Rating Label
Each automatic transfer switch contains a rating label to
define the loads and fault circuit withstand / closing ratings.
Refer to the label on the transfer switch for specific values
Nameplate
The Transfer Switch nameplate includes data for each
specific 7000 Series ATS. Use the switch only within the
limits shown on this nameplate. A typical catalog number 30-230 ampere sizes
is shown on the next page with its elements explained.
381333-229 F
Florham Park, NJ 07932-1591 USA
Call 1 800 800-2726 (ASCO) for sales or service www.ascopower.com
ASCO POWER TECHNOLOGIES CANADA PO Box 1238, 17 Airport Road, Brantford, Ontario, Canada N3T 5T3
Series 7000 Automatic Transfer Switch Operator’s Manual
TABLE OF CONTENTS
page
INSTALLATION............................................................................................................................................................. 4-7
Supporting Foundation, Mounting, Line Connections, Testing Power Conductors, Connecting Power Conductors ............. 4
Controller Ground, Harnesses, Engine Starting & Auxiliary Circuits ...................................................................................... 5
Functional Test .................................................................................................................................................................. 6-8
Functional Test – Manual Operation Test ............................................................................................................................... 6
Functional Test – Voltage Checks .......................................................................................................................................... 7
Functional Test - -Electrical Operation ................................................................................................................................... 8
INDEX ................................................................................................................................................................................. 12
D7ATS A 3 150 N 5 C
Frame Neutral Phase Poles Amperes Voltage Controller Enclosure
& A-solid 2-single 30 A 115 J 400 5- standard C- Type 1
Series 70 B 120 K 415 F- Type 3R
B-switched 3-three 5X- if
C 208 L 440 G- Type 4
100 accessories
C-overlapping D 220 M 460 L- Type 12
150 ordered
E 230 N 480 M- Type 3R secure
blank- none N- Type 4 secure
200 F 240 P 550
230** P- Type 4X secure
G 277 Q 575
Q- Type 12 secure
**230 amp limited to H 380 R 600 blank- open type
480 volts
load power
connections Transfer
Control &
lights
emergency power
connections
maintenance
handle
(see WARNING
under Manual
Operation)
terminals for
Controller
engine start
contacts
normal power
connections
cable spacers
(see INSTALLATION)
Installation
The ASCO 7000 Series Automatic Transfer Switch (ATS)
Testing Power Conductors
is factory wired and tested. Field installation requires Do not connect the power conductors to the transfer
mounting, connecting service cables, and connecting switch until they are tested. Installing power cables in
engine start and auxiliary control circuits (if required). conduit, cable troughs and ceiling-suspended hangers
often requires considerable force. The pulling of cables
Supporting Foundation can damage insulation and stretch or break the conductor’s
The supporting foundation for the enclosure must be level strands. For this reason, after the cables are pulled into
and straight. Refer to the applicable enclosure outline position, and before they are connected, they should be
drawing included with the switch for all mounting details tested to verify that they are not defective or have been
including door opening space. damaged during installation
If bottom cable entry is used, the foundation must be
prepared so that the conduit stubs are located correctly.
Connecting Power Conductors
Refer to the enclosure outline drawing for specified area After the power cables have been tested, connect them to
and location. Provide cable bending space and ½ inch the appropriate terminal lugs on the transfer switch as
minimum clearance to live metal parts. When a concrete shown on the wiring diagram provided with the switch.
floor is poured, use interlocking conduit spacer caps or a Make sure the lugs provided are suitable for use with the
wood or metal template to maintain proper conduit cables being installed. Standard terminal lugs are
alignment. solderless screw type and will accept the wire sizes listed
on the drawings provided with the switch. Be careful
Mounting when stripping insulation from the cables; avoid nicking
Refer to the Outline and Mounting Diagram provided with or ringing the conductor. Remove surface oxides from
the ATS; it shows all mounting details and instructions. cables by cleaning with a wire brush. When aluminum
cable is used, apply joint compound to conductors.
Tighten cable lugs to the torque specified on rating label.
Protect the automatic transfer switch from Three cable spacers are included with 150, 200, & 230 A
construction grit and metal chips to prevent transfer switches. When installing power cables, run the
malfunction or shortened life of the transfer switch. cables through the cable spacers as shown in Figure 1.
Position the cable spacers within 1½ inches from the lugs.
Mount the ASCO ATS vertically to a rigid supporting
structure. Level all mounting points by using flat washers
behind the holes to avoid distortion of the switch.
The cable spacers must be located as shown
The controller is mounted on the cabinet door. An add-on for 150, 200, and 230 ampere transfer switches.
DIN rail is provided for some optional accessories and is
mounted below the controller on the door.
Line Connections
A Wiring Diagram is furnished with the ASCO 7000
Series ATS (separate from this manual). Refer to this
drawing. All wiring must be made in accordance with
the National Electrical Code and local codes.
Installation
Controller Ground
A grounding wire must be connected to the controller’s
lower left mounting stud. Because the controller is
mounted on the enclosure door, a conductive strap must be
used between the enclosure and the door. This connection
provides proper grounding which does not rely upon the
door hinges.
Harnesses
The transfer switch is connected to the left side of the
controller by a plug-in harness (two plugs).
Auxiliary Circuits
Connect auxiliary circuit wires to appropriate terminals on
the transfer switch. Note the control features that are
furnished on this switch. Make the necessary auxiliary
connections by referring to the Wiring Diagram.
Installation
Functional Test
The Functional Test consists of three checks:
□ 1 - Manual Operation Test, on this page
□ 2 - Voltage Checks, page 7
□ 3 - Electrical Operation, page 8
Note: If Normal and Emergency connections are Now continue to 2 – Voltage Checks on next page
reversed this operation is also reversed.
Installation
observe
these lights
* If necessary, adjust voltage regulator on the generator Use a phase rotation meter to
according to the manufacturer’s recommendations. The check phase rotation of
5
Automatic Transfer Switch will respond only to the rated emergency source; it must be
voltage specified on the Transfer Switch nameplate. the same as the normal source.
Installation
operate
this switch
observe
these lights
PREVENTIVE MAINTENANCE
Reasonable care in preventive maintenance will insure Do not unplug the controller
high reliability and long life for the 7000 Series ATS. An until steps 1a or 1b is completed.
annual preventive maintenance program is recommended
1. Observe the position of the transfer switch.
ASCO Power Services, Inc. is ASCO Power Technologies a. If the transfer switch is in the Normal position,
service organization for the United States and Canada. first place standby engine starting control in the off
Call 1-800-800-2726 (ASCO) to request a service call and position. Second, then open the emergency source
information on preventive maintenance agreements. circuit breaker. Third, open the normal source
circuit breaker.
Annual Inspection Checklist b. If the transfer switch is in the Emergency position,
first open the normal source circuit breaker.
Second, place the engine starting control in the test
or run position. Third, open the emergency
Hazardous voltage capable of causing source circuit breaker.
shock, burns, or death is used in this switch.
Deenergize both Normal & Emergency power 2. Separate the two quick disconnect plugs by squeezing
sources before performing inspections! the latches. Do not pull on the harness wires.
□ Clean the ATS enclosure. De–energize all sources, Reconnecting the Plugs
then brush and vacuum away any excessive dust
accumulation. Remove moisture with a clean cloth.
Do not unplug the controller
□ Check the transfer switch contacts. De-energize all until steps 1a or 1b is completed.
sources, then remove the transfer switch barriers and
check contact condition. The non–replaceable main 1. Observe the position of the transfer switch.
contacts are designed to last the life of the transfer a. If the transfer switch is in the Normal position,
switch. Reinstall the barriers carefully. first be sure that both normal and emergency
source circuit breakers are open. Second, be sure
□ Maintain transfer switch lubrication. If the that the standby engine starting control is still in
transfer switch is subjected to severe dust or abnormal the off position.
operating conditions, renew factory lubrication on all b. If the transfer switch is in the Emergency position,
movements and linkages. Re-lubricate the solenoid first be sure that both normal and emergency
operator if the TS coil is replaced. Do not use oil; source circuit breakers are open.
order lubrication 625550–001 (Castrol EndurexR
4000 lubricant). 2. The two harness plugs and sockets are keyed.
Carefully align the plugs with the sockets and press
Check all cable connections & retighten them. straight in until both latches click. Close the door!
REPLACEMENT PARTS 3. Restore the two sources in sequence as follows:
Replacement parts are available in kit form. When ordering a. If the transfer switch is in the Normal position,
parts provide the Serial No., Bill of Material No. (BOM), and first close the normal source circuit breaker.
Catalog No. from the transfer switch nameplate. Contact your Second, close the emergency source circuit
local ASCO Power Technologies Sales Office or ASCO Power breaker. Third, place the standby engine starting
Services, Inc. control in the automatic position.
In the United States and Canada b. If the transfer switch is in the Emergency position,
call 1 – 800 – 800 – ASCO ( 2726 ) first close the emergency source circuit breaker.
Second close the normal source circuit breaker.
Testing & Service 2. Use the maintenance handle to manually operate the
transfer switch to the opposite source. See Manual
MANUAL LOAD TRANSFER Operation on page 7.
This procedure will manually transfer the load if the
3. Then remove the maintenance handle. See page 7.
controller is disconnected.
TROUBLE-SHOOTING
Note any optional accessories that may be furnished on
Hazardous voltage capable of causing shock,
the automatic transfer switch (ATS) and review their
burns, or death is used in this switch. Do not
operation. Refer to any separate drawings and/or
touch the power or load terminals of the
instructions that may be packed with the ATS.
transfer switch!
If the problem is isolated to circuits on the controller or the transfer switch, call your local ASCO Power Technologies
sales office or ASCO Power Services, Inc.: in the United States or Canada, call 1–800–800–2726. Furnish the Serial No.,
Catalog No., and Bill of Material (BOM) No. from the transfer switch nameplate
INDEX
A I P
auxiliary circuits, 5 inspection, 9 parts, 9
installation, 4-8 phase rotation check, 7
problem, 1-
C L
cable
labels, R
lugs, 4
engine start contacts, 3, 5 rating label, cover
preparation, 4
rating, cover, 1 replacement parts, 9
spacers, 4
lights, 7, 8
illustration of, 4
lubrication, 9 S
catalog number, inside cover
settings
cleaning, 9
M see Controller User’s Guide
connections
maintenance, preventive, 10
line, 4
controller, 3, 4
manual load transfer, 11 T
warning, 11 test, functional, 6, 7, 8
disconnecting, 9
manual operation, 7 time delays, 10
see Controller User’s Guide
illustration of, 7 see Controller User’s Guide
grounding, 5 warning, 7 Transfer Control selector switch
Retransfer Delay Bypass, 8
E N Transfer Test, 9
electrical operation, 7 nameplate, cover Transfer Switch Connected to
Emergency Source Accepted light, Normal Source Accepted light, 8, 9 Emergency light, 7, 8
7, 8
Transfer Switch Connected to
F O Normal light, 7, 8
operation transfer test, 9
frequency, generator, 9 transfer to emergency, 8
electrical, 9
functional test, 6, 7, 8 transfer to normal, 8
manual, 7
illustration of, 7 trouble–shooting, 10
H warning, 7
harness, 5
sequence of, 11 V
disconnect plugs, 9 voltage checks, 7
optional accessories
help voltage, pickup and dropout settings
see Controller User’s Guide
powerwarranty@ascopower.com see Controller User’s Guide
800–800–ASCO (2726)
Printed in U.S.A
©2018 ASCO Power Technologies.
All Rights Reserved.