The solenoid operated valve shall be a 24V D.C operated valve which will get energized on
operation of MCP from annunciation panel. The status of its function (open/close) shall be
indicated in the control panel (field junction box). In case the solenoid valve fails to open
within a stipulated time period, the corresponding signal shall appear in the control panel.
The quantity and type of solenoid valves required are as per the bill of quantity mentioned
in annexure-I
Table 12: Technical Parameters of Solenoid Operated Valve
For actuation of Deluge system in auto mode, Quartzoid bulb (QBD) will be used. It shall
be provided with approved SS protection caps. Temperature rating of the QBD's are as
given in table no: 13
The quantity and type of QBD's are required as per the bill of quantity mentioned in
annexure-I
25
S.N. Parameter Description
by purchaser inspection team.
12. Approval UL / FM / BIS
M.S. pipe along with pipe fittings including flanges structural piping and supports shall
be provided from tapping point from yard hydrant pipeline onwards. ERW heavy grade
pipe as per IS 1239 (Part 1) and 1239(Part.2) for size range 15 NB to 150 NB, Material
Specification FE 410 Grade and as per IS 3589:1991 for size 200 NB to 600 NB,
Material Specification FE 410 Grade.
A. Air Compressor
The quantity and type of air compressors required as per the bill of quantity mentioned in
annexure-I
1) Dry type suction air filter cum silencer with filtering element of fiber glass felt
sandwiched between wire mesh with supporting arrangement and fixing bolts, nuts etc.
The suction filter design will be such that it will draw air from minimum 4 sides.
2) Belt guard with fixing arrangement.
3) Intercooler/After coolers.
4) Rotary gear oil pump with oil filter / strainer, oil level indicator and oil piping, pipe
coupling / unions and oil cooler.
5) Teflon rings for piston and teflon gland packing.
6) Foundation bolts & washers for the compressor and after cooler.
7) Non return valve and isolating valve at the discharge side of the compressor.
8) Companion flanges, reducers. tee, bends, nuts, bolts and gaskets for all types of flanged
connections in pipes, valves and equipment.
9) Compressor motor should have 10% margin above the maximum power demand of the
compressor.
10) Pressure gauge at the outlet of compressed air discharge pipe line.
11) Interconnecting pipe work between compressor & air receiver.
12) Erection, testing and commissioning of the compressor.
B. Horizontal Receiver
Horizontal/Vertical self supporting in cylindrical design with dished ends at both ends
having water holding capacity of each air receiver is 0.2 m3. Air receiver will be connected
to compressor. Material of the air receiver shall be IS:2002/equivalent. The air receiver
shall be designed for a working pressure of 7 kg/cm2 (g) and shall be supplied with
following accessories.
27
C. Pipes, Valves & Fittings for compressor & air receiver
1) All the pipes and fittings including valves required for compressed air units & air receiver
unit shall be provided by the Tenderer.
2) The pipe work shall be completed with necessary fittings, valves, strainers, supports,
clamps, etc. whichever is necessary and shall form part of the contract.
3) The values of velocity used in pipe sizing shall conform to 8-10m/s as per normal design
practice.
4) All compressed air piping shall conforming to IS : 1239 Part–I and 1239 Part–II as far as
applicable. The compressed air pipe shall be of “Heavy” thickness, M.S. & black, plain
ends and suitable for arc welding.
D. DOL starter for compressor & electrical wiring from DOL starter to PCC panel in
service room
E. TESTING OF COMPRESSOR
Unless otherwise stated, main equipment, valves and other ancillary units shall be tested to
various stipulations stated in Indian Standards of BIS or any other reputed international
standard listed.
The Water Sprinkler System is a special fixed pipe system. It is connected to a reliable
and dedicated water supply source. The system is well equipped with sprinkler nozzles
of specific water discharge and temperature rating (refer table 13) and impingement over
the area to be protected. The piping system is connected to the water supply through an
automatically actuated Alarm valve which initiates the flow of water. Alarm valves for
the sprinkler system are actuated by activation of sprinkler nozzles.
In event of fire in the facility, the heat responsive frangible glass bulb shatters and water
flows through the sprinkler and strike the deflector. After striking the deflector, flow
deflects and uniform water spray pattern forms which then suppress the fire.
28