Professional Documents
Culture Documents
EPRI Compressor and Instrument Air Maint Guide
EPRI Compressor and Instrument Air Maint Guide
Final Report
March 1998
LICENSED
M AT E R I A L
Revision to NP-7079
TR-108147
Final Report
March 1998
Prepared by
EPRI
3412 Hillview Avenue
Palo Alto, California 94304
EPRI
Nuclear Maintenance Applications Center
1300 W.T. Harris Boulevard
Charlotte, North Carolina 28262
ORDERING INFORMATION
Price: $10,000
Requests for copies of this report should be directed to the EPRI Distribution Center, 207 Coggins Drive,
P.O. Box 23205, Pleasant Hill, CA 94523, 510/934-4212.
Electric Power Research Institute and EPRI are registered service marks of Electric Power Research Institute, Inc.
Copyright © 1998 Electric Power Research Institute, Inc. All rights reserved.
EPRI Licensed Material
REPORT SUMMARY
The instrument air system in most nuclear power plants is designated as a non-safety-
related system; however, instrument air is required for the operation of both safety-
related and non-safety-related systems. A failure of the instrument air system can result
in power reduction or even a reactor scram. A thorough understanding of the system by
plant operation and maintenance personnel can assist in eliminating related problems
presently experienced in power plants.
This guide provides descriptions of system layouts in power plants, as well as types of
available equipment, their characteristics, and the relative advantages and disadvan-
tages of each type. In addition, step-by-step maintenance troubleshooting guides are
included to provide insight into possible system difficulties and ways to avoid them.
Recommendations that will provide air quality that meets or exceeds the Instrument
Society of America standards are furnished for proactive maintenance of the system.
Background
In the past, NRC Generic Letter 88-14 and INPO SOER 88-1 raised serious questions
regarding the failure of instrument air systems to operate consistently within their
design parameters. NMAC published a guide in 1990 (NP-7079) to assist utility person-
nel in improving system maintenance. Since then, a number of utilities have decided to
replace their instrument air system equipment with newer models and types. This
revised guide addresses maintenance of the latest types of compressors and other in-
strument air system equipment currently in use in power plants.
Most of the problems with the instrument air system can be traced to inadequate system
understanding and maintenance. Voluminous amounts of information on compressors
and compressed air system components are available from vendors and other industry
sources. This guide condenses the available information and provides only what is
applicable to the power generation industry.
Objectives
iii
EPRI Licensed Material
Compressor and Instrument Air System Maintenance Guide
Approach
Large amounts of information on compressors and other compressed air system compo-
nents are available; however, most of this information is not applicable to the power
generation industry. EPRI’s Nuclear Maintenance Applications Center (NMAC) re-
viewed this extensive information and included here only that information pertaining
to the operation of an instrument air system in a power plant. Discussions were held
with equipment suppliers and with utility personnel responsible for maintenance of
instrument air systems, and the guide was reviewed by a number of NMAC member
utilities and other industry specialists for accuracy and completeness.
Results
This guide approaches the maintenance of instrument air on a system basis. Instrument
air problems due to various contaminants have been thoroughly investigated and
solutions recommended. Problems due to leaks and component failures have also been
addressed. Detailed recommendations have been made for air filters and dryer desic-
cants. Troubleshooting charts have been added in the appendices for quick diagnosis of
maintenance problems.
EPRI Perspective
The instrument air system is an important support system in any power generation
plant. Recently, there has been heightened awareness of the importance of this system,
especially in nuclear power plants. Regulatory bodies and industry organizations are
concerned that the maintenance of instrument air systems has not received enough
emphasis. This guide should assist the utilities in identifying system problems and
maintaining their system to the required standard.
TR-108147
Interest Categories
System engineers
Maintenance engineers
Training managers
Keywords
Compressor
Compressed air
Instrument air
Air filters
Air dryers
Maintenance
iv
EPRI Licensed Material
ACKNOWLEDGMENTS
Principal Investigator:
Mr. David M. McCulloch
NMAC would also like to acknowledge the contribution of the following individuals
for providing information and reviewing the draft prior to publication. The time and
attention provided by each is greatly appreciated.
NMAC also acknowledges the contribution of The Compressed Air and Gas Institute
(CAGI), 1300 Sumner Avenue, Cleveland, OH 44115-2851 for allowing us to use techni-
cal material from their various publications. Finally, NMAC acknowledges the contribu-
tion of the various manufacturers and vendors who provided us with illustrations and
other information for this guide. The material received from CAGI and other sources
has been identified within the body of this guide.
v
EPRI Licensed Material
CONTENTS
vii
EPRI Licensed Material
Compressor and Instrument Air System Maintenance Guide
viii
EPRI Licensed Material
Compressor and Instrument Air System Maintenance Guide
ix
EPRI Licensed Material
LIST OF FIGURES
Figure 2-1 A Typical Instrument Air System Layout for a Single Unit Station with Service Air
Backup .......................................................................................................................... 2-1
Figure 2-2 A Typical Instrument Air System Layout for a Multi-Unit Station with Shared
Compressor Bank ......................................................................................................... 2-2
Figure 2-3 A Typical Compressed Air System Layout Supplying Service Air and Instrument Air ... 2-3
Figure 2-4 A Typical Instrument Air System Layout with Service Air Backup ................................. 2-4
Figure 3-3a Crosshead Assembly for a Non-Lubricated Double-Acting Compressor ...................... 3-5
Figure 3-5 Compression Cycle of an Oil-Injected Rotary Screw Compressor ................................ 3-7
Figure 3-12 Characteristic Curves for a Centrifugal Air Compressor at 90°F ................................. 3-19
Figure 3-13 Characteristic Curves for a Centrifugal Air Compressor at 60°F ................................. 3-20
Figure 3-14 Centrifugal Air Compressor—Integrally Geared Multiple Impellers ............................. 3-21
Figure 3-15 Pressure Lubrication System for an Air Compressor .................................................. 3-23
xi
EPRI Licensed Material
Compressor and Instrument Air System Maintenance Guide
Figure 4-2 Atmospheric vs. Pressure Dew Point Conversion Chart ............................................... 4-5
xii
EPRI Licensed Material
LIST OF TABLES
Table 4-1 Moisture Content of Saturated Air in Gallons per 1000 Standard Cubic Feet ............... 4-2
Table 4-2 Pressure and Temperature Correction Factors for Compressed Air Dryers .................. 4-3
xiii
EPRI Licensed Material
1
INTRODUCTION
The objective of this report is to provide technical guidance to assist utility personnel in
improving compressor and instrument air system maintenance and operability. Section
2 of this report provides information about typical system layouts in U.S. nuclear power
plants.
Service air is the term used for compressed air that is used for a variety of purposes,
mainly for the operation of pneumatic tools, such as air drills, nut runners, grinders,
and sand blasters, and for paint spraying and general cleaning. Because there are no
national standards for service air, the quality of service air should not be specified, but
it is desirable to have relatively clean, dry air to prevent undue wear on tools from
washed out lubricant, condensate in paint, or other contaminants.
Instrument air is the term used for compressed air that is used for motive power for
valves, instrument and control functions, and breathing. Instrument air requires a
higher degree of cleanliness from contaminants. This document addresses the following
basic aspects of power plant instrument air systems:
• Compressed air production: The compressors producing the compressed air. Ad-
dressed in Section 3.
• Compressed air treatment: The dryers and filters that remove contaminants. Ad-
dressed in Section 4.
• Compressed air distribution: The piping, storage volume, and accessories to get the
compressed air to each point of use. Addressed in Section 5.
• Compressed air applications: The points of use and their requirements. Addressed
in Section 6.
• Compressed air system safety: Safety considerations and recommendations. Ad-
dressed in Section 7.
• Component and system maintenance: Maintenance considerations. Addressed in
Section 8.
A discussion on instrument air quality is included in Section 4.4, and relevant specifica-
tion references are provided in Section 9. A glossary of terms is included in Section 10.
1-1
EPRI Licensed Material
Introduction
In a nuclear power plant, the instrument air system is typically classified as a non-
safety-related system. However, both non-safety-related and safety-related systems
require the use of instrument air for their operation; therefore, a failure of instrument
air can adversely affect plant operation. On loss of air, air-actuated valves fail in the
open, closed, or as-is condition. This can cause serious transients in operating systems
throughout the plant.
Some safety-related systems in a nuclear power plant are provided with backup accu-
mulators for a safe shutdown or system isolation, as required. These accumulators
require periodic inspection, maintenance, and testing to ensure proper functioning.
In an effort to enhance system reliability, a number of utilities are replacing the old
compressors, dryers, and ancillary equipment, or are installing additional ones. This
guide provides descriptions of available air system equipment and the characteristics,
application, advantages, and disadvantages of each. This information will assist plant
engineers in understanding the system requirements and in selecting the correct equip-
ment. Extensive information is included on selecting air dryers, desiccants, traps, and
filters. Finally, recommendations are provided for a proactive maintenance of the sys-
tem to provide air quality that meets or exceeds the Instrument Society of America (ISA)
standards.
1-2
EPRI Licensed Material
2
COMPRESSED AIR SYSTEMS
This section provides information about typical instrument air system layouts in U.S.
nuclear power plants.
The system layout in Figure 2-1 shows the dryers, with pre-filters, located before the air
receivers. Pre-filters are necessary to prevent fouling of the dryer desiccant bed from
lubricant carryover from the compressor. After-filters prevent desiccant fines from
being carried downstream into instruments and controls. The receiver tanks located
after the dryers ensure that only the maximum air capacity of the compressors can pass
through the dryers, even in the event of a sudden demand for compressed air that
exceeds the rated capacity of the dryer. The extra capacity is drawn from the receivers,
which have clean, dried air stored in them. Duplicate pre-filters, dryers and, receivers
allow redundancy for maintenance.
Compressors
Possible
Service Air
Backup Possible
(Mode-1) Service Air
Backup
(Mode-2)
To
Instrument After-Filters
Air System
Notes:
Figure 2-1
A Typical Instrument Air System Layout for a Single Unit Station with Service Air Backup
2-1
EPRI Licensed Material
Compressed Air Systems
Some power plants use the service air compressors to provide backup service for the
instrument air system in the event of a loss of pressure in the instrument air lines. This
layout shows two possible modes of hookup for service air backup compressors. Mode
1, which connects the service air compressors before the pre-filter, is the preferred mode
because it treats the air through filters and dryers prior to entering the system piping.
This protects the system piping and end-user equipment from moisture and other
contaminants usually found in the service air. The mode 2 option, which connects the
service air compressors after the receivers, is not recommended because it injects un-
treated moist air directly into the system piping.
The layout shown in Figure 2-2 is sometimes used in multi-unit power stations. A single
bank of compressors is used to supply instrument air to all units at the site. This layout
has definite economic advantages in terms of the initial investment and operating cost.
However, USNRC report NUREG 1275, Volume 2, “Operating Experience Feedback
Report—Air System Problems,” notes that “Losses of shared IA systems at multi-plant
stations have resulted in simultaneous transients. The recovery from some of those
events has been complex.”
To
Unit 1
After-Filters
Compressors
Pre-Filters Dryers
To
Unit 2
(Similar to Unit 1)
“A” Header
Receivers
Located
Throughout “B” Header
System
Figure 2-2
A Typical Instrument Air System Layout for a Multi-Unit Station with Shared
Compressor Bank
This layout also has the air receivers located throughout the system. While this has the
advantage of storage volume close to points of use with varying demands and cycle
time, the compressor controls may experience far more fluctuation of pressure than
with a receiver closer to the compressor, as in Figure 2-1. Therefore, the compressor
may experience more starts and stops, increasing compressor wear and maintenance.
2-2
EPRI Licensed Material
Compressed Air Systems
The backup compressor (with dryer) in this figure is shown with a closed manual valve.
This indicates that this service is designed only for use in an emergency, when an op-
erator will open the valve to allow the backup compressors to pressurize the instrument
air system. Since the backup compressor unit is provided with its own dryer, system
contamination is not a consideration during its use.
The layouts shown in Figures 2-3 and 2-4 generally are better suited to reciprocating-
type compressors, where the air receivers provide a buffer for discharge pressure pulsa-
tions. Receivers before the dryers also provide radiant cooling and removal of conden-
sate before the air reaches the dryers. These systems also have desiccant dryers for only
the instrument air. While service air does not need to be of the same quality as instru-
ment air, it is recommended that a dryer, such as a refrigerant-type dryer, be installed
for service air to protect the system piping from ingress of moisture. Untreated service
air should not be introduced into an instrument air system. If service air is to be used as
a backup for instrument air, then appropriate drying and filtration should be provided.
To
Instrument
Air System
Compressors
Pre-Filters Dryers
Receivers To
Service Air
System
(Simliar To Instrument Air)
After-Filters
Notes:
1. Number, size and type of compressors vary.
2. Drawing does not contain details such as drains,
vents, check valves, etc.
Figure 2-3
A Typical Compressed Air System Layout Supplying Service Air and Instrument Air
2-3
EPRI Licensed Material
Compressed Air Systems
Compressors
To
Instrument
Air System
To or From
Service Air
System
Notes:
Figure 2-4
A Typical Instrument Air System Layout with Service Air Backup
2-4
EPRI Licensed Material
3
COMPRESSED AIR PRODUCTION
(COMPRESSORS AND ACCESSORIES)
There are various mechanisms used in the compression of air, resulting in a variety of
compressor types and sizes. Compressor types in common use are listed in Figure 3-1
with their ranges of horsepower (hp), size in cubic feet per minute (cfm), and pressure
capability. Only those stationary types and sizes common to instrument air systems are
discussed in the ensuing text. Normally, these operate in the 100–125 psig (6.9–8.62
bars) range.
3-1
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Stationary
Compressors
Dynamic
Positive
Displacement
Reciprocating Rotary
Rating Ranges
1,000-10,000 H.P.
40-400 PSIG
8,000-13,000,000 CFM
Figure 3-1
Types and Capacity Ranges of Compressors
Over the last decade, there has been a significant trend toward rotating machinery and,
in the case of compressors, to rotary screw and/or centrifugal types.
3-2
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Cylinders and cylinder heads have external finning for radiant heat dissipation, and in
two stage designs, cooling between the stages is accomplished with a finned pipe inter-
cooler. Belt drive is most common, and the compressor sheaves/flywheel can also serve
as a cooling fan with suitably contoured spokes. A cross-section of a typical unit is
shown in Figure 3-2. An aftercooler of similar construction to the intercooler or a sepa-
rate aftercooler can be used. The location of the compressor must allow for unrestricted
cooling air flow.
Cylinders generally are lubricated by splash lubrication where a dipper on the connect-
ing rod dips into the oil in the crankcase and splashes it towards the cylinder. A pres-
sure lubrication system is used on some compressors of this type. Oil-free or oil-less,
single-acting air compressors also are available where oil is excluded from the compres-
sor cylinder. In this case PTFE (polytetra fluoro ethylene) or similar material can be
used for piston rings.
These compressors commonly are supplied as packages and mounted on an air receiver
or tank and are called tank-mounted compressors. The receiver tank also provides some
additional radiation cooling and requires that resulting condensate be drained regularly.
Generally, these packages are installed close to the point of use of the compressed air.
3-3
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
ASME-Code
Interstage
Safety Valves
Intake Unloaders
Cylinder and
Head Gaskets
Valve Design
High-Performance
Three-Piece Oil Rings
Cast Iron
Flywheel
Coalescing
Stainless Steel
Mesh Crankcase
Breather
Bearings
Counter-
Weighted
Crankshaft Oil Level
Bayonet
Oil Reservoir
Figure 3-2
Single-Acting Reciprocating Compressor
(Source: Quincy Compressor Division, Coltec Industries, Inc.)
3-4
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Oil Scraper 'NL' Distance Cross Head & Frame Port Outer Port
Assembly Piece Distance Piece Plate Plate
Figure 3-3a
Crosshead Assembly for a Non-Lubricated Double-Acting Compressor
(Source: Ingersoll-Rand Company)
Partition
Stuffing Ring
Box
Oil Oil Drain
Port
Oil Relief
Groove
Frame End Cylinder End
Cylinder Frame
End End
Partition
Scraper
Plate
Figure 3-3b
Details of Oil Scraper Rings
3-5
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Double-acting air compressors generally have cooling water jackets around the cylinder
body and in the cylinder head. This, combined with their relatively slow speed of op-
eration and water-cooled intercooling, results in excellent compression efficiency.
Single and two cylinder compressors of this type generally require a substantial founda-
tion due to unbalanced reciprocating forces.
3.2 Rotary-Type Air Compressors (adapted from The Compressed Air and Gas
Institute Rotary Air Compressor Selection Guide)
The oil-injected rotary screw compressor consists of two intermeshing rotors in a stator
housing that has an inlet port at one end and a discharge port at the other. The male
rotor has lobes formed helically along its length, and the female rotor has correspond-
ing helical grooves or flutes. A typical oil-injected rotary screw compressor is shown in
Figure 3-4.
Figure 3-4
Cross-Section of an Oil-Injected Rotary Screw Compressor
(Source: Sullair Corporation)
3-6
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Air flowing in through the inlet port fills the spaces between the lobes on each rotor.
Rotation then causes the air to be trapped between the lobes and the stator as the
interlobe spaces pass beyond the inlet port. As rotation continues, a lobe on one rotor
rolls into a groove on the other rotor, and the point of intermeshing moves progres-
sively along the axial length of the rotors, which reduces the space occupied by the air,
resulting in increased pressure. Compression continues until the interlobe spaces are
exposed to the discharge port when the compressed air is discharged. This cycle is
illustrated in Figure 3-5.
Figure 3-5
Compression Cycle of an Oil-Injected Rotary Screw Compressor
(Source: Sullair Corporation)
Oil is injected into the compression chamber during compression and serves three basic
functions:
• It lubricates the intermeshing rotors and associated bearings.
• It removes most of the heat caused by compression.
• It acts as a seal in the clearances between the meshing rotors and between the rotors
and stator.
The generic term oil has been used. Generally, this is understood to be a hydrocarbon
product, but most compressors now use cleaner and longer life synthetic lubricants,
including diesters, polyglycols, polyalphaolefins, and silicon-based fluids. These newer
products are suitable for a wider range of temperatures and have higher flash points.
However, compatibility of the lubricant and its volatile additives with downstream
components, especially elastomeric materials, should be checked.
A mixture of compressed air and injected oil leaves the air discharge end of the com-
pressor and is passed to a sump/separator where the oil is removed from the com-
pressed air. Directional and velocity changes are used to separate most of the liquid.
The remaining aerosols in the compressed air are separated by a coalescing filter, result-
ing in only a few parts per million (ppm) of oil carryover. Most oil-injected rotary screw
compressor packages use the air pressure in the oil sump/separator, after the discharge
of the air end, to circulate the oil through a filter and cooler prior to re-injection into the
compression chamber. Some designs use an oil pump.
3-7
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Single stage, oil-injected rotary screw compressor packages are available from 3–900 hp
and with capacities from 8–5000 cubic feet per minute (cfm) (.2–141.6 cubic meters per
minute or cm/m), with discharge pressures from 50–200 psig (3.45–13.8 bars). Two
stage versions can improve the power required for a given rate of flow by up to 15%,
and some can achieve higher discharge pressures.
In the dry type, the intermeshing rotors are not allowed to touch, and their relative
positions are maintained by means of lubricated timing gears external to the compres-
sion chamber. Because there is no injected fluid to remove the heat of compression,
most designs use two stages of compression with an intercooler between the stages and
an aftercooler after the second stage. The lack of a sealing fluid also requires higher
rotational speeds than for the oil-injected type. A typical air end is shown in Figure 3-6.
Figure 3-6
Oil-Free Rotary Screw Compressor
(Source: Atlas Copco Compressors Inc.)
3-8
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Dry-type, oil-free rotary screw compressors have a range from 50–4000 hp and capaci-
ties from 200–20,000 cubic feet per minute (5.6–566.3 cm/m). Single stage units can
operate up to 50 psig (3.45 bars), while two stage units generally can achieve 125 psig
(8.62 bars).
In the water-injected type, similar timing gear construction is used, but water is injected
into the compression chamber to act as a seal in internal clearances and to remove the
heat of compression. This allows pressures in the 100–150 psig (6.9–10.34 bars) range to
be accomplished with only one stage as illustrated in Figure 3-7. The injected water,
together with condensed moisture from the atmosphere, is removed from the dis-
charged compressed air by a conventional moisture separation device. Similar to the oil-
injected type, oil-free rotary screw compressors generally are packaged with all neces-
sary accessories.
Figure 3-7
Water-Injected Rotary Screw Compressor
(Source: Gardner Denver Machinery, Inc.)
3-9
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Similar to the standard rotary screw compressor, the single screw compressor is a dis-
placement type, which means that a given quantity of air or gas is trapped in a com-
pression chamber and the space is mechanically reduced, causing a corresponding rise
in pressure prior to discharge.
Air enters the compression chamber through an inlet port, and compression begins
when a tooth of a star rotor enters and seals the groove in the helical rotor. As rotation
continues, the tooth follows the path of the groove, reducing the space occupied by the
air with a corresponding rise in pressure. When the discharge port is reached, the com-
pressed air is discharged as illustrated in Figure 3-8. The two gate, or star, rotors allow
compression to take place simultaneously on both sides of the helical rotor and main-
tain axial balance of the helical rotor, but axial force is exerted on each gate rotor.
3-10
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Star
Screw
Star
Screw
Star
Screw
Figure 3-8
Operation of a Rotary Single Screw Compressor
(Source: Grimmerschmidt Corporation)
3-11
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
As with the conventional rotary screw compressor, oil is injected into the compression
chamber to lubricate, seal, and take away the heat of compression. A mixture of com-
pressed air and injected oil leaves the air end of the compressor and is passed to a
sump/separator where the oil is removed from the compressed air. Directional and
velocity changes are used to separate most of the liquid. The remaining aerosols in the
compressed air then are separated by a coalescing filter, resulting in only a few parts
per million of oil carryover. Most oil-injected rotary screw compressor packages use the
air pressure in the oil sump/separator, after the discharge of the air end, to circulate the
oil through a filter and cooler prior to re-injection into the compression chamber. Some
designs use an oil pump.
Oil-injected rotary single screw compressor packages are available from 20–150 hp and
capacities from 62–700 cfm (1.8–19.8 cm/m) and pressures to 150 psig (10.34 bars).
The basic design consists of a circular stator in which is housed a cylindrical rotor,
smaller than the stator bore and supported eccentrically in it. The rotor has radial
(sometimes off-set) slots in which vanes, or blades, slide. Rotation of the rotor exerts
centrifugal force on the vanes, causing them to slide out to contact the bore of the stator,
forming “cells” bounded by the rotor, adjacent vanes, and the stator bore. Some designs
have means of restraining the vanes so that a minimal clearance is maintained between
the vanes and the stator bore.
Inlet
Discharge
Figure 3-9
Oil-Injected Rotary Sliding Vane Compressor
(Source: CAGI)
3-12
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
An inlet port is positioned to allow air to flow into each cell exposed to the port, filling
each cell by the time it reaches its maximum volume. After passing the inlet port, the
size of the cell is reduced as rotation continues, as each vane is pushed back into its slot
in the rotor. Compression continues until the discharge port is reached, when the com-
pressed air is discharged.
Similar to the oil-flooded rotary screw compressor, oil is injected into the compression
chamber to lubricate, seal, and take away the heat of compression. Single and two stage
versions are available with either in-line or over-under arrangement of the stages.
A ring of liquid is swirled around the bore of the stator as the rotor turns. The depth of
penetration of each vane, or blade, into the liquid varies as rotation occurs. The space
between the rotor hub and the liquid ring therefore varies. Axial inlet porting allows air
to fill the space between adjacent vanes up to its maximum volume. Further rotation
then causes the space to be reduced and compression to occur until the discharge port is
reached when the compressed air is discharged. This is illustrated in Figure 3-10. The
liquid ring also serves to remove the heat of compression. The lubricated bearings are
external to the compression chamber and isolated from it, so oil-free compression is
obtained.
This type of design is used most commonly as a single stage vacuum pump to generate
up to 26 in. (66 cm) Hg. Two stage units can achieve higher vacuum levels. Capacities
range from 2–16,000 actual cubic feet per minute (acfm) (.06–450 cm/m). As a compres-
sor, it is limited to about 100 psig (6.9 bars) and is much less efficient than other rotary
positive displacement types due to the energy required to swirl the liquid in the stator.
3-13
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Figure 3-10
Liquid Ring Rotary Compressor
Demand for compressed air seldom exactly matches the output from the compressor, so
some form of capacity control is essential. The type of capacity control is based on both
the type and size of air compressor, the application, and the number of compressors in
the system. Typical capacity control systems are described here.
An air receiver is essential to prevent too frequent starting and stopping, which affects
the life of the motor insulation due to high inrush current at each start. This type of
control normally is limited to compressors in the 30 hp and under range. The advantage
of this type of control is that power is used only while the compressor is running, but
this is offset by having to compress to a higher receiver pressure to allow air to be
drawn from the receiver while the compressor is stopped.
3-14
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
On rotary air compressors, when the upper pressure setting is reached, the pressure
switch sends a signal to open a blowdown valve that is installed in a line coming from
the compressor discharge but prior to a discharge check valve. When the blowdown
valve is opened, the compressor discharge pressure is lowered, and the discharge check
valve prevents back flow from the system or receiver. The lower discharge pressure
reduces energy requirements.
At the same time, the signal from the pressure switch also is arranged to close a valve at
the inlet of the compressor, reducing the mass flow of air entering the compressor,
further reducing power requirements although the pressure ratio across the compressor
does increase. In the case of oil-injected rotary compressors, the rate of blowdown must
be limited to prevent foaming of the lubricant in the sump/separator. In oil-free rotary
compressors, this is the most common type of control, and it requires an adequate
receiver or system volume to prevent too frequent operation.
On liquid ring compressors, when the upper pressure setting is reached, the pressure
switch sends a signal to open a valve in the recirculation line from the moisture separa-
tor back to the compressor suction, which unloads the compressor. When this occurs,
the discharge check valve closes and isolates the system receiver from the moisture
separator. There is an orifice in the recirculation line that maintains moisture separator
pressure high enough to provide sufficient differential pressure across the seal water
heat exchanger and compressor to provide adequate seal water flow while in the un-
loaded condition for cooling.
3-15
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Because the pressure at the compressor inlet is reduced while discharge pressure is
rising slightly, the compression ratios are increased so that energy savings are some-
what limited. Inlet valve modulation normally is limited to the range from 100% to
about 40% of rated capacity, at which point the discharge pressure has reached full load
pressure plus 10 psi (0.67 bars) and it is assumed that demand is insufficient to require
continued air discharge to the system. At this point, the compressor is unloaded as
previously described in Load/Unload Control.
speeds, requiring an increase in torque. Electric motors and controllers currently are
available to satisfy these needs but their efficiency and power factor at reduced speeds
must be taken into consideration. Steam turbines and engines also are variable speed
drivers but rarely are used in power plants.
3.4 Instrumentation
Discharge pressure and temperature indicators are essential for monitoring operating
conditions, but additional indicators and safety feature also are required, including a
pressure relief valve prior to any shutoff valve or discharge check valve. Normally, on
rotary air compressors, this is part of the sump/separator design. A high temperature
shutdown device also is required at the discharge from the compressor air end.
Maintenance indicators also are desirable for the air inlet filter, air/oil separator, and oil
filter. Except on the smallest compressors, conventional pressure and temperature
gauges and electromechanical devices have been superseded by solid state or micropro-
cessor controls that offer several additional features and benefits. Generally, they have
an LCD or LED display with appropriate messages and a schematic diagram on the
panel so that components and status are readily identified. A communication port
(RS232 or RS485) allows two-way communication with other compressor panels or
computer systems.
A dynamic air compressor has a continuously flowing air stream that has velocity
energy, or kinetic energy, imparted to it by an impeller, or impellers, which rotate at
speeds that can exceed 50,000 rpm. Approximately half of the pressure energy is devel-
oped in the impeller with the other half achieved by converting the velocity energy to
pressure energy as the air speed is reduced in a diffuser and volute. The most common
is the centrifugal air compressor with from two to four stages for pressures in the 100–
125 psig (6.9–8.62 bars) range. A typical multi-stage dynamic air compressor is shown in
Figure 3-11. A water-cooled intercooler and separator between each stage returns the air
temperature to approximately ambient temperature and removes condensed moisture
before entering the next stage. An aftercooler and separator cools the air from the final
stage and removes more moisture prior to air delivery to distribution.
3-17
3-18
Stage 3
Optional Lube Heater
(not shown)
Water Out
Water In
Oil Cooler
Reservoir
Oil Filter
Intercoolers Stage 1
Guide Vanes
Figure 3-11
Typical Multi-Stage Centrifugal Air Compressor
(Source: Cooper Turbocompressor, Inc.)
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
The inherent characteristic of the centrifugal air compressor is that discharge pressure
falls as capacity increases, as shown in Figure 3-12. The steepness of the pressure head/
capacity curve is dependent upon the impeller design. The more the impeller blades
lean backward from the true radial position, the steeper the curve.
210.
190.
90˚F Day
170. (Rated Conditions)
150.
PSIG
130.
110.
90.
A
B
70.
C
50.
600. 800. 1000. 1200. 1400. 1600. 1800.
SCFM
Figure 3-12
Characteristic Curves for a Centrifugal Air Compressor at 90°F
(Source: Cooper Turbocompressor)
3-19
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Most standard centrifugal air compressor packages are designed for an ambient tem-
perature of 90°F (32.2°C) and near sea-level barometric pressure. The dynamic nature of
the centrifugal compressor results in the pressure head generated by each impeller
increasing as the air density increases. The compressor mass flow and actual cfm capac-
ity at a given discharge pressure increase as the ambient temperature decreases as
shown in Figure 3-13.
210.
60˚F Day
190.
170.
150. Maximum
60˚F Day
Capacity
Is 1380 SCFM
PSIG
130.
110.
90. A
C B
70.
50.
600. 800. 1000. 1200. 1400. 1600. 1800.
SCFM
Figure 3-13
Characteristic Curves for a Centrifugal Air Compressor at 60°F
(Source: Cooper Turbocompressor)
Typically, a capacity control system is provided with the compressor to maintain the
desired capacity and to operate within the motor horsepower limits. The control system
regulates the air flow by means of an inlet throttle valve or inlet guide vanes. The
amount of reduction in the flow rate is limited by a minimum point flow reversal phe-
nomenon known as “surge.” Control systems normally unload the compressor to avoid
this occurrence, which could result in excessive vibration and potential damage to the
compressor.
3-20
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Centrifugal air compressors range from around 500 to over 100,000 acfm (14.1–2831.7
cm/m), but the more common instrument air compressors are from 1,000 to 5,000 acfm
(28.3–141.6 cm/m) with discharge pressures up to 125 psig (8.62 bars). These may have
several impellers in line on a single shaft or with separate impellers integrally geared as
shown in Figure 3-14.
3rd Stage
2nd Stage
1st Stage
Figure 3-14
Centrifugal Air Compressor—Integrally Geared Multiple Impellers
(Source: Cooper Turbocompressor)
Centrifugal air compressors provide oil-free air delivery because there is no oil in the
compression chambers. Lubrication, for speed increasing gears and the special high-
speed shaft bearings, is kept away from the compression chambers by shaft seals that
may also have air purge and vent connections.
3-21
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Centrifugal air compressors are high speed rotating machines, and as such, shaft vibration
monitoring is mandated to record operational trends and protect the equipment. Auto-
matic control of the compressors is typical and has been greatly improved by the use of
microprocessors that monitor the pressure/capacity/temperature characteristics as well
as main drive motor current draw. It is important that the manufacturer’s recommended
maintenance procedures be followed and that certain maintenance procedures be carried
out by factory-qualified staff. This is particularly true of attempts to remove an impeller
from its shaft because special procedures and tools may be involved.
Oil-injected rotary compressors generally use the pressure differential between dis-
charge and inlet to circulate the lubricant for the bearings, any gears, and for the com-
pression chamber. Some designs utilize an oil pump.
3-22
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
(15)
Compressor
Gear Box
D
Gravity
Return
(1) (2) (9) To Tank
(14)
Main Auxiliary
Power Power
Supply Supply
Figure 3-15
Pressure Lubrication System for an Air Compressor
3.6.1 Lubricants
Lubricants vary from a straight hydrocarbon mineral oil to sophisticated synthetics. Oil
types should never be mixed or changed without the approval of the compressor manu-
facturer. A lubricant that meets the specifications of the compressor manufacturer
should be used at all times and changed at the specified intervals.
It is estimated that the useful life of a lubricating oil is halved for every 18°F above
200°F (10°C above 93°C) of operating temperature. Compressors operating in high
ambient conditions need to have the oil checked frequently, and a quarterly sampling
and analysis program is recommended. For additional details on compressor lubricants,
refer to the EPRI Lubrication Guide, NP-4916, Revision 2.
3-23
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Taking the estimated full load brake horsepower (bhp) requirement of each compressor
type at 100 psig (6.89 bars) discharge pressure at the compressor, a main drive motor
typical efficiency of 92% and 0.746 kW/bhp, the following approximate costs of opera-
tion are obtained:
These costs are based upon the discharge pressure at the compressor, not at the points
of use and are at full load operating conditions. In most cases, reduced capacity require-
ments result in operation at a reduced efficiency and increased power requirement.
Disadvantages include:
• Oil carryover (which should be avoided in instrument air systems)
• Relatively high cost of compression
3-24
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Disadvantages include:
• Relatively high first cost compared with equivalent rotary air compressors
• Relatively high space requirements
• Seldom sold as complete independent package
• Relatively high vibrations require high foundation costs
• Require sufficient flywheel mass to overcome torque and current pulsations
Disadvantages include:
• Less efficient full and part load operation compared with water-cooled reciprocating
air compressors
• Oil carryover into delivered air requires proper maintenance of air/oil separator and
the oil itself.
3-25
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Disadvantages include:
• Significant premium over oil-injected type
• Less efficient than oil-injected type
• Limited to load/unload type capacity control
• Higher maintenance costs than oil-injected type
Disadvantages include:
• Less efficient at full and part load operation compared with water-cooled reciprocat-
ing air compressors
Disadvantages include:
• Less efficient full and part load operation compared with water-cooled reciprocating
air compressors
• Less efficient than equivalent oil-injected rotary screw type
3-26
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
Disadvantages include:
• Designed mainly for vacuum service. Very inefficient as an air compressor.
• Much less efficient than equivalent oil-injected rotary screw type
• Does not offer good part load capacity control
Disadvantages include:
• Limited capacity control modulation, requiring unloading for reduced capacities
• High rotational speeds require special bearings, sophisticated monitoring of vibra-
tions and clearances
• Specialized maintenance considerations
Selection of air compressors must take into account the requirements of the different
points of use, the air capacity for each when fully loaded, and the frequency of these
requirements. Demands often are intermittent but the “worst case scenario” also must
be considered. Standby compressor capacity also must be considered, taking into ac-
count the essential nature of an application and the cost of downtime compared with
the cost of a spare compressor.
The capacity required is a major factor in determining the type of compressor chosen. A
general rule is that centrifugal and rotary air compressors are better suited to continu-
ous base-load type of service. Reciprocating air compressors are better suited to swings
in loads. This means that a centrifugal or rotary air compressor can be sized for the
minimum or average demand, while a reciprocating air compressor then can handle the
swings in load from minimum or average to the peaks. The anticipated load swings also
are a determining factor in the selection of a single compressor and its type of capacity
control or multiple compressors with sequential controls.
3-27
EPRI Licensed Material
Compressed Air Production (Compressors and Accessories)
The need for truly oil-free air also influences the type of compressors required. To
maintain the ISA standard of instrument air quality in a nuclear power station, it is
recommended that oil-free air compressors should be specified. If the air supply is
obtained from lubricated air compressors, it must be treated with coalescing filters and
rigorously monitored to achieve the required quality.
Breathing air must meet Occupation Safety and Health Act (OSHA) regulations and
specialized air treatment filtration packages are manufactured for this specific purpose.
These involve not only the contaminant levels of particulate, moisture, and oil but also
NOX (nitrogen oxides). In some cases, the air is supplied to the special filtration package
from the general plant compressed air system, while in others, a separate breathing air
supply is provided. See Section 6.3 for further details.
3-28
EPRI Licensed Material
4
COMPRESSED AIR TREATMENT
(DRYERS AND FILTERS)
(Adapted from text prepared on air dryers and filtration for The Compressed Air and
Gas Institute)
Compressed air leaving an air compressor is not normally of a quality suitable for the
intended use. This is due to several factors. Atmospheric air, particularly in an indus-
trial environment, contains pollutants that include moisture, particulate, and hydrocar-
bons. The air inlet filter on an air compressor is a particulate filter, designed to protect
the compressor rather than any downstream equipment, and it may not be sufficiently
fine for the equipment using the compressed air. The air compressor itself can contrib-
ute contaminants in the form of wear particles and the carryover of the compressor
lubricant. The discharge temperature from the compressor may be too high for distribu-
tion and use.
Cooling after compression results in condensation of moisture and saturated air leaving
the aftercooler. This can have a serious effect upon instruments, pneumatic tools, spray
painting, and other applications. Such cooling can occur not only in an aftercooler but in
the compressed air distribution system by radiation from air receivers and piping ex-
posed to relatively cold atmospheric conditions. Freezing of the condensate also can
occur.
Generally, it is not recognized how large a volume of water needs to be removed during
the process of compressing and cooling of air. The following example is used to give an
idea of the quantity of water handled through the intercoolers and aftercoolers during
the compression process. Table 4-1 shows the moisture content of saturated air in gal-
lons per 1000 cubic feet of air at various temperatures and pressures.
4-1
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Table 4-1
Moisture Content of Saturated Air in Gallons per 1000 Standard Cubic Feet
Temperature, °F
PSIG 35 40 50 60 70 80 90 100 110 120
0 .0392 .0479 .0702 .1016 .1450 .2046 .2857 .3956 .5443 .7460
10 .0233 .0283 .0416 .0600 .0854 .1200 .1667 .2290 .3119 .4217
20 .0165 .0201 .0295 .0426 .0605 .0849 .1176 .1612 .2186 .2939
30 .0128 .0156 .0229 .0330 .0469 .0657 .0909 .1243 .1682 .2256
40 .0105 .0128 .0187 .0269 .0383 .0536 .0741 .1012 .1367 .1830
50 .0089 .0108 .0158 .0228 .0323 .0452 .0625 .0853 .1152 .1540
60 .0077 .0093 .0137 .0197 .0280 .0391 .0540 .0737 .0995 .1329
70 .0068 .0082 .0121 .0174 .0246 .0345 .0476 .0649 .0876 .1169
80 .0060 .0074 .0108 .0155 .0220 .0308 .0425 .0580 .0782 .1043
90 .0055 .0067 .0098 .0140 .0199 .0279 .0385 .0524 .0706 .0942
100 .0050 .0061 .0089 .0128 .0182 .0254 .0351 .0478 .0644 .0858
110 .0046 .0056 .0082 .0118 .0167 .0234 .0323 .0439 .0592 .0789
120 .0043 .0052 .0076 .0109 .0155 .0216 .0298 .0407 .0548 .0729
130 .0040 .0048 .0071 .0102 .0144 .0201 .0278 .0378 .0509 .0678
140 .0037 .0045 .0066 .0095 .0135 .0188 .0260 .0354 .0476 .0634
150 .0035 .0042 .0062 .0089 .0126 .0177 .0244 .0332 .0447 .0595
160 .0033 .0040 .0058 .0084 .0119 .0167 .0230 .0313 .0421 .0561
170 .0031 .0038 .0055 .0080 .0113 .0158 .0217 .0296 .0398 .0530
180 .0029 .0036 .0052 .0075 .0107 .0149 .0206 .0281 .0378 .0503
190 .0028 .0034 .0050 .0072 .0102 .0142 .0196 .0267 .0359 .0478
200 .0027 .0032 .0048 .0068 .0097 .0136 .0187 .0254 .0342 .0455
Notes:
To convert the above data into SI units, use the following conversion factors:
1.0 psi (lbs/sq. in.) = 0.06895 bars
°C = 5/9 x (°F - 32°)
1.0 U.S. gallon = 3.7854 liters
1000 cubic feet = 28.32 cubic meters
4-2
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
From the foregoing, the need for removing moisture from the compressed air is obvi-
ous. All liquid must be removed before the compressed air enters the dryer. This can be
accomplished by installing a suitable moisture separator and/or a coalescing filter, each
with a drain trap. Moisture content in air more than doubles from 0°F to 20°F (-17.8 to
-6.7°C), and continues to double for each increase of 20°F or 10°C (see Table 4-1). A
refrigerant dryer can achieve a pressure point of 35°F to 40°F (1.7°C to 4.4°C) and cannot
maintain the quality of instrument air required in a power plant. Routine checks and
maintenance of dryers and drain traps are essential because a malfunctioning dryer of
any type and associated drain traps can allow moist air to enter the distribution system.
Different types of compressed air dryers are available, each having different characteris-
tics and degrees of dew point suppression. Liquid moisture must be removed before the
air enters the dryer. This can be accomplished with a moisture separator and/or a
coalescing filter. Most dryers are rated at what is commonly referred to as the three
100s, that is, 100 psig, 100°F, and 100% relative humidity (saturated air). An increase in
operating pressure (within the capability of the dryer) increases the rated mass flow or
standard cubic feet per minute (scfm) capacity, while an increase in inlet temperature
(within the capability of the dryer) decreases the rated mass flow or scfm capacity due
to the higher moisture content at a saturated condition. Typical capacity correction
factors are given in Table 4-2.
Table 4-2
Pressure and Temperature Correction Factors for Compressed Air Dryers
4-3
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Precoolers (A)
Dry Air Outlet
Dry Air
Moisture
Temperature Separator
Sensor Moist Air (C)
Moist Air
Evaporator (B)
Chiller Section
Temperature
Control Valve
Hot Gas
Bypass Valve
Unit
Fan Cooling
Coils
Refrigeration
Compressor
To Drain
Trap (D)
Figure 4-1
Refrigerant Dryer
The pressure dew point of this type of dryer, therefore, is 35°F (1.7°C). This is equiva-
lent to a dew point of -10°F (-23.3°C) at atmospheric conditions (see Figure 4-2). The
estimated operational cost, excluding the effect of pressure drop through the dryer, is
0.54 kW/100 cfm (0.2 kW/cm/m).
4-4
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
140
130
120
110
100
90
0
80
G
SI
80
,P
00
0
re
10
50
su
70
es
0
Pr
0
40
25
60
15
60
0
0
20
00
30
80 1
50
60
30
ere
20
40
ph
os 20
m
At
10
10
-10
-20
-30
-40
-50
-60
-70
-80
-90
-100
-120 -100 -90 -80 -70 -60 -50 -40 -30 -20 -10 0 10 20 30 40 50 60 70 80 90 100
To obtain the dew point temperature expected if the gas were expanded to a lower pressure
proceed as follows:
1. Using “dew point at pressure,” locate this temperature on the scale at the right side of the
chart. 2. Read horizontally to the intersection of the curve corresponding to the operating
pressure at which the gas was dried. 3. From that point, read vertically downward to the
curve corresponding to the expanded lower pressure. 4. From that point, read horizontally
to the scale on the right side of the chart to obtain dew point temperature at the expanded
lower pressure. 5. If dew point temperatures at atmospheric pressure are desired, after step
2 above, read vertically downward to the scale at the bottom of chart which gives “dew point
at atmospheric pressure.”
Figure 4-2
Atmospheric vs. Pressure Dew Point Conversion Chart
4-5
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Normally the desiccant is contained in two separate towers as shown in Figures 4-3a
and 4-3b. Compressed air to be dried flows through one tower, while the desiccant in
the other is being regenerated. Regeneration is accomplished by reducing the pressure
in the tower and passing previously dried purge air through the desiccant bed. The
purge air may also be heated to reduce the amount of purge air required. Dryers of this
type normally have a built-in regeneration cycle, which can be based upon time, dew
point, or a combination of the two.
Orifice Orifice
Left Right
S S Tower
Tower
(B) (B)
Control
Panel
Temperature
Indicator
Left Moisture Right
Tower Indicator Tower
Heater Heater
(D) (D)
(C)
Figure 4-3a
Heat Regenerative Desiccant Dryer
4-6
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
through the dryer, reducing the air flow available to the system from the compressor by
this amount. Estimated operating cost, excluding pressure drop through the dryer, is
1.8–2.7 kW/100 cfm (.063–.095 kW/cm/m).
Control Air
Isolation
Valve
Moisture Right
Left Indicator
Tower Dryer Tower
(B) Outlet (B)
(C)
Dryer
Control
Panel
Moisture Moisture
Probe (E) Probe (E)
Inlet Air
Switching
Valve (A)
Tower Tower
Depressurizing S S Depressurizing
Valve Valve
Purge
Muffler (D) Dryer
Inlet
Figure 4-3b
Heatless Regenerative Desiccant Dryer
Deliquescent dryers normally have a design dew point suppression of 20–36°F (-6.7 to
+2.2°C) below an inlet temperature of 100°F (37.8°C), providing a pressure dew point at
100 psig (6.9 bars) of 80–64°F (26.7–17.8°C). Deliquescent dryers are sensitive to the
saturated air inlet temperature; the lower the inlet temperature, the lesser the dew point
suppression. They also are limited to a maximum inlet temperature of 100°F (37.8°C).
Because the drying medium is consumed and not regenerated, there is no requirement
for purge air; therefore, pressure drop through the dryer (and any associated filtration)
and loss of air volume during the drain cycle are the operating costs that are estimated
at 0.2 kW/100 cfm (0.07 kW/cm/m).
4-7
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Dry
Air
Out
Wet
Air
In
Figure 4-4
Deliquescent Dryer
(Source: Hankison International)
A portion of the hot air taken directly from the air compressor at its discharge, prior to
the aftercooler, flows through the opposite side of the dryer drum (c) to regenerate the
desiccant bed. The hot air, after being used for regeneration (d), passes through a regen-
eration cooler before being combined with the main air stream by means of an ejector
nozzle before entering the dryer. This means that there is no loss of purge air. Drying
and regeneration cycles are continuous as long as the air compressor is in operation.
This type of dryer requires air from the compressor at sufficiently high temperature to
accomplish regeneration. For this reason, it is used almost exclusively with oil-free
rotary screw compressors.
4-8
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Drum
Rotation
Figure 4-5
Heat of Compression-Type Dryers
(Source: Atlas Copco Compressors Inc.)
Technically, there is no reduction of air capacity with this type of dryer. However, an
inefficient entrainment-type nozzle has to be used for the purge air, and an electric
motor also is used to rotate the dryer drum. Considering pressure drop and compressor
operating cost, it is estimated that the total power requirement is approximately 0.8
kW/100 cfm (0.3 kW/cm/m).
4-9
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
4.1.5 Desiccants
The most commonly used desiccants are:
• Silica gel
• Activated alumina
• Molecular sieve
Silica gel is available in both granular and beaded form. In beaded form, it has high
resistance to attrition and produces little or no fines. Silica gel’s ability to achieve -40°F
(-40°C) dew point at 100–125 psig (6.9–8.62 bars) line pressure and its low regeneration
temperatures make it an extremely cost-effective medium for instrument air drying
applications.
Lower dew points can be obtained at less cost using activated alumina; however, it is
susceptible to a greater percentage of fines and requires a slightly higher regeneration
temperature.
Molecular sieve has the capability to adsorb small molecules while excluding the large
ones. Therefore, it should be used only as a polishing or trimming agent in a mixed bed
operation. Use of molecular sieve as a primary agent may not remove sufficient mois-
ture in dryers with small desiccant capacities. Also, the regeneration temperature for
molecular sieve is higher than for silica gel or activated alumina. Table 4-3 shows the
various desiccant types available and the reason to use each type.
4-10
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Table 4-3
Desiccant Types and Application
4-11
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Water Vapor
Out
Compressed Compressed
Air Out Air In
Figure 4-6
Membrane-Type Dryers
(Source: Hankison International)
Typically, the pressure drop through a compressed air dryer is 3–5 psig (0.2–0.34 bars)
and should be taken into account in system requirements.
A refrigerant-type dryer does not require a filter before or after it, but a desiccant- or
deliquescent-type dryer requires a prefilter to protect the drying medium or desiccant
from contamination and from being rendered ineffective. An after-filter also is required
to catch desiccant fines from being carried downstream to sensitive equipment.
The Nominal Rating is determined by the filter manufacturer and is an arbitrary value.
Usually it is a percentage retention by weight of a specified contaminant of a given size.
4-12
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Glass beads are the normal test contaminant. The only known related standards are
MIL-E5504A and MIL-5504B, where the retention rate is based upon 10 microns and 10–
20 microns respectively. This is too large for instrument air quality.
The Beta Ratio is designed to give a more accurate comparison among filter media. It is
described in Note b under Table 4.4.
4-13
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Mechanisms of Air/Gas
Filtration
Mechanisms of Filtration
Direct impaction occurs when a particle collides with a fiber of the filter medium without
deviating out of the streamline flow. This mechanism tends to take place on the surface of
the filter material, affecting mainly the larger particles, over 1 micron in size.
Inertial impaction occurs when a particle traveling in the air stream through the maze of
filter fibers, is unable to stay within the air stream and collides with a fiber and adheres to
it. This occurs normally in particles from 0.3 to 1.0 microns in size.
Diffusion, or Brownian movement, occurs with the smallest particles below 0.3 microns,
which tend to wander through the filter medium within the gas stream, increasing their
chances of colliding with and adhering to a fiber.
Figure 4-7
Mechanisms of Air/Gas Filtration
(Source: domnick-hunter, inc.)
Pressure drop increase in a coalescing filter is normally due to particulate matter foul-
ing the element. The coalescing filter should be preceded by a particulate filter.
The rated pressure drop should be the “wet” pressure drop after the element has be-
come saturated. A coalescing filter is recommended before any dryer whose drying
medium may be damaged by lubricant. Materials should be compatible with the type of
lubricant being used.
4-14
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Pre-Filter
Medium
Coalescing
Filter
Medium
Figure 4-8
Coalescing Filter
(Source: domnick-hunter, inc.)
4-15
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Figure 4-9
Adsorption Filter
(Source: domnick-hunter, inc.)
4-16
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
The amount of condensate will vary with geographic location and atmospheric condi-
tions of temperature and relative humidity. Drain traps should be sized for the antici-
pated rate of accumulated condensate and chosen for the specific location and antici-
pated contamination by lubricants being used.
The float is connected by linkage to a drain valve that opens when an upper level set-
ting is reached and closes when the drain is emptied. The float device varies from a
simple ball to an inverted bucket, but the basic principle is the same. An adequately
sized drain valve is essential for satisfactory operation and to prevent blockage. A float
that sticks in the closed position does not allow condensate to be drained, while a float
that sticks in the open position allows the costly loss of compressed air. A float-type
trap is shown in Figure 4-10.
Figure 4-10
Float-Type Drain Trap
(Source: Ultrafilter International)
Condensate enters through the trap inlet (1) and is collected in the vessel (2). The float (3)
rises with the level until the control valve (4) opens and pressurizes the surge chamber (5).
The air pressure on the diaphragm (6) moves the piston (7) to open the diaphragm (8).
Now the condensate drains through the outlet (11) via the passages (9) and (10).
4-17
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
The potential problem with this type of device, apart from an electrical malfunction, is
that the valve is set to operate without reference to the presence of condensate, or lack
of it. The period during which the valve is open may not be long enough for adequate
drainage of the amount of accumulated condensate. On the other hand, the valve can
operate even when little or no condensate is present, resulting in the expensive loss of
compressed air through the drain valve.
Figure 4-11a
Solenoid-Operated Drain Valve
(Source: Pneumatech, Inc.)
Some electrically operated drain valves use a magnetic reed switch or a capacitance
device to detect the level of condensate present and operate only when drainage is
called for. A drain valve of this type is shown in Figure 4-11b.
4-18
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Outlet Connection
Solenoid
Discharge
Valve
Inlet Connection
HOW IT WORKS:
Condensate enters the drain collection bowl under pressure
through one of the three inlet ports. At this stage, a pilot supply
line ensures that the air pressure above the valve diaphragm 3
(3) retains the valve in the closed position.
After the condensate has filled the collection bowl to the upper
level probe sensor (2), it will signal the solenoid to open the pilot
supply line. This enables the air pressure above the valve
diaphragm to vent, allowing the diaphragm to lift from the valve
seat. The pressure in the drain collection bowl discharges the
condensate up to the dip tube (5) past the diaphragm and out
through one of the two outlet ports.
As condensate discharges from the drain collection bowl, the 2
lower level probe sensor (1) will signal the solenoid to close the 1
pilot line before any compressed air can escape from the system.
At the bottom of the drain collection bowl, the weir (4) prevents 5
large dirt particles from entering the dip tube and blocking the
drain outlet. 4
Figure 4-11b
Electronically Controlled Drain Trap
(Source: domnick-hunter, inc.)
4-19
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
From the example of moisture content of compressed air given earlier in this section, it
is easy to see why it is vital to maintain traps and drains in good operating condition. If
the drains and traps are clogged, the cooler shells fill up with condensate in a short
period of time, and the condensate is carried over into the system in the form of liquid
water droplets. These droplets may:
• Deposit in the receiver and cause corrosion of the tank walls and bottom.
• Prematurely exhaust the capacities of prefilters and desiccant dryers.
• Overload refrigerant-type dryers.
• Cause moisture accumulation in the system piping, resulting in corrosion. Some of
the system piping may be installed outdoors and exposed to varying ambient tem-
peratures. Accumulated water may freeze during winter and cause damage to
piping and instruments.
• Cause malfunction of air-operated valves (sluggish or erratic). Wash away lubricants
from operating cylinders of air-operated valves or other similar equipment.
• Cause some of the lubricants used on solenoid valve O-rings to become sticky or
gummed up, causing the solenoid valve to become inoperable.
Air quality better than the atmospheric air entering the air compressor can be obtained
with a combination of all three filter types. Instrument air quality specified by the
American National Standards Institute and the Instrument Society of America in Stan-
dard ANSI/ISA-S7.0.01-1996 is summarized below. This may be cited or changed by
different manufacturers.
Particulate - no particles larger then 40 microns (met by ISO 8573.1 Class 5). Pneumatic
devices that require instrument air with less than 40 micrometer particle sizes shall have
additional filtration to meet the particulate size limit for the device.
Dew Point - at line pressure at least 18°F below the lowest expected ambient tempera-
ture and in no case higher than 39°F (met by ISO 8573.1 Class 4 and for low ambient
temperatures by Class 2).
Hydrocarbons - less than 1 ppm hydrocarbon contamination (met by ISO 8573.1 Class 3).
ISO 8573.1 Class 5.4.3 combines the requirement of all the above classes.
Air quality classes have been established in an International Standard ISO 8573-1 and
are shown in Table 4-4.
4-20
EPRI Licensed Material
Compressed Air Treatment (Dryers and Filters)
Table 4-4
Air Quality per ISO 8573.1
Notes:
a Number of air classes for each contaminant is not the same due to widely varied requirements of
compressed air applications.
b Particle size based on a filtration ratio βµ=20. The so called “Beta Ratio” is the ratio of the number of
particles larger than a given micron size upstream of the filter to the number of particles larger than the
given size downstream of the filter. The higher the Beta Ratio, the more particles are retained by the filter
and, hence, the higher the efficiency.
c At 1 bar (14.5 psia), 20 °C (68°F) and a relative humidity of 60%.
d Oil concentration at 1.0 bar (14.5 psia), 20 °C (68°F) and a relative humidity of 60%.
e 1.0 mg by weight of oil in 1.0 cu. m volume of air is approximately equal to 0.83 ppm by weight.
Air samples can be analyzed to determine the air quality in regard to moisture, oil, and
other foreign particles. Also analysis of particles from downstream filters can be used to
determine the nature and source of these particles. Microscopic comparison can be
made with particles displayed on wall charts. Fourier-transform infrared (FTIR) analy-
sis can be used to compare with spectra of bonding found in typical materials.
4-21
EPRI Licensed Material
5
COMPRESSED AIR DISTRIBUTION SYSTEM
The basic purpose of a compressed air distribution system is to transport the com-
pressed air from its point of production (compressors), through treatment (dryers and
filters), to its points of use (applications) in sufficient quantity and quality and at ad-
equate pressure for efficient operation of each application.
Ideally, the air compressor should be located as close as possible to the point of use of
the compressed air. This is not always feasible and other factors must be considered.
The location of the compressors chosen must take into account the type of cooling
required. Air cooled compressors eliminate the need for expensive cooling water and
drainage costs. Large radiator-type coolers located outdoors in cold climates also can
present the problems of oil temperature, oil viscosity at start-up when the compressor is
idle overnight, and freezing of condensate from the compressed air aftercooler. Immer-
sion heaters and frost-free traps are readily available. It is recommended that outside
radiators be located adjacent to a North-facing wall to minimize the heating effect of
direct sunlight. The compressor room should be well ventilated.
The location of the point at which air is drawn in from outside is extremely important.
This should avoid the potential of exhaust fumes from other sources, including, but not
limited to, emergency diesel engines. Inlet air to the compressor from the compressor
room may be using air that has been air conditioned at a significant cost. The tempera-
ture within a compressor room may also be higher than the outside ambient tempera-
ture and will reduce the mass flow of air through the compressor. Air drawn from
outside the compressor room should be from a location where contaminants from an
industrial atmosphere will not be a problem. The compressor air inlet filter also must be
readily accessible for regular routine maintenance.
When the air compressor inlet filter is mounted remotely from the compressor, the
piping from the air inlet filter to the compressor inlet must be clean and non-corrosive
and may be of plastic material. As previously stated, the air compressor inlet filter is for
the protection of the compressor and not for any equipment downstream.
5-1
EPRI Licensed Material
Compressed Air Distribution System
This has been mentioned relative to the location of the air dryer. Other factors also must
be considered. It is common for an air receiver to be close to the air compressor. This
has the advantage of allowing the air receiver to act as a buffer against pressure pulsa-
tions from a reciprocating air compressor and provides a close location for measure-
ment of pressure for the compressor capacity control system. It also provides some
radiant cooling (unless in direct sunlight) and condensate separation due to reduced
velocities and directional changes.
The downside of this location is that it may be far removed from the points of use with
fluctuating and transient demands. A long length of piping from the air receiver to the
point of use with related valves, dryers, and filters results in pressure losses and a
significantly lower pressure at the point of use than what the compressor’s control
system is sensing at the air receiver. The pressure at the point of use may not be suffi-
cient for efficient operation.
One solution is to have primary and secondary air receivers, particularly where there
are intermittent large demands for air with a substantial recovery time between de-
mands. The secondary air receivers should be close to the point of use that has the high
intermittent demand. Compressed air management systems with intermediate pressure
regulation are available.
A general rule for an air receiver following a reciprocating air compressor has been a
volume size equivalent to three minutes of the compressor delivery volume. This means
that for an air compressor with a capacity of 1000 acfm (28.32 cm/m) at an inlet pres-
sure of 1.0 atmosphere (14.7 psia) and delivering to an air receiver at 100 psig or 114.7
psia (6.9 bars), the recommended receiver size would be: 1000 x 3 x 14.7/114.7 = 384 cu.
ft. (10.87 cu. m). The nearest standard size receiver then would be specified. This also
may be applied to an air receiver following a compressor having a start/stop or load/
5-2
EPRI Licensed Material
Compressed Air Distribution System
unload capacity control; with a compressor having modulating control, one third of this
size should be adequate.
All air receivers should meet the ASME Unfired Pressure Vessel Code and be stamped
accordingly. This also requires a suitable pressure relief valve. Federal, state, and local
codes also must be met.
Certain pieces of equipment may require a higher quality of compressed air than others.
A filter specific to the application should be installed immediately before the equip-
ment. By specifying the required air quality classes from ISO 8573.1, the supplier can
provide the necessary degree of drying and filtration.
Filters should be located where they are readily accessible for reading of differential pres-
sure and for changing of elements as necessary. Excessive pressure drop is costly in terms
of air production and can cause damage to the filter element. A very low differential pres-
sure across the filter can indicate a damaged element or improperly installed filter.
A useful rule of thumb for a typical 100 psig (6.9 bars) compressed air system is that for
every additional one psi (0.07 bars) at the compressor discharge, the power required is
increased by one-half of 1%. This means that if 100 psig( 6.9 bars) is required at the
points of use and that dryers and the piping system between the compressor and the
points of use result in a 10 psi (0.69 bars) pressure drop, the compressor discharge
pressure will rise to 110 psig (7.59 bars), and its power will rise to 105%.
The cross-sectional area of piping increases as the square of the diameter. Doubling the
diameter gives four times the area, one-fourth the velocity and one-sixteenth the pres-
sure drop. Installation of properly sized distribution piping pays ongoing dividends by
reducing pipe friction and pressure drop in the system. In addition, making the distri-
bution piping into a loop provides alternate flow directions for varying demands and
reduces pressure drop.
Distribution header piping should be arranged with a slight slope away from the com-
pressor and the air receiver. The header connection from the air receiver should be suffi-
ciently high to be above any potential liquid level in the air receiver should it not have
5-3
EPRI Licensed Material
Compressed Air Distribution System
been properly drained. Drop legs from headers should be included with traps for conden-
sate removal. Properly located and maintained compressed air dryers can prevent con-
densate in headers. Piping from the header to points of use should connect to the top or
side of the header to avoid being filled with condensate and should be kept as short as
possible. Pressure drop from the header to the point of use should not exceed 1 psi (50
mm Hg) during the duty cycle. An ample number of tapped connections in the headers
and piping also allows evaluation of air pressure at points throughout the system.
Some plants have their air distribution piping near the roof of buildings, which exposes
the piping and associated valves to increased heat in summer conditions. On the other
hand, distribution piping may run between buildings and be exposed to direct sunlight
in the summer and extreme cold in the winter. Piping must be adequately supported
and must allow for thermal expansion.
Ideally, piping should be corrosion free to eliminate corrosion particles that can block
orifices, instruments, and valves and to avoid deterioration of the pipe itself. Stainless
steel obviously has its advantages but can be very costly to install. Galvanized steel pipe
is a common compromise. Copper tubing has been used, but joints may have pressure
limitations, and the maximum possible pressure and temperature conditions must be
taken into consideration. Copper also has a relatively high rate of thermal expansion.
As previously stated, air piping from the header to the point of use should be taken
from the top of the header to prevent the inclusion of condensate.
5-4
EPRI Licensed Material
6
APPLICATIONS (POINTS OF USE)
Compressed air has applications in almost all industries from ore mining through
sophisticated finished products, from aircraft to automobiles. It also is used widely in
producing food and beverages, in pharmaceutical and electronic applications, and in
processing and packaging. It is used for motive power, process functions, and control
functions. It also is used widely in plant maintenance. Its uses keep growing.
Fossil power plants use compressed air for pneumatic conveying, for soot blowing of
boilers, and for instruments and controls. Nuclear power plants use compressed air for
motive power for valves, instrument and control functions, pneumatic tools, and gen-
eral maintenance.
Pneumatic thermostats, which control the heating and air conditioning cycles in large
and small buildings, also require clean, dry air. Instruments and pneumatic controllers
in power plants need clean, dry air for efficient operation.
Clean, dry compressed air results in lower operating costs. Water, oil, and dirt en-
trained in air deposit inside pipes, fittings, and orifices, causing an increase in pressure
drop and an increase in energy used to compress the air. A reduced pressure at the
point of use results in a loss of performance efficiency.
Liquid water accelerates corrosion and can cause malfunction of valves, pressure regu-
lators, and positioners. In addition, it can shorten the useful life of equipment.
Carryover of corrosion particles can plug valves, orifices, fittings, pressure regulators,
positioners, and instrument control lines and result in their malfunctioning. Water also
can freeze in these components with similar results.
Some of the largest users of instrument air in a nuclear plant are air-operated valves
(AOVs) held open by compressed air, including main steam isolation valves and tur-
bine bypass valves.
6-1
EPRI Licensed Material
Applications (Points of Use)
Dirty, wet air can result in sluggish operation, frequent repair, and replacement of parts
due to sticking, jamming, and rusting of wearing parts. Water can also wash out the
required lubricants, resulting in excessive wear. A decrease in pressure at the tool
causes a reduction in the efficiency of the tool. Clean, dry air at the required pressure
can help to maintain productivity and prolong tool life.
Pneumatic tools should be powered by service air. The use of instrument air to power
pneumatic tools should be avoided in order to prevent sudden air demands that can
cause a drop in instrument air pressure and adversely impact instrument and control
operation, affecting the nuclear plant.
The air coming from an air compressor, whether a lubricated or oil-free type, is not
suitable for breathing. Additional conditioning or purification of the air is required
before the air can be considered suitable for breathing, and certain health and safety
standards must be met. In industrial plants, air may be supplied to respirators, hoods,
and helmets and for applications such as sandblasting. The Occupation Safety and
Health Act (OSHA) requires filtration and treatment to meet specific levels, including
carbon monoxide, with an alarm system. Special filtration and treatment packages are
available for this purpose and should be used whether the air supply is taken from the
general plant air system or from an air compressor dedicated to the supply of the air for
breathing. Other related standards for breathing air are The American National Stan-
dards Institute/compressed gas association standard ANSI/CGA-7 and the Canadian
Standards Association (CSA) standard CAN3-Z180.1-M85.
Some plants may have no air headers, except for breathing air, inside the reactor con-
tainment building. In such cases, the breathing air system will be used for service air
(for refueling tools, etc.) during a refueling outage, even if no respirators are used.
6.4 General
The optimum pressure for the efficient operation of the equipment at each point of use
should be maintained. This may vary among the various points of use and applications.
The pressure drop between the air compressor and the point of use should be taken into
account, including dryers, filters, piping, and valves.
The quality of the air for each application should also be considered. This includes
particulate matter, moisture, and oil content.
Applications having intermittent but high air flow requirements should have adequate
compressed air storage located close to the point of use to prevent an undesirable drop
in pressure.
6-2
EPRI Licensed Material
7
COMPRESSED AIR SYSTEM SAFETY:
CONSIDERATIONS AND RECOMMENDATIONS
Manufacturers have become very conscious of safety considerations, and this is re-
flected in operator’s manuals, parts lists, and warning decals applied to the machinery.
OSHA also legislates certain safety requirements for the work place, which are the
responsibility of the owner and operator rather than the manufacturer.
1. Equipment should be installed and operated in full compliance with all pertinent
OSHA, federal, state, and local regulations, codes, and standards. Each operator of
compressed air equipment should have been trained to follow the appropriate
regulations, codes, and standards and should have a copy of the operator’s manual
for each air compressor and dryer and their accessories. Each operator should read
and understand the manual and operate the equipment in accordance with it.
2. A compressor should not be started unless it is safe to do so. A compressor consid-
ered to have an unsafe condition should be tagged and rendered inoperative by
disconnecting and locking out all power to the compressor at its source until the
unsafe condition has been rectified.
3. The safety shutdown features incorporated in the compressor or dryer package
should be tested periodically for proper functioning, as specified in the operator’s
manual.
4. The maximum pressure rating of any piece of pneumatic equipment should not be
exceeded at any time. Pressure relief valves installed to safeguard against excessive
pressure build-up should be tested at specified intervals. All internal pressure
should be vented prior to opening any air line, fitting, hose, valve, drain plug, con-
nection, or component in the system.
5. Modifications to air compressors, controls, and other pneumatic equipment should
not be made without the written approval of the manufacturer.
6. The area around air compressors should be kept clean. Spills of lubricant or other
combustible or volatile substances such as cleaning fluid, paint, or solvent should be
cleaned up immediately.
7-1
EPRI Licensed Material
Compressed Air System Safety: Considerrations and Recommendations
7-2
EPRI Licensed Material
Compressed Air System Safety: Considerrations and Recommendations
15. Each location should have a formalized program of safety checks at specified inter-
vals and with appropriate responsibilities assigned for carrying out the procedure,
recording data, and monitoring safety operations.
The following questions are designed to aid power plant personnel in determining if
proper safety measures have been taken in the installation and operation of their com-
pressed air systems. If the answer to any of the following questions is No, the work
conditions should be thoroughly reviewed from the work safety point of view. They are
based on California/OSHA standards and are general in nature.
7-3
EPRI Licensed Material
Compressed Air System Safety: Considerrations and Recommendations
• Before compressed air is used to empty containers of liquid, is the safe working
pressure of the container checked?
• When compressed air is used with abrasive blast cleaning equipment, is the operat-
ing valve of a type that must be held open manually?
• When compressed air is used to inflate auto tires, are a clip-on chuck and an in-line
regulator preset to 40 psi (2.76 bars) required?
• Is it prohibited to use compressed air to clean up or move combustible dust if such
action could cause the dust to be suspended in the air and cause a fire or explosion
hazard?
7-4
EPRI Licensed Material
Compressed Air System Safety: Considerrations and Recommendations
– Before workers are permitted to enter the tank, the tank atmosphere is tested for
(a) oxygen, carbon dioxide concentrations, and (b) toxic, flammable, or combus-
tible gases and vapors.
– Respiratory equipment is required to be used (supplied-air type) if a hazardous
atmosphere is present.
– Workers entering the tank are required to be equipped with a lifeline, and a
safety watch is positioned at the tank opening.
– Workers are required to wear proper footwear, eye and face protection, and
work gloves to prevent injuries.
– Portable electric lamps or tools used inside the tank are explosion-proof and
grounded.
– After cleaning, the inside is inspected for removal of loose scale, wiping rags,
tools, or pieces of lint.
– New gaskets are placed on the manhole covers.
• Has a record been maintained of all discrepancies and have corrective actions been
taken?
7-5
EPRI Licensed Material
8
COMPRESSED AIR SYSTEM MAINTENANCE
Instrument air system reliability is of utmost importance for the continued reliability
and operation of power generation facilities—whether they are fossil or nuclear. Opera-
tion of instrument air systems has a tremendous impact on the operation of a plant.
Virtually every piping system in a power plant has pneumatically operated valves or
controls associated with it. Degradation or failure of an instrument air system could
have an adverse effect on the operation of many of the plant operating systems and
might also affect plant safety and the availability factor.
To improve instrument air system reliability and, consequently, overall plant safety and
reliability, the instrument air system and its components should be capable of providing
compressed air at a quality that meets or exceeds the ANSI/ISA S7.0.01-1996 specifica-
tion. The instrument air system should then be maintained to operate at optimum
efficiency. This may require some plants to change from a “reactive“ or “corrective“
maintenance mode to a “proactive“ or “preventive“ maintenance mode.
An aggressive valve testing program detects air valves that leak. Repair or replacement
of these valves should be placed on a prioritized maintenance schedule to be accom-
plished as required, based on operational decisions. Predictive maintenance and trend-
ing techniques should be employed that assist in establishing preventive maintenance
periods for such tasks as desiccant change out, filter replacement, and system
blowdowns.
All maintenance recommendations for instrument air system components in this guide
are general suggestions to assist in setting up a proactive or preventive maintenance
program, which helps to combat problems that are inherent to instrument air systems.
These problems, as discussed in earlier sections, may be caused by particulate, hydro-
carbon, or water incursion into the system. These problems can sometimes be attributed
to lack of adequate maintenance in the past. However, the object of this guide is not to
change the past; it is to make personnel aware of what caused the problems and to help
prevent them from recurring in the future.
Recommended maintenance activities and frequencies suggested are not designed for
any particular installation, but are generic in nature. They will differ with types of
equipment, manufacturer, and installation. Individual facilities should research their
own pieces of equipment and determine their maintenance requirements, methods, and
frequencies.
8-1
EPRI Licensed Material
Compressed Air System Maintenance
Conduct a visual examination of all internal and external areas of filter housing and
silencer surfaces for coating condition and hydrocarbon impingement. Rusty interior
surfaces require immediate correction to prevent compressor damage. External corro-
sion should be corrected as time permits to protect the equipment. A walkdown should
be conducted semiannually.
Verify inlet filter differential pressure. If a differential pressure indicator is not included
by the manufacturer, check with a U-tube manometer or a differential pressure gauge
set. An initial reading should be taken on each new filter element installed as baseline
operating data (BOD). An increase of 4–5” (100–125 mm) of water over the initial read-
ing indicates the filter needs replacing or cleaning. A sudden drop in differential pres-
sure may indicate a failed or torn element and need for replacement. Cleanable intake
filters can be cleaned either by blowing low-pressure air in a counterflow direction or
by soaking and agitating them in warm (140–150°F/60–65°C) water containing a non-
volatile cleaning solution. Air dry the washed elements for 24 hours before reuse. After
two or three cleanings, filters should be replaced, regardless of their condition.
The flexible coupling on the inlet piping (see Figure 8-1) should be checked for tightness
and material condition. A cracked surface or signs of boundary penetration indicate a
need for replacement.
Compressor
Hard Rubber Inlet
Hose Cover
Figure 8-1
Flexible Coupling for a Compressor
8-2
EPRI Licensed Material
Compressed Air System Maintenance
Visually inspect the external surfaces of the air compressor for leaks, loose connections,
belt conditions, paint condition, hot spots, etc. This inspection may provide indicators
of serious operating problems, such as high vibration, oil leaks, or inadequate cooling.
Conduct vibration and bearing temperature monitoring. This can simply be done using
a vibration meter and a handheld pyrometer. Because of the differences in construction,
typical vibration levels are not available. The manufacturer should be asked to provide
suitable vibration levels for each compressor.
On belt-driven machines, the drive belts should be checked for evidence of deteriora-
tion, excessive wear, and improper tightness. A proper fit is indicated by the V belts
saddling the sheave groove so that the top surface rides above the highest point of the
sheave. Stresses are then evenly distributed. A low riding belt can cause slipping and a
high riding belt loses contact.
Belt guards are required for safety. Be sure that the guards are replaced after any main-
tenance work.
Verify compressor operation by checking compressor load and unload times against
BOD. Observe load and unload pressure set points while checking load and unload
frequencies.
The compressor oil pressure and reservoir level should be monitored each shift and the
results recorded for reference and comparison with the next set of readings.
Calibrate all pressure gauges, pressure switches, temperature switches, and alarms. All
indicators serving a single component or machine should be calibrated as a group to
establish BOD.
Conduct a visual examination of all internal components for wear. Bearing clearances,
piston clearances, rod alignments, cylinder bore sizes, etc. should be recorded for BOD.
A similar inspection should be conducted for helical screw compressors. With oil-
injected rotary compressors, the condition of the oil is extremely important, and an oil
sampling procedure is recommended. Hydrocarbon lubricants need to be changed
every 1,000 hours of operation. Synthetic lubricants usually have a longer life and
should be changed at the recommended intervals. The oil filter should be changed
when the oil is changed and sooner if the pressure differential gauge indicates the need.
8-3
EPRI Licensed Material
Compressed Air System Maintenance
The air/oil separator element should be changed on the same basis. The air inlet filter
element should be changed when the differential pressure indicates the need or every
six months if there is no indicator. Pressure and temperature indicators and shutdown
devices should be checked at least every month. Newer rotary compressors equipped
with microprocessor controls generally indicate the need for specific maintenance items.
Monitor and record cooling water inlet, outlet, and approach temperatures. This provides
baseline data to identify indications of reduced heat transfer in the heat exchanger due to
corrosion buildup or reduced flow. It is common for the approach temperature (the
difference between the water supply temperature and the air outlet temperature) to be
15°F or 8°C. Where desirable, it is possible to have coolers with a much smaller approach
temperature, down to 2°F or 1°C, but with a significant increase in size and cost.
Inspect and clean the intercooler and aftercooler heat exchanger tubes in accordance
with the manufacturers’ recommendations. The most common cause of intercooler and
aftercooler inefficiency is a buildup of scale deposits on the heat exchanger surfaces.
Where no manufacturers’ recommendations are available, the scale deposits can be
removed by using a stiff brush or a strong blast of steam or air. In heavily fouled tube
nests, the units should be boiled for half an hour in a cleaning solution using 4 ounces
(120 ml) of trisodium phosphate per gallon (4 l) of water, followed by a thorough flush-
ing with plain water. Scale inside the tubes can be removed by using a mild citric acid
soak, followed by brushing and water flushing.
Closed cooling water and makeup water chemistry should be closely monitored to
ensure that all rust inhibitors, biocides, and antifoaming agents are present in the
proper concentrations.
Drain traps should have bypass piping and valves to facilitate required maintenance.
Inspect operation of drain traps and valves to prevent condensate accumulation in the
moisture separators and subsequent carryover into the air receiver and distribution
system. Open and inspect separator internals for wear and corrosion. Remove any
corrosion or debris by wiping with a wiping cloth. The wiping cloth should be moist-
ened with the lubricant being used to help retard corrosion of the metal surfaces. If the
lubrication is required for separator internals, the specified lubricant should be used.
Drain traps should be checked to ensure that they are functioning and that drain flow is
free. If clogged, the traps should be disassembled and cleaned to restore free flow. Most
drain traps do not require priming, but the manufacturer’s instructions should be
checked for this requirement.
8-4
EPRI Licensed Material
Compressed Air System Maintenance
Conduct an internal and external visual inspection of all receiver tank surfaces, includ-
ing bolted and welded connections, for physical damage, pitting, erosion, and corro-
sion. If there are areas of severe pitting or if cracks are detected, a nondestructive test
with ultrasound or radiography should be performed. Photographs should be taken so
that the extent of damage can be recorded as baseline operating data (BOD).
Plant documents should be consulted to determine minimum wall thickness. For the
first inspection after BOD and succeeding maintenance cycles, the wall thickness should
be measured so that the minimum wall thickness requirement is maintained.
Clean the receiver inside with a hot water-soaked wiping cloth. Do not leave surface
moisture. Do not wire brush, needle gun, or sandblast because these methods expose
new metal and lead to accelerated corrosion of the tank walls.
ASME pressure tests and inspections should be performed in accordance with the code
requirements (ASME Section VIII; Unfired Pressure Vessels) In addition to the system
safety valve, a safety valve should be installed between the hydra pump and the vessel
to prevent over pressure of the pump and vessel during the hydrostatic test.
Set the receiver and system safety valves. Gauges should be calibrated prior to the
setting of the safety valves.
Note: Some QA requirements specify gauge ranges and accuracies. Typically, a pressure
test gauge with accuracy of ±0.5% and a total range of approximately two times the
system pressure is used.
Check prefilter automatic drain valves for proper operation. These valves often stick
open and cause costly air losses.
Perform air quality tests to check for compliance with ANSI/ISA-S7.0.01-1996 require-
ments. Dew points can be checked using in-line hygrometers or portable measuring
equipment. Particulate can be measured by using a laser-based particle counter or by
blowing air through a paper filter for one minute and sending it to a lab for analysis.
Hydrocarbon or oil contamination can be measured by blowing an air sample into a
Tedlar bag and shipping it to a lab for analysis or by using an oil stick that uses a dye to
indicate hydrocarbon concentration. Each of these methods has its own advantages and
disadvantages that must be addressed for each plant’s application. The particular
equipment mentioned in this paragraph is not the only equipment available to do these
tests; it is mentioned here as an example of the various methods currently available.
Check the pressure drop across the prefilters and afterfilters to determine available filter
capacity. This can be accomplished by using a differential pressure gauge or subtracting
the outlet pressure from the inlet pressure. Allowable pressure drop at which the filter
8-5
EPRI Licensed Material
Compressed Air System Maintenance
elements are to be replaced should be determined for each installation, based on its size
and vendor recommendations. Old elements should be tagged and marked for cleaning
as they are removed, or they should be destroyed. New elements should be color coded
and tagged by size and type if stored in a common area.
8.7 Dryers
Check the outlet dew point by using an in-line hygrometer, a portable handheld hy-
grometer, or a moisture indicator. A silica gel moisture indicator does not produce an
accurate dew point reading, but starts changing color from blue to pink or red at a dew
point of approximately 0°F (-17.8°C).
Check the operation of the inlet switching valve on desiccant dryers. This valve, if not
properly maintained, can cause the dryer towers to either not switch over or get stuck in
between towers. Depending on the manufacturer, the dryer may vent to atmosphere or
may block flow. Either way, instrument air supply pressure is lost to the downstream
piping. Repair or replace the inlet switching valve as necessary to ensure that the dryer
operates properly.
Note: Some of the switching valves on older model dryers require frequent grease lubrica-
tion and a complete overhaul once a year. Excessive grease has been found on some
occasions to be a source of air system degradation.
Check the operation of automatic drain valves and traps on refrigerant dryers. Repair or
replace as necessary to ensure that condensate does not accumulate in the dryer.
Pressure drop across the air dryer should be tested periodically to ensure a free air path
through the dryer. On desiccant-type dryers, a high differential pressure may indicate a
breakdown of the desiccant and its subsequent compaction. On a refrigerant dryer, a
high differential pressure indicates blocked or fouled tubing. A zero differential pres-
sure may indicate a torn or incorrectly installed filter.
On desiccant dryers, the purge air flow rate should be checked to ensure proper flow
for efficient regeneration.
Desiccant levels in the towers should be checked to ensure that proper amounts of
desiccant are installed. Low desiccant levels may be an indication of desiccant break-
down and the need for replacement. This may also indicate desiccant carryover. Desic-
cant should be replaced in accordance with the manufacturer’s recommendations. If the
dryer manufacturer permits, the recommendations in Table 4-3 and the following can
be used as a guide in desiccant selection:
• On heat regenerative dryers, silica gel beads can be used to conserve power. Silica
gel beads regenerate at lower temperatures than activated alumina.
8-6
EPRI Licensed Material
Compressed Air System Maintenance
If cost is the only consideration in desiccant selection, the following prices can be used
as a guide. These are approximate costs of desiccant purchased in large quantities at the
time of printing of this guide (1998).
Activated Alumina $1.30 per pound
Granular Silica Gel $5.95 per pound
Silica Gel Beads $5.95 per pound
Silica Gel Beads (water blockers) $6.25 per pound
Molecular Sieve $3.85 per pound
It is highly recommended that prior to selection of a desiccant, both the dryer vendor
and a desiccant manufacturer be contacted to recommend the best possible desiccant
available for the particular application. Recent developments in desiccant manufactur-
ing have made new products available that might not have existed when the original
dryers were purchased. It should also be considered that in a heated regenerative sys-
tem, frequency of regeneration influences the aging of the desiccant. Therefore, if fre-
quent regenerations occur either due to system leaks or low capacity dryer trains, desic-
cants may have to be replaced earlier than their recommended life.
Check the blowdown devices (automatic drain valves and traps) for blowby and proper
operation. Repair or replace as necessary to ensure that condensate and particulate do
not accumulate in the air lines.
Periodically blow down line filters to ensure that they are not clogged with particulate
or desiccant fines, which can damage the end-use component they serve.
8-7
EPRI Licensed Material
Compressed Air System Maintenance
Compressed air distribution systems generally use piping made of carbon steel, stain-
less steel, or copper. As expected, stainless steel piping experiences the fewest failures
due to corrosion or physical damage. However, a stainless steel distribution system is
quite expensive. A carbon steel piping system provides satisfactory service as long as
the dew point of air is maintained at or below that required by ISA standard. Corrosion
and leaks in carbon steel piping are quite common where the moisture content of air
remains consistently high. It is recommended that all distribution systems be provided
with blowdown points to eliminate corrosion products that can accumulate due to
occasional moisture intrusion.
8.9.1 Piping
When installing new or additional headers or piping:
• Carbon steel piping should be in accordance with ASTM-A106.
• Stainless steel piping should be in accordance with ASTM-A213.
• Steel tubing should be in accordance with ANSI B93.
All piping installations should be in accordance with the standard originally used for
plant design (ANSI/ASME B31.1 for most U.S. plants) or any later revision that may
have been adopted by the plant.
Copper piping is easily damaged with physical impact or misuse. Also, the joints in a
copper pipe are soldered or brazed. Soldered joints can fail due to poor joint insertion,
inadequate solder penetration, or external stress. There are no national codes or specifi-
cations for soldering. The American Welding Society (AWS) considers a 70% filled joint
to be adequate if the voids are small and discreetly dispersed. ASME Code provides
specifications for brazing of copper piping. Brazing is preferred to soldering, particu-
larly for copper pipes above 1" (2.5 cm) in diameter, to ensure that a joint has sufficient
strength under pressure.
A frequently used, reliable method for locating air leaks is to systematically apply a
soap solution to the piping joints and connections. Ultrasonic leak detection devices can
also be used, depending on the location of the leak and the background noise level. In
some cases, tracer gases have been used to test the distribution system for leaks.
8-8
EPRI Licensed Material
Compressed Air System Maintenance
To ensure piping integrity, questionable piping sections and joints can be tested with
ultrasonic equipment that can provide information on pipe wall thickness and joint
insertion (especially for soldered/brazed joints). However, the effectiveness of the
ultrasonic equipment depends on the knowledge and experience of the technician
interpreting the data obtained.
Another method of testing questionable joints is with real-time x-ray. The x-ray picture
of the joint can be evaluated for its integrity. The disadvantage of this system is that the
image quality may sometimes be poor for proper evaluation. Also, due to ALARA
considerations, strict administrative procedures must be in place for personnel safety
during operation of the x-ray equipment.
All valves should be cycled periodically to ensure proper operation and freedom of
movement. Solenoid valves should also be cycled and inspected for indication of physi-
cal damage that might affect proper operation (bent or pinched vent lines, etc.). In
addition, solenoids should be checked for blowby or seat leakage.
Blowdowns should be performed on all air lines to end-use components to remove any
desiccant fines or spalled particulate from the system. Air lines should be blown down
through a clean white blowdown cloth such as a cloth diaper. The lines should be
blown until all visible particulate is removed. During blowdown, ensure that adequate
safety precautions are followed.
Pressure decay testing should be performed on all accumulators and associated check
valves to detect back leakage into the system.
If compressor loading indicates excessive system leakage, perform pressure decay tests
or flow measurement tests or soap test the headers to identify the location of leaks.
8-9
EPRI Licensed Material
9
REFERENCES
Aging Control and Service Air Compressors and Dryers used in Nuclear Power Plants.
NUREG/CR-5519, Volume 1. U.S. Nuclear Regulatory Commission.
Air Operated Valve Maintenance Guide. NMAC, NP-7412, Revision 1. EPRI, Palo Alto, CA:
July 1992.
Application and Maintenance of Steam Traps, NMAC, TR-105853, EPRI, Palo Alto, CA:
December 1996.
Compressed Air and Gas Handbook, Fifth Edition, Compressed Air and Gas Institute, 1989.
Gas Purification, Fourth Edition, Arthur Kohl and Fred Riesenfeld, 1985.
Lubrication Guide. NMAC, NP-4916, Revision 2. EPRI, Palo Alto, CA: February 1995.
Maintaining Operability of Nuclear Plant Air Systems. NSAC-137, EPRI, Palo Alto, CA:
February 1990.
Pneumatic Systems and Nuclear Plant Safety. NSAC-128, EPRI, Palo Alto, CA:
October 1988.
Preoperational Testing of Instrument and Control Air Systems. Regulatory Guide 1.68.3. U.S.
Nuclear Regulatory Commission. April 1982.
9-1
EPRI Licensed Material
References
Report of the Instrument Air Working Group. TR-103595, EPRI, Palo Alto, CA: April 1994.
Self-Inspection Check Lists. SCIF#17813. State Compensation Insurance Fund. San Fran-
cisco, CA. May 1983.
Significant Operating Experience Report, SOER 88-1. Institute of Nuclear Power Op-
erations. May 1988.
Solenoid Valve Maintenance and Application Guide. NMAC, NP-7414, EPRI, Palo Alto, CA:
April 1992.
Three Mile Island Unit 2 Accident. Case Study Materials 88-008. Institute of Nuclear
Power Operations.
9-2
EPRI Licensed Material
10
GLOSSARY OF TERMS
adsorption. The process by which a desiccant with a highly porous surface attracts and
holds the moisture in compressed air. The desiccant is capable of being regenerated.
aftercooler. A heat exchanger for cooling air or gas discharged from a compressor. The
resulting condensate can be removed by a moisture separator following the aftercooler.
air-cooled compressor. A compressor having its compressed air and oil cooled by
atmospheric air flowing across radiator type heat exchangers.
atmospheric dew point. The dew point at atmospheric pressure. (See dew point.)
base plate. A metallic structure on which a compressor and its accessories are mounted.
capacity. The actual volume flow rate of air or gas compressed and delivered from a
compressor package but measured at conditions of pressure, temperature, and composi-
tion prevailing at the inlet to the compressor.
capacity, actual. The actual volume flow rate of air or gas compressed and delivered
from a compressor running at its rated operating conditions of speed, pressures, and
temperatures. Actual capacity generally is expressed in actual cubic feet per minute
(acfm) at conditions prevailing at the compressor inlet.
capacity controls. The means of adjusting the actual volume flow rate from a compres-
sor to match the demands from the compressed air system.
casing. The pressure-containing stationary element (stator) that encloses the rotors and
associated internal components of a compressor and includes the inlet and discharge
connections or nozzles.
10-1
EPRI Licensed Material
Glossary of Terms
compression ratio. The ratio of absolute discharge pressure to the absolute inlet pres-
sure.
desiccant. A material that has a large proportion of surface pores and is capable of
attracting and retaining water vapor from the air.
dew point. The temperature at which moisture in the air will begin to condense if the
air is cooled at constant pressure. At this point, the relative humidity is 100%.
displacement. The displacement of a compressor is the swept volume per unit of time,
usually expressed in cubic feet per minute (cfm). It may also be considered as the
theoretical capacity if the volumetric efficiency is 100%.
efficiency, isothermal. The ratio of the work calculated on an isothermal basis to the
actual work transferred to the gas during compression.
efficiency, polytropic. The ratio of polytropic compression energy transferred to the gas
during compression to the actual energy transferred to the gas.
filter. A device for removing particulate and/or liquid from the air stream. The liquid
may be water or oil.
10-2
EPRI Licensed Material
Glossary of Terms
flange connection (inlet or discharge). The means of connecting the compressor to the
piping system.
free air. Air at atmospheric conditions at any specified location and unaffected by the
compressor.
gas. Gas is one of the three basic phases of matter; thus, air is a gas. However, in com-
pressor practice, the term gas normally is applied to a gas other than air.
horsepower, brake. Horsepower is a rate of doing work and brake horsepower is the
horsepower input to the machine (compressor) drive shaft.
humidity, relative. The relative humidity of a gas (or air) vapor mixture is the ratio of
the partial pressure of the vapor to the vapor saturation pressure at the dry bulb tem-
perature of the mixture.
humidity, specific. The weight of water vapor in an air vapor mixture per pound of dry
air.
intercooler. A heat exchanger for removing the heat of compression between the stages
of a multi-stage compressor. Normally, this also results in the removal of a substantial
amount of moisture.
intercooling, perfect. When the temperature of the air or gas leaving the intercooler is
equal to the temperature of the air or gas entering the compressor inlet.
liquid piston (or liquid ring) compressor. A rotary compressor in which a fixed vane
rotor revolves in an elliptical stator and carries with it a ring of liquid within the stator.
The space between vanes varies with depth of penetration of the vanes into the liquid
ring.
load factor. The ratio of the average compressor load during a given period of time to
the maximum rated load of the compressor. In the case of air tools, it is the ratio of the
time actually working to the total time available.
moisture separator. A device that separates liquid moisture from the air stream by
means of velocity and/or directional changes, impaction, or centrifugal force.
10-3
EPRI Licensed Material
Glossary of Terms
piston. The component that reciprocates within the cylinder of a reciprocating type
compressor to displace and compress the air or gas in the cylinder.
pressure, absolute. The total pressure measured from absolute zero (perfect vacuum).
pressure, discharge. The total pressure at the specified discharge connection (of the
compressor package). This can be expressed as an absolute or gauge pressure.
pressure, inlet. The total pressure at the specified inlet point (of the compressor pack-
age).
pressure dew point. The dew point at the prevailing pressure.(See dew point).
pressure rise. The difference between discharge pressure and inlet pressure.
pressure, static. The pressure measured in a flowing stream in such a way that the
velocity of the stream has no effect on the measurement.
pressure, total. The pressure that would be obtained by stopping a moving stream of
gas or liquid. It is the pressure measured by an impact tube.
pressure, velocity. The total pressure minus the static pressure in an air or gas stream.
receiver. A vessel (or tank) used for the storage of air or gas discharged from a com-
pressor. In a large compressed air system, there can be primary and secondary storage
locations.
rotors. The rotating elements of a machine such as a compressor. This may include shaft
sleeves and a thrust balancing device.
10-4
EPRI Licensed Material
Glossary of Terms
rotating speed. The number of revolutions per unit of time of the compressor drive
shaft, normally expressed in revolutions per minute (rpm).
rotor tip speed. The distance traveled per unit of time of a point on the outside diameter
of a rotor. For rotary screw compressors, this refers to the male rotor (drive rotor) and is
expressed in meters per second.
seal. A device used between a rotating and a stationary part of a compressor to separate
them and minimize leakage between areas of unequal pressure.
shaft. The part of the rotating element on which bearings and seals are normally located
and through which energy is transmitted from the prime mover.
single-stage centrifugal compressor.- Dynamic compressor that has only one impeller.
sliding vane compressor. A compressor in which vanes slide in radial slots in a rotor
mounted eccentrically in a stator.
specific gravity. The ratio of the specific weight of air or gas to that of dry air at the
same pressure and temperature.
specific power. The power required to drive the compressor per unit of flow rate. This
often is expressed as bhp/100 cfm.
specific weight. The weight of air or gas per unit volume. Unless otherwise specified, in
compressor practice it is the weight per unit volume at conditions of total pressure, total
temperature, and composition that prevail at the inlet to the compressor.
stages. A series of steps in the compression process, normally requiring separate pistons
and cylinders or rotors and stators and with intercooling between them.
standard air. The Compressed Air and Gas Institute (CAGI) and Pneurop have adopted
the definition used in ISO standards. This is air at a pressure of 1 bar (14.5 psia), 20°C
(68°F), and 0% relative humidity.
In the past, the U.S. compressor industry defined standard air as air at 14.7 psia, 68°F,
and 36% humidity. The process gas industries normally use 14.7 psia; 60°F (15.55°C),
and dry air as definition of standard air. Some process companies may have their own
standard. When standard air or SCFM is specified, it is best to confirm which standard
is being used.
stator. The casing in which a rotor or rotors are housed and in which compression takes
place.
10-5
EPRI Licensed Material
Glossary of Terms
swept volume. The theoretical amount of air or gas displaced by the pistons or rotors
per unit of time assuming 100% volumetric efficiency. This is normally expressed in
cubic feet per minute (cfm).
temperature, absolute. The temperature of the air or gas measured from absolute zero.
The absolute temperature is the Fahrenheit temperature plus 459.6 and is known as the
Rankine temperature. In the metric system, the absolute temperature is the Centigrade
temperature plus 273 and is known as the Kelvin temperature.
temperature, discharge. The total temperature at the discharge connection of the com-
pressor.
temperature, inlet. The absolute temperature at the inlet connection of the compressor.
temperature rise ratio. The ratio of the computed isentropic temperature rise to the
measured total temperature rise during compression. For a perfect gas, this is equal to
the ratio of the isentropic enthalpy rise to the actual enthalpy rise.
temperature, static. The actual temperature of a moving gas stream. It is the tempera-
ture indicated by a thermometer moving in the stream and at the same velocity.
temperature, total. The temperature that would be measured at the stagnation point if a
gas stream were stopped with adiabatic compression from the flow condition to the
stagnation pressure.
thrust balancing device (balance piston). Part of a rotating element arranged to coun-
teract any inherent thrust developed by the rotors during compression.
water-cooled compressor. A compressor that uses water to remove the heat of compres-
sion by means of shell and tube heat exchangers. See also water-injected compressor.
10-6
EPRI Licensed Material
APPENDIX A
TROUBLESHOOTING GUIDE FOR REFRIGERANT-
TYPE DRYERS
The dryer consists of three basic systems: air, refrigerant, and electrical. An air leak at
100 psig provides an audible signal, indicating where there is a problem. R-22 has no
color or odor; therefore, a small refrigerant leak is difficult to find. However, it can be
detected by a bubble test, halide torch (with a flame that changes from red-orange to
blue on contact with refrigerant), or an electronic detector.
The electrical system consists of transformers, starter, switches, relays, etc. The use of a
volt-ohm meter or similar equipment is required for checking continuity, amperage,
and voltage.
A-1
EPRI Licensed Material
Appendix A
A-2
EPRI Licensed Material
Appendix A
Note:
An increase in refrigerant suction pressure causes an increase in refrigerant evaporator
temperature. This in turn raises the dew point of the compressed air delivered into the
system.
A-3
EPRI Licensed Material
APPENDIX B
TROUBLESHOOTING GUIDE FOR REGENERATIVE
DESICCANT DRYERS
B-1
EPRI Licensed Material
Appendix B
B-2
EPRI Licensed Material
APPENDIX C
TROUBLESHOOTING GUIDE FOR DOUBLE-ACTING
RECIPROCATING COMPRESSORS
This table provides symptoms and probable causes for double-acting reciprocating
compressor problems. This table is provided as an aid for troubleshooting commonly
occurring problems in this type of compressor.
C-1
EPRI Licensed Material
Appendix C
C-2
EPRI Licensed Material
Appendix C
C-3
EPRI Licensed Material
Appendix C
C-4
EPRI Licensed Material
Appendix C
C-5
EPRI Licensed Material
Appendix C
C-6
EPRI Licensed Material
Appendix C
C-7
EPRI Licensed Material
Appendix C
C-8
EPRI Licensed Material
APPENDIX D
TROUBLESHOOTING GUIDE FOR ROTARY
COMPRESSORS
The table in this appendix provides symptoms and probable causes for rotary screw-
type compressor problems. This table is provided as an aid for troubleshooting com-
monly occurring problems in this type of compressor.
D-1
EPRI Licensed Material
Appendix D
D-2
EPRI Licensed Material
Appendix D
D-3
EPRI Licensed Material
Appendix D
D-4
EPRI Licensed Material
APPENDIX E
TROUBLESHOOTING GUIDE FOR CENTRIFUGAL
COMPRESSORS
After a brief period, compressor operators should become accustomed to the sound of a
smooth running machine. Any change in the noise or vibration level should become
immediately noticeable. Often, this variation in sound indicates a potential malfunction
or failure.
E-1
EPRI Licensed Material
Appendix E
E-2
EPRI Licensed Material
Appendix E
E-3
EPRI Licensed Material
Appendix E
E-4
EPRI Licensed Material
Appendix E
E-5
EPRI Licensed Material
Appendix E
E-6
EPRI Licensed Material
Appendix E
E-7
EPRI Licensed Material
Appendix E
E-8
EPRI Licensed Material
Appendix E
E-9
EPRI Licensed Material
Appendix E
The next level of panel troubleshooting involves the use of a multimeter and the control
panel schematic drawing that will allow a step-by-step search for any problem.
NOTE: Troubleshooting at this level is intended for the more electronically sophisticated
operator. Some basic problems are discussed below. Other difficulties can be diagnosed
using the same logic. Consult the vendor’s manual and, if in doubt, contact the vendor’s
service department.
CAUTION: Be careful when adjusting the control panel. Errors can lead to greater problems
or even equipment damage.
E-10
EPRI
Electric Power Research Institute
3412 Hillview Avenue
P.O. Box 10412
Palo Alto, California 94303
800-313-EPRI
www.epri.com
About EPRI
Electricity is increasingly recognized
as a key to societal progress
throughout the world, driving
economic prosperity and improving
the quality of life. The Electric Power
Research Institute delivers the
science and technology to make the
generation, delivery, and use of
electricity affordable, efficient, and
environmentally sound.
LICENSED
M AT E R I A L