Download as pdf or txt
Download as pdf or txt
You are on page 1of 1

Print PDF Email 100% 100% Undo

Capacitor Testing and Replacement Procedure


hvacrschool.com/capacitor-testing-and-replacement-procedure/

Bryan Orr July 13, 2020

❶ Understand What a Run Capacitor Does


The run capacitor provides continuous phase-shifted current to the motor start winding allowing the motor to run

1. With the design efficiency


2. In the right direction
3. With the appropriate torque
4. With near “unity” power factor (power factor near 1.0)

If the run capacitor is failed often the motor won’t run in the case of high torque motors like a compressor or in the case of fans
they may run backwards or slowly or with high amperage or overheat.

❷ Understand Why a Run Capacitor Fails


A run capacitor fails due to

1. Poor manufacturing quality


2. Overtemperature (They got hot)
3. Over Voltage (The voltage was too high)

Many will say a failed motor “takes out” the capacitor. In actuality a failed or weak capacitor can take out a motor

Watch Video At: https://youtu.be/dVCROCUBxDw

❸ Visually Inspect
If a capacitor shows physical damage such as the top bubbling or oil leakage then it should be replaced. Normal rust is not a reason
to replace a capacitor. Note the MFD or uF rating listed on the capacitor. The voltage rating is also worth noting but you may use a
HIGHER voltage rated capacitor but not lower.

❹ Decide if under load or bench testing is best


If the system is currently running then an under load test may be best. Do not do an under load test on blower capacitors due to
the risk of the meter leads around a spinning blower wheel. If the system is NOT running then a bench test will be the best bet.

❺ Bench or Under Load Test?


Choose bench for simplicity or if the system is not running. Choose under load because it can be done in real load conditions on a
running system.

Bench Test Go to step ❼

Under Load Test Go to step ❻

❻ Test Under Load


In order to test under load, you need to take measurements with the system running. Wear proper PPE and only do so when safe.
You need to have an accurate multimeter that can measure Voltage and Amperage reliably. Often under load measurements may
come out high if the amp clamp picks up interference from other circuits. Measure the amperage on the start wire with the wire
centered in the clamp and multiply by 2652. Now measure the voltage across the capacitor and divide the amperage x 2652 by that
voltage to find the capacitance in MFD.If the under load MFD is less than 10% low we suggest replacement. If it is over the rating it
is often a mis-measurement

If a capacitor measures weak via under load test go ahead and perform the bench test.

Watch Video At: https://youtu.be/zgrAFq1Gf20

❼ Bench Test
Bench Testing is simply removing both leads from the run capacitor after safely disconnecting power and discharging the
capacitor. You then place a meter designed to test capacitance across the terminals and note the reading. Be careful not to touch
the meter probes and to get a good solid connection to the metal connection spades on the capacitor.If the measurement is more
than 10% we suggest a replacement

❽ Inspect the dual run capacitor and note where each wire is connected
Taking a picture is one of the easiest ways to remember before removing the wires.

❾ Remove disconnect
It is imperative that the disconnect is removed or the unit is off and without potential. Test using a meter that is pre-tested to a
known voltage source and check L1 to L2 and L1 – ground and L-2 ground to ensure no voltage is present.

❿ Discharge capacitor
Before testing, touching or removing the capacitor, you need to discharge it. Do this using a high resistance resistor bridging
HERM and Fan terminals across to C or across a single capacitor.

NOTE: It is actually very rare for a run capacitor to contain a charge on a normally running system because it bleeds off through
the compressor windings UNLESS one of the windings is open. FOr this reason many techs opt to just use a screwdriver to
discharge which is controversial but common practice.

⓫ Disconnect wires and remove used dual run capacitor


To remove, disconnect wires on the top of the capacitor and also remove the strap holding the capacitor in place.

⓬ Replace capacitor with same MFD rating


Apples to Apples: You must use the same MFD rating capacitor during this process. This will be located on the box and also the
side of the capacitor. Mount the capacitor upright with terminals pointed up.TEST THE NEW CAPACITOR VIA BENCH TEST
BEFORE INSTALLING

⓭ Re-sizing of strap
Sometimes the new capacitor might be larger or smaller. At this time, use the metal strapping and create a new strap for the
capacitor, by cutting it to the correct size and using self tapping screws to attach to the correct area. Always check before using self
tappers to confirm that you are not in any danger of puncturing the coil.

⓮ Attach the wires


At this time reattach the wires onto the top of the dual run capacitor. Make sure that the common is connected, the HERM
(compressor) is connected and the FAN is connected. You should always double-check to make sure all wires are in their proper
places. Make sure the terminal fit very snug, tighten them by squeezing with a needle nose before installing to make sure they are
very tight.

⓯ Test system
Reconnect the disconnect or flip the breaker back on. Check to make sure that all aspects of the system are running and the
compressor and fan are running at the proper amperage.Using a power meter and testing motor power factor to ensure it is near
unity is a good additional practice.

⓰ Clean up and reattach panel on the condenser


Make sure you clean up the area and reattach the panel to the condenser

Powered by PrintFriendly.com Privacy

You might also like