Model: LGH-F470RX5-E

Indoor unit Indoor unit


Lossnay

Job Name:
Remote controller
Schedule Reference: Date:
Line up of LOSSNAY units
LGH-F300RX5-E 300cfm 1-phase 208-230V, 60Hz
ENERGY RECOVERY VENTILATOR
LGH-F470RX5-E 470cfm 1-phase 208-230V, 60Hz
LGH-F600RX5-E 600cfm 1-phase 208-230V, 60Hz
LGH-F1200RX5-E 1200cfm 1-phase 208-230V, 60Hz

GENERAL FEATURES

• Lossnay® cross-flow energy recovery core


• Minimal cross contamination (<1% overall) between entering and leaving air streams
• Stand-alone control
• M-NET
• External input bypass damper control
• Stand alone or interlocks with all Mitsubishi product

SPECIFICATIONS
Capacity . . . . . . . . . . . . . . . . . . . . . . . . . . . . 470 CFM / 17 m3/min External static pressure (In. W.G.)
(fan speed: extra low - low - high - extra high)
Power @ 208V. . . . . . . . . . . . . . . . . . . . . . . . . . . 0.07 - 0.33 - 0.54 - 0.80
Power Source. . . . . . . . . . . . . . . . . . . . 208 - 230V, 1-Phase, 60 Hz @ 230V. . . . . . . . . . . . . . . . . . . . . . . . . . . 0.09 - 0.40 - 0.66 - 0.96
Power Consumption . . . . . . . . . . . . . . . . . . . . . . . 0.120 - 0.538 kW
Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 0.60 - 2.50 A External Finish . . . . . . . . . . . . . . . . . . . . . .Galvanized steel sheet
Starting Current . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4.5 A
Minimum Circuit Ampacity (MCA) . . . . . . . . . . . . . . . . . . . . . . . 3.1 A Dimensions
Maximum Overcurrent Protection (MOCP) . . . . . . . . . . . . . . . . 15 A inches. . . . . . . . . . . . . . . . . . . . .15-3/4 H x 39-1/2 W x 45-1/16 D
mm . . . . . . . . . . . .. . . . . . . . . . . . . . . . . 399 H x 1004 W x 1144 D
Controllers
PZ-60DR Lossnay® Controller: Controls 1-15 Lossnay® units, Net Weight. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 119 lb / 54 kg
ON/OFF, Fan Speed, and Vent Mode
Energy Transfer. . .. . . . . . . . . . . . . . . . . . . . . . . . . Lossnay® core
Operation Mode
• Heat Recovery Heat Exchange System . . . . . . . . . . . . . . . . . . . . . . . Air-to-air
• Bypass total heat (sensible heat + latent heat) exchange, no moving parts
• Auto
Heat Exchange Material . . . . . . . . . . . . . . . . . . Partition, spacing
Air Volume plate-cellulose fiber membrane
(fan speed: extra low - low - high - extra high)
@ 208V . . . . . . . . . . . . . . . . . . . . . . . . 147 - 330 - 420 - 470 CFM Blower . . . . . . . . . . . . . . . . . . . . . . . 9.625 in. dia. centrigugal fan
@ 230V . . . . . . . . . . . . . . . . . . . . . . . . 177 - 365 - 470 - 470 CFM
Motor . . Totally enclosed capacitor permanent split-phase 0.52 HP
Temperature recovery efficiency induction motor, 4 poles, 2 units
(fan speed: extra low - low - high - extra high)
@ 208V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82 - 74 - 70.5 - 69% Filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Washable fiber (2)
@ 230V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 - 72 - 69 - 69%
Entering Air Temperature Operation Range
Enthalphy recovery efficiency 14° F to 104° F (-10° C to 40° C), RH 80% or less
(fan speed: extra low - low - high - extra high)
Heating Sound Pressure Level
@ 208V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80 - 70 - 66 - 64 % (fan speed: extra low - low - high - extra high)
@ 230V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78 - 68 - 64 - 64 % @ 208V . . . . . . . . . . . . . . . . . . . . . . . . . 18 - 28.5 - 33 - 36 dB (A)
@ 230V . . . . . . . . . . . . . . . . . . . . . . . . . 8.5 - 31 - 35.5 - 38 dB (A)
Cooling
@ 208V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69 - 58 - 53 - 51%
@ 230V. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67 - 55 - 51 - 51%
Notes:

Specifications are subject to change without notice.


© 2013 Mitsubishi Electric US, Inc.
(double flanges at SA and EA sides)

øG
øH
• Slim-Lossnay connection cable

N LGH-F470RX5-E – DIMENSIONS (gray: two wires) ................................................... x1


ition where duct Air filters Model:
ction change is possible
Unit: Inch (mm)
Dimensions Ceiling suspension fixture pitch Nominal Duct connecting flange Duct pitch
diameter Weight
A B C D E F G H J K L M N
34 15/16 40 12 3/8 34 1/2 41 7/8 2 9/16 7 7/8 7 9/16 8 3/16 3 1/8 29 3/8 5 5/16 4 7/8 1 3/16 73 lbs
RX5 (888) (1016) (315) (875)
Position where (1063)
duct direction(65)
change is (200) (192) and
possible *LGH-F470 (208) (79)
F600RX5-E types (745) (135.5) (124) (30) (33 g)
Bypass damper plate (4-9/16” X 13/16” (4-15 X 20) oval)
45 1/16 39 1/2 15
Air 3/4
exhaust39fan3/4 40 13/16 15 5/16 Ceiling
M 9 7/8 9 1/2 10 3/16 3 1/8 27 3/16 6 3/16 6 1/2 119 lbs
RX5 (1144) (1004) (399) (1010) (1036)D (389) (4-1/2”
suspension fixture
(250) (242) F (258) (79) (690) (157) (165) (54 g)
X 13/16”
(4-13 X 20) oval)*
45 1/16 48 1/2 15 3/4 39 3/4 49 3/4 15 5/16 9 7/8 9 1/2 10 3/16 3 1/8 36 1/8 6 3/16 6 1/2 132 lbs
RX5 (1144) (1231) (399) (1010) (1263) (389) (250) (242) (258) (79) (917) (157) (165) (60 g)
L

EA RA
(exhaust air outlet) (return air)
B
K

3 3/4 (95)
200RX5-E OA
(outside air intake)
SA
(supply air)
More than 23 5/8 (600)

Bypass damper plate Power supply


13/16
Core, air filter,39
High-
M
Ceiling suspension fixture
cable opening (20) F
5 7/8 ~ 9 7/8

3/4 (1010) N
(150~250)

Air exhaustEfficiency
fan filter, fan, (4-9/16 X 1-3/16 (4-15
Inspection X 30)fan
Air supply o al) C
maintenance space opening
Control box
10 5/8

RA Maintenance cover
(270)

A (return air)
) Lossnay core High-Efficiency filter (sold separately) attachment position
J A J Accessory parts
• Mounting screws ............................................... x16

4 5/16 (110)
A
B

C
D

• Duct connecting flanges ...................................... x4


(double flanges at SA and EA sides)
øG
øH

e) SA
10 5/8

• P-Series - Lossnay connection cable


(270)

(supply air)
(gray: two wires) ................................................... x1
Position where duct Air filters
direction change is possible
More than 23 5/8 (600)

Unit: Inch (mm)


1 1/8 (27)

er 15 3/4 (399)
5 7/8 ~ 9 7/8

y Dimensions Ceiling suspension fixture pitch Nominal Duct connecting flange Duct pitch
(150 ~ 250)

Model Inspection Weight


openingA B C D E 31F7/16diameter
(798) G H J K L M N
e 34 15/16 40 12Air3/8
supply34 fan
1/2 41 7/8 2 9/16 7 7/8 7 9/16 8 3/16 3 1/8 29 3/8 5 5/16 4 7/8 1 3/16 73 lbs
e LGH-F300RX5-E
(888) (1016) Control (315) box (875) (1063) (65) (200) (192) cable
ower supply (208) (79) (745) (135.5) (124) (30) (33 kg)
Maintenance co er
45 1/16 39 1/2 15 3/4 39 3/4 40 13/16 15 5/16 9opening 7/8 9 1/2 10 3/16 3 1/8 27 3/16 6 3/16 6 1/2 – 119 lbs
LGH-F470RX5-E
Lossnay cores High-Efficiency
(1144) (1004) filter (sold
(399)separately)
(1010)attachment
(1036) position
(389) (250) (242) (258) (79) (690) (157) (165) (54 kg)
45 1/1645
1 3/4 (44) LGH-F600RX5-E 1/16 48 1/2 3151/8
(1144) 3/4(79)39 3/4 49 3/4 15 5/16 9 7/8 9 1/2 10 3/16 3 1/8 36 1/8 6 3/16 6 1/2

132 lbs
(1144) (1231) (399) (1010) (1263) (389) (250) (242) (258) (79) (917) (157) (165) (60 kg)

• Duct connecting flanges ...................................... x4


ø10 3/16
ø9 1/2

(ø258)
(ø242)
27 9/16 (700)

• Mounting screws ................................................ x16


• Slim-Lossnay connection cable
LGH-F1200RX5-E1 (gray: two wires) ................................................... x1
ø10 3/16
ø9 1/2

(ø258)
(ø242)

Bypass damper plate


Ceiling suspension fixture Unit: Inch (mm)
39 3/4 (1010) (4-9/16 X 1-3/16 (4-15 X 30) oval)
Air exhaust fan
Air filters Model
A B C D Weight
48 1/2 36 1/8 36 1/8 50 1/8 265 lbs
10 5/8

RA
(270)

LGH-F1200 RX5
EA (return air) (1231) (917) (917) (1272) (120 g)
(exhaust air outlet)
4 5/16 (110)
A
B

C
D

OA
(outside air intake) SA
10 5/8
(270)

(supply air)
More than 23 5/8 (600)

1 1/8 (27)

Core, air filter, 15 3/4 (399)


5 7/8 ~ 9 7/8

High-Efficiency
(150 ~ 250)

filter, Inspection
opening 31 7/16 (798)
fan,
maintenance Air supply fan
space Control box Power supply cable
Maintenance cover opening
Lossnay cores High-Efficiency filter (sold separately) attachment position
1 3/4 (44) 45 1/16 (1144) 3 1/8 (79)
Accessory parts
• Duct connecting flanges ...................................... x4
ø10 3/16
ø9 1/2

(ø258)
(ø242)
27 9/16 (700)

• Mounting screws ................................................ x16


1340 Satellite
• P-Series - Lossnay Boulevardcable
connection
Suwanee, GA 30024
(gray: two wires) ...................................................
Tele: 678-376-2900 • Fax: 800-889-9904
x1
ø10 3/16
ø9 1/2

(ø258)
(ø242)

Toll Free: 800-433-4822


www.mehvac.com
FORM# LGH-F470RX5 - 201310 Unit: Inch (mm)
Specifications are subject to change without notice.
Air filters
© 2013 Mitsubishi Electric US, Inc. Model A B C D Weight
48 1/2 36 1/8 36 1/8 50 1/8 265 lbs