100MGD Pump House Dhabeji - Electrical BOQ
100MGD Pump House Dhabeji - Electrical BOQ
PRICING PREAMBLES
a) This Contract Document, consisting of Tender Specifications, Bill of Quantities and Tender
Drawings are the property of Exponent Engineers (Pvt.) Ltd and shall be returned on the date
of Tender submission even if the Contractor choses not to participate in the Tender. Any
reproduction or transmission of this Contract document without prior explicit approval of
Exponent Engineers (Pvt.) Ltd is illegal and may be subject to legal action
b) All pages of the BoQ and specifications shall be signed and stamped by the authorized
representative of the Contractor. Only the signed and stamped copy of the BoQ shall be
entertained and considered part of the Contract. A soft copy of the BoQ shall be provided to
facilitate the process of costing. Any change in the BoQ text from the original shall be
deemed as breech of contract and liable for penalty.
c) All items shall to be executed as per specifications, drawings, and as directed by the
Consultant/Engineer, and shall confirm to the latest edition of the IEEE wiring regulations.
Contractor shall test relevant installation to be witnessed by Electrical Consultant and or
Client representative and provide all relevant test reports.
d) Samples of all items including but not limited to shop drawings for DB's, raceways, back
boxes, outlets for switch sockets and voice/data, cables etc., shall to be got approved by the
Consultant / Engineer prior to installation.
e) Any item not meintioned herein but necessary for the completion of works to the
satisfaction of the owner/client shall be deemed to be part of the appropriate electrical
works. Details of such works shall be submitted for Consultant/Engineer's approval before
start of work.
f) All works related to active IT equipment, including but not limited to provision of PRI, ISDN,
POTS lines, installation and configuration of routers/switches etc., inter office /WAN
connectivity, internet / remote / radio link etc. are not covered under the scope of this
contract, unless specifically stated in the BoQ.
g) NoC for all electrical works shall shall be obtained from relavant authorities before project
handing over. Costs for obtaining approvals shall be quoted separately.
h) Quotations shall be based on the approved equipment list / supplier. Deviations, if any,
shall have to be got approved prior to installation works. Any discrepancy found shall be
rectified / replaced at the cost of the contractor.
i) Any conflict between the wiring standards and instructions as per drawings, specifications
or Consultant instructions shall be immediately brought to the notice of the Consultant for
appropriate consideration.
m) All items quoted for aginst this Contract shall be new and of latest make /model. Any
outdated, obsolete or end-of-life products shall be replaced with alternate models from the
same manufacturer and gotten approved from the Client or his representative (Architect,
Consultant) during the bidding process. The Client or his representative shall have the right to
ask for replaceent of any item, with similar or better specification, which is found faulty or
substandard or is a subject of discrepancy not clarified during the bidding process.
PRICING PREAMBLES
Contractor
Contractor
1 Job
3 Obtaining NOC/approval certificate for entire electrical
installation works (excluding gensets) at the proposed
building including all wiring installations, from Electric
Inspector, Karachi Region office (official inspection
charges/fee will be paid separately upon production of
receipt, in addition to price quoted above)
1 Job
Particular Notes:
a) See general notes on Summary Page
b) Refer Power Cable Ordering Sheet for details
WIRING - MV CABLES
1 Supply, installation, connecting up, testing and
commissioning of PVC insulated PVC sheathed
non armoured / armoured Copper conductor MV
cable 15kV grade in already laid raceway as per
details shown on drawings from KESC Substaton /
Owner Main MV panel to EMEC MV Panel,
including designation labels at both ends etc., in
the following sizes (Actual length of cable shall
be measured at site by the contractor before
placing the order with the manufacturer,
however approximate length of cable are shown
herewith)
RACEWAY
5 Supply, laying and installation of following PVC /
GI / MS pipe to be recessed in walls / floors or
clipped to surface, as required at site and as
shown on the drawing including accessories steel
pull wires, complete in all respects;
CABLE TRAY
7 Providing and fixing of 16 SWG, powder coated,
perforated, sheet steel cable trays complete with
all installation accessories including angle iron
support of size 1-1/2"x1-1/2"x1/8", MS round
bars of 1/2" dia, nuts, bolts etc., complete in all
respects in the following sizes;
Particular Notes:
a) See general notes on Summary Page
WIRING ACCESSORIES
Particular Notes:
a) See general notes on Summary Page
b) Fluorescent fixtures should be compatible with and fit
exactly into the false ceilng
c) All lamps shall be color 84 or cool white unless otherwise
stated or instructed by Architect / Consultant
d) Ballast shall be of electronic type as indicated
e) Exit light fixtures shall be LED type
a) Fixture type 'F1': Surface type, 1'x4' LED Flat Panel 40W
(Refer: FT LED Smart PANEL)
37 Nos.
b) Fixture type 'F2': Surface mounted general purpose
batten luminaire for 1 x 18W T5 LED lamp (Refer:
Pierlite type Flora Slim T5) (Warm White)
24 Nos.
c) Fixture type 'F3' Surface mounted Bulkhead
weatherproof type Luminaire with 1 x 18W T5 LED lamp
(Refer: Philips pacific II TCW097)
24 Nos.
d) Fixture type 'F4' Surface mounted 100W Flood Light
fixture (Refer: Philips ClearFlood-BVP650) 16 Nos.
e) Fixture type 'F5' Surface mounted Highbay Lighting
fixture with 315W LED Lamp with Wide Beam(Refer:
Philips VerseBay Elite MPK518)
16 Nos.
f) Fixture type 'F6': Surface mounted type LED Downlight
fixture including 18 W LED lamp (warm white) 8 Nos.
g) Fixture type 'F7': 60W LED Lamp (Pole Mounted Type) 24 Nos.
h) Fixture type 'E1': Reccesd/False ceiling mounting
rechargable battery-operated (3hrs) non-maintainted
type Emergency light with LED lamp (refer PIERLITE
FFRLED C0/C90 D25)
23 Nos.
i) Fixture type 'E2': Recessed/False ceiling mounting
rechargable battery-operated (3hrs) maintainted type
emergency LED Exit Light with lamp (refer PIERLITE
LEDXM2P C0/C90 D1.25)
3 Nos.
Particular Notes:
a) See general notes on Summary Page
b) All earth pits are to be connected with each other in
parallel at test point in pit
EARTHING SYSTEM
1 Supply, installation, & connecting up plate type earth
electrodes with 600mm x 600mm x 3.2mm tinned
copper plate connected with 2x50mmsq PVC insulated
copper earth conductors in 50mm PVC pipe class D/E
up to main earth bar including all accessories,
inspection chamber, heavy duty C.I. Cover etc.
2 Jobs
2 Supply, installation, & connecting up Rod type earth
electrodes with 3/4" dia copper rod 10ft long ( in 3
equal sections) connected with 2x70mmsq bare copper
conductor in 50mm GI pipe class up to earth connecting
point in pit, including clamps inpection chamber heavy
duty C.I. Cover etc. and all accessories, complete in all
respects and as per drawing
17 Jobs
3 Supply, installation of earth Connecting points (outside
pit) consisting of Copper plate 12” long, 2” wide and ½”
thick to be installed as and where shown on drawings
on the wall, complete with fixing arrangement, brass,
nuts, bolts, complete in all respects to facilitate
connections of incoming copper strip and outgoing
CPC‟s.
10 Nos.
4 Providing & fixing of substation main earth bar, with
800mm x 50mm x 20mm copper bar with terminals,
insulator supports, lugs, bolts, etc., including bonding to
rebars of foundation structure
2 Nos.
5 Providing, fixing and connecting up of PVC insulated
450/750V grade copper conductor earth cable (green),
in already laid raceway including all fixing, jointing &
termination accessories, etc., in the following sizes:
1 Job
8 Supply, installation of lightining protection terminal 1 m
long, installed as and where shown on drawings on the
roof, complete with fixing arrangement, connecting /
cad welding with copper tape/conductor, base plate,
brass nuts, bolts, complete in all respects
1 No.
9 Supply, installation and connecting up of 25x3mm
copper tape along the periphery of the building, on the
roof, including all fixing clamps, cad welding and
accossories etc. complete in all respects
140 Mtr.
10 Supply, installation and connecting up of 25x3mm
copper tape as down conductors, along the side of the
building, on the roof, including all fixing clamps, earth
test links and connecting to the earth pits, and
accossories etc. complete in all respects
50 Mtr.
11 Bonding of reinforcement steel bars of underground
foundation pad (retaining walls, column footings) with
cad welding, and copper connection to main earth-bar
at substation.
1 Job
Particular Notes:
a) See general notes on Summary Page
MISCELLANEOUS ITEMS
Particular Notes:
a) See general notes on Summary Page
b) Short-circuit ratings to IEC 947-2, Icu/Ics at 415V
c) All components (ELCBs, Contactors etc.) are to be
provided with backup protection
d) DBs of incoming size 100A or less may be provided
with cascading
MV SWITCHGEAR
1 Supply, installing, testing & commissioning of following
MV Switchgear equipment (as per KESC approved
specifications, including connecting up with existing MV
panels, all mounting accessories etc. complete in all
respects
LV SWITCHGEAR
2 Supply, installing, testing & commissioning of following
switchgear equipoment ( made of 12 SWG sheet steel )
with hinged doors and locks, including bus bars of tin
plated copper conductor for phases, neutral and
ground, of short circuit rating as mentioned below and
all TP MCCBs shall also have minimum ultimate
interrupting capacities (Icu) as mentioned in the
drawings or more ( All circuit breakers will be having co-
ordination and selectivity properties for this system ) ,
with proper brass glands for incoming cables. All DBs
are Flush / surface Mounted type and of suitable
dimensions to fit-in the location / space shown on
drawings. The contarctor shall take the dimensions of
the site, prepare the shop drawing of DB / Panel and
approval from the Consultant before manufacturing)
and with following configuration (Maximum current
density of each Phase, Neutral and Earth bus bar shall
not be more than 1.5 Amp per sq. mm & arrangement /
onnections of bus bar will be as required. All of the
mcbs & MCCBs will be having thermal as well as
magnetic short circuit releases).
Particular Notes:
a) See general notes on Summary Page
b) Short-circuit ratings to IEC 947-2, Icu/Ics at 415V
c) All components (ELCBs, Contactors etc.) are to be
provided with backup protection
Power Transformer
1 Supply, installing, testing & commissioning of following
Transformer (as per KESC approved specifications,
including all mounting accessories etc. complete in all
respects
1. TELEPHONE SYSTEM
NOTES:
The Contractor shall provide cables, telephone junction
boxes and telephone instruments of 15 lines Intercom
System with 30% spare lines.
Proposed cable routes and places where telephone
connections are to be provided will be decided by the
Contractor.
The telephone cables shall have minimum 30% additional
pairs for future use/ replacement purposes.
Cables shall be laid in underground heavy gauge PVC
conduits, minimum dia 75 mm. Water tight cable draw-pits
shall be provided at convenient locations viz at bends and
entry to the building etc.
Vandal proof and weather proof Distribution Cabinets on
C.C pads shall be provided at appropriate locations.
2. CCTV/SECURITY SYSTEM
DB Ground Floor
Incoming:
MCCB TP 80A, 15KA 1
Outgoing:
R1 MCB SP 10A 1 100W Flood Light External
Y1 MCB SP 10A 1 400W High bay light
B1 MCB SP 10A 1 400W High bay light
R2 MCB SP 10A 1 400W High bay light
Y2 MCB SP 10A 1 400W High bay light
B2 MCB SP 10A 1 Transformer Room
R3 MCB SP 10A 1 Main LV Room
Y3 MCB SP 10A 1 Store
B3 MCB SP 10A 1 MV Room
R4 MCB SP 10A 1 Motor Room
Y4 MCB SP 10A 1 Stair + Entrance
B4 MCB SP 10A 1 Walk Way/Corridor
B4 MCB SP 10A 1 Emergency Lights
R5 MCB SP 10A 1 Emergency Lights
Y5 MCB SP 16A 1 16A Switch Socket
B5 MCB SP 16A 1 16A Switch Socket
R6 MCB SP 16A 1 16A Switch Socket
Y6 MCB SP 16A 1 16A Switch Socket
B6 MCB SP 16A 1 16A Switch Socket
R7 MCB SP 16A 1 16A Switch Socket
Y7 MCB SP 16A 1 16A Switch Socket
B7 MCB SP 16A 1 16A Switch Socket
R8 MCB SP 16A 1 16A Switch Socket
Y8 MCB SP 16A 1 16A Switch Socket
B8 MCB SP 16A 1 16A Switch Socket
R9 MCB SP 16A 1 16A Switch Socket
Y9 MCB SP 16A 1 16A Switch Socket
B9 MCB SP 16A 1 Spare
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 Spare
DB First Floor
Incoming:
MCCB TP 60A, 15KA 1
Outgoing:
R1 MCB SP 10A 1 100W Flood Light External
Y1 MCB SP 10A 1 400W High bay light
B1 MCB SP 10A 1 400W High bay light
R2 MCB SP 10A 1 400W High bay light
Y2 MCB SP 10A 1 400W High bay light
B2 MCB SP 10A 1 Stairs+Terrace+Washroom
R3 MCB SP 10A 1 Control Room
Y3 MCB SP 10A 1 Battery Room
B3 MCB SP 10A 1 Kitechen+Washroom
R4 MCB SP 10A 1 Offices
Y4 MCB SP 10A 1 Conference Room
B4 MCB SP 10A 1 Walk Way/Corridor
B4 MCB SP 10A 1 Emergency Lights
R5 MCB SP 10A 1 Emergency Lights
Y5 MCB SP 16A 1 15A Switch Socket
B5 MCB SP 16A 1 15A Switch Socket
R6 MCB SP 16A 1 15A Switch Socket
Y6 MCB SP 16A 1 15A Switch Socket
B6 MCB SP 16A 1 15A Switch Socket
R7 MCB SP 16A 1 15A Switch Socket
Y7 MCB SP 16A 1 15A Switch Socket
B7 MCB SP 16A 1 5A Switch Socket
R8 MCB SP 16A 1 5A Switch Socket
Y8 MCB SP 16A 1 5A Switch Socket
B8 MCB SP 16A 1 5A Switch Socket
R9 MCB SP 16A 1 5A Switch Socket
Y9 MCB SP 16A 1 5A Switch Socket
B9 MCB SP 16A 1 Spare
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 16A 3-phase Industrial Socket
MCB TP 16A 1 Spare
MCB SP 20A 1 Air Conditioner
MCB SP 20A 1 Air Conditioner
MCB SP 20A 1 Air Conditioner
MCB SP 20A 1 Spare