity allows the measure-
ment of the probability of generating an interruption in a process
or in a device. Recently, the IEEE Guide for Voltage Sag Indices
have the highest occurrence frequency [2]. Additionally, it has
IEEE Std. 1564-2014 introduced methods for further calculat-
been estimated that voltage sags generate between 92% and
ing the severity of voltage sags [7]. This study shows the need
98% of interruptions attributed to disturbances in power supply
to use this standard in the analysis of the impact of voltage sags
in industrial distribution systems, and additionally, the need to
Manuscript received August 1, 2015; revised November 19, 2015; accepted considered the actual conditions of the connections of end-user
January 16, 2016. Date of publication August 26, 2016; date of current version loads. Additionally, the fastest way to calculate the average
January 18, 2017. Paper 2015-PSEC-0602.R1, presented at the 2015 Industry severity value is presented. This paper is organized as follows.
Applications Society Annual Meeting, Addison, TX, USA, Oct. 18–22, and ap-
proved for publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS Section II presents the results of a research carried out to identify
by the Power System Engineering Committee of the IEEE Industry Applica- the main power quality problems for industrial users. Section III
tions Society. This work was supported in part by the Universidad Nacional introduces the theoretical framework used as base to calculate
de Colombia (Research Found Office of Manizales—DIMA) (Distribution and
Power Network Research Group—GREDyP; Power Quality and Power Elec- the severity of voltage sags. Section IV describes the avail-
tronics Research Group—GICEP; and Laboratory in Quality of Energy and able measurement system of the network operator. Section V
Power Electronics—LACEP). presents severity of voltage sags and measurement records in
S. Arias-Guzmán, O. A. Ruiz-Guzmán, L. F. Garcia-Arı́as, M. Jaramillo-
Gonzáles, P. D. Cardona-Orozco, and E. A. Cano-Plata are with the Universidad the substation and a fastest way to calculate the average severity
Nacional de Colombia, Manizales 111321, Colombia (e-mail: saariasgu@unal. value. Section VI shows measurement records of each industrial
edu.co; oaruizg@unal.edu.co; lufgarciaar@unal.edu.co; marjaramillogon@ user and voltage sag severity. Section VII presents a compar-
unal.edu.co; pdcardonao@unal.edu.co; eacanopl@unal.edu.co).
A. J. Ustariz-Farfán is with the Electrical, Electronic and Computer Engi- ison between severity and the impact of voltage sags. Finally,
neering Department, Universidad Nacional de Colombia, Manizales 111321, Section VIII presents the conclusions of this study.
Colombia (e-mail: ajustarizf@unal.edu.co).
A. F. Salazar-Jiménez is with the Central Hidroeléctrica de Caldas—CHEC,
Manizales 111321, Colombia (e-mail: andres.salazar@chec.com.co). II. MAJOR PROBLEMS OF POWER QUALITY: CASE STUDY
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. A study was carried out to identify the main problems
Digital Object Identifier 10.1109/TIA.2016.2603470 of power quality for each industrial user. This process was
0093-9994 © 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
16 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 53, NO. 1, JANUARY/FEBRUARY 2017
Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
ARIAS-GUZMÁN et al.: ANALYSIS OF VOLTAGE SAG SEVERITY CASE STUDY IN AN INDUSTRIAL CIRCUIT 17
Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
18 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 53, NO. 1, JANUARY/FEBRUARY 2017
Fig. 2. Simple one line diagram of the industrial distribution system under study.
TABLE II TABLE IV
RECORDS ACQUIRED DURING THE PERIOD 2008–2014 VOLTAGE SAG QUANTIFICATION IN SUBSTATION 1 IN THE YEAR 2008
Site Name Time Phase Magnitude Magnitude Duration Duration Duration (s)
Stamp (kV) (p.u.) (s) (cycles)
Magnitude (p.u.) < 0.1 0.1–0.25 0.25–0.5 1–3 3–20 20–60 60–300
SUB_1 25/01/08 C 14 724.084 0.631 0.491 29.5
20:47:15.831 0.8–0.9 p.u. 74 54 27 7 0 0 0
SUB_1 27/01/08 B 14 374.066 0.616 0.133 8 0.7–0.8 p.u. 22 12 9 0 0 0 0
09:27:24.321 0.6–0.7 p.u. 13 8 2 0 0 0 0
SUB_1 06/02/08 C 16 194.159 0.694 0.083 5 0.5–0.6 p.u. 5 5 0 0 0 0 0
15:01:16.939
0.4–0.5 p.u. 5 1 1 0 0 0 0
... ... ... ... ... ... ...
0.3–0.4 p.u. 0 0 0 0 0 0 0
SUB_1 31/12/14 C 19 390.989 0.831 0.316 19
0.2–0.3 p.u. 0 0 0 0 0 0 0
13:29:03.561
0.1–0.2 p.u. 0 0 0 0 0 0 0
ࣘ0.1 p.u. 0 0 0 0 0 0 0
TABLE III
VOLTAGE SAG SEVERITY VALUES FOR THE SUBSTATION UNDER STUDY TABLE V
BETWEEN 2008 AND 2014 VOLTAGE SAG QUANTIFICATION IN SUBSTATION 1 IN THE YEAR 2014
Year
Duration (s)
Parameter Analyzed 2008 2009 2010 2011 2012 2013 2014
Magnitude (p.u.) < 0.1 0.1–0.25 0.25–0.5 1–3 3–20 20–60 60–300
Nannual 245 306 292 369 480 452 420
0.8–0.9 p.u. 66 115 56 24 8 0 0
N30 20.13 25.15 24 30.32 39.5 37.15 34.52
0.7–0.8 p.u. 56 18 9 3 0 0 0
Ssite 113.811 151.668 146.824 175.014 239.588 244.765 216.248
0.6–0.7 p.u. 23 9 7 1 0 0 0
Saverage 0.464 0.495 0.502 0.474 0.499 0.541 0.514
0.5–0.6 p.u. 4 3 1 1 0 0 0
0.4–0.5 p.u. 8 1 1 0 0 0 0
0.3–0.4 p.u. 4 0 0 0 0 0 0
0.2–0.3 p.u. 0 0 1 0 0 0 0
threshold of higher retained voltage and short duration. Results 0.1–0.2 p.u. 0 0 1 0 0 0 0
ࣘ0.1 p.u. 0 0 0 0 0 0 0
obtained are shown in Tables IV and V, respectively.
Specifically, instantaneous sags (0–30 cycles) accounted for
81% and 73% of voltage sags in 2008 and 2014, respectively.
Moreover, more than 80% of voltage sags had a retained voltage be assumed that 80% of voltage sags will be representative of
superior to 0.7 p.u. in both years. the behavior of the point of interest. This way, the calculation of
Now, from Tables IV and V, it can be identified the percentage voltage sag severity can be based on the worst scenario (Wss );
of voltage sags between the intervals of interest (magnitude and that is, assuming that in each interval of frequency, all voltage
duration) with the highest frequency of occurrence (Fo ). It can sags have the lower magnitude and longer duration possible.
Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
ARIAS-GUZMÁN et al.: ANALYSIS OF VOLTAGE SAG SEVERITY CASE STUDY IN AN INDUSTRIAL CIRCUIT 19
TABLE VI
VOLTAGE SAG DISTRIBUTION IN 2008
TABLE VII
VOLTAGE SAG DISTRIBUTION IN 2014 Fig. 3. Electrical equipment room with high moisture.
Magnitude Duration Frequency of Worst Severity Representative was detected. Table VIII shows typical records obtained in a
(p.u.) (ms) occurrence Fo Scenario Ws s severity
(%) value (Ws s .Fo ) measurement period of two months.
Eighty-three voltage sags occurred during the measurement
0.8–0.9 < 100 15.71 0.400 0.062
100–250 27.38 0.666 0.182
period. Additionally, the total severity index was 34 189 or an
250–500 13.33 0.666 0.088 average severity of 0.411. According to (3), 41.5 voltage sags
0.7–0.8 < 100 13.33 0.600 0.079 would have occurred over a period of 30 days. These values
100–250 4.28 1.00 0.042
250–500 2.14 1.00 0.021
are consistent with the rates of voltage sags calculated in the
substation feeding the industrial circuit presented in Table III.
The amount of voltage sags in the substation under study has
TABLE VIII increased between 2012 and 2014 but the average severity has
RECORDS OF VOLTAGE SAGS DETECTED IN INDUSTRIAL PCC FOR A PERIOD OF remained within tolerable values. Therefore, end users should
TWO MONTHS IN THE YEAR 2011
maintain this severity trend in their facilities. When discrimi-
nating the amount of voltage sags recorded by each user, only
Site Time Phase Magnitude Magnitude Duration Duration a total average of 3.6 voltage sags were measured. The highest
Name Stamp (kV) (p.u.) (s) (cycles)
amount of voltage sags recorded by a single user was 22.
PCC_User_1 16/09/11 A 18 795.533 0.792 0.116 7
12:31:22.583
PCC_User_2 16/09/11 A 18 536.455 0.803 0.108 6.5 VII. COMPARISON BETWEEN SEVERITY AND THE IMPACT OF
12:31:22.583
PCC_User_16 20/10/11 B 20 641.702 0.884 0.108 6.5 VOLTAGE SAGS
14:18:22.150
Based on the calculated voltage sag severity values in the
substation under study, it can be concluded that there is a good
supply of voltage waveform in relation to voltage sags for each
Subsequently, the representative severity value will be equal industrial user. This result contradicts the statement of users
to the worst severity by the frequency of occurrence of each who said that interruption of operations was caused by deficient
interval. For last, the average severity value will be the sum of supply voltage. It was, therefore, necessary to check the protec-
each representative severity value. By applying this method in tion system of users who reported problems of short duration
2008 and 2014, the results are listed in Tables VI and VII. interruptions. This conclusion is based on the values of retained
Applying this method, the average severity value calculated voltage and duration recorded in Tables IV and V which do not
for the year 2008 is 0.476 and 0.478 for 2014. Comparing the justify the interruption of an industrial process. These interrup-
average severity values obtained in Tables VI and VII with the tions can be explained by poor engineering practices. Sugges-
values of Table III, it shows that only a percentage of error tions of good engineering practice should be made to users to
of 2.58 for the year 2008 and of 7.00 for 2014 is obtained. increase the sensitivity of equipment when facing short dura-
Thus, in this way, the average severity value can be obtained tion sags. Two particular cases of poor engineering practices are
in a reasonable approximation without the need of calculate the described below.
severity of each registered voltage sag. Case 1 shows deterioration caused by excessive moisture in
contact with electrical equipment found in a facility inspection
of an industrial user who had many records of voltage sags (see
VI. VOLTAGE SAG SEVERITY IN PCC OF INDUSTRIAL USERS
Fig. 3).
Measurements using portable analyzers were done for a pe- Case 2 shows a picture taken in a low-voltage cell of another
riod of two months in 2011 to some users of Fig. 2. The available facility (see Fig. 3). Fig. 4 shows that the post of 13, 2 kV of
information is: 1) the lower retained voltage during sags; 2) du- the interval network has the required protection in transmission
ration; and 3) the phase in which the lower retained voltage lines. Additionally, isolators and DPS are installed. However, the
Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
20 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 53, NO. 1, JANUARY/FEBRUARY 2017
Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
ARIAS-GUZMÁN et al.: ANALYSIS OF VOLTAGE SAG SEVERITY CASE STUDY IN AN INDUSTRIAL CIRCUIT 21
[14] E Compatibility, Part 2–8: Environment—Voltage Dips and Short Inter- Marı́a Jaramillo-Gonzáles was born in Manizales,
ruptions on Public Electric Power Supply Systems With Statistical Mea- Caldas, Colombia, in 1994. She is currently working
surement Results, IEC 61000-2-8, 2002. toward the B.Sc. degree in electronic engineering at
[15] Norma Técnica Colombiana Grados de Protección dado por Encer- the National University of Colombia, Manizales.
ramientos de Equipo Eléctrico, NTC 3279, 2001. Her research interests include biomedical sensitiv-
[16] Reglamento Técnico de Instlaciones Eléctricas (RETIE), Resolución NO. ity in measurement equipment’s from power quality.
9 0708 de AGOSTO 30 de, 2013.
[17] D. Gallo, C. Landi, M. Luiso, and E. Fiorucci, “Survey on voltage dip mea-
surements in standard framework,” IEEE Trans. Instrum. Meas., vol. 63,
no. 2, pp. 374–387, Feb. 2014.
[18] S. Arias-Guzman, A. J. Ustariz-Farfan, and E. A. Cano-Plata, “Voltage
sag segmentation under deformation tensor parameters,” in Proc. 2014
IEEE 16th Int. Conf. Harmon. Qual. Power, pp. 541–545.
[19] S. Arias-Guzman, A. J. Ustariz-Farfan, and E. A. Cano-Plata, “Detection Pablo Daniel Cardona-Orozco (S’15) was born in
Of power quality disturbances using deformation tensor parameters,” IEEE Manizales, Caldas, Colombia, in 1994. He is cur-
Trans. Latin Amer. Trans., vol. 13, no. 7, pp. 2106–2113, Jul. 2015. rently working toward the B.Sc. degree in electrical
[20] M. R. Alam, K. M. Muttaqi, and A. Bouzerdoum, “Characterizing voltage engineering at the National University of Colombia,
sags and swells using three-phase voltage ellipse parameters,” IEEE Trans. Manizales.
Ind. Appl., vol. 51, no. 4, pp. 2780–2790, Jul./Aug. 2015. His research interests include power quality anal-
ysis and smart grids.
Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.