Executive Summary Report

Site KOD, MP 132 KV KOD SS

Date 18.12.2020

Sr. No. M/c Detail Dir. No Particuler Cause Photos Remarks Order Details

Not able to reset LED/IED


Diffrential P642 font fasia was New GE Replaced. Kindly Send removed
1 malfuncitioning. However Protection was one for repair.
functioning Fine.

Concern contact removed for now.


1 TR 1 2 LV master getting trip repeatative. BCU trip malfunctioning. Haven't analyse problem as BCU in
inconsistent/Hang mode.

LV Breaker able to close even though


3 Problem with N/C of 86. Corrected physically
master remain trip.

Page 1 of 3
Executive Summary Report
Sr. No. M/c Detail Dir. No Particuler Cause Photos Remarks Order Details

Consider Replacement. Else get ir repair


CCU at TR MB itself faulty. Fusing
1 Remote Main tank OTI open indication. from local repairer shop. Chhanging
resistor has been blown.
resistor shall fix unit.

2 TR 03

2 Standby supply fail RTCC. Single phasing preventor faulty Consider Replacement.

Page 2 of 3
Executive Summary Report
Sr. No. M/c Detail Dir. No Particuler Cause Photos Remarks Order Details

Pole replaced with FDR 6 B-Ph. Which


R phase IR in open condition 294 was spare bay BTW.
3 FDR 5 1 Vaccum passout
Mohm CRM 27 Micro-ohm
IR Across VI - 589 Gohm

HV SIDE 89D interlocking was in series False TC fail if Isolator 89D Lopped Exsisted one and interlocking
1 opened. Wrong Breaker closing
with TCS circuit. routed to Closing circuit.
interlock at same time.

4 Common

Hardwiring parallel to SCADA reset


button wiring to master reset
pushbutton considering future front
2 fasia failure in mind. For all Relays. No NA NA
longer needs HMI button to reset
IEDs..

END

Page 3 of 3