Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 53, NO.

1, JANUARY/FEBRUARY 2017 15

Analysis of Voltage Sag Severity Case Study in an


Industrial Circuit
Santiago Arias-Guzmán, Student Member, IEEE, Oscar Andrés Ruiz-Guzmán, Student Member, IEEE,
Luı́s Felipe Garcia-Arı́as, Marı́a Jaramillo-Gonzáles, Pablo Daniel Cardona-Orozco, Student Member, IEEE,
Armando J. Ustariz-Farfán, Member, IEEE, Eduardo A. Cano-Plata, Senior Member, IEEE,
and Andrés Felipe Salazar-Jiménez

Abstract—This paper presents the results of a power quality [3]. This is due to the widespread use of equipment sensitive
study carried out in an industrial distribution system. The main to this disturbance [4], even if they are of very short duration
objective of this study was to quantify the negative impact caused (1–6 cycles) [3]. Consequently, voltage sags have become an im-
by voltage sags in industrial processes and its relationship to gen-
erated interruptions. A series of measurements of power quality portant problem for network operators and end users. Multiple
variations were taken at the substation that feeds the circuit and studies are needed to analyze the relationship between voltage
at the point-of-common coupling of each industrial user. The new sags and the generation of interruptions in industrial processes
standard IEEE Std 1564-2014 “Guide for Voltage Sag Indices” was and also the destruction of equipment [3]–[6]. This problem was
used to determine the indicators to assess the severity of voltage detected in an industrial distribution system when the network
sags and also the calculation method. Sag severity was selected as
it allows the calculation of the probability of voltage sags to gen- operator (OR) of the city of Manizales (Colombia) conducted a
erate interruptions in industrial processes or electrical equipment. study of power quality in an industrial circuit. First, research car-
Thus, an analysis of the quality of the supply voltage can be done. ried out in 25 industrial users revealed that 60% of these compa-
Severity was initially calculated at the substation that feeds the in- nies reported the occurrence of voltage variations. Also, around
dustrial circuit and later, at the point-of-common coupling of each 80% of these companies reported using equipment sensitive to
user. Subsequently, the relationship between user interruptions
and severity values was determined. Finally, recommendations of such disturbances. Therefore, the need to quantify the quality
good engineering practices in industrial processes were done. of voltage supply arose. A series of measurements was taken at
the substation that feeds the industrial distribution system and
Index Terms—Distortion measurement, IEEE Std 1564, power
distribution, power quality, voltage fluctuations.
at the point-of-common coupling (PCC) of each industrial user.
First, the duration and retained voltage of each voltage sag
I. INTRODUCTION was recorded. These two parameters were selected given the
possibility of combining them into a single indicator known as
HE need to prevent and reduce the effects of disturbances
T on electrical systems has acquired great importance in re-
cent years [1]. Among all possible disturbances, voltage sags
voltage sag severity. Voltage sag severity allows the measure-
ment of the probability of generating an interruption in a process
or in a device. Recently, the IEEE Guide for Voltage Sag Indices
have the highest occurrence frequency [2]. Additionally, it has
IEEE Std. 1564-2014 introduced methods for further calculat-
been estimated that voltage sags generate between 92% and
ing the severity of voltage sags [7]. This study shows the need
98% of interruptions attributed to disturbances in power supply
to use this standard in the analysis of the impact of voltage sags
in industrial distribution systems, and additionally, the need to
Manuscript received August 1, 2015; revised November 19, 2015; accepted considered the actual conditions of the connections of end-user
January 16, 2016. Date of publication August 26, 2016; date of current version loads. Additionally, the fastest way to calculate the average
January 18, 2017. Paper 2015-PSEC-0602.R1, presented at the 2015 Industry severity value is presented. This paper is organized as follows.
Applications Society Annual Meeting, Addison, TX, USA, Oct. 18–22, and ap-
proved for publication in the IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS Section II presents the results of a research carried out to identify
by the Power System Engineering Committee of the IEEE Industry Applica- the main power quality problems for industrial users. Section III
tions Society. This work was supported in part by the Universidad Nacional introduces the theoretical framework used as base to calculate
de Colombia (Research Found Office of Manizales—DIMA) (Distribution and
Power Network Research Group—GREDyP; Power Quality and Power Elec- the severity of voltage sags. Section IV describes the avail-
tronics Research Group—GICEP; and Laboratory in Quality of Energy and able measurement system of the network operator. Section V
Power Electronics—LACEP). presents severity of voltage sags and measurement records in
S. Arias-Guzmán, O. A. Ruiz-Guzmán, L. F. Garcia-Arı́as, M. Jaramillo-
Gonzáles, P. D. Cardona-Orozco, and E. A. Cano-Plata are with the Universidad the substation and a fastest way to calculate the average severity
Nacional de Colombia, Manizales 111321, Colombia (e-mail: saariasgu@unal. value. Section VI shows measurement records of each industrial
edu.co; oaruizg@unal.edu.co; lufgarciaar@unal.edu.co; marjaramillogon@ user and voltage sag severity. Section VII presents a compar-
unal.edu.co; pdcardonao@unal.edu.co; eacanopl@unal.edu.co).
A. J. Ustariz-Farfán is with the Electrical, Electronic and Computer Engi- ison between severity and the impact of voltage sags. Finally,
neering Department, Universidad Nacional de Colombia, Manizales 111321, Section VIII presents the conclusions of this study.
Colombia (e-mail: ajustarizf@unal.edu.co).
A. F. Salazar-Jiménez is with the Central Hidroeléctrica de Caldas—CHEC,
Manizales 111321, Colombia (e-mail: andres.salazar@chec.com.co). II. MAJOR PROBLEMS OF POWER QUALITY: CASE STUDY
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. A study was carried out to identify the main problems
Digital Object Identifier 10.1109/TIA.2016.2603470 of power quality for each industrial user. This process was

0093-9994 © 2016 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications standards/publications/rights/index.html for more information.
Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
16 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 53, NO. 1, JANUARY/FEBRUARY 2017

conducted to analyze the perception of the power quality service


of each user. The different industrial users included: 1) Tool
manufacturing; 2) coffee processing; 3) timber industry;
4) chemical production; 5) data processing centers; 6) plastic
manufacturing; 7) alcohol production; 8) food and candy
production; and 9) metal production. A series of surveys was
conducted in 25 companies in order to get measurable results.
The results showed that only two of these companies had voltage
stabilization systems. Some of the remaining companies re-
ported problems such as: 1) damage to PLCs due in some cases to
internal programming, and 2) damage to automation equipment,
screens, and automata caused by voltage variations. A total of
80% of users reported using equipment sensitive to voltage sags.
This problem was described by operators as very short interrup- Fig. 1. SEMI-F47 fitting curve for calculating severity of voltage sags [6].
tions. The problems caused by this situation include: 1) inter-
ruption of data processing; 2) resumption of lighting systems; The Colombian regulation integrates voltage sags and elevations
3) interruption of production processes (PLCs damage, poor in the calculation of the PST . Moreover, in this study, the network
operation of contactors, relays, variable speed drives); 4) loss operator needed to quantify the individual impact of voltage
of property; 5) loss of materials; and 6) equipment malfunction. sags in order to improve service delivery to the industrial users
Twelve companies reported this problem during the period of mentioned in Section II.
data collection. Some of the effects were: 1) interruption of On the other hand, the Standard [7] provides the method to
centrifuges in food factories; 2) equipment damage in closed calculate the severity index in each voltage sag, substation, and
circuit television in plastic producers; 3) loss of production power system. This method is also suitable for calculating the
time in timber; 4) voltage sags that generated loss of material voltage sag severity at different sites such the PCC of a single
in tool factories; 5) failure in variable speed drives in candy user. The method presented in [7] focuses solely on voltage sags.
factories; 6) alteration in the manufacturing processes in users The IEEE 1564 of 2014 determines that sag severity calculation
producing household appliances such as refrigerators; 7) and must be performed in records captured in monitoring periods
finally, the loss of raw materials due to heating and cooling of at least one month. The method used to calculate severity
processes in food factories. The interruption of the production according to [7] is as follows.
process represents 90% of the problems reported by users. After 1) Obtain the records of waveforms for a period of measure-
analyzing all the information collected, it was then decided ment (minimum one month).
that it was necessary to calculate the impact caused by voltage 2) Calculate the retained voltage and duration of voltage
sags. At first place, a review of existing national regulations sags.
on how to assess the severity of this disturbance was done. 3) Calculate the voltage sag severity of voltage sags.
It was concluded that the assessment needed to be broadened 4) Calculate the voltage sag severity on the studied substation
to international levels. The reason for choosing the IEEE as the sum of individual contributions of voltage sags.
Std 1564-2014 standard and the differences with Colombian For this, the IEEE 1564-2014 proposes the calculation as
regulations are presented as follows. follows.
Each sag severity is obtained using the following equation:
III. VOLTAGE SAG SEVERITY: IEEE 1564-2014 AND
CREG 017-2005 1 − V
Se = (1)
In the Colombian regulatory framework, the Commission of 1 − Vcurve (d)
Energy and Gas Regulation (CREG) defines the quality stan- where V is the retained voltage per unit (p.u.), d is the duration
dards that network operators must meet to ensure conditions of of the sag, and Vcurve is the voltage of a reference curve in
quality and continuity. The document CREG-017 of March 8, a device. The standard IEEE Std 1564-2014 [7] recommends
2005 “Power Quality” [8] includes a parameter that relates the using the F47 curve of the International group of Semiconductor
different types of voltage disturbances including voltage sags. Equipment and Materials (SEMI) [10] as a benchmark. Fig. 1
The CREG-017 seeks to combine all voltage disturbances (sags, shows the SEMI-F47 which is used as a fitting curve.
peaks, elevations, flicker, etc.) into a single indicator. Voltage sags with a severity value of less than 1 are considered
This approach aims to measure the severity of voltage fluc- within the operation area of the equipment but it is not implied
tuations in a shorter time interval without storing vast amounts that the equipment or the process will not be affected [7]. Voltage
of information needed for further analysis [8]. The parameter of sag severity with values greater than 1 produces interruptions.
the Colombian regulation calculates an indicator of statistical Table I provides an algorithm when the SEMI-F47 curve is
physics that assigns a severity level to all disturbances occurring used as reference for each value of retained voltage V and a
over a period of time known as PST [9]. duration d.
The indicator proposed by the Colombian regulation is based It is possible to evaluate severity in a substation or PCC from
on the proposal presented in the IEC 61000-4-15 of 2003 [9]. each voltage sag severity as the sum of individual contributions

Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
ARIAS-GUZMÁN et al.: ANALYSIS OF VOLTAGE SAG SEVERITY CASE STUDY IN AN INDUSTRIAL CIRCUIT 17

TABLE I The measurement equipment, voltage (PT) and current (CT)


ALGORITHM FOR CALCULATING VOLTAGE SAG SEVERITY—SEMI-F47 [7]
transformers are referenced to ground and the configuration of
the measurement equipment in the substations corresponds to
Duration range Calculation of voltage sag severity connections of three elements (three PTs and three CTs).
d ࣘ 20 ms Se = 1 − V Table II shows the records acquired from the database in the
20 ms ࣘ d ࣘ 200 ms Se = 2 (1 − V ) substation of 33 kV.
200 ms ࣘ d ࣘ 500 ms Se = 3.3 (1 − V ) A total of 2700 records of variations of RMS including voltage
500 ms ࣘ d ࣘ 10 s Se = 5 (1 − V )
d > 10 s Se = 10 (1 − V ) sags, elevations, and interruptions were acquired in the substa-
tion under study. From these records, the PST indicator can be
calculated but it would not represent voltage sag severity. There-
of voltage sags. Total severity (Ssite ) and average severity fore, records belonging only to voltage sags were extracted. A
(Saverage ) are calculated as shown in (2), where N is the to- total of 2676 of the 2700 records were voltage sags. The avail-
tal number of voltage sags in a period of time, and Sn _th is able information is: 1) the lower value of voltage retained during
the severity of the sag nth. The amount of voltage sags taking the sag; 2) duration; and 3) the phase in which the lower value
place every 30 days (N30 ) in the total period of measurement of voltage was detected. Additionally, records obtained in each
(Tm easurem ent ) is calculated using (3): user PCC were acquired in 2011 in a period longer than two

N months. Based on this information, it is possible to calculate
Ssite = Sn th the severity indicators of voltage sags in the substation under
i=1 study and in the PCC of each industrial user. This paper will not
Ssite show the severity of each record but it will present the results of
Saverage = (2) applying the methodology in Section III to the substation under
N
study and the PCC of each industrial user.
N
N30 = 30 · . (3)
Tmeasurement

IV. AVAILABLE MEASUREMENT SYSTEM V. SEVERITY IN THE SUBSTATION UNDER STUDY


An evaluation of a medium-voltage industrial distribution Initially, voltage sag severity was calculated using the SEMI-
system was carried out using the severity indicators. In this F47 of the algorithm shown in Table I. Then, (2) was used to
industrial system, a 33-kV substation feeds a shunt circuit to calculate total voltage sag severity and the average voltage sag
some industrial consumers of Manizales (Colombia). This as- severity in the substation. These two parameters were obtained
sessment was conducted from 01/01/2008 to 12/31/2014. Fig. 2 between 2008 and 2014 (annual comparison). The amount of
shows the one-line diagram of the industrial circuit under study. voltage sags were also obtained every 30 days by (3). Results
This figure shows the diverse elements involved in supplying are shown in Table III.
industrial users and also the position of the equipment to mea- Table III shows that the amount of voltage sags every 30
sure information (UAD) in the 33-kV substation. Users connect days during seven years has increased from an average of 20
to a distribution circuit in a topology with guard cable cover- to 34 voltage sags. Also, the total severity in the substation has
ing 100% of its length. This circuit provides its entire load to increased with the years. The total severity value appears to have
industrial users. Its topology is radial. The information used doubled between 2008 and 2014. Still, the average severity in
was provided by the quality management system of the electric all the years has changed little from a value of 0.5 resulting in
network operator. an allowable value for the circuits fed by this substation.
The network operator has a total of 86 class “A” analyzers of Given the values presented in Section III, Fig. 1, the average
quality (as described in [11]–[13]) and each substation has its severity has remained remote from the interruption threshold
own analyzer. The basic characteristics of these analyzers are: value. Thus, it is considered that the power quality service for
1) they allow measurements applicable to Class A equipment voltage sags meets SEMI F47 standards. This also shows that,
(according to the IEC 61000-4-30 [12]); 2) they count on eight although the number of voltage sags has increased in the differ-
channels, four of current and four of voltage configurable ac- ent years, average severity has remained at acceptable values.
cording to the type of measurement (single phase, three phase Therefore, the severity average value becomes a more important
in star or delta, the two wattmeter method, two elements and a parameter of analysis than the amount of voltage sags in a year.
half); 3) they record harmonic components of up to 3000 Hz; The low severity average value can be explained taking into ac-
4) they are able to acquire 512 samples per cycle; and 5) they count the amount of sags with durations shorter than 500 ms and
are able to configure the reference voltage (sliding voltage Usr a high retained voltage. A series of tables allows a quick com-
or declared voltage Un ). parison in different years. Therefore, the method proposed in
Additionally, the network operator has portable equipment IEC 61000-2-8 Environment-Voltage Dips and Short Interrup-
with touch interface that allows field parameterization. Even tions on Public Electric Power Supply Systems With Statistical
though portable equipment has lower specifications than fixed Measurement Results [14] is used.
equipment, the main differences are: 1) acquisition of 256 sam- Applying this distinction to records in 2008 and 2014 showed
ples per cycle and 2) configuration of the Un reference voltage. that the greatest amount of voltage sags remained within the

Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
18 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 53, NO. 1, JANUARY/FEBRUARY 2017

Fig. 2. Simple one line diagram of the industrial distribution system under study.

TABLE II TABLE IV
RECORDS ACQUIRED DURING THE PERIOD 2008–2014 VOLTAGE SAG QUANTIFICATION IN SUBSTATION 1 IN THE YEAR 2008

Site Name Time Phase Magnitude Magnitude Duration Duration Duration (s)
Stamp (kV) (p.u.) (s) (cycles)
Magnitude (p.u.) < 0.1 0.1–0.25 0.25–0.5 1–3 3–20 20–60 60–300
SUB_1 25/01/08 C 14 724.084 0.631 0.491 29.5
20:47:15.831 0.8–0.9 p.u. 74 54 27 7 0 0 0
SUB_1 27/01/08 B 14 374.066 0.616 0.133 8 0.7–0.8 p.u. 22 12 9 0 0 0 0
09:27:24.321 0.6–0.7 p.u. 13 8 2 0 0 0 0
SUB_1 06/02/08 C 16 194.159 0.694 0.083 5 0.5–0.6 p.u. 5 5 0 0 0 0 0
15:01:16.939
0.4–0.5 p.u. 5 1 1 0 0 0 0
... ... ... ... ... ... ...
0.3–0.4 p.u. 0 0 0 0 0 0 0
SUB_1 31/12/14 C 19 390.989 0.831 0.316 19
0.2–0.3 p.u. 0 0 0 0 0 0 0
13:29:03.561
0.1–0.2 p.u. 0 0 0 0 0 0 0
ࣘ0.1 p.u. 0 0 0 0 0 0 0

TABLE III
VOLTAGE SAG SEVERITY VALUES FOR THE SUBSTATION UNDER STUDY TABLE V
BETWEEN 2008 AND 2014 VOLTAGE SAG QUANTIFICATION IN SUBSTATION 1 IN THE YEAR 2014

Year
Duration (s)
Parameter Analyzed 2008 2009 2010 2011 2012 2013 2014
Magnitude (p.u.) < 0.1 0.1–0.25 0.25–0.5 1–3 3–20 20–60 60–300
Nannual 245 306 292 369 480 452 420
0.8–0.9 p.u. 66 115 56 24 8 0 0
N30 20.13 25.15 24 30.32 39.5 37.15 34.52
0.7–0.8 p.u. 56 18 9 3 0 0 0
Ssite 113.811 151.668 146.824 175.014 239.588 244.765 216.248
0.6–0.7 p.u. 23 9 7 1 0 0 0
Saverage 0.464 0.495 0.502 0.474 0.499 0.541 0.514
0.5–0.6 p.u. 4 3 1 1 0 0 0
0.4–0.5 p.u. 8 1 1 0 0 0 0
0.3–0.4 p.u. 4 0 0 0 0 0 0
0.2–0.3 p.u. 0 0 1 0 0 0 0
threshold of higher retained voltage and short duration. Results 0.1–0.2 p.u. 0 0 1 0 0 0 0
ࣘ0.1 p.u. 0 0 0 0 0 0 0
obtained are shown in Tables IV and V, respectively.
Specifically, instantaneous sags (0–30 cycles) accounted for
81% and 73% of voltage sags in 2008 and 2014, respectively.
Moreover, more than 80% of voltage sags had a retained voltage be assumed that 80% of voltage sags will be representative of
superior to 0.7 p.u. in both years. the behavior of the point of interest. This way, the calculation of
Now, from Tables IV and V, it can be identified the percentage voltage sag severity can be based on the worst scenario (Wss );
of voltage sags between the intervals of interest (magnitude and that is, assuming that in each interval of frequency, all voltage
duration) with the highest frequency of occurrence (Fo ). It can sags have the lower magnitude and longer duration possible.

Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
ARIAS-GUZMÁN et al.: ANALYSIS OF VOLTAGE SAG SEVERITY CASE STUDY IN AN INDUSTRIAL CIRCUIT 19

TABLE VI
VOLTAGE SAG DISTRIBUTION IN 2008

Magnitude Duration Frequency of Worst-Severity Representative


(p.u.) (ms) occurrence Scenario Ws s severity
Fo (%) value (Ws s .Fo )

0.8–0.9 < 100 30.20 0.400 0.120


100–250 22.04 0.666 0.146
250–500 11.02 0.666 0.073
0.7–0.8 < 100 8.97 0.600 0.053
100–250 4.89 1.00 0.048
250–500 3.67 1.00 0.036

TABLE VII
VOLTAGE SAG DISTRIBUTION IN 2014 Fig. 3. Electrical equipment room with high moisture.

Magnitude Duration Frequency of Worst Severity Representative was detected. Table VIII shows typical records obtained in a
(p.u.) (ms) occurrence Fo Scenario Ws s severity
(%) value (Ws s .Fo ) measurement period of two months.
Eighty-three voltage sags occurred during the measurement
0.8–0.9 < 100 15.71 0.400 0.062
100–250 27.38 0.666 0.182
period. Additionally, the total severity index was 34 189 or an
250–500 13.33 0.666 0.088 average severity of 0.411. According to (3), 41.5 voltage sags
0.7–0.8 < 100 13.33 0.600 0.079 would have occurred over a period of 30 days. These values
100–250 4.28 1.00 0.042
250–500 2.14 1.00 0.021
are consistent with the rates of voltage sags calculated in the
substation feeding the industrial circuit presented in Table III.
The amount of voltage sags in the substation under study has
TABLE VIII increased between 2012 and 2014 but the average severity has
RECORDS OF VOLTAGE SAGS DETECTED IN INDUSTRIAL PCC FOR A PERIOD OF remained within tolerable values. Therefore, end users should
TWO MONTHS IN THE YEAR 2011
maintain this severity trend in their facilities. When discrimi-
nating the amount of voltage sags recorded by each user, only
Site Time Phase Magnitude Magnitude Duration Duration a total average of 3.6 voltage sags were measured. The highest
Name Stamp (kV) (p.u.) (s) (cycles)
amount of voltage sags recorded by a single user was 22.
PCC_User_1 16/09/11 A 18 795.533 0.792 0.116 7
12:31:22.583
PCC_User_2 16/09/11 A 18 536.455 0.803 0.108 6.5 VII. COMPARISON BETWEEN SEVERITY AND THE IMPACT OF
12:31:22.583
PCC_User_16 20/10/11 B 20 641.702 0.884 0.108 6.5 VOLTAGE SAGS
14:18:22.150
Based on the calculated voltage sag severity values in the
substation under study, it can be concluded that there is a good
supply of voltage waveform in relation to voltage sags for each
Subsequently, the representative severity value will be equal industrial user. This result contradicts the statement of users
to the worst severity by the frequency of occurrence of each who said that interruption of operations was caused by deficient
interval. For last, the average severity value will be the sum of supply voltage. It was, therefore, necessary to check the protec-
each representative severity value. By applying this method in tion system of users who reported problems of short duration
2008 and 2014, the results are listed in Tables VI and VII. interruptions. This conclusion is based on the values of retained
Applying this method, the average severity value calculated voltage and duration recorded in Tables IV and V which do not
for the year 2008 is 0.476 and 0.478 for 2014. Comparing the justify the interruption of an industrial process. These interrup-
average severity values obtained in Tables VI and VII with the tions can be explained by poor engineering practices. Sugges-
values of Table III, it shows that only a percentage of error tions of good engineering practice should be made to users to
of 2.58 for the year 2008 and of 7.00 for 2014 is obtained. increase the sensitivity of equipment when facing short dura-
Thus, in this way, the average severity value can be obtained tion sags. Two particular cases of poor engineering practices are
in a reasonable approximation without the need of calculate the described below.
severity of each registered voltage sag. Case 1 shows deterioration caused by excessive moisture in
contact with electrical equipment found in a facility inspection
of an industrial user who had many records of voltage sags (see
VI. VOLTAGE SAG SEVERITY IN PCC OF INDUSTRIAL USERS
Fig. 3).
Measurements using portable analyzers were done for a pe- Case 2 shows a picture taken in a low-voltage cell of another
riod of two months in 2011 to some users of Fig. 2. The available facility (see Fig. 3). Fig. 4 shows that the post of 13, 2 kV of
information is: 1) the lower retained voltage during sags; 2) du- the interval network has the required protection in transmission
ration; and 3) the phase in which the lower retained voltage lines. Additionally, isolators and DPS are installed. However, the

Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
20 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, VOL. 53, NO. 1, JANUARY/FEBRUARY 2017

index allows to assign responsibilities and in this case, it can


be concluded that interruption problems do not arise from the
quality of voltage supply by the network operator. Additionally,
it was observed that it is not necessary to calculate the severity of
each voltage sag registered to estimate an approximate average
severity value.
Moreover, poor engineering practices affecting the sensitivity
of the equipment were identified. The capacity of immunity of
the equipment affected by the breakdown or by poor protection
systems, as in the cases presented in Section VII, should be
taken into account in future studies of voltage sag severity.
In addition, it is necessary for a more in-depth study of the
methods of voltage sag analysis and its relationship to the inter-
ruption of industrial processes. The results might be included
in the existing Colombian regulation of power quality. This is
important considering that voltage sags were 99% of the varia-
Fig. 4. Grounding conductor of the DPS cut in half the stretch.
tions of RMS voltage values recorded during the seven years of
measurement.
DPS are connected in common mode to a grounding conductor
A feasible alternative in Colombia is to review the records
that is cut and disconnected from the grounding system.
of voltage sags in the substation that feeds a circuit of interest.
These types of users require a more detailed study to identify
In the case of this particular study, mitigation schemes must be
faults in connections. Based on the findings, it is accurate to say
considered against voltage sags of short duration (more than
that the sensitivity of the equipment might increase in the face
80% of voltage sags have a duration shorter than 30 cycles) and
of voltage sags. Thus, corrective actions should be carried out
high retained voltage (upper to 0.7 p.u.).
taking into account the pertinent regulations. In case 1, it is nec-
essary to revise the regulations on degrees of protection given
to electrical equipment enclosures [15], taking special care of ACKNOWLEDGMENT
the boards or enclosures that protect sensitive equipment. In
case 2, proper connections in accordance with Colombian es- The authors would like to thank the Central Hidroeléctrica
tablished regulations (regulations of electric installation RETIE) de Caldas—CHEC for providing the equipment and sufficient
must be ensured [16]. It should be noted that there is still ongo- information of power quality records to carry out this study.
ing research on the relationship between equipment failure and
voltage sags [3]–[6]. After the inspection of the users’ facilities,
it was concluded that it is necessary to determine the minimum REFERENCES
standards of protection when conducting future studies on the [1] M. Madrigal and B. H. Rocha, “A contribution for characterizing measured
severity of voltage sags. Considering that short duration sags three-phase unbalanced voltage sags algorithm,” IEEE Trans. Power Del.,
vol. 22, no. 3, pp. 1885–1890, Jul. 2007.
(0–30 cycles) accounted for over 80% of the recorded voltage [2] J. Esteves, K. Brekke, K. Niall, M. Delfanti, and M. Bollen, “Voltage
sags, further efforts should be made to accurately analyze these quality monitoring, dips classification and responsibility sharing,” in Proc.
disturbances. According to [17], there are still delays in the de- IEEE 15th Int. Conf. Harmon. Qual. Power, 2011, pp. 1–6.
[3] A. Bendre, D. Divan, W. Kranz, and W. E. Brumsickle, “Are voltage sags
tection of short-duration voltage sags by the existing network destroying equipment?” IEEE Ind. Appl. Mag., vol. 12, no. 4, pp. 12–21,
analyzers. Therefore, other detection tools such as [18]–[20], Jul./Aug. 2006.
might be used to calculate the duration of these voltage sags. [4] A. Moreno-Munoz and J. J. G. De la Rosa, “Voltage sag in highly auto-
mated factories,” in Proc. 2008 IEEE Ind. Appl. Soc. Annu. Meet., pp. 1–6.
[5] A. K. Goswami, C. P. Gupta, and G. K. Singh, “Voltage sag assessment
VIII. CONCLUSION in a large chemical industry,” IEEE Trans. Ind. Appl., vol. 48, no. 5,
pp. 1739–1746, Sep./Oct. 2012.
Voltage sag severity can be used as an additional tool to [6] S. R. Naidu, G. V. de Andrade, and E. G. da Costa, “Voltage sag perfor-
traditional classification processes in studies that seek to char- mance of a distribution system and its improvement,” IEEE Trans. Ind.
Appl., vol. 48, no. 1, pp. 218–224, Jan./Feb. 2012.
acterize and determine the quality of power quality at certain [7] IEEE Guide for Voltage Sag Indices, IEEE Standard 1564, 2014.
points; for this reason and as an example, voltage sag severity [8] Calidad de la Potencia, Comisión Reguladora de Energı́a y Gas Docu-
in a medium-voltage industrial distribution network was calcu- mento CREG-017, 2005.
[9] Compatibility, E. (2009). Part 4–15: Testing and Measurement
lated. As a result, a tendency lower to 50 voltage sags every Techniques—Flickermeter—Functional and Design Specifications, IEC
30 days was detected and average severity at this point was 0.5 Standard 61000-4-15, 2009.
per sag. The severity in this industrial system meets the limits [10] Specification for Semiconductor Processing Equipment Voltage Sag Im-
munity, SEMI, F47-0706, 2006.
of the SEMI-F47 reference curve avoiding entering the area of [11] IEEE Recommended Practice for the Design of Reliable Industrial and
interruption of the connected equipment. Moreover, the value Commercial Power Systems, IEEE Standard 493, 2007.
of the severity obtained in the substation feeding this circuit [12] Testing and Measurment Techniques—Section 30: Power Quality Mea-
surement Methods, IEC Standard 61000-4-30, 2003.
is consistent with the calculated severity in the PCC of the in- [13] IEEE Recommended Practice for Monitoring Electric Power Quality,
dustrial users under study. Similarly, the voltage sag severity IEEE Standard 1159-1995, 1995.

Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.
ARIAS-GUZMÁN et al.: ANALYSIS OF VOLTAGE SAG SEVERITY CASE STUDY IN AN INDUSTRIAL CIRCUIT 21

[14] E Compatibility, Part 2–8: Environment—Voltage Dips and Short Inter- Marı́a Jaramillo-Gonzáles was born in Manizales,
ruptions on Public Electric Power Supply Systems With Statistical Mea- Caldas, Colombia, in 1994. She is currently working
surement Results, IEC 61000-2-8, 2002. toward the B.Sc. degree in electronic engineering at
[15] Norma Técnica Colombiana Grados de Protección dado por Encer- the National University of Colombia, Manizales.
ramientos de Equipo Eléctrico, NTC 3279, 2001. Her research interests include biomedical sensitiv-
[16] Reglamento Técnico de Instlaciones Eléctricas (RETIE), Resolución NO. ity in measurement equipment’s from power quality.
9 0708 de AGOSTO 30 de, 2013.
[17] D. Gallo, C. Landi, M. Luiso, and E. Fiorucci, “Survey on voltage dip mea-
surements in standard framework,” IEEE Trans. Instrum. Meas., vol. 63,
no. 2, pp. 374–387, Feb. 2014.
[18] S. Arias-Guzman, A. J. Ustariz-Farfan, and E. A. Cano-Plata, “Voltage
sag segmentation under deformation tensor parameters,” in Proc. 2014
IEEE 16th Int. Conf. Harmon. Qual. Power, pp. 541–545.
[19] S. Arias-Guzman, A. J. Ustariz-Farfan, and E. A. Cano-Plata, “Detection Pablo Daniel Cardona-Orozco (S’15) was born in
Of power quality disturbances using deformation tensor parameters,” IEEE Manizales, Caldas, Colombia, in 1994. He is cur-
Trans. Latin Amer. Trans., vol. 13, no. 7, pp. 2106–2113, Jul. 2015. rently working toward the B.Sc. degree in electrical
[20] M. R. Alam, K. M. Muttaqi, and A. Bouzerdoum, “Characterizing voltage engineering at the National University of Colombia,
sags and swells using three-phase voltage ellipse parameters,” IEEE Trans. Manizales.
Ind. Appl., vol. 51, no. 4, pp. 2780–2790, Jul./Aug. 2015. His research interests include power quality anal-
ysis and smart grids.

Armando J. Ustariz-Farfán (S’08–M’12) was born


in Urumita, Colombia, in 1973. He received the Bach-
Santiago Arias-Guzmán (S’14) was born in Man- elor’s degree in electrical engineer and the Master’s
izales, Caldas, Colombia, in 1990. He received the degree in electric power from the Industrial Univer-
B.Sc. degree in electrical engineering from the Na- sity of Santander, Santander, in 1997 and 2000, re-
tional University of Colombia, Manizales, in 2013, spectively, and the Ph.D. degree in electrical engi-
where he is currently working toward the Ph.D. de- neering from the National University of Colombia,
gree in electrical engineering. Manizales, Colombia, in 2011.
His research interests include segmentation, power He is currently a Researcher and Associated
quality, and Kalman filtering. Professor in the Electrical, Electronic and Com-
puter Engineering Department, National University
of Colombia. His research interests include power definitions under nonsinu-
soidal conditions, power quality, and power electronics.

Eduardo A. Cano-Plata (S’96–M’98–SM’15) was


born in Neiva, Colombia, in 1967. He received the
Oscar Andrés Ruiz-Guzmán (S’14) was born in B.Sc. and Specialist Engineering degree in electrical
Manizales, Caldas, Colombia, in 1991. He received engineering from the National University of Colom-
the B.Sc. degree in electrical engineering from the bia, Manizales, Colombia, in 1990 and 1994, respec-
National University of Colombia, Manizales, in 2014, tively, and the Doctorate degree in Engineering from
where he is currently working toward the M.Sc. de- the Universidad de Buenos Aires, Buenos Aires, Ar-
gree in engineering, electrical engineering. gentina, in 2006.
His research interests include power quality, elec- Since 1994, he has been a Full Professor at the
trical vehicles, and smart grids. National University of Colombia. He is currently the
Director of the Transmission and Distribution Net-
work Group—GREDyP. His research interests include power quality, power
electronics, power systems grounding, and smart grids.

Andrés Felipe Salazar-Jiménez was born in Santa


Luı́s Felipe Garcı́a-Arias was born in Manizales, Rosa de Cabal, Risaralda, Colombia, in 1974. He re-
Caldas, Colombia, in 1995. He is currently working ceived the B.Sc. Engineering degree in industrial en-
toward the B.Sc. degree in electronic engineering at gineering from Universidad Autónoma de Manizales,
the National University of Colombia, Manizales, and Manizales, Colombia, in 2012. He is currently work-
the B.Sc. degree in mechatronics engineering at the ing toward the M.Sc. degree in engineering, electrical
University of Caldas, Manizales. engineering at the National University of Colombia,
His research interests include Kalman filtering, Manizales.
biomechanics, and assistive technologies. He is with the Central Hidroeléctrica de Caldas—
CHEC, Manizales, in the area of projects. His re-
search interests include power quality.

Authorized licensed use limited to: University of the Phillippines. Downloaded on March 19,2020 at 09:47:59 UTC from IEEE Xplore. Restrictions apply.

You might also like