Pages From Report Stage 1

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 29

NA - NOT APPLICABLE

CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL


ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT
2.0 FIRE WATER STORAGE TANK :
(Above Ground)

2.1 Design and Construction Code Not Known NFPA-22 (2003 Ed.) Since this tank is not the

main firewater tank, therfore


2.2 Working Capacity 20000 x 4 -
has not been evaluated for
80,000 US Gallons
2.3 Location of Tank. Yes Away from fire Exposure fire scenarios.
(clause 4.2.1)
2.4 Type of Construction R.C.C. Steel, R.C.C, Wood, etc,. MR
(clause 4.3.1)
2.5 Roof on Tank. Yes Yes MR
(clause 4.14.1)
2.6 Roof Vent Yes Yes MR
(clause 4.15)
2.7 Roof Hatch Yes Dia. 24"-2 Nos. MR
(clause 5.7.3)
2.8 Ladder Interior Exterior and interior Accessable from ground
(clause 5.7.4) MR
2.9 Water Level Gauge / LL/HL Alarm No Yes SRAP
(clause 13.1.11)
2.10 Tank Outlet Nozzle Size 4" 6" <= 25000 USG
SRAP
8" => 30000 to 100000 USG
10" = Greater capacities
(clause 13.2.2.2)
2.11 Controlling Valve Yes Gate with indicator Post MR
or OS&Y
(clause 13.2.12)
2.12 Antivortex Plate Assembly Not Known Yes
(clause 13.2.13)
2.13 Overflow Yes Yes MR
(clause 13.5)
2.14 Shell Manholes N/A 2 nos. in first course
(clause 13.6.2)
2.15 Dual Service Tank Yes May be
(clause 13.7.1)
2.16 Water Quality Good -

2.17 Source of Water Out source -

2.18 Fire Water Tank Condition Satisfactory -

2.19 Notes:

Doc.: 2951-CL-001 Rev.0 Page 20


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT
3.0 FIRE PUMP:
(a) (DIESEL ENGINE DRIVEN)

3.1a Design code NFPA 20 NFPA-20 (2003 Ed.)

3.2a UL listed and FM approved Yes -

3.3a. Pump Characteristics

i Clause 7.1.2.1
Pumps shall furnish not less than 150 percent Yes MR
of rated capacity at a total head of not less
than 65 percent of the total rated head.

ii The total shutoff head shall not exceed 140 Clause 7.1.2.2.
Yes MR
percent of the total rated head on vertical
turbine pumps.

3.4a Design Flow Rate 500 US gpm -

3.5a Design Head 104 Psi - SRAP

3.6a Type of pump Centrifugal Centrifugal


(clause 5.2.1)
- Horizontal, in line fire pump OR Horizontal For +ve suction head
(clause 6.1.2)
- Vertical turbine pump N/A For Suction Lift MR
(clause 7.1.1)
3.7a Pressure Gauges No At discharge & suction SRAP
(clause 5.10)
3.8a Pressure Relief Valve No if Static head + Pump shut off SRAP
> system design pressure
(clause 5.18)
3.9a Circulation Relief Valve Not Applicable For recirculation
(clause 5.11)
(Not applicable for Engine Pump)
3.10a Valves at Suction Piping Yes OS&Y Gate MR
(clause 5.14.5)
3.11a Valves at Discharge Piping Yes Check & OS&Y Gate MR
(clause 5.15)
3.12a Water Flow Test Device No To test the pump SRAP
(clause 5.19)
3.13a Automatic Air Release Valve Yes For vertical turbine and for side MR
suction/side discharge pumps
(clause 6.3.3)
3.14a Suction strainer Yes Basket strainer on suction MR
manifold of each pump
(clause 7.3.4)

Doc.: 2951-CL-001 Rev.0 Page 21


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

3.15a Starting and Control Manual Automatic / Manual MR


(clause 10.5)
Each pump shall have
individual pressure sensing line

3.16a - Diesel Engine Drive Yes Listed by Testing Lab. MR


(clause 11.2.1)
I - Instrumentation & Control Yes Governor MR
Yes Over speed shut down device MR
Yes Tachometer MR
Yes Oil pressure gauge MR
Yes Temperature Gauge MR
Yes Instrument panel MR
Yes (clause 11.2.4.1 to 11.2.4.7) MR
ii - Starting Method Yes 2 storage battery units MR
Yes 2 means for recharging - MR
storage batteries
(clause 11.2.5.2.1 & 11.2.5.3)
iii - Engine Cooling Heat Exchanger Heat exchanger / radiator MR
(clause 11.2.6)
iv - Fuel Tank Capacity Min. 8-hours (clause 11.4.3) MR

v - Fuel Tank Construction SRAP


Single wall Without containment

vi - Fuel Tank Level Gauge No - SRAP

3.17a Pump Condition Not Good -


Shaft Packing is leaked

3.18a Service Sweet Water -

3.19a Pump Controller UL Listed Listed by Testing Lab.


Not connected with Fire
(clause 12.1.3) water Pump
I Locked cabinet for switches with Yes All switches required to keep MR
break glass panel controller in automatic position
shall be in locked cabinet with
break glass panels(clause 12.3.4)

ii Automatic position indicator Yes clause 12.4.1.2 MR

iii Low oil pressure indicator Yes Visible indication critically low MR
oil pressure in the lubrication
system (clause 12.4.1.3(1))

iv clause 12.4.1.3 (2) MR


High eng. Jacket coolant temperature Yes

v Engine start failure indication Yes clause 12.4.1.3 (3) MR

Doc.: 2951-CL-001 Rev.0 Page 22


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

vi Shutdown from over speed indicator Yes clause 12.4.1.3 (4) MR

vii Battery failure indicator for each Yes clause 12.4.1.3 (5) MR
battery

viii Low hydraulic pressure indicator Yes clause 12.4.1.3 (7) MR

ix Battery charger failure indicator for Yes clause 12.4.1.3 (6) MR


each controller.

x Common audible alarm Yes clause 12.4.1.3 MR

xi Alarm silencing switch Yes Not allowed, clause 12.4.1.4 MR

xii Pressure switch Yes clause 12.5.2.1 MR

xiii Pressure recorder device or Yes clause 12.4.4 (Not reqd. for non- MR
pressure sensing line pressure actuated controller.

xiv Voltmeter for each battery bank Yes Accuracy +/- 5% MR


clause 12.4.5

xv Shutdown Manual clause 12.5.5 MR

xvi Weekly program timer Yes clause 12.5.2.7 MR

Doc.: 2951-CL-001 Rev.0 Page 23


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

3.0 PRESSURE MAINTENANCE


(b) (JOCKEY PUMP) Not Available
3.1b Design Code

3.2b UL listed and FM approved -

3.3b Type of pump -

3.4b Pressure Gauges -

3.5b Valves at Suction Piping -

3.6b Valves at Discharge Piping -

3.7b Rated Flow Rate -

3.8b Maximum Head -

3.9b Service -

3.10b Pump Condition -

3.11b Pressure Switch -

3.12b Pressure Safety Valve

Doc.: 2951-CL-001 Rev.0 Page 24


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(a) FLOOR Ist (divided into two portions i.e., half at east and half at west side)
4.1a Design code Not known NFPA-14 (1996 Ed.)

4.2a Controlling valves N/A Indicating type listed


(Clause 2-6)

4.3a (i) Hose Station - Cabinets Easily accessible in case MR


East side Cabinet is accessible of fire

West side Cabinet is inside (Clause 2-7.1.1) SRAP


Toilet and not accessible.
4.3a (ii) Dedicated for fire equipement
Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3a (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4a Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5a Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6a Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7a Hose Station - Label No label " fire hose for use by SRAP
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 25


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8a Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9a Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet MR
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10a Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 26


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(b) FLOOR 2nd (divided into two portions i.e., half at east and half at west side)
4.1 b Design code Not known NFPA-14 (1996 Ed.)

4.2 b (i) Controlling valves N/A Indicating type listed


(Clause 2-6)

4.3 b (i) Hose Station - Cabinets Easily accessible in case MR


East side Cabinet is accessible of fire
(Clause 2-7.1.1) SRAP
West side Cabinet is inside
Server Room and not accessible.
4.3b (ii) Dedicated for fire equipement
Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3b (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4b Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5 b Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6 b Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7 b Hose Station - Label No label " fire hose for use by SRAP
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 27


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8 b Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9 b Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10 b Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 28


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(c) FLOOR 3rd (divided into two portions i.e., half at east and half at west side)
4.1 c Design code Not known NFPA-14 (1996 Ed.)

4.2 c Controlling valves N/A Indicating type listed


(Clause 2-6)

4.3c (i) Hose Station - Cabinets Both East and West Sides are Easily accessible in case MR
accessible of fire
(Clause 2-7.1.1)

4.3c (ii) Dedicated for fire equipement


Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3c (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4 c Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5 c Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6 c Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7 c Hose Station - Label No label " fire hose for use by MR
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 29


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8 c Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9 c Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10 c Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 30


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(d) FLOOR 4th (divided into two portions i.e., half at east and half at west side)
4.1 d Design code Not known NFPA-14 (1996 Ed.)

4.2 d Controlling valves N/A Indicating type listed MR


(Clause 2-6)

4.3d (i) Hose Station - Cabinets Both East and West Sides are Easily accessible in case MR
accessible of fire
(Clause 2-7.1.1)

4.3d (ii) Dedicated for fire equipement


Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3d (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4 d Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5 d Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6 d Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7 d Hose Station - Label No label " fire hose for use by SRAP
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 31


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8 d Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9 d Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10 d Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 32


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(e) FLOOR 5th (divided into two portions i.e., half at east and half at west side)
4.1e Design code Not known NFPA-14 (1996 Ed.)

4.2e Controlling valves N/A Indicating type listed


(Clause 2-6)

4.3e (i) Hose Station - Cabinets Easily accessible in case MR


West side Cabinet is accessible of fire
East side Cabinet is not (Clause 2-7.1.1) SRAP
accessable.
4.3e (ii) Dedicated for fire equipement
Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3e (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4e Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5e Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6e Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7e Hose Station - Label No label " fire hose for use by SRAP
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 33


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8e Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9e Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10e Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 34


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(f) FLOOR 6th (divided into two portions i.e., half at east and half at west side)
4.1f Design code Not known NFPA-14 (1996 Ed.)

4.2f Controlling valves N/A Indicating type listed


(Clause 2-6)

4.3f (i) Hose Station - Cabinets Easily accessible in case MR


West side Cabinet is accessible of fire
East side Cabinet is not (Clause 2-7.1.1) SRAP
accessable.
4.3f (ii) Dedicated for fire equipement
Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3f (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4f Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5f Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6f Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7f Hose Station - Label No label " fire hose for use by MR
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 35


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8f Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9f Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10f Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 36


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(g) FLOOR 7th (divided into two portions i.e., half at east and half at west side)
4.1g Design code Not known NFPA-14 (1996 Ed.)

4.2 g Controlling valves N/A Indicating type listed


(Clause 2-6)

4.3g (i) Hose Station - Cabinets Easily accessible in case MR


West side Cabinet is accessible of fire
East side Cabinet is not (Clause 2-7.1.1) SRAP
accessable.
4.3g (ii) Dedicated for fire equipement
Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3g (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4 g Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5 g Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6 g Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7 g Hose Station - Label No label " fire hose for use by MR
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 37


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8 g Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9 g Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10 g Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 38


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(h) FLOOR 8th (divided into two portions i.e., half at east and half at west side)
4.1h Design code Not known NFPA-14 (1996 Ed.)

4.2h Controlling valves N/A Indicating type listed


(Clause 2-6)

4.3h (i) Hose Station - Cabinets Easily accessible in case MR


West side Cabinet is accessible of fire
East side Cabinet is not (Clause 2-7.1.1) SRAP
accessable.
4.3h (ii) Dedicated for fire equipement
Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3h (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4h Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5h Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6h Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7h Hose Station - Label No label " fire hose for use by MR
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 39


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8h Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9h Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10h Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 40


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(i) FLOOR 9th (divided into two portions i.e., half at east and half at west side)
4.1i Design code Not known NFPA-14 (1996 Ed.)

4.2i Controlling valves N/A Indicating type listed


(Clause 2-6)

4.3i (i) Hose Station - Cabinets Easily accessible in case MR


West side Cabinet is accessible of fire
(Clause 2-7.1.1)

4.3i (ii) Dedicated for fire equipement


Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3i (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4i Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5i Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6i Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7i Hose Station - Label No label " fire hose for use by MR
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 41


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8i Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9i Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10i Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

Doc.: 2951-CL-001 Rev.0 Page 42


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(j) FLOOR Ground
4.1j Design code Not known NFPA-14 (1996 Ed.)

4.2j Controlling valves N.A. Indicating type listed


(Clause 2-6)

4.3j (i) Hose Station - Cabinets Not Available Easily accessible in case SRAP
of fire
(Clause 2-7.1.1)

4.3j (ii) Dedicated for fire equipement


N.A. and conspicuously identified
(Clause 2-7.1.1)

4.3j (iii) For break glass type cabinet


N.A. device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4j Hose Station - Hose No UL listed Hose SRAP


(Clause 2-7.2)

- Maximum length of hose


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5j Hose Station - Hose rack No Each 1 1/2" hose station with SRAP
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6j Hose Station - Nozzle No Listed for class II SRAP


(Clause 2-7.4)

4.7j Hose Station - Label No label " fire hose for use by SRAP
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 43


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8j Hose Connection N.A. Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9j Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10j Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

4.11j Fire Department Connection Yes No Shut-off valve b/w fire MR


department Connection and the
system

(Clause 4-3.1)

Yes Listed Check valve b/w fire MR


department Connection and the
system

(Clause 4-3.2)

No Location shall be on street side of Coupling is not connected


buildings, fully visible and SRAP
accessable.

(Clause 4-3.5.1)

1 No. 2 Nos. remotely located for High SRAP


rise buildings.
(Clause 5-12.2)

Doc.: 2951-CL-001 Rev.0 Page 44


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.0 FIRE WATER NETWORK:


(k) FLOOR Basement
4.1k Design code Not known NFPA-14 (1996 Ed.)

4.2k Controlling valves Yes Indicating type listed


(Clause 2-6)

4.3k (i) Hose Station - Cabinets 2 Nos. Available Easily accessible in case MR
of fire
(Clause 2-7.1.1)

4.3k (ii) Dedicated for fire equipement


Yes and conspicuously identified MR
(Clause 2-7.1.1)

4.3k (iii) Break Glass Device is not For break glass type cabinet SRAP
available device break the glass panel
shall be attached securely
(Clause 2-7.1.2)

4.4k Hose Station - Hose Yes UL listed Hose MR


(Clause 2-7.2)

100 - 150 ft. Maximum length of hose MR


100 ft and Dia.1 1/2" attached
for ready use
(Clause 2-7.2)

4.5k Hose Station - Hose rack Yes Each 1 1/2" hose station with MR
1 1/2" hose shall be equiped
with listed rack or approved
facility
(Clause 2-7.3)

N/A Each 1 1/2" hose station with


less than 1 1/2" hose shall be
equiped with listed continous
flow reel
(Clause 2-7.3)

4.6k Hose Station - Nozzle Yes Listed for class II MR


(Clause 2-7.4)

4.7k Hose Station - Label No label " fire hose for use by SRAP
occupants" and operating
instructions shall be available
on each rack
(Clause 2-7.5)

Doc.: 2951-CL-001 Rev.0 Page 45


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

4.8k Hose Connection Yes Hose connection externally MR


threaded per NFPA 1963 shall
be equiped wuth cap
(Clause 2-8)

4.9k Type of Standpipe System Automatic Wet Automatic Dry, Automatic Wet
Semi-Automatic Dry,
Manual Dry & Manual Wet
(Clause 3-2)

4.10k Class of Standpipe System Class II Class I, Class II & Class III
(Clause 3-3)

4.11k Isolation Valves No Isolation Valve should be SRAP


provided at each standpipe.
(Clause 4-2.2)

4.12 k (i) Drains No Each standpipe shall have


draining system at downstream of SRAP
isolation valve

(Clause 5-11.1)

4.12 k (ii) No Sizes as per Standpipe : SRAP


Upto 2" : 3/4" or lrager
2 1/2" to 3 1/2" : 1 1/4" or lrager
4" or > : 2" only
(Clause 5-11.2)

Doc.: 2951-CL-001 Rev.0 Page 46


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

5.0 OTHER REQUIREMENTS


(a) FLOOR Ist
5.1a Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (6 Nos.)
- MR
CO2 - 6 Kg CO2 - 6 Kg (4 Nos.)

5.2a Inergen System / CO2 System - - -

5.3a FM 200 System - - -

5.0 OTHER REQUIREMENTS


(b) FLOOR 2nd
5.1b Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (5 Nos.)
- MR
CO2 - 6 Kg CO2 - 6 Kg (3 Nos.)

5.2b Inergen System / CO2 System - - -

5.3b FM 200 System Yes (Server Room) - MR

5.0 OTHER REQUIREMENTS


(c) FLOOR 3rd
5.1c Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (5 Nos.)
- SRAP
CO2 - 6 Kg CO2 - 6 Kg (5 Nos.)

5.2c Inergen System / CO2 System - - -

5.3c FM 200 System - - -

5.0 OTHER REQUIREMENTS


(d) FLOOR 4th
5.1d Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (5 Nos.)
- MR
CO2 - 6 Kg CO2 - 6 Kg (2 Nos.)

5.2d Inergen System / CO2 System - - -

5.3d FM 200 System - - -

5.0 OTHER REQUIREMENTS


(e) FLOOR 5th
5.1e Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (5 Nos.)
- MR
CO2 - 6 Kg CO2 - 6 Kg (3 Nos.)

5.2e Inergen System / CO2 System - - -

5.3e FM 200 System - - -

5.0 OTHER REQUIREMENTS


(f) FLOOR 6th
5.1f Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (5 Nos.)
- MR
CO2 - 6 Kg CO2 - 6 Kg (3 Nos.)

5.2f Inergen System / CO2 System - - -

5.3f FM 200 System - - -

Doc.: 2951-CL-001 Rev.0 Page 47


NA - NOT APPLICABLE
CHECKLIST/ SURVEY REPORT SRAP - SEE REMEDIAL
ACTION PLAN
STAGE-I (GAP ANALYSIS OF EXISTING FIRE MR - MEETS REQUIREMENT
NR - NOT REQUIRED

FIGHTING SYSTEM AT PSO HOUSE-CLIFTON)

S.NO. DESCRIPTION EXISTING NFPA REMARKS


REQUIREMENT

5.0 OTHER REQUIREMENTS


(g) FLOOR 7th
5.1g Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (5 Nos.)
- MR
CO2 - 6 Kg CO2 - 6 Kg (3 Nos.)

5.2g Inergen System / CO2 System - - -

5.3g FM 200 System - - -

5.0 OTHER REQUIREMENTS


(h) FLOOR 8th
5.1h Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (5 Nos.)
- MR
CO2 - 6 Kg CO2 - 6 Kg (3 Nos.)

5.2h Inergen System / CO2 System - - -

5.3h FM 200 System Yes (IT Room) - MR

5.0 OTHER REQUIREMENTS


(i) FLOOR 9th
5.1i Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (4 Nos.) - SRAP

5.2i Inergen System / CO2 System - - -

5.3i FM 200 System - - -

5.0 OTHER REQUIREMENTS


(j) FLOOR Ground
5.1j Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (6 Nos.)
- SRAP
CO2 - 6 Kg CO2 - 6 Kg (3 Nos.)

5.2j Inergen System / CO2 System No (Generator Room) - SRAP

5.3j FM 200 System - - -

5.0 OTHER REQUIREMENTS


(k) FLOOR Basement
5.1k Fire Extinguisher
Type: DCP- 6 Kg Yes DCP- 6Kg (8 Nos.)
- SRAP
CO2 - 6 Kg CO2 - 50 Kg (2 Nos.)

5.2k Inergen System / CO2 System No (Generator Room) - SRAP


No (K.E.S.C. Room)
No (A.C. Plant Room)

5.3k FM 200 System - - -

Doc.: 2951-CL-001 Rev.0 Page 48

You might also like