Professional Documents
Culture Documents
Diferencijalan Zastita Application and Testing - Zoran Gajic
Diferencijalan Zastita Application and Testing - Zoran Gajic
Abstract—Application of standard 87T differential relays for Alternatively, matrix transformation is used when op-
special power transformers is quite simple. In most cases, all tional zero-sequence current reduction is also required.
necessary data are readily available on the rating plate of pro- elements are smaller for than numerical values of corre-
tected special transformers. The presented test cases are either
disturbance data captured in actual installations of special power sponding matrix elements, see [1] and [3].
transformers or RTDS simulations based on actual data for a
dual-core, symmetric, phase-shifting transformer. II. PRACTICAL INSTALLATIONS
Index Terms—Converter transformers, phase-shifting trans- Disturbance files captured in existing special transformer in-
formers, power transformer protection, protective relaying. stallations are used in order to test the proposed universal 87T
differential relay for such applications as shown in [1] and [3].
I. INTRODUCTION A. Converter Transformer
In this section, the recorded file from an installation of a
HIS paper describes the application and testing of a stan-
T dard 87T differential relay for protection of any special
three-phase power transformer [1]. The use of standard trans-
24-pulse converter transformer is presented. The transformer is
constructed by using two, three-winding transformers, of very
similar design. They are used together in order to achieve a re-
former differential protection for these applications is consid- quired phase-angle shift. The first transformer (i.e., T1) has the
ered impossible in the protective relaying standards and prac- vector group while the second transformer (i.e.,
tices currently applied [4], [6]. T2) has the vector group in accordance with [7].
As stated in [1] and [3], the following equation can be used to All of the necessary information to apply the differential protec-
calculate differential currents for arbitrary power transformers: tion for this application is given in Fig. 1.
Due to CT availability, the differential protection for this con-
(1.1) verter transformer can be arranged in two different ways:
• With two, three-winding 87T differential relays each pro-
tecting one transformer as shown in Fig. 1.
where are phase-wise differential currents, are • With one, overall 87T differential relay with six restraint
winding phase currents, is the number of windings within inputs protecting both transformers as one unit.
the protected power transformer, is a factor providing The presented disturbance recording was captured during the
magnitude compensation of winding i currents, and is normal through-load condition by an existing digital overcurrent
a 3 3 matrix that provides phase-angle shift compensation relay installed on transformer T2 with a sampling rate of 20
and optional zero-sequence current reduction. When only the samples/power system cycle. The 13.8-kV winding is taken as
phase-angle shift compensation for angle is needed, the MX the reference winding for phase-angle shift compensation, and
matrix is equal to matrix transformation defined in [1] the maximum power has a value of 7.0 MVA for transformer
T2. Thus, base currents and required compensation matrices for
every T2 winding are shown in Table I. Once these base currents
and MX matrices are determined, differential currents can be
calculated in accordance with
(1.2)
Manuscript received February 06, 2009; revised May 05, 2010; accepted
March 06, 2011. Date of publication March 13, 2012; date of current version
June 20, 2012. Paper no. TPWRD-00104-2009.
The author is with the ABB AB, Substation Automation Products, Vasteras
SE-721 59, Sweden (e-mail: zoran.gajic@se.abb.com).
Color versions of one or more of the figures in this paper are available online
at http://ieeexplore.ieee.org. (1.3)
Digital Object Identifier 10.1109/TPWRD.2011.2178273
TABLE I
COMPENSATION DATA FOR T2
(1.4)
30 confirming the rules stated in [3]. Note that neither the fault
inception nor the fault clearance has any practical influence on
the phase-angle shift of 16 between sequence current compo-
nents from the two sides of the protected PST.
TABLE II
NAMEPLATE IN THE PST OPERATING MODE
Fig. 6. Evaluation of the DR file during an external L3-N fault on the 220-kV
side.
IV. CONCLUSION
In this paper, it has been shown that the standard 87T differen-
tial relay for an arbitrary three-phase power transformer [1], [3]
will remain fully stable for all symmetrical and nonsymmetrical
external faults irrespective of actual construction details of the
protected transformer. At the same time, this differential protec-
tion will correctly operate for all types of internal faults.
The application of such universal 87T relays for special trans-
formers is quite straightforward because all necessary data are
readily available on the protected transformer rating plate.
REFERENCES
[1] Z. Gajić, “Use of standard 87T differential protection for special three-
Fig. 10. External L2-L3-G fault at F1, for a 25 phase-angle shift. phase power transformers part I: Theory,” IEEE Trans. Power Del., vol.
27, no. 3, pp. 1035–1040, Jul. 2012.
[2] Z. Gajić, I. Ivanković, and B. Filipović-Grčić, “Differential protection
issues for combined autotransformer—Phase shifting transformer,”
presented at the Inst. Elect. Eng. Conf. Develop. Power Syst. Protect.,
Amsterdam, The Netherlands, Apr. 2004.
[3] Z. Gajić, “Differential protection for arbitrary three-phase power trans-
formers,” Ph.D. dissertation, Lund University, Lund, Sweden, 2008.
[4] Working Group K1, “Protection of phase angle regulating transformers
(PAR), ” Oct. 1999, Report to the Substation Subcommittee of the IEEE
Power Syst. Relay. Comm.
[5] RTDS Technologies Inc., Real time digital simulators (RTD) and sim-
ulation services for the electrical power industry. [Online]. Available:
http://www.rtds.com
[6] Guide for the Application, Specification, and Testing of Phase-Shifting
Transformers, Int. Standard IEC 62032/IEEE C57.135, Mar. 2005, 1st
ed.
[7] Power Transformer, IEC 60076, Oct. 1997, 1st ed.