Control Room Slab Design & Drawing Doc. No.

Rev. : 00 Date :
Checks for Control Room Slab Design & Drawing
Reference 01 : Bureau of Indian Standards ( IS : 456_2000), & Other relavent IS Standards
Reference 02 : Suzlon Technical Specification No.: ENG:PEV:T-012 , CEA Te
Standards for Construction of Electrical Plants and Electric Lines Regulations, 2010.
Sl.No Parameters to be Checked OK NOT OK

A DESIGN UNITS
All Design units are as per Standard International (SI) Metric System
1

B DESIGN ASSUMPTIONS

1 General design Methodology is provided

2 All Design assumptions are clearly described

C DESIGN PARAMETERS

1 Concrete & Reinforcement grades

2 Soil Unit weight is provided

3 Young's modulus is provided

D DESIGN LOADS

1 Design Loads are as per Project Design Basis /IS Codes

2 Dynamic loads are as Per Vendor Data for Heavy Rotating Equipment

3 Thermal loads are as per Project Design Basis


Load combinations for Allowable Stress Design are as per Project Design Basis ,
4 IS Codes
Load combinations for Ultimate Strength Design are as per Project Design
5 Basis , IS Codes

F SLAB DESIGN
a Effective span of slab:
Effective span of slab shall be lesser of the two
L = clear span + d (effective depth)
1 L = Center to center distance between the support

b Depth of slab:
One way slab d=(L/22) to (L/28).
Two way simply supported slab d=(L/20) to (L/30)
1 Two way restrained slab d=(L/30) to (L/32)

c Load on slab:
The load on slab comprises of Dead load, floor finish and live load. The loads
are calculated per unit area (load/m2). Dead load = D x 25 kN/m2 ( Where D is
thickness of slab in m) Floor finish (Assumed as)= 1 to 2 kN/m2 Live load
1 (Assumed as) = 3 to 5 kN/m2 (depending on the occupancy of the building)

d Nominal Cover:
For Mild exposure – 20 mm For Moderate exposure – 30 mm However, if the
diameter of bar do not exceed 12 mm, or cover may be reduced by 5 mm. Thus
1 for main reinforcement up to 12 mm diameter bar and for mild exposure, the
nominal cover is 15 mm.

e Minimum reinforcement:
The reinforcement in either direction in slab shall not be less than
0.15% of the total cross sectional area for Fe-250 steel
1 0.12% of the total cross-sectional area for Fe-415 & Fe-500 steel.

f Spacing of bars:
The maximum spacing of bars shall not exceed
Main Steel – 3d or 300 mm whichever is smaller.

Distribution steel –5d or 450 mm whichever is smaller Where, ‘d’ is the


1 effective depth of slab. Note: The minimum clear spacing of bars is not kept less
than 75 mm (Preferably 100 mm) though code do not recommend any value.

G CALCULATION PRESENTATION
Calculations Cover Sheet with Document Number, Project title, Caculation
1 Subject, Date, etc. is provided
Name of calculation originator/Checker on Claculation Sheets
2
Subject of Structural Calculations
3
Reference drawing number,Table of contents , List of appilcable coded,&
4 Standards .
General description of Structure design Methodology/Design Criteria /Primary
5 Loads Definition
Drawings
H
Check North Direction, Check Scale, Check units, Check Grid Dimensions
1
The information within the Title Block of each drawing has been reviewed for
accuracy including the “Designed By”, “Drawn By”, “Checked By” and “File No.”
2 fields.

The Index Sheet has been coordinated with the current list of
3 architectural drawings with respect to drawing number and title.

A drawing has been included to identify abbreviations and symbols utilized on


the project drawings and have been coordinated with the other architectural
4 drawings for compliance.

Loading plans, vertical loads layout


5
Deviations, if any

Verification team
Reviewed & Verfied by Approved & Accepted by
Remarks
Name
Date
Sign.
Prepared by Reviewed by Accepted by
Rupesh Khandekar Swapnil Kauthekar/Pravinkumar Patil/Jagadish G. Pravinkumar Patil
Doc. No.
Rev. : 00 Date :

CEA Technical

Remarks, if any
Approved & Accepted by
Accepted by
Pravinkumar Patil