Download as pdf or txt
Download as pdf or txt
You are on page 1of 6

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO.

3, JULY 2012 1041

Use of Standard 87T Differential Protection for


Special Three-Phase Power Transformers—Part II:
Application and Testing
Zoran Gajić, Member, IEEE

Abstract—Application of standard 87T differential relays for Alternatively, matrix transformation is used when op-
special power transformers is quite simple. In most cases, all tional zero-sequence current reduction is also required.
necessary data are readily available on the rating plate of pro- elements are smaller for than numerical values of corre-
tected special transformers. The presented test cases are either
disturbance data captured in actual installations of special power sponding matrix elements, see [1] and [3].
transformers or RTDS simulations based on actual data for a
dual-core, symmetric, phase-shifting transformer. II. PRACTICAL INSTALLATIONS
Index Terms—Converter transformers, phase-shifting trans- Disturbance files captured in existing special transformer in-
formers, power transformer protection, protective relaying. stallations are used in order to test the proposed universal 87T
differential relay for such applications as shown in [1] and [3].
I. INTRODUCTION A. Converter Transformer
In this section, the recorded file from an installation of a
HIS paper describes the application and testing of a stan-
T dard 87T differential relay for protection of any special
three-phase power transformer [1]. The use of standard trans-
24-pulse converter transformer is presented. The transformer is
constructed by using two, three-winding transformers, of very
similar design. They are used together in order to achieve a re-
former differential protection for these applications is consid- quired phase-angle shift. The first transformer (i.e., T1) has the
ered impossible in the protective relaying standards and prac- vector group while the second transformer (i.e.,
tices currently applied [4], [6]. T2) has the vector group in accordance with [7].
As stated in [1] and [3], the following equation can be used to All of the necessary information to apply the differential protec-
calculate differential currents for arbitrary power transformers: tion for this application is given in Fig. 1.
Due to CT availability, the differential protection for this con-
(1.1) verter transformer can be arranged in two different ways:
• With two, three-winding 87T differential relays each pro-
tecting one transformer as shown in Fig. 1.
where are phase-wise differential currents, are • With one, overall 87T differential relay with six restraint
winding phase currents, is the number of windings within inputs protecting both transformers as one unit.
the protected power transformer, is a factor providing The presented disturbance recording was captured during the
magnitude compensation of winding i currents, and is normal through-load condition by an existing digital overcurrent
a 3 3 matrix that provides phase-angle shift compensation relay installed on transformer T2 with a sampling rate of 20
and optional zero-sequence current reduction. When only the samples/power system cycle. The 13.8-kV winding is taken as
phase-angle shift compensation for angle is needed, the MX the reference winding for phase-angle shift compensation, and
matrix is equal to matrix transformation defined in [1] the maximum power has a value of 7.0 MVA for transformer
T2. Thus, base currents and required compensation matrices for
every T2 winding are shown in Table I. Once these base currents
and MX matrices are determined, differential currents can be
calculated in accordance with

(1.2)

Manuscript received February 06, 2009; revised May 05, 2010; accepted
March 06, 2011. Date of publication March 13, 2012; date of current version
June 20, 2012. Paper no. TPWRD-00104-2009.
The author is with the ABB AB, Substation Automation Products, Vasteras
SE-721 59, Sweden (e-mail: zoran.gajic@se.abb.com).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. (1.3)
Digital Object Identifier 10.1109/TPWRD.2011.2178273

0885-8977/$31.00 © 2012 IEEE


1042 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012

Fig. 2. Evaluation of the DR file captured in the converter transformer


installation.

B. PST of Asymmetrical Type, Dual Core Design


In this section, the recorded files from two identical PSTs po-
sitioned at one end of the two parallel 380-kV overhead lines
(OHL) are presented. Every PST is of asymmetric, dual-core de-
sign [6] with a rating of 1630 MVA, 50 Hz, and 400 kV .
A relevant part of the PST rating plate is shown in Fig. 3. The
onload tap changer (OLTC) was on position 30 when this fault
occurred. From data presented in Fig. 3 the following equation is
written for OLTC position 30 in accordance with the universal
87T relay methodology presented in [1] and [3]. These PSTs
have five-limb core construction for both internal transformers
(i.e., serial and excitation transformers). Therefore, the zero-se-
quence current will be properly transferred across the PST, and
Fig. 1. Application data and vector diagram for the 24-pulse transformers. matrices shall be used on both PST sides

TABLE I
COMPENSATION DATA FOR T2

(1.4)

In a similar way, this matrix equation can be written for any


other OLTC position if appropriate values from Fig. 3 are given
The recorded currents were imported into the MATLAB for the base current and the phase-angle shift on the load side of
model incorporating the universal differential protection the PST.
method [3], and the results of its calculation are shown in The captured fault involved two simultaneous single-
Fig. 2. In this figure, the following traces are presented: phase-to-ground faults on two OHLs on the L-side of the PSTs.
• T2-W1 current waveforms in %; On OHL #1, it was a phase L2 to ground fault and on OHL #2,
• T2-W2 current waveforms in %; it was a phase L1 to ground fault. These two recordings were
• T2-W3 current waveforms in %; captured by existing numerical differential relays having sam-
• instantaneous differential current waveforms calculated by pling rates of 12 samples/power system cycle. Recorded source
using (1.3) in %; and load-side current waveforms were run in the MATLAB
• rms value of differential currents calculated by using (1.3) model of the universal 87T differential relay. In Figs. 4 and 5,
in %. the following traces are presented:
From the waveforms shown in Fig. 2, it can be seen that W2 • PST S-side current waveforms in per unit;
and W3 load currents are reached in odd harmonics. However, • PST L-side current waveforms in per unit;
these harmonics do not cause any problem for the presented • instantaneous differential current waveforms calculated by
87T differential relay principle because all three differential rms using (1.4) in per unit;
currents, shown as the fifth trace in the same figure, are well • rms values of differential currents calculated by using (1.4)
under 1% when transformer load is 40% of rated. in per unit;
GAJIĆ: USE OF STANDARD 87T DIFFERENTIAL PROTECTION FOR SPECIAL THREE-PHASE POWER TRANSFORMERS—PART II 1043

Fig. 5. Evaluation of the DR file for the second PST.

30 confirming the rules stated in [3]. Note that neither the fault
inception nor the fault clearance has any practical influence on
the phase-angle shift of 16 between sequence current compo-
nents from the two sides of the protected PST.

C. PST With Special Construction


In this section, the recorded files from PST with special
construction are presented. This transformer can be used as a
conventional 400-MVA, 50-Hz, 400/220/(10.5)kV, YNauto(d5)
autotransformer with an OLTC in the neutral point or as a
phase-shifting transformer connecting 400-kV and 220-kV
networks. The power transformer has a tertiary, unloaded,
Fig. 3. Part of nameplate for 1630-MVA, 400-kV, 18 quad booster PST. delta-connected, equalizer winding. A relevant part of the PST
rating plate is shown in Table II. More information about this
PST can be found in [2].
The presented disturbance recordings were captured by an ex-
isting numerical differential relay with a sampling rate of 20
samples/power system cycle. The OLTC was on position 25
when the presented fault case occurred. Thus, from data pre-
sented in Table II, (1.5) can be written for OLTC position 25
in accordance with the universal 87T differential relay theory
presented in [1] and [3]. Due to the existence of a tertiary delta
winding, the M0 compensation matrices shall be used on both
sides of the protected transformer in order to remove the zero-se-
quence current. This is necessary in order to stabilize the 87T
relay for any external faults involving ground

Fig. 4. Evaluation of the DR file for the first PST.

• phase-angle difference between positive- and negative-se- (1.5)


quence currents from two PST sides during a disturbance.
Figs. 4 and 5 show that during this special external fault,
individual phase currents had values on the order of 10 p.u., The recorded currents were imported into the MATLAB
while the differential rms currents calculated by the universal model incorporating the universal differential protection
87T differential relay remain within 0,15 p.u. (i.e., 15%) of the method, and the results of its calculation are shown in Fig. 6.
PST rating for both transformers. This indicates that the uni- The following traces, either extracted or calculated from this
versal 87T differential relays would remain completely stable recorded file, are presented:
during this special external fault. The measured phase-angle • 400-kV current waveforms in percent;
shift between positive- and negative-sequence current compo- • 220-kV current waveforms in percent;
nents from the two PST sides is and it corresponds well • instantaneous differential current waveforms calculated by
with the actual phase-angle shift for this PST at OLTC position using (1.5) in percent;
1044 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012

TABLE II
NAMEPLATE IN THE PST OPERATING MODE

Fig. 6. Evaluation of the DR file during an external L3-N fault on the 220-kV
side.

Fig. 7. Evaluation of the DR file captured during OLTC tapping.

are used to calculate differential currents within the universal


87T differential relays for this PST at OLTC position 14 and 15,
respectively

• rms value of differential currents calculated by using (1.5)


in percent;
• calculated phase-angle difference between positive- and
negative-sequence current components from the two PST
sides. (1.6)
Fig. 6 shows that for this heavy external fault, the differen-
tial rms current values remain within 1% of the PST rating,
indicating that the universal differential relay will remain
completely balanced during this external fault. The measured
phase-angle shift between positive- and negative-sequence
current components from the two PST sides is and (1.7)
it corresponds extremely well with the actual transformer
phase-angle shift for OLTC position 25. Note that neither the
fault inception nor the fault clearance has any practical influ- In Fig. 7, the following traces, either extracted or calculated
ence on the phase-angle shift of 6.7 between sequence current from the recorded file, are presented:
components from the two sides of the protected PST. • 400-kV current waveforms in percent;
Disturbance files have also been captured at the moment of • 220-kV current waveforms in percent;
an OLTC tapping in the PST operating mode. The PST OLTC • rms values of the differential currents calculated by using
tap position was changed from position 14 to position 15 and (1.6) and (1.7), in percent;
the behavior of the universal differential protection method was • calculated phase-angle difference between positive-se-
checked during OLTC operation. The following two equations quence current components from the two PST sides.
GAJIĆ: USE OF STANDARD 87T DIFFERENTIAL PROTECTION FOR SPECIAL THREE-PHASE POWER TRANSFORMERS—PART II 1045

Fig. 9. Overall system SLD used for RTDS simulations.

The main goal of this RTDS simulation was to gain current


waveforms on both sides of the PST during faults (either
external or internal) for different phase-angle shifts across
the PST. The current measurement was performed on circuit
breakers (CBs) located on both sides of the PST. In this sim-
ulation, the current transformers (CTs) were not simulated,
so the influence of the CT saturation during a fault could not
be obtained. The external faults F1 and F2 were simulated on
the source and load side. The internal faults F3 and F4 were
simulated on the series transformer as well as on the booster
transformer. The simulated fault positions are shown in Fig. 8.
Fig. 8. Used PST model and fault locations. For each fault point, four different fault types are simulated:
L1-L2-L3, L1-L2, L2-L3-G, and L3-G. The sampling rate of
400 samples/power system cycle was used in output files from
Number one in Fig. 7 indicates the time instant of OLTC tap- the RTDS simulator.
ping and number two indicates the time instant when the uni- The first group of faults was simulated for 25 no-load phase-
versal 87T relays changes internal compensation to the values angle shift in the advanced operating mode. This was the highest
which correspond to the new OLTC position 15 (i.e., when the phase-shift angle that could be obtained for this particular PST.
87T relay starts to internally use (1.7) instead of (1.6) to calcu- All aforementioned fault types in all four fault location points
late differential currents). were simulated.
The second group of faults was simulated for 15 no-load
phase-angle shift in the advanced operating mode. All afore-
III. RTDS SIMULATIONS
mentioned fault types in all four fault-location points were
Data files obtained by RTDS simulations [5] are used in this simulated.
section in order to test the universal 87T differential relay prin- The third group of faults was simulated for a 2.5 no-load
ciples presented in [1] and [3]. phase-angle shift in the advanced operating mode. All afore-
The simulated PST (Fig. 8) was of symmetric type, dual core mentioned fault types in all four fault-location points were
design. The main PST data used for this simulation are rated simulated.
power 1400 MVA, rated voltages 400/400 kV, rated frequency The source and load-side currents obtained from the RTDS
50 Hz, and angle variation 25 (at no load). The PST data are simulator were run in the MATLAB model of the universal 87T
based on a practical PST designed used in actual installation. differential protection. Once the six currents from the two PST
Each PST phase was simulated as two separate single-phase sides for each fault were obtained, the next step involved cal-
transformers. The simulation was preformed with the RTDS culation of the differential currents in accordance with the new
simulator [5]. The simulated network consisted of a PST, two method introduced in [1] and [3]. The calculations were made
20-km-long, 400-kV lines (one on each PST side) and two ac- with the MATLAB model of the universal differential current
tive sources (one on each PST side). In this simulation case, measurement technique. In Figs. 10 and 11, the following traces
the 400-kV lines were simulated with a T-line model in the are presented:
RTDS. To demonstrate the influence of the PST phase-angle • PST S-side individual phase current waveforms in per unit;
shift change, a parallel path had to be introduced in the circuit • PST L-side individual phase current waveforms in per unit;
connecting the two 400-kV buses (i.e., in parallel with the se- • instantaneous differential current waveforms calculated by
rial connection of the PST and two 400-kV OHLs). This parallel the new method in per unit;
path is simulated with a -section line model in RTDS. Overall • rms values of differential currents calculated by the new
SLD of the simulated system is shown in Fig. 9. method in per unit.
1046 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 27, NO. 3, JULY 2012

IV. CONCLUSION
In this paper, it has been shown that the standard 87T differen-
tial relay for an arbitrary three-phase power transformer [1], [3]
will remain fully stable for all symmetrical and nonsymmetrical
external faults irrespective of actual construction details of the
protected transformer. At the same time, this differential protec-
tion will correctly operate for all types of internal faults.
The application of such universal 87T relays for special trans-
formers is quite straightforward because all necessary data are
readily available on the protected transformer rating plate.

REFERENCES
[1] Z. Gajić, “Use of standard 87T differential protection for special three-
Fig. 10. External L2-L3-G fault at F1, for a 25 phase-angle shift. phase power transformers part I: Theory,” IEEE Trans. Power Del., vol.
27, no. 3, pp. 1035–1040, Jul. 2012.
[2] Z. Gajić, I. Ivanković, and B. Filipović-Grčić, “Differential protection
issues for combined autotransformer—Phase shifting transformer,”
presented at the Inst. Elect. Eng. Conf. Develop. Power Syst. Protect.,
Amsterdam, The Netherlands, Apr. 2004.
[3] Z. Gajić, “Differential protection for arbitrary three-phase power trans-
formers,” Ph.D. dissertation, Lund University, Lund, Sweden, 2008.
[4] Working Group K1, “Protection of phase angle regulating transformers
(PAR), ” Oct. 1999, Report to the Substation Subcommittee of the IEEE
Power Syst. Relay. Comm.
[5] RTDS Technologies Inc., Real time digital simulators (RTD) and sim-
ulation services for the electrical power industry. [Online]. Available:
http://www.rtds.com
[6] Guide for the Application, Specification, and Testing of Phase-Shifting
Transformers, Int. Standard IEC 62032/IEEE C57.135, Mar. 2005, 1st
ed.
[7] Power Transformer, IEC 60076, Oct. 1997, 1st ed.

Zoran Gajić (M’95) was born in Serbia. He received


the Ph.D. degree in electrical engineering from Lund
Fig. 11. Internal L3-G fault at F3, for a 25 phase-angle shift. University, Lund, Sweden, in 2008.
Since 1993, he has been working in the area of
power system protection and control within ABB,
where he has held various engineering positions.
Fig. 10 shows an external fault at location F1, for a 25 phase- Currently, he is Product Manager for Transformer
angle shift, for which differential rms currents remain smaller and Generator Protection with ABB AB, SA Prod-
ucts, Vasteras, Sweden. His main working areas are
than 0,05 p.u. (i.e., 5%) of the PST rating, indicating that the practical applications of protection relays, computer
universal differential relay will remain completely stable during applications for the protection and control of elec-
this external fault. trical power systems, and the development of advanced protection algorithms
for numerical relays and power system simulations.
Fig. 11 shows an internal fault at location F3, for a 25 phase- Dr.Gajić is a member of CIGRÉ and the IEEE Power and Energy Society. He
angle shift, for which the differential rms currents will reach a was the convener for CIGRÉ, Study Committee B5, WG16 “Modern techniques
value of 1,5 p.u. (i.e., 150%) of the PST rating, indicating that for protecting busbars in hv networks.” Currently, he is the convener for CIGRÉ,
Study Committee B5, WG44 “Protection schemes for special transformers.” He
the universal differential relay will operate correctly for such an has published many technical papers in the relay protection area. He is the holder
internal fault. or co-holder of several patents.

You might also like