Load Calculation2019.11.17
Load Calculation2019.11.17
B1. Preliminary load estimation (for total building based Archi. Drawings)
Typically, in office buildings two third from the maximum demand will be utilized for fulfill the power
requirement of the air conditioning system(as per the instructions given by the supervisor and previous
project experience-rule of thumb). In addition to the air conditioning system, few special load are available in
this builfing compare to the office builfding. They are medical gas system, CT scan machine, X-ray machine,
theaters and Insentive care units. Therefore,
= 567.31 kVA
Wattage
Single
or Three
Diversity/U phase
Item Description Quantity expected phase
tilization current
current per current (A)
(A)
unit
LIGHTING
Fans
6 75W Ceiling fan at 0.8 p.f. 115 75.00 80.00% 37.50 -
7 51.9W wall fan at 0.8 p.f. 14 51.90 80.00% 3.16 -
Sub total for fans in single phase current (A) 87.06 -
Sub total for fans in three phase current (A) 29.02
Socket outlets
13A Socket outlets for fore exit
8 15 7.00 100.00% 0.57 -
signs (W)
9 13A Socket outlet (A) 524 1.00 40.00% 209.60 -
10 13A dedicated socket outlet (A) 61 7.00 30.00% 128.10 -
338.27 -
Sub total for socket outlets in three phase current (A) 112.76
= 20 MVA
Therefore the possibility to run the generator below 1/3rd load is minimum.This will ensure long life
time of engine of the generator.
CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
B4.Design current calculation sheet for Floor Distribution Boards (FDB) and Distribution Boards (DB)
GFDB 1FDB 2FDB 3FDB
Wattage(W) / Diversity/
Item Description
Ammpere(A) Utilization(1) Qntity Current Current Qntity
Current Current
Qntity
Current Current
Qntity
Current Current
(A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser
and electronic ballast at 0.99 p.f. (Ballast loss 16.0 80% 18 1.01 - 26 1.46 - 31 1.74 - 2 0.11 -
2W)
1 × 28, single fluorescent fitting with diffuser
and electronic ballast at 0.97 p.f. (Ballast loss 32.7 80% 6 0.70 - 0 0.00 - 0 0.00 - 10 1.17 -
4.7W)
4 x 14W ceiling recessed mounted lights with
opal diffusers & electronic ballast at 0.99 p.f. 61.0 90% 76 18.32 - 75 18.08 - 92 22.18 - 92 22.18 -
(Ballast Loss 5W )
4 x 14W ceiling recessed mounted lights with
opal diffusers & electronic ballast at 0.99 p.f. 61.0 90% 29 6.99 - 40 9.64 - 24 5.79 - 48 11.57 -
(Ballast Loss 5W )
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% 13 5.30 - 34 13.86 - 38 15.49 - 8 3.26 -
51.9W wall fan at 0.8 p.f. 51.9 90% 3 0.76 - 4 1.02 - 4 1.02 - 2 0.51 -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 4 0.08 - 4 0.08 - 4 0.08 - 6 0.11 -
13A Socket outlet (A) 1.0 50% 113 56.50 - 112 56.00 - 147 73.5 - 237 118.50 -
13A dedicated socket outlet (A) 7.0 30% 7 14.70 - 16 33.60 - 19 39.9 - 16 33.60 -
Air Conditioning
10kW three phase AHU at 0.8 p.f. 10000.0 90% - - - - - - - - - -
8kW three phase AHU at 0.8 p.f. 8000.0 90% - - - - - - - - - -
2kW three phase AHU at 0.8 p.f. 2000.0 90% - - - - - - - - - -
1.5kW three phase AHU at 0.8 p.f. 1500.0 90% 3 - 7.34 5 - 12.23 5 - 12.23 - - -
100W Single phase fan coil unit at 0.8p.f. 100.0 100% 25 13.59 - 5 2.72 - 2 1.09 - - - -
150W Single phase fan coil unit at 0.8p.f. 150.0 100% 4 3.26 - - - - 1 0.82 - - - -
250W Single phase fan coil unit at 0.8p.f. 250.0 100% 2 2.72 - - - - - - - - - -
Other Special Loads
500W single phase Operation theatre lamp @
500.0 100% - - - - - - - - 2 5.43 -
0.8 p.f.
Sub Total 01 124.98 7.34 138.48 12.23 163.81 12.23 198.48 0.00
Three phase line current in each pase(2) 49.00 A 58.39 A 66.83 A 66.16 A
Add 10% for single phase load inbalance (2)
4.17 A 4.62 A 5.46 A 6.62 A
Sub Total 02 53.16 A 63.00 A 72.29 A 72.78 A
Add 10% for future exapansions(3) 5.32 A 6.30 A 7.23 A 7.28 A
Sub Total 03 58.48 A 69.30 A 79.52 A 80.05 A
Light fittings
1 × 14, single fluorescent fitting with diffuser
and electronic ballast at 0.99 p.f. (Ballast loss 16.0 80% 31 1.74 - - - - - - - - - -
2W)
1 × 28, single fluorescent fitting with diffuser
and electronic ballast at 0.97 p.f. (Ballast loss 32.7 80% 0 0.00 - 3 0.35 - 8 0.94 - - - -
4.7W)
4 x 14W ceiling recessed mounted lights with
opal diffusers & electronic ballast at 0.99 p.f. 61.0 90% 92 22.18 - - - - - - - - - -
(Ballast Loss 5W )
4 x 14W ceiling recessed mounted lights with
opal diffusers & electronic ballast at 0.99 p.f. 61.0 90% 23 5.55 - - - - - - - - - -
(Ballast Loss 5W )
Ceiling recessed mounted down light with
15.0 80% 34 2.22 - - - - - - - - - -
1x15W CFL and bottom glass at 0.8p.f.
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% 13 5.30 - - - - - - - - - -
51.9W wall fan at 0.8 p.f. 51.9 90% 3 0.76 - - - - - - - - - -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 4 0.08 - 1 0.02 - 1 0.02 - - - -
13A Socket outlet (A) 1.0 50% 81 40.50 - 4 2.00 - 4 2 - - - -
13A dedicated socket outlet (A) 7.0 30% 7 14.70 - 1 2.10 - 1 2.1 - - - -
Air Conditioning
10kW three phase AHU at 0.8 p.f. 10000.0 90% - - - - - - - 2 - 32.61
8kW three phase AHU at 0.8 p.f. 8000.0 90% - - - - - - - 2 - 26.09
2kW three phase AHU at 0.8 p.f. 2000.0 90% - - - - - - - 1 - 3.26
1.5kW three phase AHU at 0.8 p.f. 1500.0 90% 5 - 12.23 - - - - - - - - -
100W Single phase fan coil unit at 0.8p.f. 100.0 100% 2 1.09 - - - - - - - - - -
150W Single phase fan coil unit at 0.8p.f. 150.0 100% 5 4.08 - - - - - - - - - -
250W Single phase fan coil unit at 0.8p.f. 250.0 100% - - - - - - - - - - - -
Lifts
15kW, three phase bed lifts @ 0.8p.f. 15000.0 100% - - - 1 - 27.17 1 - 27.17 - - -
Sub Total 01 98.19 12.23 4.47 27.17 5.06 27.17 0.00 61.96
Three phase line current in each pase(2) 44.96 A 28.66 A 28.86 A 61.96 A
Add 10% for single phase load inbalance (2)
3.27 A 0.15 A 0.17 A 0.00 A
Sub Total 02 48.23 A 28.81 A 29.03 A 61.96 A
Add 10% for future exapansions(3) 4.82 A 2.88 A 2.90 A 6.20 A
Sub Total 03 53.05 A 31.69 A 31.93 A 68.15 A
- - -
Other Special Loads - - -
9.3kW three phase Water
pump (01- Duty) @ 0.8 p.f. 9300.0 100% - - - - - - 1 - 16.85 - - - - - -
40kW three phase Xray
Machine @ 0.8 p.f. 40000.0 100% - - - - - - - - - 1 - 72.46 - -
70kW three phase C.T.
Machine @ 0.8 p.f. 70000.0 100% - - - - - - - - - - - - 1 - 126.81
Sub Total 01 0.00 333.33 0.00 36.59 0.00 16.85 0.00 72.46 0.00 126.81
Three phase line current in each pase(2) 333.33 A 36.59 A 16.85 A 72.46 A 126.81 A
Add 10% for single phase load inbalance (2)
0.00 A 0.00 A 0.00 A 0.00 A 0.00 A
Sub Total 02 333.33 A 36.59 A 16.85 A 72.46 A 126.81 A
Add 10% for future exapansions(3) 33.33 A 3.66 A 1.68 A 7.25 A 12.68 A
Sub Total 03 366.67 A 40.25 A 18.53 A 79.71 A 139.49 A
Design current for FDBs 367.00 A , 3Φ 41.00 A , 3Φ 19.00 A , 3Φ 80.00 A , 3Φ 140.00 A,3Φ
Selected breaker(5) 400A, 4P MCCB 63A, 4P MCCB 40A, 4P MCCB 100A, 4P MCCB 160A, 4P MCCB
Note: 1) Diversity/utilization is not applied in calculation of lighting, fan and other fixed loads. It was considered only for general socket outlets.
2) Three phase line current in each panel is taken by dividing single phase currents by 3 assuming three phase balanced load. But practically single phase currents can not be converted to balanced three phase
system. For this reason additional 10% is added for single phase currents.
3) 20% additional margin was added for the future expansions for all consumer units except the CUs for fixed loads and CU-LM & CU-WT (only 10% was added for those CUs).
4) For the socket out lets, following currents were taken. * 13A =1A, 13A dedicated Socket= 7A.
5) Rating of MCCBs/MCBs were selected based on design current & unexpected imbalance of single phase loads etc.
6) All Consumer Units are designed with spare breakers for future expansions.
A,3Φ
CONSTRUCTION OF VIJAYA KUMARATHUNGA MEMORIAL HOSPITAL, SEEDUWA
B4.Design current calculation sheet for Distribution Boards (FDB) and Consumer units (DB) of ground floor
Wattage GDB1 GDB2 CUXR CUCT
Diversity/
(W)
Item Description Utilization Current Current Current Current Current Current Current Current
/Ammpe (1) Qntity Qntity Qntity Qntity
re(A) (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ (A) - 1Φ (A) - 3Φ
Light fittings
1 × 14, single fluorescent fitting with diffuser and
16.0 80% 10 0.56 - 8 0.45 - - - - - - -
electronic ballast at 0.99 p.f. (Ballast loss 2W)
1 × 28, single fluorescent fitting with diffuser and
32.7 80% - - - 6 0.70 - - - - - - -
electronic ballast at 0.97 p.f. (Ballast loss 4.7W)
4 x 14W ceiling recessed mounted lights with opal
diffusers & electronic ballast at 0.99 p.f. (Ballast Loss 61.0 90% 28 6.75 - 28 6.75 - 6 1.45 - 16 3.86 -
5W )
Fans
75W Ceiling fan at 0.8 p.f. 75.0 100% 10 4.08 - 3 1.22 - - - - - -
51.9W wall fan at 0.8 p.f. 51.9 90% - - - 2 0.51 - - - - - -
Small power -
13A Socket outlets for fore exit signs (W) 3.5 100% 2 0.04 - 2 0.04 - - - - - - -
13A Socket outlet (A) 1.0 50% 33 16.50 - 48 24.00 - 8 4 - 24 12.00 -
13A dedicated socket outlet (A) 7.0 30% 3 6.30 - 4 8.40 - - - 1 2.10 -
Air Conditioning
10kW three phase AHU at 0.8 p.f. 10000.0 90% - - - - - - - - - - -
8kW three phase AHU at 0.8 p.f. 8000.0 90% - - - - - - - - - - -
2kW three phase AHU at 0.8 p.f. 2000.0 90% - - - - - - - - - - -
1.5kW three phase AHU at 0.8 p.f. 1500.0 90% - - - - - - - - - - -
100W Single phase fan coil unit at 0.8p.f. 100.0 100% - - - - - - - - - - -
150W Single phase fan coil unit at 0.8p.f. 150.0 100% - - - - - - - - - - -
250W Single phase fan coil unit at 0.8p.f. 250.0 100% - - - - - - - - - - -
Other Special Loads -
500W single phase Operation theatre lamp @ 0.8 p.f. 500.0 100% - - - - - - - - - - -
Sub Total 01 41.08 0.00 48.29 0.00 5.51 0.00 18.02 0.00
Three phase/ single phase line current in each pase(2) 13.69 A 16.10 A 5.51 A 18.02 A
Add 10% for single phase load inbalance(2) 1.37 A 1.61 A 0.18 A 0.60 A
Sub Total 02 15.06 A 17.71 A 5.70 A 18.62 A
Add 10% for future exapansions(3) 1.51 A 1.77 A 0.57 A 1.86 A
Sub Total 03 16.57 A 19.48 A 6.27 A 20.49 A
Three phase/ single phase line current in each pase(2) 17.13 A 24.42 A 11.98 A
Add 10% for single phase load inbalance(2) 1.71 A 2.44 A 0.40 A
Sub Total 02 18.84 A 26.86 A 12.37 A
Add 10% for future exapansions(3) 1.88 A 2.69 A 1.24 A
Sub Total 03 20.72 A 29.55 A 13.61 A
Design current for FDBs 21.00 A , 3Φ 30.00 A , 3Φ 14.00 A , 1Φ
Selected breaker(5) 32A, 4P MCB 40A, 4P MCB 32A, 2P MCB
Three phase/ single phase line current in each pase(2) 26.52 A 22.81 A 11.98 A
Add 10% for single phase load inbalance(2) 2.65 A 2.28 A 0.40 A
Sub Total 02 29.17 A 25.09 A 12.37 A
Add 10% for future exapansions(3) 2.92 A 2.51 A 1.24 A
Sub Total 03 32.09 A 27.59 A 13.61 A
Three phase/ single phase line current in each pase(2) 17.15 A 13.94 A 31.00 A 30.46 A
Add 10% for single phase load inbalance(2) 0.57 A 1.39 A 1.03 A 1.02 A
Sub Total 02 17.73 A 15.34 A 32.03 A 31.48 A
Add 10% for future exapansions(3) 1.77 A 1.53 A 3.20 A 3.15 A
Sub Total 03 19.50 A 16.87 A 35.24 A 34.63 A
Three phase/ single phase line current in each pase(2) 20.40 A 51.09 A 14.39 A 12.65 A
Add 10% for single phase load inbalance(2) 0.68 A 1.70 A 1.44 A 0.42 A
Sub Total 02 21.08 A 52.79 A 15.83 A 13.07 A
Add 10% for future exapansions(3) 2.11 A 5.28 A 1.58 A 1.31 A
Sub Total 03 23.19 A 58.07 A 17.41 A 14.38 A
Three phase/ single phase line current in each pase(2) 24.07 A 21.69 A 11.98 A
Add 10% for single phase load inbalance(2) 2.41 A 2.17 A 0.40 A
Sub Total 02 26.48 A 23.86 A 12.37 A
Add 10% for future exapansions(3) 2.65 A 2.39 A 1.24 A
Sub Total 03 29.13 A 26.25 A 13.61 A
Three phase/ single phase line current in each pase(2) 6.91 A 3.00 A
Add 10% for single phase load inbalance(2) 0.00 A 0.00 A 0.00 A 0.00 A
Sub Total 02 0.00 A 0.00 A 0.00 A 0.02 A
Add 10% for future exapansions(3) 0.00 A 0.00 A 0.00 A 0.00 A
Sub Total 03 0.00 A 0.00 A 0.00 A 0.02 A