Professional Documents
Culture Documents
A Novel Approach To Detect Fault During Power Swing Using Three Phase Active Power
A Novel Approach To Detect Fault During Power Swing Using Three Phase Active Power
Abstract - A novel, fast and reliable distance relay approach is dynamic transient reactions, for instance load fluctuations,
proposed in this work to detect fault during power swing. First of short circuits, and switching phenomenon [9]. The power
all, the voltage and current at relay end is measured and then
swing may cause loss of synchronism between areas within
processed using phasor estimation technique. Next, average of
power system, and results in cascaded events if not attended
three phase active power is estimated and based on the
magnitude of the calculated value the swing and different fault properly [ 10]. In relaying, power swing blocking (PSB)
cases can be discriminated. During power swing, the value is function is provided to restrict any relay malfunction during
always less than the threshold and with the inception of fault the stable swing condition. Also, out-of-step tripping (OST)
value is more than the threshold. The main advantage of the function is provided to differentiate stable from unstable
proposed technique is that within one power cycle time period
swing and to isolate the predetermined network location to
symmetrical fault detection is possible. The system is simulated
maintain system stability and system continuity [7]. For any
on EMTDC/PSCAD environment using and results are presented
for 230-kV, 50 Hz two-area four machine system and New balance or unbalance fault during stable or unstable swing
England 39 test bus system to highlight the effectiveness of the phenomena, the relay should properly detect the fault and
proposed technique. discriminate from swing condition. Also, zone-3 unit of
distance relay is unable to discriminate three phase fault from
Keywords - Stable swing; unstable swing; symmetrical fault; power swing situation and further issues false command [11].
unsymmetrical fault; distance relay; transmission system; high
resistance fault. Over the years, a number of protective relay algorithms
have been developed to detect the swing condition and to
I. INTRODUCTION perform correctly for any further fault in the system [12]-[22].
Distance protection is one of the most widely used Based on magnitude of swing centre voltage (SCV) and its
rate a method is proposed in [12]. For detecting high
protection scheme in long and sub-transmission system [ 1]
resistance fault during power swing the phase angle of voltage
[2]. The fundamental principle of distance relaying is mainly
is applied in [13]. A superimposed based approach is proposed
based on the local end measurements of currents and voltages
in [14]. A rate of change of resistance based fault detection
where the relay responds to the computed impedance value
approach during power swing is applied in [15]. A fast
between the relay terminal and the fault point in the unblocking scheme for distance protection on the basis of the
transmission line [3]-[5]. Distance relay is implemented with changes rates of three phase active-and reactive powers is
primary zone protection setting to attain the fault within its proposed in [16 ]. The presence of decaying dc in the current
protected section and provide tripping command without any waveform is a good detector of symmetrical fault during
time delay. Second zone and third zone protection schemes are power swing [17]. An adaptive neuro-fuzzy inference
the backup protection schemes in distance relay and are approach is presented in [18]. A moving average filter based
implemented with some intentional time delay logic [6 ]. In technique is reported in [19] to distinguish three phase fault
power system, the operation of distance relay is sometimes from power swing. Data mining approach based power swing
unexpected due to the certain critical cases such as power detection logic is proposed in [20]. In the literature, several
swing [7]. Several researchers working in the area to provide methods for series compensated line are also available. In
better solutions in order to avoid cascaded events initiated due [21], comparative study report of different power swing
to false tripping during swing. Recent blackout in India during detectors for a series compensated line during power swing is
30th_31st July, 20 12 is one of them [8]. presented. Using negative sequence current the fault detection
Power swing is a phenomenon that causes large fluctuations task is performed during power swing in [22].
of power between two areas of a power network. Power swing As symmetrical fault and power swing are balanced
condition arises in interconnected power network due to phenomena distance relay unable to discriminate them. For
any symmetrical fault in zone-3 section of distance relay is
=I� ::t(ddPJ
to distinguish three phase fault from different system stress
condition. In addition, a synchrophasor assisted relay
algorithm is proposed in [24] for secure operation of zone-3 p
av
5 n�lt I n
(2)
B. Threshold Selection
In this paper, the magnitude of average of rate of change of 7 8 9 I
5 6 II 3
three phase active power is used to improve the relay Line 1
B\ B2
performance during power swing. Threshold selection has an
�R
important role in the performance of the proposed algorithm,
B3 B4
while has no impact on the relay decision period. This means,
Line2
relay provides decision within one power cycle time period i.e.
for SO Hz power system 20 msec. Threshold settings for
different zones will be select so as to avoid any nuisance relay
PI TQI
=
Q2:J P2
operation.
Gen-2 Gen-4
Any sudden change in system condition, such as switching
of lines, initiation of fault can cause increase in average rate of
change of power. At the same time, the magnitude of average
Fig. 2. Two-area, four-machine power system.
rate of change of active power depends on the severity of the
event at the switching instant. The 230-kV, SO Hz two-area
four machine system is considered for study and it is observed A. Stable Power Swing
after vigorous simulation that threshold value for zone-l fault The algorithm is tested for different symmetrical and
is 1 p.u.so as to discriminate the power swing event. Also the unsymmetrical fault case during stable power swing and
New-England 39-test bus system is considered for simulation results are demonstrated below. A stable power swing
and threshold selection for zone-3 faults to discriminate the condition is developed in the system by opening the circuit
breaker B3 and B4 for a three phase fault in line-2. Fault is
same from power swing. Despite the fact that the fault
initiated at 0.7 s and cleared after lSOms.
detection criterion is examined in five consecutive values of
(dPldt), inspections have shown that, Sp.u. for threshold is a 1) Close-in fault: A three phase close-in fault case is
proper choice for the proposed algorithm in the fault detection simulated during stable power swing. Fault is created in line-l
task in zone-3 region during power swing. The threshold value at a distance of S km from relay location and at 3 sec. The
also maintains its integrity in large power network. measured value of average rate of change of active power
(Pav) during that period is shown in Fig. 3. The index value
III. SIMULATION RESULTS which is used to detect fault is less than the threshold value
The proposed symmetrical fault detection technique is before the occurrence of fault and exceeds the threshold with
tested in 230-kV, SO Hz two-area four machine system as the initiation of three phase fault. Hence, it is clear from the
shown in Fig. 2. Parameters of the network are gathered in figure that during stable swing phenomenon detection of three
Appendix A. Distributed parameter line model is used. Relay phase fault is possible using the proposed method.
80
(R) is located near bus 7. The current and voltage signals are
collected from current transformer (CT) and potential
60
�th
transformer (PT) secondary having ratios SOO: 1 and 230
40
'"C
kV: 110 V respectively. In normal power system condition, "
�
power is flowing from bus 7 towards 8. Sampling rate of data
is maintained at 1 kHz. Simulation are carried out for various
ct 20
scheme. Also the proposed method is tested for balanced fault Fig. 3. Performance of the proposed method for close-in fault during stable
in zone-3 region during power swing. The one cycle recursive power swing.
window based Discrete Fourier Transform (DFT) based
approach is applied to collect the fundamental components of 2) Single line to ground fault: Next, a single-line-to
current and voltage. The threshold setting is such that it is able ground fault i.e. ag fault at 3.S sec is created in line-l with a
to protect 8S % of the first protected line also the adjacent fault resistance of SO Q. The performance of the proposed
lines. The threshold value for zone-l fault to discriminate the method is based on the measured value of Pav which declares
swing situation is 1 p.u. for the system as shown in Fig. 2. a fault situation as it lies above the threshold setting as cleared
This helps in discriminating the fault event from power swing. from Fig. 4.
IEEE International Conference on Recent Advances and Innovations in Engineering (ICRAIE-2016), December 23-25, 2016, Jaipur, India
15 -----,---,-----T the line-2 between bus 7-8 is created. Fault inception time
�th is I sec and fault is cleared at 1.35sec. Breaker B3 and B4 are
operated to clear the fault. Such a long dely for fault clearance
introduce unstable power swing condition for relay R.
rf: 5 1) Close-in fault: To assure the correct operation of
o r------:------�------ ------:- -------------�------ ;'------
proposed method for close-in fault case during unstable power
swing a three phase fault case is developed. The fault case is
2 2.5 3 3.5 4 4.5 5 5.5 6 same as mentioned in section A. The performance report of
Time (s) the proposed method is shown in Fig. 7. As the computed
value of Pav lies below the threshold setting, the proposed
Fig. 4. Performance of the proposed method for a-g fault during stable power
method declared it as a fault case.
40 ,----�--_,,_--,,--_c----,----c----c---�
swing.
?th
30
::i
3) Line to line fault:The perfonnance of the proposed �
rf: ::i
�
10 8
rf:
o .......................
2 2.5 3 3.5 4 4.5 5 5.5 6
Time (s) 2 2.5 3.5 4 4.5 5.5
Time (s)
Fig. 5. Performance of the proposed method for a-b fault during stable power
swing. Fig. 8. Performance of the proposed method for a-g fault during unstable
power swing.
4
�th 3) Line to line fault: Similarly, bc fault in line-I at 3 sec
is created. The response of the proposed method is shown in
Fig. 9. From the figure, it is clear that line-to-line fault is
1
easily detected during unstable power swing using the
•••••••••••••••••••••••••• ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••
proposed method.
20
Time (s) ---- �th
::i
�
o
15
Fig. 6. Performance of the proposed method for far-end high resistance fault rf:
10
during stable power swing.
unsymmetrical fault cases during unstable power swing and Time (s)
Fig. 9. Performance of the proposed method for tbc fault during unstable
results are demonstrated below. For developing unstable
power swing.
power swung condition, three phase fault at a middle point in
IEEE International Conference on Recent Advances and Innovations in Engineering (ICRAIE-2016), December 23-25, 2016, Jaipur, India
4) Far-end high resistance fault: To test the between line 29-26 . Fault is initiated at 0.7 s and cleared at
performance of proposed average rate of change of three 0.95 s by opening breaker Bl and B2. The delayed fault
phase active power method during far end high resistance fault clearance operation introduces swing in the system. As three
case with unstable swing condition, ab-g fault is created in phase fault in zone-3 region is a major cause of relay
line-l at 3 sec at a distance of 100 km from relay location. The maloperation lead to cascading events, the performance
performance report of proposed as shown in Fig. 10 assured evaluation of the proposed method is extended for three phase
that the method also holds its promise during such a critical fault in zone-3 region of relay. A three phase fault (F2) is
fault case created in zone-3 region of distance relay connected at bus 29
6 for the line 29-28. Fault is initiated at 2.5 sec at 100 km
between lines 28-26 . The fault resistance is considered as 2 n.
':;th
4
'"':
"
The corresponding result is provided below. The threshold
�,
0:;
selected to discriminate the zone-3 fault from power swing is
2 5 p.u .. From Fig. 12 it is clear even for three phase fault in
zone-3 section during swing, the average rate of change of
three phase active power method provide correct decision.
This proves that the proposed method supports the relay
Time(s) decision during power swing.
Fig. 10. Performance of the proposed method for far-end high resistance fault
during unstable power swing.
20 . '......... ¢"�,
'l "',I
-;
E,
C. Results for New England System r:f: 10
The perfonnance of proposed method is tested in the IEEE o ...........(....1:. . . . . . . . . . ;...................;. . . . . . . . . . :. . . . . . :
.
Fig. 12. Performance of the proposed method for three phase fault in zone-3
section during power swing.
IV. CONCLUSION
ApPENDIX
[13] A. Mechraoui and D. W. P. Thomas, "A new principle for high
resistance earth fault detection during fast power swings for distance
The parameters of 230-kV, 50 Hz two-area four machine protection," IEEE Trans. Power. Del., vol. 12, no. 4, pp. 1452-1457,
as shown in Fig. 3 are given below. Oct. 1997.
[14] A. P. Apostolov, D. Tholomier, and S. H. Richards, "Superimposed