Governing system controls the steam flow to the turbine in response to the control signals like speed error, power
error. It can also be configured to respond to pressure error. It is a closed loop control system in which control action
goes on till the power mismatch is reduced to zero.
The inlet steam flow is controlled by the control valve or the governor valve. It is a regulating valve. The stop valve
shown in the figure ahead of control valve is used for protection. It is either closed or open. In emergencies steam
flow is stopped by closing this valve by the protective devices.
The governing process can be functionally expressed in the form of signal flow block diagram.
The electronic part output is a voltage or current signal and is converted into a hydraulic pressure or a piston position
signal by the electro- hydraulic converter (EHC). Some designs use high pressure servo valves. The control valves are
finally operated by hydraulic
The steam flow through the control valve is proportional to the valve opening in the operating range. So when valve
position changes, turbine steam flow changes and turbine power output also changes proportionally. Thus governing
system changes the turbine mechanical power output. In no load unsynchronized condition, all the power is used to
accelerate the rotor only (after meeting rotational losses) and hence the speed changes. The rate of speed change is
governed by the inertia of the entire rotor system. In the grid connected condition, only power pumped into the
system changes when governing system changes the valve opening
TURBINE SPEED
Load control loop deals only with MW error, which is obtained using a MW- transducer and is mainly a proportional
integral (PI) controller. This loop is active when the steam turbine generator is connected to the grid. There is a
selection logic which decides which control loop should prevail
LOAD SET
Governor Follower Load Regulator is governor setter automatically follow the value a little bit lower than a load
limit set value.
Load Limit Follower Load Regulator is the load limit setter automatically follows to the value a little higher than
the load demand.
generation has to be increased by 20 % with droop of 5 %. In Indian situation most of the generating units operate
at their peak values and no additional generation is possible. With the result many units do not increase their
generation and load shedding is resorted to. In some cases, due to various operational reasons generating
companies do not like to their machines to respond, even though spare capacity is available. The governing is
bypassed. If most of the generating stations in a grid do not respond naturally, there is a danger of grid becoming
unstable also.
In the recently approved Grid code it has been made mandatory for each generator to be provided with capability to
allow up to 105 % MCR( maximum continuous rating capacity) generation whenever situation demands. This is called
Free Governor Mode of operation (FGMO).
It has been reported that after introduction of FGMO, frequency profile has improved considerably.
Valve Opening Dead band or insensitive zone Speed frequency
Turbine Speed Droop
where
s = speed droop
Nr = rated speed
Npr = speed at full load
No = speed at no load
for example
Nr = 3000 RPM
Npr = 3000 RPM
No = 3150 RPM
s = 5%