Control Transformers: Section 1
Control Transformers: Section 1
Control Transformers: Section 1
Control Transformers
Pri. Volts Sec. Volts Part No. Page Pri. Volts Sec. Volts Part No. Page
2400 120/240 MVC***RE 65 600 120/240 Q**9P 64
3300 120/240 MVC***QE 65 600 12/24 Q***PRC* 64
4160 120/240 MVC***SE 65 240/480 120/240 Q**6P 64
4800 120/240 MVC***TE 65
6600 120/240 MVC***UE 65
7200 120/240 MVC***VE 65
30
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
SECTION 1
(regulation) during a brief period of overload condition (also referred to as “inrush current” ). Control transformers
are also known as Machine Tool Transformers, Industrial Control Transformers or Control Power Transformers.
When you calculate the VA requirement of a Transformer, do you use the Primary or
the Secondary Voltage?
When selecting the VA requirement, you use the Secondary Voltage.
Insulating Materials; what are they made of and what is their purpose?
Hammond Power Solutions utilizes Mylar, Nomex and other high quality insulating materials. Insulation is used to
electrically insulate turn-to-turn windings, layer-to-layer windings, primary to secondary windings and ground.
31
© Hammond Power Solutions Inc. Data subject to change without notice.
INDUSTRIAL CONTROL
SECTION 1 TRANSFORMERS
CONTROL TRANSFORMER SELECTION
Selecting a Control Transformer Therefore, HPS is recommending 5. If the nominal supply voltage
requires that you have first hand that a value of 40% power factor does not fluctuate more than 5%,
knowledge of the application for the be utilized. Although some other then reference the 90% secondary
transformer and that you understand control transformer manufacturers voltage column in the Regulation
some basic terms related to the still recommend a power factor of Data Table for the correct VA
SECTION 1
selection process. By using the fol- only 20%, HPS, through recent tests rating.
lowing information, you will be sure to conducted on many popular brands If the supply voltage varies
select the HPS Control Transformer of control devices, has determined upwards of 10%, the 95% secondary
which best meets your application. that the 40% power factor value is voltage column should be used to
The HPS Imperator Series more accurate. size the transformer.
machine tool control transformers Once the above circuit variables Current standards require
are specifically designed for high have been determined, transformer electromagnetic devices to operate
inrush applications requiring reliable selection is a six step process. reliably at a minimum of 85%
output voltage stability. Designed to of their rated voltage. However,
meet industrial applications where SIX EASY STEPS contact life may be affected with
electromagnetic devices such as continuous start-ups at that voltage
relays, solenoids, etc. are used, the 1. Determine what your Primary level. Therefore, the minimum 85%
HPS Imperator series transformers (supply) and Secondary (output) secondary voltage column should
maximize inrush capability and voltage requirements are, as well only be used as a reference.
output voltage regulation when as your required frequency (i.e. 60
electromagnetic devices are initially Hz) 6. Using the regulation data tables
energized. below, select the appropriate VA
To select the proper transformer, 2. Calculate the Total Sealed VA rated transformer:
three characteristics of the load of your circuit. (See Step A)
circuit must first be determined. A) With a continuous VA rating that
They are total steady-state (sealed) 3. Now calculate the Inrush is equal to or greater than the value
VA, total inrush VA, and inrush load VA by adding the inrush VA of in Step 2.
power factor. all components being energized B) With a maximum inrush VA
together. Remember to add the equal to or greater than the value
1 (A). The total steady state sealed VA of all components that do obtained in Step 4.
“sealed” VA is the amount of VA not have inrush VA, (lamps, timers
that the transformer must supply etc.) as they do, however, present To determine the correct HPS
to the load circuit for an extended a load to the transformer during Transformer and its Catalog Number,
length of time. Simply add the total maximum inrush. If the inrush for just refer to the tables in this catalog
steady-state VA of all devices in your the components in your circuit are for the voltage ratings, frequency
control circuit. The operating VA data not known, assume a 40% Inrush and corresponding VA required.
of these components is available Power Factor.
from the manufacturers.
4. Calculate the Total Inrush VA “HPS IMPERATOR® TRANSFORMERS
using one of the two methods: REGULATION DATA TABLE
1 (B). The total inrush VA
Continuous VA Inrush VA @ 40% Power Factor
is the amount of VA that the Transformer 85% 90% 95%
Nameplate Secondary Secondary Secondary
transformer must supply for all A. Total Inrush VA = Rating Voltage Voltage Voltage
components in the control circuit
(VA sealed)2 + (VA inrush)2 50
75
330 259
258
192
170
which are energized together. 100
350
620 467 321
150 699 512
Some consideration to the start-up 895
OR 250
350
1596 1229
1889
880
1345
sequence may be required. Inrush VA 500
2464
3939 2854 1819
750 4778 3228
should be obtained from the device 6422
B. Total Inrush VA = 1000
1500
9842 7102
9018
4530
5489
manufacturer. 12797
VA Sealed + VA Inrush 2000
3000
17833
37406
12656
26217
7865
15940
5000 55629 38788 23601
1 (C). The inrush load power It is recommended that a Control Transformer be
Note: method B will result in a slightly
factor is difficult to determine without sized at a 40% Power Factor. Some components
larger transformer being selected. in a circuit, such as electromagnetic devices,
detailed vector analysis of all the typically operate at that level due to their
inherently lower power factor. Selecting a
control circuit components. Such For VA sealed definition please refer to 1 (A).
transformer at 40% Power Factor will more than
For VA inrush definition please refer to 1 (B).
information is not generally available. adequately size the unit for all the various loads
in the circuit.
32
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
HPS Imperator® Series Control Transformer - Applications
SECTION 1
control transformers are specifically designed to meet the innovative compact design that provides the ideal
high inrush industrial applications where electromagnetic solution for any industrial control application and will
components such as relays, solenoids etc. are used. change the way the industrial machine tool industry
looks at the control transformer.
With 11 standard voltage groups, a VA range from 50VA
to 5000VA and available with standard secondary and The HPS Imperator’s unique terminal block design
optional primary fuse kits, the HPS Imperator series from (patent pending) allows for the quick and easy
HPS provides the perfect solution for any applications. installation of standard secondary or optional primary
13/32” x 1 1/2” midget/type CC fuse clips on every unit.
This is the simplest and most inexpensive fusing
installation provided on any industrial control
Superior Quality and Value transformer in the market today.
The HPS Imperator series design, utilizing superior The windings and internal terminations of the HPS
insulation systems and being constructed with high quality Imperator are encapsulated, which protects them
silicon steel laminations for optimum performance, will from moisture, dirt and other airborne contaminants.
meet or exceed UL and CE standards. The custom molded coil covers with their unique ‘fin
shaped’ design combine superior transformer cooling
Backed by an industry leading LIFETIME warranty, the properties with a clean bold look.
HPS Imperator® industrial control transformer line offers
The HPS Imperator utilizes custom serrated terminals,
superior performance, quality and value.
in combination with standard SEMS washer screws
making assembly easier and quicker to install;
and provides superior connection strength when
connecting with bare, solid or stranded wire. It also
allows for ring or spade termination connectors.
STANDARDS
HPS Industrial and Machine Tool Control and Instrument Transformers meet or
exceeds the standards established by UL, IRC, ANSI, NEMA.
At HPS, we rate the VA capacity of our transformers at the output ..... where it counts.
Other transformer manufacturers rate their capacity on the input side of the
transformer, which can result in a 5% to 20% lower actual VA at the output.
33
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
• Optional primary fuse kits available utilizing 13/32” x 1 1/2” midget/type CC fuse
clips (available on all standard units up to and including 1500VA)
• Optional finger safe terminal covers available on all units up to and including
1500VA
• UL Listed (approved for U.S. and Canada)
• CE Mark standard on all molded units up to and including 1500VA
• LIFETIME Warranty (Limited)
• RoHS Compliant
1
special voltages and VA sizes available upon request
2
excluding PH750PG, PH1000PG, PH750MLI, PH1000MLI
Warranty
Lifetime
34
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
SECTION 1
Terminal connection numbers molded into the
terminal block and correspond to the nameplate
and wiring diagrams which makes
connecting the HPS Imperator
quick and simple. Standard secondary and optional
primary fuse kits utilizing 13/32” x 1 1/2”
midget/type CC fuse clips provide an
economical solution to your fusing
requirements (fuses not available).
35
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
C
SECTION 1
C
GxH GxH
D E
D E A B
A
B
FIGURE A
FIGURE C
C
GxH
D E
A FIGURE B
Group A
Primary Voltage: 600 575 550
Secondary Voltage: 120 x 240 115 x 230 110 x 220 60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50AJ A 0.42/0.21 3.00 3.81 3.19 2.50 2.25 0.22 x 0.44 4.00 5.25 2.70 PFK1
75 PH75AJ A 0.63/0.31 3.25 3.69 3.56 2.63 2.50 0.22 x 0.44 4.37 5.13 2.80 PFK1
100 PH100AJ A 0.83/0.42 3.25 4.06 3.63 2.63 2.63 0.22 x 0.44 4.44 5.50 4.10 PFK1
150 PH150AJ B 1.25/0.63 4.00 4.63 3.81 3.38 2.75 0.22 x 0.75 4.50 6.13 4.90 PFK2
250 PH250AJ B 2.08/1.04 4.50 5.25 3.81 3.75 3.13 0.22 x 0.75 4.50 6.75 6.97 PFK2
350 PH350AJ B 2.92/1.46 4.50 4.88 4.44 3.75 3.75 0.22 x 0.75 4.94 6.38 8.30 PFK3
500 PH500AJ B 4.17/2.08 4.75 5.56 4.31 4.06 3.44 0.31 x 0.94 4.81 7.06 11.6 PFK3
750 PH750AJ B 6.25/3.13 5.13 6.38 4.31 4.38 4.00 0.31 x 0.81 4.81 7.88 16.6 PFK3
1000 PH1000AJ B 8.33/4.17 5.25 6.50 4.94 4.50 4.09 0.31 x 0.81 5.56 8.00 21.0 PFK3
1500 PH1500AJ B 12.5/6.25 5.25 7.56 4.94 4.50 5.44 0.38 x 1.00 5.56 9.06 30.0 PFK3
2000 PH2000AJ C 16.7/8.33 6.38 7.50 5.50 4.38/5.31 6.00 0.31 x 1.13 N/A N/A 35.7 N/A
3000 PH3000AJ C 25.0/12.5 6.38 7.50 5.50 4.38/5.31 6.00 0.31 x 1.13 N/A N/A 43.9 N/A
All dimensions in inches
5000 PH5000AJ C 41.7/20.8 9.00 10.38 7.63 5.25/7.00 6.38 0.44 x 1.00 N/A N/A 97.9 N/A
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied standard with transformers up to All dimensions in inches
and including 1500VA. Refer to page 52 for wiring schematic drawing. Special voltage and VA sizes available upon request.
Units over 1500VA are UL approved and CSA certified.
36
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
B
B
SECTION 1
C
GxH C
GxH
D E
A
D E
A
FIGURE A FIGURE B
Group B
Primary Voltage: 600 575 550
Secondary Voltage: 12 x 24 11.5 x 23 11 x 22 60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50AR A 4.17/2.08 3.00 3.81 3.19 2.50 2.25 0.22 x 0.44 4.00 5.25 2.70 PFK1
75 PH75AR A 6.25/3.13 3.25 3.69 3.56 2.63 2.50 0.22 x 0.44 4.37 5.13 2.80 PFK1
100 PH100AR A 8.33/4.17 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK1
150 PH150AR B 12.5/6.25 4.00 4.94 3.81 3.38 2.75 0.22 x 0.75 4.50 6.44 5.70 PFK2
250 PH250AR B 20.8/10.4 4.50 5.44 3.81 3.75 3.13 0.22 x 0.75 4.50 6.94 7.50 PFK2
350 PH350AR B 29.2/14.6 4.50 4.88 4.44 3.75 3.75 0.22 x 0.75 4.94 6.38 8.30 PFK3
500 PH500AR B 41.7/20.8 4.75 5.56 4.31 4.06 3.44 0.31 x 0.94 4.81 7.06 11.6 PFK3
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied with transformers up to All dimensions in inches
and including 500VA. Refer to page 53 for wiring schematic drawing. Special voltages and VA sizes available upon request.
Units over 1500VA are UL approved and CSA certified.
37
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
C
SECTION 1
C
GxH GxH
D E
D E A B
A
B
FIGURE A
FIGURE C
C
GxH
D E
A FIGURE B
Group C
Primary Voltage: 240 x 480 230 x 460 220 x 440
Secondary Voltage: 120 x 240 115 x 230 110 x 220 50/60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50MQMJ A 0.42/0.21 3.00 4.38 3.19 2.50 2.25 0.22 x 0.44 4.00 5.82 3.50 PFK1
75 PH75MQMJ A 0.63/0.31 3.25 3.88 3.56 2.63 2.50 0.22 x 0.44 4.37 5.32 3.54 PFK1
100 PH100MQMJ A 0.83/0.42 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK1
150 PH150MQMJ B 1.25/0.63 4.00 4.94 3.81 3.38 2.75 0.22 x 0.75 4.50 6.44 5.70 PFK2
250 PH250MQMJ B 2.08/1.04 4.50 5.44 3.81 3.75 3.13 0.22 x 0.75 4.50 6.94 7.50 PFK2
350 PH350MQMJ B 2.92/1.46 4.50 5.19 4.44 3.75 3.75 0.22 x 0.75 4.94 6.69 10.1 PFK3
500 PH500MQMJ B 4.17/2.08 4.75 5.94 4.31 4.06 3.81 0.31 x 0.94 4.81 7.44 14.2 PFK3
750 PH750MQMJ B 6.25/3.13 5.13 6.69 4.31 4.38 4.31 0.31 x 0.81 4.81 8.19 16.6 PFK3
1000 PH1000MQMJ B 8.33/4.17 5.25 6.81 4.94 4.50 4.44 0.31 x 0.81 5.56 8.31 23.6 PFK3
1500 PH1500MQMJ B 12.5/6.25 5.25 8.19 4.94 4.50 6.06 0.38 x 1.00 5.56 9.69 32.0 PFK3
2000 PH2000MQMJ C 16.7/8.33 6.38 7.50 5.50 4.38/5.31 6.00 0.31 x 1.13 N/A N/A 45.4 N/A
3000 PH3000MQMJ C 25.0/12.5 7.50 10.00 6.25 4.50/6.00 7.00 0.38 x 1.00 N/A N/A 76.7 N/A
5000 PH5000MQMJ C 41.7/20.8 9.00 11.00 7.63 5.25/7.00 7.00 0.44 x 1.00 N/A N/A 121.2 N/A
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied standard with transformers up to All dimensions in inches
and including 1500VA. Refer to page 54 for wiring schematic drawing. Special voltages and VA sizes available upon request.
Units over 1500VA are UL approved and CSA certified, but do not carry the CE mark.
*** Available with FACTORY INSTALLED Primary and Secondary Fuse Kits up to 1500VA. To order, add the suffix “-FK” to the above part number. Refer to page 49 for details. ***
38
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
SECTION 1
B
B
C
C
GxH GxH
D E
A D E
A
FIGURE A FIGURE B
Group D
Primary Voltage: 240 x 480 230 x 460 220 x 440
Secondary Voltage: 12 x 24 11.5 x 23 11 x 22 50/60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50QR A 4.17/2.08 3.00 4.38 3.19 2.50 2.25 0.22 x 0.44 4.00 5.82 3.50 PFK1
75 PH75QR A 6.25/3.13 3.25 3.88 3.56 2.63 2.50 0.22 x 0.44 4.37 5.32 3.54 PFK1
100 PH100QR A 8.33/4.17 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK1
150 PH150QR B 12.5/6.25 4.00 4.94 3.81 3.38 2.75 0.22 x 0.75 4.50 6.44 5.70 PFK2
250 PH250QR B 20.8/10.4 4.50 5.44 3.81 3.75 3.13 0.22 x 0.75 4.50 6.94 7.50 PFK2
350 PH350QR B 29.2/14.6 4.50 5.19 4.44 3.75 3.75 0.22 x 0.75 4.94 6.69 10.1 PFK3
500 PH500QR B 41.7/20.8 4.75 5.94 4.31 4.06 3.81 0.31 x 0.94 4.81 7.44 14.2 PFK3
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied standard with transformers up to All dimensions in inches
and including 500VA. Refer to page 55 for wiring schematic drawing. Special voltages and VA sizes available upon request.
39
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
SECTION 1
B
B
C C
GxH GxH
D E
A D E
A
FIGURE A FIGURE B
Group E
Primary Voltage: 208 x 416 200 x 400 190 x 380
Secondary Voltage: 120 x 240 115 x 230 110 x 220 50/60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50SP A 0.42/0.21 3.00 4.38 3.19 2.50 2.25 0.22 x 0.44 4.00 5.82 3.50 PFK1
75 PH75SP A 0.63/0.31 3.25 3.88 3.56 2.63 2.50 0.22 x 0.44 4.37 5.32 3.54 PFK1
100 PH100SP A 0.83/0.42 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK1
150 PH150SP B 1.25/0.63 4.00 4.94 3.81 3.38 2.75 0.22 x 0.75 4.50 6.44 5.70 PFK2
250 PH250SP B 2.08/1.04 4.50 5.44 3.81 3.75 3.13 0.22 x 0.75 4.50 6.94 7.50 PFK2
350 PH350SP B 2.92/1.46 4.50 5.19 4.44 3.75 3.75 0.22 x 0.75 4.94 6.69 10.1 PFK3
500 PH500SP B 4.17/2.08 4.75 5.94 4.31 4.06 3.81 0.31 x 0.94 4.81 7.44 14.2 PFK3
750 PH750SP B 6.25/3.13 5.13 6.69 4.31 4.38 4.31 0.31 x 0.81 4.81 8.19 16.6 PFK3
1000 PH1000SP B 8.33/4.17 5.25 6.81 4.94 4.50 4.44 0.31 x 0.81 5.56 8.31 23.6 PFK3
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied standard with transformers up to All dimensions in inches
and including 1000VA. Refer to page 56 for wiring schematic drawing. Special voltages and VA sizes available upon request.
40
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
SECTION 1
C
GxH GxH
D E
D E A B
A
B
FIGURE A
FIGURE C
C
GxH
D E
A
FIGURE B
Group F
Primary Voltage: 120 x 240 115 x 230 110 x 220
Secondary Voltage: 120 x 240 115 x 230 110 x 220 50/60 Hertz
Overall Mounting Height Depth Approx. Optional
Mtg. Slot
VA Catalog Mtg. Output Dimensions Centers with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50PP A 0.42/0.21 3.00 4.38 3.19 2.50 2.25 0.22 x 0.44 4.00 5.82 3.50 PFK1
75 PH75PP A 0.63/0.31 3.25 3.88 3.56 2.63 2.50 0.22 x 0.44 4.37 5.32 3.54 PFK1
100 PH100PP A 0.83/0.42 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK1
150 PH150PP B 1.25/0.63 4.00 4.94 3.81 3.38 2.75 0.22 x 0.75 4.50 6.44 5.70 PFK2
250 PH250PP B 2.08/1.04 4.50 5.44 3.81 3.75 3.13 0.22 x 0.75 4.50 6.94 7.50 PFK2
350 PH350PP B 2.92/1.46 4.50 5.19 4.44 3.75 3.75 0.22 x 0.75 4.94 6.69 10.1 PFK3
500 PH500PP B 4.17/2.08 4.75 5.94 4.31 4.06 3.81 0.31 x 0.94 4.81 7.44 14.2 PFK3
750 PH750PP B 6.25/3.13 5.13 6.69 4.31 4.38 4.31 0.31 x 0.81 4.81 8.19 16.6 PFK3
1000 PH1000PP B 8.33/4.17 5.25 6.81 4.94 4.50 4.44 0.31 x 0.81 5.56 8.31 23.6 PFK3
1500 PH1500PP B 12.5/6.25 5.25 8.19 4.94 4.50 6.06 0.38 x 1.0 5.56 9.69 32.0 PFK3
2000 PH2000PP C 16.7/8.33 6.38 7.50 5.50 4.38/5.31 6.00 0.31 x 1.13 N/A N/A 45.4 N/A
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied with transformers up to All dimensions in inches
and including 1500VA. Refer to page 57 for wiring schematic drawing. Special voltages and VA sizes available upon request.
Units over 1500VA are UL approved and CSA certified, but do not carry the CE mark.
41
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
SECTION 1
C C
GxH
GxH
D E E
A
D
A
FIGURE A FIGURE B
Group G
Primary Voltage: 120 x 240 115 x 230 110 x 220
Secondary Voltage: 12 x 24 11.5 x 23 11 x 22 50/60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50PG A 4.17/2.08 3.00 4.38 3.19 2.50 2.25 0.22 x 0.44 4.00 5.82 3.50 PFK1
75 PH75PG A 6.25/3.13 3.25 3.88 3.56 2.63 2.50 0.22 x 0.44 4.37 5.32 3.54 PFK1
100 PH100PG A 8.33/4.17 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK1
150 PH150PG B 12.5/6.25 4.00 4.94 3.81 3.38 2.75 0.22 x 0.75 4.50 6.44 5.70 PFK2
250 PH250PG B 20.8/10.4 4.50 5.44 3.81 3.75 3.13 0.22 x 0.75 4.50 6.94 7.50 PFK2
350 PH350PG B 29.2/14.6 4.50 5.19 4.44 3.75 3.75 0.22 x 0.75 4.94 6.69 10.1 PFK3
500 PH500PG B 41.7/20.8 4.75 5.94 4.31 4.06 3.81 0.31 x 0.94 4.81 7.44 14.2 PFK3
750 PH750PG B 62.5/31.3 5.13 6.69 4.31 4.38 4.31 0.31 x 0.81 4.81 8.19 16.6 PFK3
1000 PH1000PG B 83.3/41.7 5.25 6.81 4.94 4.50 4.44 0.31 x 0.81 5.56 8.31 23.6 PFK3
Secondary fuse clips and fuse clip mounting screws supplied standard with transformers up to and including 500VA. All dimensions in inches
Secondary voltage links/jumpers supplied standard with transformers up to and including 1000VA.
Primary voltage links supplied standard with transformers up to and including 1000VA.
Refer to page 58 for wiring schematic drawing. Special voltages and VA sizes available upon request.
*** Available with FACTORY INSTALLED Primary and Secondary Fuse Kits up to 1500VA. To order, add the suffix “-FK” to the above part number. Refer to page 49 for details. ***
42
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
SECTION 1
C
GxH GxH
D E
D E A B
A
FIGURE A B
FIGURE C
C
GxH
D E
A
FIGURE B
Group H
Primary Voltage: 600/480/240 575/460/230 550/440/220
Secondary Voltage: 120/100 115/95 110/90 50/60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50MBMH A 0.43 3.25 4.06 3.63 2.63 2.63 0.22 x 0.44 4.44 5.50 4.10 PFK4
75 PH75MBMH A 0.65 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK5
100 PH100MBMH B 0.87 4.00 4.63 3.81 3.38 2.75 0.22 x 0.75 4.50 6.13 4.90 PFK6
150 PH150MBMH B 1.30 4.00 5.44 3.81 3.38 2.75 0.22 x 0.75 4.50 6.94 7.60 PFK6
250 PH250MBMH B 2.17 4.50 5.19 4.44 3.75 3.75 0.22 x 0.75 4.94 6.69 10.1 PFK6
350 PH350MBMH B 3.04 4.50 5.56 4.44 3.75 3.75 0.22 x 0.75 4.94 7.06 11.0 PFK7
500 PH500MBMH B 4.35 4.75 6.69 4.31 4.06 4.50 0.31 x 0.94 4.81 8.19 16.3 PFK7
750 PH750MBMH B 6.52 5.25 6.81 4.94 4.50 4.44 0.31 x 0.81 5.56 8.31 23.6 PFK7
1000 PH1000MBMH B 8.70 5.25 8.19 4.94 4.50 5.81 0.31 x 0.81 5.56 9.69 31.2 PFK7
1500 PH1500MBMH B 13.0 5.25 8.19 4.94 4.50 6.06 0.38 x 1.0 5.56 9.69 32.0 PFK7
2000 PH2000MBMH C 17.4 6.38 7.50 5.50 4.38/5.31 6.00 0.31 x 1.13 N/A N/A 43.6 N/A
3000 PH3000MBMH C 26.1 7.50 11.00 6.25 4.50/6.00 7.13 0.38 x 1.00 N/A N/A 78.7 N/A
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied standard with transformers up to All dimensions in inches
and including 1500VA. Refer to page 59 for wiring schematic drawing. Special voltage and VA sizes available upon request.
Units over 1500VA are UL approved and CSA certified, but do not carry the CE mark.
43
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
SECTION 1
C
C GxH
GxH
D E D E
A A
FIGURE A FIGURE B
Group I
Primary Voltage: 480/240 460/230/208 440/220/200
Secondary Voltage: 120/25 115/24 110/23 50/60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50MLI A 0.43/2.08 3.25 4.06 3.56 2.63 2.50 0.22 x 0.44 4.37 5.50 4.00 PFK5
75 PH75MLI A 0.65/3.13 3.25 4.25 3.56 2.63 2.50 0.22 x 0.44 4.37 5.69 4.60 PFK5
100 PH100MLI A 0.87/4.17 3.25 4.69 3.63 2.63 2.63 0.22 x 0.44 4.44 6.13 5.20 PFK5
150 PH150MLI B 1.30/6.25 4.00 5.44 3.81 3.38 2.75 0.22 x 0.75 4.50 6.94 7.60 PFK6
250 PH250MLI B 2.17/10.42 4.50 5.19 4.44 3.75 3.75 0.22 x 0.75 4.94 6.69 10.1 PFK6
350 PH350MLI B 3.04/14.58 4.50 5.56 4.44 3.75 3.75 0.22 x 0.75 4.94 7.06 11.0 PFK7
500 PH500MLI B 4.35/20.83 4.75 6.69 4.31 4.06 4.50 0.31 x 0.94 4.81 8.19 16.3 PFK7
750 PH750MLI B 6.52/31.25 5.25 6.50 4.94 4.50 4.13 0.31 x 0.81 5.56 8.00 21.0 PFK7
1000 PH1000MLI B 8.70/41.67 5.25 8.19 4.94 4.50 5.81 0.31 x 0.81 5.56 9.69 31.2 PFK7
Secondary fuse clips and fuse clip mounting screws supplied standard with transformers up to and including 500VA. All dimensions in inches
Secondary voltage links/jumpers supplied standard with transformers up to and including 1000VA.
Primary voltage links supplied standard with transformers up to and including 1000VA.
Refer to page 60 for wiring schematic drawing. Special voltages and VA sizes available upon request.
*** Available with FACTORY INSTALLED Primary and Secondary Fuse Kits up to 1500VA. To order, add the suffix “-FK” to the above part number. Refer to page 49 for details. ***
44
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
SECTION 1
B
C C
GxH
GxH
D E
D E
A
A
FIGURE A FIGURE B
Group J
Primary Voltage: 415/400/380
Secondary Voltage: 110 x 220 50/60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50MEMX A 0.45/0.23 3.00 4.38 3.19 2.50 2.25 0.22 x 0.44 4.00 5.82 3.50 PFK4
75 PH75MEMX A 0.68/0.34 3.25 4.06 3.63 2.63 2.63 0.22 x 0.44 4.44 5.50 4.10 PFK5
100 PH100MEMX A 0.91/0.45 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK5
150 PH150MEMX B 1.36/0.68 4.00 4.94 3.81 3.38 2.75 0.22 x 0.75 4.50 6.44 5.70 PFK6
250 PH250MEMX B 2.27/1.14 4.50 5.44 3.81 3.75 3.13 0.22 x 0.75 4.50 6.94 7.50 PFK6
350 PH350MEMX B 3.18/1.59 4.50 5.19 4.44 3.75 3.75 0.22 x 0.75 4.94 6.69 10.1 PFK7
500 PH500MEMX B 4.55/2.27 4.75 5.94 4.31 4.06 3.81 0.31 x 0.94 4.81 7.44 14.2 PFK7
750 PH750MEMX B 6.82/3.41 5.25 6.50 4.94 4.50 4.13 0.31 x 0.81 5.56 8.00 21.0 PFK7
1000 PH1000MEMX B 9.09/4.55 5.25 6.81 4.94 4.50 4.44 0.31 x 0.81 5.56 8.31 23.6 PFK7
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied with transformers up to All dimensions in inches
and including 1000VA. Refer to page 61 for wiring schematic drawing. Special voltages and VA sizes available upon request.
45
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
SECTION 1
C C
GxH
GxH
D E
D E
A
A
FIGURE A FIGURE B
Group K
Primary Voltage: 380/277/208
Secondary Voltage: 120 x 240 50/60 Hertz
Overall Mounting Mounting Height Depth Approx. Optional
VA Catalog Mtg. Output Dimensions Centers Slot with with Ship Primary
Rating Number Fig. Amps Finger Finger Weight Fuse
A B C D E GXH Guard Guard Lbs. Kit P/N
50 PH50MGJ A 0.42/0.21 3.25 3.88 3.56 2.63 2.50 0.22 x 0.44 4.37 5.32 3.54 PFK4
75 PH75MGJ A 0.63/0.31 3.25 4.19 3.63 2.63 2.63 0.22 x 0.44 4.44 5.63 4.50 PFK5
100 PH100MGJ A 0.83/0.42 3.25 4.69 3.63 2.63 2.63 0.22 x 0.44 4.44 6.13 5.20 PFK5
150 PH150MGJ B 1.25/0.63 4.00 5.44 3.81 3.38 2.75 0.22 x 0.75 4.50 6.94 7.60 PFK6
250 PH250MGJ B 2.08/1.04 4.50 4.88 4.44 3.75 3.75 0.22 x 0.75 4.94 6.38 8.30 PFK6
350 PH350MGJ B 2.92/1.46 4.50 5.56 4.44 3.75 3.75 0.22 x 0.75 4.94 7.06 11.0 PFK7
500 PH500MGJ B 4.17/2.08 4.75 6.69 4.31 4.06 4.50 0.31 x 0.94 4.81 8.19 16.3 PFK7
750 PH750MGJ B 6.25/3.13 5.25 6.81 4.94 4.50 4.44 0.31 x 0.81 5.56 8.31 23.6 PFK7
1000 PH1000MGJ B 8.33/4.17 5.25 7.25 4.94 4.50 4.83 0.31 x 0.81 5.44 8.75 25.5 PFK7
Secondary fuse clips, fuse clip mounting screws, voltage links/jumpers and primary voltage links supplied with transformers up to All dimensions in inches
and including 1000VA. Refer to page 62 for wiring schematic drawings. Special voltages and VA sizes available upon request.
46
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
Recommendations For Overcurrent Protection
UL AND CSA (NORTH AMERICAN) STANDARDS
North American standards, including UL 508, National Electric Code 450 and the Canadian Electrical
Code Part I, require overcurrent protection on all control circuit transformers. There are two options for over-
SECTION 1
current protection:
Option 1
Provide an overcurrent device in the primary circuit rated to the current of the transformer. The
overcurrent limits are as follows:
This method is considered less desirable as start-up inrush to the transformer can frequently
surpass the current rating of the device and result in nuisance interruptions.
Option 2
The second option is to install overcurrent devices in both the primary and secondary circuits of the
transformer. In this option, the secondary device must be rated no more than 125% of rated current
of the transformer and the primary no more than 250%. CEC permits 300% overcurrent on the
primary for this option.
In both options listed, it is recommended that time delay fuses be considered to avoid unnecessary
interruptions.
Secondary
The overcurrent protection listed below, in amperes, is 125% of the rated current of the transformer. Choose
the next higher fuse rating if these numbers do not correspond with standard fuse selections.
Sec. VA Rating
Voltage
25 50 75 100 150 200 250 300 350 500 750 1000 1500 2000 3000 5000
47
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
Recommendations for Overcurrent Protection continued...
Primary (UL and CSA)
To assist in the selection of fuses, the following chart recommends the maximum primary fuse rating in amperes. The
first number shown is the maximum overcurrent protection when the primary current is less than 2 amps and the overcurrent
protection device is rated for 300%. The second number shown (italic) is recommended when the primary is less than 2 amps
and the overcurrent device is to be rated at 500% of rated current. Where only one number is indicated, the primary is 2 amps
SECTION 1
or more and one rating of over current protection is shown as optimal. Choose the next higher fuse rating if these numbers do
not correspond with standard fuse selections.
Pri. VA Rating
Volt 25 50 75 100 150 200 250 300 350 500 750 1000 1500 2000 3000 5000 7500
115 0.6 1.25 1.8 2.5 3.5 5 4 5 5 8 10 15 20 25 - - -
1 2 3.2 4 6.25 8
120 0.6 1.25 1.8 2.25 3.5 5 4 5 5 8 10 15 15 20 - - -
1 2 3 4 6.25 8
200 0.3 0.75 1.125 1.5 2.25 3 3.5 4.5 5 4.5 7 9 15 15 20 - -
0.6 1.25 1.8 2.5 3.5 5 6.25 7.5 8
208 0.3 0.6 1 1.4 2 2.8 3.5 4 5 4 6 8 12 15 20 30 -
0.6 1.125 1.8 2.25 3.5 4.5 6 7 8
220 0.3 0.6 1 1.25 2 2.5 3.2 4 4.5 4 6 8 12 15 20 30 -
0.5 1.125 1.6 2.25 3.2 4.5 5.6 6.25 7.5
230 0.3 0.6 0.8 1.25 1.8 2.5 3.2 3.5 4.5 4 6 8 10 15 20 30 -
0.5 1 1.6 2 3.2 4 5 6.25 7.5
240 0.3 0.6 0.8 1.25 1.8 2.25 3 3.5 4 3.5 5 7 10 15 15 30 -
0.5 1 1.5 2 3 4 5 6.25 7
277 0.25 0.5 0.8 1 1.6 2 2.5 3.2 3.5 5 5 6 9 12 15 25 -
0.4 0.8 1.25 1.8 1.5 3.5 4.5 5 6.25 9
347 0.25 0.5 0.8 1 1.6 2 2.5 3.2 3.5 5 6.25 5 7.5 10 15 20 30
0.4 0.8 1.25 1.8 2.5 3.5 4.5 5 6.25 9
380 0.1875 0.3 0.5 0.75 1.125 1.5 1.8 2.25 2.5 3.5 5.6 4.5 6.25 9 15 20 25
0.3 0.6 0.8 1.25 1.8 2.5 3.2 3.5 4.5 6.25 9
400 0.1875 0.3 0.5 0.75 1.125 1.5 1.8 2.25 2.5 3.5 5.6 4.5 6.25 9 12 15 20
0.3 0.6 0.8 1.25 1.8 2.5 3 3.5 4 6.25 9
416 0.15 0.3 0.5 0.6 1 1.4 1.8 2 2.5 3.5 5 4 6 8 12 15 20
0.3 0.6 0.8 1.125 1.8 2.25 3 3.5 4 6 9
440 0.15 0.3 0.5 0.6 1 1.25 1.6 2 2.25 3.2 5 4 6 8 12 15 20
0.25 0.5 0.8 1.125 1.6 2.25 2.8 3.2 3.5 5.6 8
460 0.15 0.3 0.4 0.6 0.8 1.25 1.6 1.8 2.25 3.2 4.5 3.5 6 8 12 15 20
0.25 0.5 0.8 1 1.6 2 2.5 3.2 3.5 5 8
480 0.15 0.3 0.4 0.6 0.8 1.25 1.5 1.8 2 3 4.5 3.5 5 7 10 15 20
0.25 0.5 0.75 1 1.5 2 2.5 3 3.5 5 7.5
550 0.125 0.25 0.4 0.5 0.8 1 1.25 1.6 1.8 2.5 4 5 4.5 6 9 15 15
0.2 0.4 0.6 0.8 1.25 1.8 2.25 2.5 3 4.5 6.25
575 0.125 0.25 0.3 0.5 0.75 1 1.25 1.5 1.8 2.5 3.5 5 4.5 6 9 15 15
0.2 0.4 0.6 0.8 1.25 1.6 2 2.5 3 4 6.25
600 0.125 0.2 0.3 0.5 0.75 0.8 1.25 1.5 1.6 2.25 3.5 5 4 6 9 15 15
0.2 0.4 0.6 0.8 1.25 1.6 2 2.5 2.8 4 6.25
SECTION 1
Optional Primary Fuse Kits (Field Installed)
All HPS Imperator series machine tool industrial control transformers up to and including 1500VA are
available with the following optional primary fuse kits:
Kit Part Applicable Transformer Applicable Parts Included in Kit
Number Part Number Suffix’s VA Sizes
PFK1 4 fuse clips, 4 mtg. screws, PHAK1 instruction sheet
PFK2 Refer to Refer to 4 fuse clips, 4 mtg. screws, PHAK1 instruction sheet
PFK3 Specification Specification 4 fuse clips, 4 mtg. screws, PHAK1 instruction sheet
PFK4 Tables Tables 4 fuse clips, 4 mtg. screws, 1 jumper, 1 finger guard, PHAK1 instruction sheet
PFK5 on Pages on Pages 4 fuse clips, 4 mtg. screws, 1 jumper, 1 finger guard, PHAK1 instruction sheet
PFK5 36 to 46 for 36 to 46 for 4 fuse clips, 4 mtg. screws, 1 jumper, 1 finger guard, PHAK1 instruction sheet
PFK6 Optional Primary Optional Primary 4 fuse clips, 4 mtg. screws, 1 jumper wire, PHAK1 instruction sheet
PFK6 Fuse Kit P/N Fuse Kit P/N 4 fuse clips, 4 mtg. screws, 1 jumper wire, PHAK1 instruction sheet
PFK7 4 fuse clips, 4 mtg. screws, 1 jumper wire, PHAK1 instruction sheet
Note: Maximum allowable current rating on all primary and secondary fuse kits is 30 amps.
On PH750PG-FK, PH1000PG-FK, PH750MLI-FK, and PH1000MLI-FK, only primary fuse clips are
included on factory installed units. Secondary fuse clips are not included or available on these units.
Other voltage groups available with factory installed fuse kits. Please contact your HPS sales or
customer service representative for details.
Note: All factory installed fuse kits are pre-wired at the transformers highest primary voltage and the lowest secondary voltage. To hook up at
a different primary or secondary voltage, please refer to the wiring instruction sheet included with the transformer.
Sample Assembly Drawing for Sample Assembly Drawing Sample Assembly Drawing
Voltage Link Installation for Secondary Fuse Clip for Primary Fuse Clip
(for 150VA to 1500VA) Installation Installation
(for 150VA to 1500VA) (for 150VA to 1500VA)
Note: HPS Imperator primary and secondary fuse kits are not suitable for branch circuit applications!
49
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
Finger Guards
The HPS Imperator series of machine tool industrial molded control transformers up to and including
1500Va are available with the following optional finger guard kits:
50
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
Accessory Installation Guide
Sample Accessory Drawings
SECTION 1
Voltage Link Fuse Clips Fuse Clips Fused & Unfused Finger Guard
(for 50, 75 and 100VA) (for 150VA to 1500VA) Finger Guard (for 150VA to 1500VA)
(for 50, 75 and 100VA)
For units from 50VA to 100VA, the voltage links supplied can be
installed between any two primary or secondary terminal bays.
Please refer to PHWD1 or PHWD2 instruction sheet included
with your transformer for connection for details.
Style A Style B Style A Sample Assembly Drawing for Sample Assembly Drawing for
(left) (center) (right) Finger Guard Installation Finger Guard Installation
(for 50, 75 and 100VA) (for 150VA to 1500VA)
For units from 150VA to 250VA, the voltage links supplied must
be installed between the primary or secondary terminal bays as
indicated above Please refer to PHWD1 or PHWD2 instruction
sheet included with you transformer for connection details.
51
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
HPS IMPERATOR Series - Wiring Schematic Drawings
Group A
HV PH***AJ Schematic for 50, 75 and 100VA Units
SECTION 1
550V
575V
600V
High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse
1 2 3 4
(Primary Volts) Links Between Terminals Connect To Clips To
6 7
600 575 550 None 1, 4 Unfused
5 8
600 575 550 None 6, 7 1-5, 4-8
1 4
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
6 (Secondary Volts) Between Terminals Connect To Clips To
4 3 2 5 1 120 115 110 3-4, 1-2 1, 4 Unfused
4 3 2 1 4 3 2 1 240 230 220 2-3 1, 4 Unfused
120 115 110 3-4, 1-2 4, 6 1-5
110V 220V 240 230 220 2-3 4, 6 1-5
115V 230V
120V 240V
LV
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
1 (Secondary Volts) Between Terminals Connect To Clips To
5 4 3 7 2 120 115 110 4-5, 2-3 2, 5 Unfused
6 5 4 3 2 1 6 5 4 3 2 1 240 230 220 3-4 2, 5 Unfused
120 115 110 4-5, 2-3 1, 5 2-7
110V 220V 240 230 220 3-4 1, 5 2-7
115V 230V
120V 240V
LV
52
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
Group B
HV PH***AR Schematic for 50, 75 and 100VA Units
SECTION 1
550V
575V
600V
High Voltage (HV) Install Supplied Jumpers/ Supply Lines Install Fuse
1 2 3 4
(Primary Volts) Links Between Terminals Connect To Clips To
6 7
5
600 575 550 None 1, 4 Unfused
8
600 575 550 None 6, 7 1-5, 4-8
1 4
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
6 (Secondary Volts) Between Terminals Connect To Clips To
4 3 2 5 1
12 11.5 11 3-4, 1-2 1, 4 Unfused
4 3 2 1 4 3 2 1 24 23 22 2-3 1, 4 Unfused
12 11.5 11 3-4, 1-2 4, 6 1-5
11V 22V
11.5V 23V 24 23 22 2-3 4, 6 1-5
12V 24V
LV
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
1 (Secondary Volts) Between Terminals Connect To Clips To
5 4 3 7 2
12 11.5 11 4-5, 2-3 2, 5 Unfused
6 5 4 3 2 1 6 5 4 3 2 1 24 23 22 3-4 2, 5 Unfused
11V 22V 12 11.5 11 4-5, 2-3 1, 5 2-7
11.5V 23V 24 23 22 3-4 1, 5 2-7
12V 24V
LV
53
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
HPS IMPERATOR Series - Wiring Schematic Drawings continued
Group C
220V HV 440V PH***MQMJ Schematic for 50, 75 and 100VA Units
SECTION 1
230V 460V
240V 480V High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
1 2 3 4 1 2 3 4 (Primary Volts) Between Terminals Connect To Clips To
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
4 3 2 65 1
(Secondary Volts) Between Terminals Connect To Clips To
120 115 110 3-4, 1-2 1, 4 Unfused
4 3 2 1 4 3 2 1 240 230 220 2-3 1, 4 Unfused
110V 220V 120 115 110 3-4, 1-2 4, 6 1-5
115V 230V 240 230 220 2-3 4, 6 1-5
120V LV 240V
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
5 4 3 17 2 (Secondary Volts) Between Terminals Connect To Clips To
6 5 4 3 2 1 6 5 4 3 2 1 120 115 110 4-5, 2-3 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
110V 220V
115V 230V 120 115 110 4-5, 2-3 1, 5 2-7
120V LV 240V 240 230 220 3-4 1, 5 2-7
54
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
Group D
220V HV 440V PH***QR Schematic for 50, 75 and 100VA Units
SECTION 1
230V 460V
240V 480V
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
1 2 3 4 1 2 3 4 (Primary Volts) Between Terminals Connect To Clips To
6 7 240 230 220 1-2, 3-4 1, 4 Unfused
480 460 440 2-3 1, 4 Unfused
5 8
2 3 240 230 220 1-2, 3-4 6, 7 1-5, 4-8
1 4 480 460 440 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
4 3 2 65 1 (Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 3-4, 1-2 1, 4 Unfused
4 3 2 1 4 3 2 1 24 23 22 2-3 1, 4 Unfused
11V 22V 12 11.5 11 3-4, 1-2 4, 6 1-5
11.5V 23V 24 23 22 2-3 4, 6 1-5
12V LV 24V
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
5 4 3 17 2 (Secondary Volts) Between Terminals Connect To Clips To
6 5 4 3 2 1 6 5 4 3 2 1 12 11.5 11 4-5, 2-3 2, 5 Unfused
24 23 22 3-4 2, 5 Unfused
11V 22V
11.5V 23V 12 11.5 11 4-5, 2-3 1, 5 2-7
12V LV 24V 24 23 22 3-4 1, 5 2-7
55
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
HPS IMPERATOR Series - Wiring Schematic Drawings continued
Group E
190V HV 380V PH***SP Schematic for 50, 75 and 100VA Units
SECTION 1
200V 400V
208V 416V
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
1 2 3 4 1 2 3 4 (Primary Volts) Between Terminals Connect To Clips To
6 7 208 200 190 1-2, 3-4 1, 4 Unfused
416 400 380 2-3 1, 4 Unfused
5 8
2 3 208 200 190 1-2, 3-4 6, 7 1-5, 4-8
1 4 416 400 380 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
4 3 2 65 1 (Secondary Volts) Between Terminals Connect To Clips To
120 115 110 3-4, 1-2 1, 4 Unfused
4 3 2 1 4 3 2 1 240 230 220 2-3 1, 4 Unfused
110V 220V 120 115 110 3-4, 1-2 4, 6 1-5
115V 230V 240 230 220 2-3 4, 6 1-5
120V LV 240V
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
5 4 3 17 2 (Secondary Volts) Between Terminals Connect To Clips To
6 5 4 3 2 1 6 5 4 3 2 1 120 115 110 4-5, 2-3 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
110V 220V
115V 230V 120 115 110 4-5, 2-3 1, 5 2-7
120V LV 240V 240 230 220 3-4 1, 5 2-7
56
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
Group F
110V HV 220V PH***PP Schematic for 50, 75 and 100VA Units
SECTION 1
115V 230V
120V 240V
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
1 2 3 4 1 2 3 4 (Primary Volts) Between Terminals Connect To Clips To
6 7 120 115 110 1-2, 3-4 1, 4 Unfused
240 230 220 2-3 1, 4 Unfused
5 8
2 3 120 115 110 1-2, 3-4 6, 7 1-5, 4-8
1 4 240 230 220 2-3 6, 7 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
4 3 2 65 1 (Secondary Volts) Between Terminals Connect To Clips To
120 115 110 3-4, 1-2 1, 4 Unfused
4 3 2 1 4 3 2 1 240 230 220 2-3 1, 4 Unfused
110V 220V 120 115 110 3-4, 1-2 4, 6 1-5
115V 230V 240 230 220 2-3 4, 6 1-5
120V LV 240V
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
5 4 3 17 2 (Secondary Volts) Between Terminals Connect To Clips To
6 5 4 3 2 1 6 5 4 3 2 1 120 115 110 4-5, 2-3 2, 5 Unfused
240 230 220 3-4 2, 5 Unfused
110V 220V
115V 230V 120 115 110 4-5, 2-3 1, 5 2-7
120V LV 240V 240 230 220 3-4 1, 5 2-7
57
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
HPS IMPERATOR Series - Wiring Schematic Drawings continued
Group G
110V HV 220V PH***PG Schematic for 50, 75 and 100VA Units
115V 230V
120V 240V
High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
SECTION 1
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
4 3 2 65 1 (Secondary Volts) Between Terminals Connect To Clips To
12 11.5 11 3-4, 1-2 1, 4 Unfused
4 3 2 1 4 3 2 1 24 23 22 2-3 1, 4 Unfused
11V 22V 12 11.5 11 3-4, 1-2 4, 6 1-5
11.5V 23V 24 23 22 2-3 4, 6 1-5
12V LV 24V
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
5 4 3 17 2
(Secondary Volts) Between Terminals Connect To Clips To
6 5 4 3 2 1 6 5 4 3 2 1 12 11.5 11 4-5, 2-3 2, 5 Unfused
11V 22V 24 23 22 3-4 2, 5 Unfused
11.5V 23V 12 11.5 11 4-5, 2-3 1, 5 2-7
12V 24V
24 23 22 3-4 1, 5 2-7
LV
HV PH***PG Schematic for 750VA and 1000VA Units
110V 220V
115V 230V
120V 240V High Voltage (HV) Install Supplied Links Supply Lines Install Fuse
1 2 3 4 5 6 1 2 3 4 5 6 (Primary Volts) Between Terminals Connect To Clips To
120 115 110 2-3, 4-5 2, 5 Unfused
1 6
240 230 220 3-4 2, 5 Unfused
7 8
3 4 120 115 110 2-3, 4-5 1, 6 2-7, 5-8
2 5 240 230 220 3-4 1, 6 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
4 3 2 1
(Secondary Volts) Between Terminals Connect To Clips To
4 3 2 1 4 3 2 1 12 11.5 11 3-4, 1-2 1, 4 Unfused
11V 22V 24 23 22 2-3 1, 4 Unfused
11.5V 23V
12V 24V Note: secondary fuse clips not available on PH750PG or PH1000PG.
LV
58
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
Group H
PH***MBMH Schematic for 50 and 75VA Units
SECTION 1
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
6 HV 4
(Primary Volts) Between Terminals Connect To Clips To
5 Dotted line represents
1 supplied jumper lead* 8 600 575 550 None 1, 3 Unfused
480 460 440 None 1, 7 Unfused
600V/575V/550V
3 240 230 220 None 1, 2 Unfused
480V/460V/440V 600 575 550 3-8 6, 4 1-5, 4-8
7
240V/230V/220V
2 480 460 440 8-7 6, 4 1-5, 4-8
240 230 220 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Jumpers/ Load Lines Install Fuse
100V/95V/90V
3 (Secondary Volts) Links Between Terminals Connect To Clips To
120V/115V/110V 120 115 110 None 1, 4 Unfused
4 100 95 90 None 1, 3 Unfused
6 120 115 110 None 4, 6 1-5
LV 5 1
100 95 90 None 3, 6 1-5
*This primary fuse jumper is supplied with the primary fuse kit only.
1 5
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
HV (Primary Volts) Between Terminals Connect To Clips To
7 Dotted line represents
2 supplied jumper lead* 8 600 575 550 None 2, 6 Unfused
480 460 440 None 2, 4 Unfused
600V/575V/550V
6 240 230 220 None 2, 3 Unfused
480V/460V/440V 4 600 575 550 8-6 1, 5 2-7, 5-8
240V/230V/220V 480 460 440 4-8 1, 5 2-7, 5-8
3
240 230 220 3-8 1, 5 2-7, 5-8
100V/95V/90V
Low Voltage (LV) Install Supplied Jumpers/ Load Lines Install Fuse
3 (Secondary Volts) Links Between Terminals Connect To Clips To
120V/115V/110V 120 115 110 None 2, 4 Unfused
4 100 95 90 None 2, 3 Unfused
1
LV 7 2 120 115 110 None 1, 4 2-7
100 95 90 None 1, 3 2-7
*This primary fuse jumper is supplied with the primary fuse kit only.
59
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
HPS IMPERATOR Series - Wiring Schematic Drawings continued
Group I PH***MLI Schematic for 50, 75 and 100VA Units
6 HV 4 High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
5
Dotted line represents
(Primary Volts) Between Terminals Connect To Clips To
1 supplied jumper lead* 8
480 460 440 None 1, 3 Unfused
SECTION 1
480V/460V/440V
3 240 230 220 None 1, 7 Unfused
240V/230V/220V
7 208 200 None 1, 2 Unfused
208V/200V 480 460 440 3-8 6, 4 1-5, 4-8
2
240 230 220 8-7 6, 4 1-5, 4-8
208 200 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse
25V/24V/23V (Secondary Volts) Between Terminals Connect To Clips To
3
25V/24V/23V Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse
3
(Secondary Volts) Between Terminals Connect To Clips To
120V/115V/110V
4
120 115 110 None 2, 4 Unfused
1 25 24 23 None 2, 3 Unfused
7 2 120 115 110 None 1, 4 2-7
LV
25 24 23 None 1, 3 2-7
*This primary fuse jumper is supplied with the primary fuse kit only.
2
25V/24V/23V Low Voltage (LV) Install Supplied Jumpers Load Lines Install Fuse
(Secondary Volts) Between Terminals Connect To Clips To
120V/115V/110V
4 120 115 110 None 1, 4 Unfused
25 24 23 None 1, 2 Unfused
1
LV Note: secondary fuse clips for 24V tap not available on the PH750MLI or PH1000MLI units.
*This primary fuse jumper is supplied with the primary fuse kit only.
60
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION
SECTION 1
9 HPS IMPERATOR®
Group J
SECTION 1
High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
6 HV 4 (Primary Volts) Between Terminals Connect To Clips To
5 Dotted line represents
1 supplied jumper lead* 415 None 1, 3 Unfused
8
400 None 1, 7 Unfused
415V 380 None 1, 2 Unfused
3
400V 7 415 3-8 6, 4 1-5, 4-8
380V 400 8-7 6, 4 1-5, 4-8
2
380 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
4 3 2 65 1 (Secondary Volts) Between Terminals Connect To Clips To
4 3 2 1 4 3 2 1 110 3-4, 1-2 1, 4 Unfused
220 2-3 1, 4 Unfused
110V 220V 110 3-4, 1-2 4, 6 1-5
LV 220 2-3 4, 6 1-5
*This primary fuse jumper is supplied with the primary fuse kit only.
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
5 4 3 17 2 (Secondary Volts) Between Terminals Connect To Clips To
6 5 4 3 2 1 6 5 4 3 2 1 110 4-5, 2-3 2, 5 Unfused
220 3-4 2, 5 Unfused
110V 220V 110 4-5, 2-3 1, 5 2-7
LV 220 3-4 1, 5 2-7
*This primary fuse jumper is supplied with the primary fuse kit only.
61
© Hammond Power Solutions Inc. Data subject to change without notice.
SECTION 1 HPS IMPERATOR®
HPS IMPERATOR Series - Wiring Schematic Drawings continued
Group K
PH***MGJ Schematic for 50, 75 and 100VA Units
SECTION 1
6 HV 4 High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
(Primary Volts) Between Terminals Connect To Clips To
5 Dotted line represents
1 supplied jumper lead* 8 380 None 1, 3 Unfused
380V
277 None 1, 7 Unfused
3 208 None 1, 2 Unfused
277V 7 380 3-8 6, 4 1-5, 4-8
208V 2 277 8-7 6, 4 1-5, 4-8
208 2-8 6, 4 1-5, 4-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
4 3 2 65 1
(Secondary Volts) Between Terminals Connect To Clips To
4 3 2 1 4 3 2 1 120 3-4, 1-2 1, 4 Unfused
240 2-3 1, 4 Unfused
120V 240V 120 3-4, 1-2 4, 6 1-5
LV 240 2-3 4, 6 1-5
*This primary fuse jumper is supplied with the primary fuse kit only.
HV High Voltage (HV) Install Supplied Jumpers Supply Lines Install Fuse
1 5
(Primary Volts) Between Terminals Connect To Clips To
7 Dotted line represents
2
supplied jumper lead*
8 380 None 2, 6 Unfused
277 None 2, 4 Unfused
380V 208 None 2, 3 Unfused
6
277V 4 380 8-6 1, 5 2-7, 5-8
208V 3
277 4-8 1, 5 2-7, 5-8
208 3-8 1, 5 2-7, 5-8
Low Voltage (LV) Install Supplied Links Load Lines Install Fuse
5 4 3 17 2 (Secondary Volts) Between Terminals Connect To Clips To
6 5 4 3 2 1 6 5 4 3 2 1 120 4-5, 2-3 2, 5 Unfused
240 3-4 2, 5 Unfused
120V 240V 120 4-5, 2-3 1, 5 2-7
LV 240 3-4 1, 5 2-7
*This primary fuse jumper is supplied with the primary fuse kit only.
62
© Hammond Power Solutions Inc. Data subject to change without notice.