Fire Code of the Philippines (RA.

1185)

Rule 3 Division 4 -Sec. 3.401 General Provisions

D. Width and Capacity of Means of Egress:

(1) level egress components (including Class A Ramps) – 100 persons; and inclined egress
components (including Class B Ramps) – 60 persons.

(2) measured in units of exit of fifty five (55) centimeters.

E. Egress Capacity and Occupant Load:

(1) the gross area figure shall then be made of those spaces where occupant load is determined
on the basis exceeds that on the gross area basis, the means of egress shall be based on the larger
occupant load figure.

H. Measurement of Travel Distance to Exits:

(1) starting thirty (30) centimeters from the remote point

(2) In case of individual rooms subject to occupancy by not more than six (6) persons; travel
from any point in the room to the room does not exceed fifteen (15) meters.

Sec. 3.403. Interior Stairs and Smokeproof Tower

B. Classes of Stairs – Stairs shall be Class A or Class B types in accordance with the following
table:

Class A Class B
Minimum width clear of all 112cm; 91 cm
obstruction, except handrails which where total
may protect not more than 89 mm occupancy of all
each side floors
And stringers which may project 112 cm Served by
not more than 38 mm each side stairways is less
than 50
Maximum height of risers 19cm 20 cm
Minimum width of tread exclusive 25cm 23cm
of nosing or projection
Winders None None
Minimum headroom 2m 2m
Maximum height between landings 2.75mm 3.70mm
Minimum dimension of landings in 112 mm 112mm
direction of travel
Doors opening immediately on No No
stairs, without landing, at least
width of door

Rule 3 – Division 5 – Features of Fire Protection

Sec 3.501. Sprinkler Vent Method

(2) The downdraft have an average of not less than ninety one and half (91.5) meters per
minute under a period of not less than thirty (30) minute.

Sec 3.504. Automatic Sprinklers and Other Extinguishing Equipment.

A. Automatic Sprinklers.

(2) Water Supplies:

(a) a public water system, a gravity tank or a pressure tank.

Rule 3 – Division 11 – Mercantile Occupancies

Sec 3.1101. General Requirements. – A. Classification of Occupancy

Class B. - less than two thousand seven hundred eighty seven (2,787) square meters

- over two hundred eighty seven (287) square meters

- more than three (3) floors are utilized, the store shall be considered Class A

B. Classification of Hazard.
(1) Exits shall be located not more than twenty three (23) meters of travel
(2) at least two (2) exits accessible by travel in different directions.
C. Occupant Load
(a) Street floor, one (1) person - (2.8) square meters gross floor area.

(c). Upper floors, used for sale: one (1) persons - (5.6) square meters gross floor area.

(d) Floors or sections used only for office, storage, shipping and not open to the general public:
one (1) person - (9.3) square meters gross floor area.
(f) Covered Walls: One (1) person - (2.8) square meters gross floor area.

F. Measurement of Travel Distance to Exits. – shall be no more than thirty and one-half (30.5)
meters.

Rule 3 – Division 12 – Business Occupancies

Sec 3.1201 C. Occupant Load

(1) The occupant load of business purposes shall be no less than (1) person per (9.3) square
meters of gross floor area.

C. Capacity of Exits

(1) minimum travel time to or from a required shall be one hundred twelve (112) centimeters in
the clear.

F. Measurement of Travel Distance to Exits. –shall not more than sixty one (61) meters.