This document provides specifications for a 3-core power cable with 1 additional messenger conductor. The key details are:
- It is a 6.35/11kV cable with 3 phase conductors of 50mm2 cross-sectional area and 1 messenger conductor of 35mm2.
- The phase conductors have stranded compacted circular aluminum insulation with an XLPE insulation layer, insulation screen, metallic shield, and outer PVC sheath.
- Key ratings are a current capacity of 140A in air, insulation thickness of 3.6mm, and maximum conductor temperature of 90°C.
- The cable will be wound on non-returnable wooden drums in lengths of 1000/500m
This document provides specifications for a 3-core power cable with 1 additional messenger conductor. The key details are:
- It is a 6.35/11kV cable with 3 phase conductors of 50mm2 cross-sectional area and 1 messenger conductor of 35mm2.
- The phase conductors have stranded compacted circular aluminum insulation with an XLPE insulation layer, insulation screen, metallic shield, and outer PVC sheath.
- Key ratings are a current capacity of 140A in air, insulation thickness of 3.6mm, and maximum conductor temperature of 90°C.
- The cable will be wound on non-returnable wooden drums in lengths of 1000/500m
This document provides specifications for a 3-core power cable with 1 additional messenger conductor. The key details are:
- It is a 6.35/11kV cable with 3 phase conductors of 50mm2 cross-sectional area and 1 messenger conductor of 35mm2.
- The phase conductors have stranded compacted circular aluminum insulation with an XLPE insulation layer, insulation screen, metallic shield, and outer PVC sheath.
- Key ratings are a current capacity of 140A in air, insulation thickness of 3.6mm, and maximum conductor temperature of 90°C.
- The cable will be wound on non-returnable wooden drums in lengths of 1000/500m
1 GENERAL Name of Manufacturer Voltage grade kV 6.35/11(12)kV ('E) Standard Applicable Generally as per IS:7098(part-2)
2 PHASE CONDUCTOR(INSULATED ) i. No of phase Conductors 3 ii. Nominal cross-sectional area Sq. mm 50 Diameter of compacted conductor iii. (Approx.) mm 8.4 iv. Max. D.C resistance at 20°C Ohm/km 0.641 v. Insulation thickness (Nominal) mm 3.6 vi. Insulation thickness (Minimum) mm 3.14 Stranded Compacted circular Aluminum of H4 Grade vii. Material as per Class 2 of IS:8130 viii. Max. D.C resistance at 20°C Ohm/km 0.641 x. Standard to which this material confirms Class - 2 of IS:8130-1934
3 CONDUCTOR TEMPERATURE i. Rated Deg. C 90 Deg.C ii. During short circuit Deg. C 250 Deg.C 4 CONDUCTOR SCREEN i. Material Extruded Semi-Conducting compound ii. Thickness(Min) mm 0.3 5 INSULATION i. Material Extruded XLPE as per IS: 7098(Part-2)/85 ii. Thickness(Nom) mm 3.6 iii. Volume Resistivity (Min) at 27 Deg. C:- 1x10 14 ohm-cm at 90 Deg. C:-1x10 12 ohm-cm 6 INSULATION SCREEN i. Material Extruded Semi-Conducting compound ii. Thickness (Min) mm 0.3
7 METALLIC SHIELD i. Material and Thickness Copper Tape of 0.045 mm (Approx.) & 10% overlap
By colored strips of Red, Yellow and blue shall be provided
8 CORE COLOUR under copper tape and R,Y &B shall be printed on outer sheath
9 OUTER SHEATH i. Material Extruded PVC Type ST-2 as per IS :5831/84 ii. Thickness(Nom.) 2 iii. Colour Black
10 MESSENGER CONDUCTOR(BARE) i. Nominal cross-sectional area Sq.mm 35 ii. Material Stranded Aluminium alloy conductor as per IS:398P-4 iii. Approx. Breaking load kN 41 iv. Standard to which this material confirms Generally as per IS:398 P-2/96
11 CABLE DATA i. Current carrying capacity a)In air Ampere 140 b)In Ground Ampere ??? ii. Embossing on any sheathed core KEI cable Electric 6.35/11kV, Cable size ,Year of Manufacture 12 Drum Details In non-Returnable wooden i. Standard Drum Length 1000/500 meter with +/-5% ii. Overall Quantity Tolerance +/-5%