PROJECTS DEPARTMENT
As per the meeting held with the contractor "QBEC" Senior Mechanical Engineer Mr.
Abdel Tawab, ON 26 September,The following comments has been discussed and should
Material Submittal for be taken into account in the submissions of all material submittals:
Fire Protection System
1.Contractor shall submit compliance statement as per approved project specification.
Alarm Check Valve
EZ01-CW04-QBEC- Note :-The contractor has submitted EZ01-CW04-QBEC-MEC-SPC-000003 Rev.01 Fire System
1 KI / IB
MEC-MAS-000010
Assembly & OS & Y Gate
Specification, which has not yet been approved. After aproval these shall be considered as final
D Noted Closed
valve Supplier: Ishield
specifications of fire-fighting system in line with NFPA, QCS 2014 and QCDD regulations.
Security and Safety
Solution
2. All materials proposed such as valves, pipes, fittings, etc... shall be compatible with working
pressure of fire fighting network according to the approved calculations.
6 COMPLIANCE STATEMENT
8 PROJECT LIST
9 OTHER’S IF ANY
10 WARRANTY CERTIFICATE
Project Name: Design & Build of Light Industrial & Logistics Units AT RAS
BUFONTAS SPECIAL ECONOMIC ZONE
Dear Sir,
We Ishield Security & Safety Solutions agreed with Qatar Building Engineering
Company QBEC to supply & Install the firefighting system at AT RAS BUFONTAS
SPECIAL ECONOMIC ZONE This is for your information and consideration.
• INTRODUCTION ...................................................................................................
WHAT WE DO ......................................................................................................
OUR MISSION
!Shield's mission is to be unconditionally committed to provide high performance security and
safety solutions to the Qatari society.
Dedicated to pioneering research and allied professional practice, we offer practical leadership
while strategizing high quality, comprehensiveness and uniformity in product offers & installation
and commissioning services.
"We dedicate ourselves to quench fire threats & fulfill the human quest for safety of self and
propertyU.
OUR VISION
We envision being the pioneer in the industry of Security & Safety Equipment Supply, installation
and commissioning.
We intend to play a central role in supporting residential, commercial and industrial sectors by
offering innovative solutions that meet international standards of safety against fire.
Articulating broader perspectives and channelled through strategic partnerships, our portfolio
will embrace products that meet the most challenging tests of safety for life and property. And
as visionaries of future, our research will materialize the evolution of groundbreaking Security &
Safety technologies.
Our "statement of success" is to be recognized as a corporate entity dedicated to embracing cor-
porate responsibility in improving the quality and consistency of Security and Safety solutions.
"We want to be assessed through our success stories of saving and protecting lives and properties
in Qatar & abroad~~
Chairman
Chairman Mr. Ghanem Sultan AI Hodaifi AI Kuwari
Chief ExecutiveOfficer
Chief Executive Officer Mr. Wael Moussa Shtayeh
Managing Director
Managing Director Mr. Atom El Hajj
General
Business Manager
Development Manager Mr. Magdy Morshdy
Bankers
Lawyers
Auditors
Telephone : :+974
Telephone +974467 48737350
4491
Fax
Fax : :+974
+974 4491
467 41407355
Emial : info@ishieldme.com
SECURITY SYSTEMS
• CClV
• Public Address
• Nurse Call
• Intrusion
• Audio I Video Solutions
• Operation and Command Centers
SPECIAL LIGHTING
• Emergency Lights
• Chemical Lights
VEHICLES
• Fire Trucks
• Ambulances
" Fire Boats
Our fire fighting solutions division encompasses some of the most exemplary and time
tested solutions that have shown long-standing credibility, through the coverage of proj-
ects across 50 countries, with applications that have proved reliable & trustworthy.
Fl RE ALARM SYSTEMS
Our Strategic partnership with companies who have credentials, as old and as strong as five de-
cades, has strengthen our capacity of supply and the comprehensive coverage that we can offer
across various industries. The R&D helps us bring in evolutionary technologies and greener prod-
ucts.
Our product line ranges from the conventional fire alarm Systems to the addressable and voice
evacuation systems, fire and smoke detection and emergency handheld devices:
" MIRCOM
Mircom has a long tradition in the fire and life safety industry with corporate roots dating back to
the 1960's.
• HOCHIKI
The Company was founded in 1918 by Japan's Insurance industry; The Hochiki Corporation under-
took design, manufacturing, installation and maintenance of fire alarm systems and produced in
excess of 3.5 million units each year.
We consistently strive to develop and introduce new product offerings and services that meet and
exceed the ongoing needs of our markets and customers.
Our solutions satisfy the needs of the multi and high rise residential, industrial and commercial
applications & new construction and retrofit markets.
~I 0
~~~
~
' ~--~ ··~
-~
--"-'
In addition to the above, ISHIELD cooperates with international manufacturers in regard to other
products range:
" J LINE FIRE FIGHITNG PUMPS UL/ FM Horizontal and Vertical turbine Fire pump
" UL/FM Sprinklers (Upright, Pendent, Concealed, Side wall, ESFR)
" Valves
" Pipes and Fittings (ERW Steel Pipes, CPVC pipes, HOPE pipes)
SEVO
NOVEC 1230
When it comes to exceeding the normal objective of minimizing the damage of the fire for criti-
cal facilities where protection of assets and people comes first, Clean Agent is the suitable solu-
tion for these applications. That's why ISHIELD introduced the next generation of halon alterna-
tive designed for human safety as well as environment safety.
Some characteristics of The SEVO system - NOVEC 1230 Fire protection fluid are:
• Zero ozone depletion potential
• 5-day atmospheric lifetime
• A global warming potential of 1
ISHIELD provides also its clients with Clean Agent System (FM200, HFC-227ae, NAF S 125 ... etc)
for their application, with optimum design and reliable equipment.
FIREPRO
This system's design is based on the latest generation of SBK aerosol forming solid compound.
Upon activation, the solid compound is transformed into a rapidly expanding, highly efficient and
highly effective fire fighting aerosol based on potassium salts.
• Halon Alternative
" Cost effective
• Autonomous & Automatic
• Does not damage property, Machinery, Electronics
• Activated Electrically, Thermally and Manually
• None pressurized containers
• Easy installation
" Ozone and Environment friendly.
The system has been constantly acquiring approvals and certifications from international organi-
zations.
ISH IELD offers the most comprehensive solutions in Access Control with the ability to incorporate
ALL devices & offers the most advanced control panel with built-in TCP/IP connectivity and a host
of user-friendly software programs.
Our Access Control Design fits most of the applications from small to medium sized and up to
large size projects.
We are proud to have a dedicated and specialized team of engineers who can meet any type of
requirements, from the objectives, via solid design procedures, to implementation.
ISHIELD offers a wide selection of Security Camera Systems, either digital or IP systems and Ac-
cessories for home and business applications. Our aim is to provide exceptional solutions which
meet your needs via wide range of products.
We are the leaders in networked video. We aim to be innovators in video technology and a lead-
ing video solution provider to government and critical infrastructures, education and corporate
enterprises, transportation, retail, banking, and a host of other industries.
"Our CCTV Solution enhance the security and operational effectiveness"
We do:
Simple and flexible
Modular architecture
Intelligent
Cost effective
Different vendors' equipment integration
Reliable and High Performing
" Retail Suite gives you the tools you need to effectively combat and prevent fraud, theft and
any other problems on the shop floor. Intelligent video and tight integration with systems
you already use ensure total control over all transactions and activities from entry points to
point-of-sale.
" Transportation Suite monitors and controls all your public or commercial vehicular traf-
fic and transportation operations. Includes Traffic Monitoring/Traffic Control, a real-time
transport and traffic detection system & Plate ID, an automatic license plate recognition and
identification system.
" Banking Suite allows users to proactively detect and prevent fraud, theft and other threats,
branch-wide. It includes Transact, digital video surveillance for every terminal in your net-
work.
Cyalume has many applications. From public to commercial and from civic to military, Cyalume
delivers reliable lighting source.
Developed for the Military, Cyalume Snap Lights are now tested, proven, and recommended for:
" Utilities: Reliable, Flame less, Waterproof lights to get the job done - indoors and outdoors
" Hotels: Evacuation lights, room and hallway lighting during power outages
" Businesses: Work lighting during power outages, evacuation lights
" Buses, railways, cars
" Boats, yachts, ships
" Police forces
• Homeland Security
" Fire Fighters
20 17/01/ 16
lllllllllllllllllllllllllllllllllll
58809 ··UlJJ·.:..I
.. ..~ I ~.I..,. ,,·: 11
fll>J.. 58809 : UlJ ~ I J.;uilll pi)J
:Cl!J~I a.o..w.ll · Dl J"
ao!LuJI 9LJ.O 1"' 1
~ :l.l.uilll
.... :UlJ~I ,a..wDI
16/01/2018 :J.;uilll .c UuJi I 2-/J1J 17/01/2013 :J.;uilll .c LlllJ I 2-/J IJ
200000 :Jl.aJ I lJ-0 IJ 6 J g:uo C4J g1.J.Uo u I.:J a5j.ll> :u1i gililll ~I
#> :oi.uu.a.ll ~ .bJill :J.;uilll iiJ b
0 :&gj.CJI JJ.C
Jlai!JI ul.ogJAo
44554975/55592449 :Jlni!JI pwJi 23761
1 of 2
58809: ~I ,abJ
u4.w o!kI OJ~ ioJ I oWu.oJ I u~ }hl ad.in g 6J~- a.6}C JJD.Jill·
. ~!JI
eu.IJ bAll
- - -
bl..UllJI ,a.w.I ,ru>.. )J·II bl..UllJI ,a.w.I I ,ru>. )J·II
545912 2000824
544700 541460
2002131 501220
2001819 544465
2004342 501210
2 of2
58809 : ~I fliJJ
.J..-..b.-9
ci.__ q J ..i.
~ QATAR CHAMBER
ISO 9001:2008
Quality Management Systems – Requirements
are authorised to use the LPCB Certification Mark on stationery and publications related to the
following products and/or services:
This certificate is maintained and held in force through regular surveillance activities.
This certificate and appendix remains the property of BRE Global Limited and is
issued subject to terms and conditions (for details visit
www.redbooklive.com/terms).
To check the validity of this certificate and appendix please scan the QR tag, visit
www.redbooklive.com/check or contact us.
LPCB is part of BRE Global Ltd., Garston, Watford WD25 9XX.
T: +44 (0)1923 664100 F: +44 (0)1923 664603 E: Enquiries@breglobal.com
Since the early 20th century the name GLOBE has been synonymous in supplying quality fire pro-
tection products.
Globe continues to develop new products as the world market demands, and is happy to state that
its relationship with the various approval authorities, such as Underwriters Laboratories Inc, FM Ap-
provals and the Loss Prevention Certification Board (UK), is excellent. Globe has the LPCB (UK)
certification for ISO 9000 series Quality Assurance, therefore exhibiting proof of the quality it con-
tinuously builds into each of its 100% factory-tested products.
has been assessed by Bureau of Assessment Services and hereby attests that
the organization complies with the requirements of Quality Management System
in accordance with
I
w Certificate issue date : 08-December-2014
Certificate valid till : 07-December-2017
Certificate No : A E-BAS-00002587
~~
Certification ~
· _::::::,
Bureau ofAsses~SeMce s
C8 ·011
Further clarification regarding the scope of the certificate and the applicability of ISO 9001 :2008 requirements may be obtained by
consuiUng the O<ganization.
This cer«ficate remains valid while the holder maintain s the management system in accordance with the standard above, which will be
audited by Bureau of Assessment Services through surveillance audits. This ceruficate remains the property of Bureau of Assessment
Services. lack of fulfillment of conditions as set out in the cer«fication agreement may render this ceruficate invalid.
Issuing Country. Bureau o f Assessment Servioes LLC, P.O. Box: 116898, AI Karama, Oubai, United Arab Emirates.
has been assessed by Bureau of Assessment Services and hereby attests that
the organization complies with the requirements of Environmental Management
System in accordance with
ISO 14001:2004
The Environmental Management System is applicable to:
~~
Certification ~
·· _:::::,
Bureau of Asses~ Se1olces
Further darification regarding the scope of the certificate and the applicability of ISO 14001:2004 requirements may be obtained b y
consulting the organization.
This certificate remains valid while the holder maintains the management system in accordance with the standard above. which wi ll be
audi ted by Bureau of Assessment Services through surveillance audits. This certificate remains the property of Bureau of Assessment
Services. Lack of fulfillment of conditions as set out in the certification agreement may render this certificate invalid.
Issuing Counlry: Bureau of Assessment Services LLC, P.O. Box: 116898, AI Karama. Oubai, Un~ed Arab Emirates.
has been assessed by Bureau of Assessment Services and hereby attests that the
organization complies with the requirements of Occupational Health and Safety
Management System in accordance with
b6~ ~
··
Certifi cation ~
Bureau of Asses~ ServiCes
CS-OU
Further clarification regarding the scope of the certificate and the applicability of OHSAS 18001 :2007 requirements may be obtained by
consulting the O<ganization.
This certificate remains valkt while the holder maintains the management system in accordance with the standard above, which will be
audited by Blf'eau of Assessment Services ttvough surveillance audits. This certificate remalns the property of Bureau of Assessment
Services. Lack of fulfillment of conditions as set out in the certification agreement may render this certificate invalid.
Issuing Counlry: Bureau of Assessment Services LLC, P.O . Box: 116898, A I Karama, Olbai, Un~ed Arab Emirates.
APPROVALS
cULus Listed
FM Approved
TECHNICAL DATA
Water Working Pressure Rating - 300 psi (20.7 bars)
Factory tested hydrostatically to 600 psi (41.4 bars).
Equivalent feet of pipe: 3” Valve = 12.2 feet,
4” Valve = 9.7 feet 6” Valve = 17 feet, 8" Valve = 21 feet
SIZE
H-2
PHYSICAL DATA
3" [80mm] 4" [100mm] 6" 150mm 8" [200mm]
ANSI/DIN ANSI/DIN ANSI DIN ANSI / DIN
12
2 4 14
18
15 13
14
16 9
10
3
6 17
1 11
3 Seat Ring Bronze 323809 323504 323564 323837 12 Disc Retainer Bolt Stainless 323817 323513 323573 323838
4 Cover Ductile Iron 323805-HP 323507-HP 323567-HP 323835-HP 13 Sealing Washer Hard Fiber 323515 323515 323515 ------
5 *Clapper Stainless 323814 323510 323507 323841 14 Hinge Pin Bushings (2) Bronze 323819 323518 323518 323846
6 Retaining Ring Stainless 323527 323517 323517 ------ 15 Name Plate Aluminum 323480 323480 323480 323847
7 Hinge Pin Stainless 323818 323516 323516 323845 16 Drive Screws (2) Stainless 323520 323520 323520 323420
8 **Cover Gasket Vellumoid 323810 323508 323568 323833 17 Torsion Spring Stainless 323528 323528 323565 ------
9 Clapper Facing Disc EPDM 323815 323511 323571 323842 18 Spring Bushing Brass ------ ------ 323579 ------
Refer to Globe's Alarm Check Valve Installation and Maintenance Guide (Bulletin A.C.V.I.M.) for
trim set-up, installation instructions, and maintenance.
*8 Inch Clapper material is Bronze
**8 Inch Cover Gasket material is Rubber
FM Approved 100 10 ft
50 ft
NYC-DOB MEA 326-91-M 90
80 100 ft
70
TECHNICAL DATA
Body - cast aluminum 60
Finish - red 10 30 50 70 90 110 130 150 170
FLOWING PRESSURE (PSI)
CROSS SECTIONS
ITEM DESCRIPTION MAT'L WM P/N WM-2 P/N ITEM DESCRIPTION MAT'L WM P/N WM-2 P/N
1 Gong Shell Aluminum 325506 325506 9 Threaded Pipe Galvanized Pipe 325517 325517
2 Hex Head Cap Screw Zinc 325521 325521 10 Striker Arm Mild Steel 325510 325510
3 Gong Mounting Bracket Aluminum 325504 325504 11 Cap Screw Zinc Plated 325520 325520
4 Motor Cover Aluminum 325509 ------ 12 Knocker Phenolic 325513 325513
Inside Gong Backing Plate Aluminum ------ 325532 13 Knocker Retaining Washer Stainless Steel 325516 325516
5 Impeller Housing Aluminum 325502 325502 14 Knocker Retaining Rivet Stainless Steel 325514 325514
6 Impeller Delrin 325507 ------ 15 Bearing-Thompson Type 6 Nylon 325518 325518
Impeller - Inside Gong Delrin ------ 32533 16 3/8 Helical Spring Lock Washer Steel 325522 325522
7 Striker Shaft Delrin 325508 325508 17 Backing Plate Gasket Velumoid 325511 325511
8 Drive Shaft Aluminum 325515 325515 18 Wall Plate Mild Steel 325528 325528
Refer to Globe's Water Motor Alarm Installation and Maintenance Guide (Bulletin WMA-I) for trim set-up, installation
instructions, and maintenance.
APPROVALS
cULus Listed
FM Approved
LPCB Approved
TECHNICAL DATA
Water Working Pressure Rating - 175 psi (12 bars).
Factory tested hydrostatically to 350 psi (24 bars).
Capacity - 1 Gallon (3.785 liters)
Body - High Tensile Cast Iron
Refer to Globe's Alarm Check Valve Installation and Maintenance Guide (Bulletin A.C.V.I.M.) for trim set-up, installation
instructions, and maintenance.
Construction & Maintenance of Supply & Installation Testing & Commisioning of Wet sprinkler
Structurel ACE Consulting
1 Arab Center for Research & Governmenet system, Fire Pump, FM-200 system, Foam system, Anti freeze
Policy Studies
Qatar Engineers sprinkler system & Fire Hydrant.
Souq Wakif Under Ground Car Supply of Fire Fighting Equipments & Installation Testing &
5 Car Park Arabian MEP PARSONS
Park Commissioning of Aerosol system, Foam system & FM-200 system.
Souq Ahmad & Souq Najada Supply Installation Testing & Commissioning of Fire Fighting
7 Tunnel UCC Louis Berger
Pedestrain Tunnel Equipments, Fire Pump & NOVEC System.
Vector
Supply, Installation, Testing & Commissioning of Wet sprinkler
13 Le Miarage Appartments 4 Residential Electromechanic LACASA
system, Novec-1230, Aerosol Fire Suppression system.
al
James Cubitt & Supply, Installation Testing & Commisioning of Wet Sprinkler
16 QIB Hotel Commercial Shannon Partner system, Fire Pump, Fire Alarm System, Aerosol Fire Suppression
Consultancy system
Porto Arabia Tower, The Pearl Supply ,Installation, Testing & Commisioning of Wet sprinkler
17 Commercial Bloom EHAF
Qatar system, Fire Pump,Aerosol Fire Suppression system, Foam system
Diversion Work : Modify the current under ground Pipes with new
18 Doha Port Pkg. 2 Commercial Ishield AEB 26 Hydrant (3 Km Under Ground Pipe)
Supply, Installation of Wet sprinkler system, Fire Pump, Novec-1230
system
Development of Land at Ein
Khaled – Commercial Commercial Supply, Installation, Testing & Commisioning of Aerosol Fire
19 HKH EHAF
Development (B+G+ME+2) for Building Suppression system.
Qatar Navigation
Qatar Academy Auditorium (Qatar PAT Supply, Installation, Testing & Commisioning of NOVEC-1230
24 Recreational AEB System
Foundation) Engineering
25 Doha Port Pkg. 1 Commercial Ishield AEB Supply, Installation, Testing & Commisioning of Fire Alarm system
Design and Supply, Installation, Testing & Commisioning of Fire Alarm system,
26 Al Hekma International School Education - Fire Pump, wet sprinkler system.
Built
Alfardan (Proposed Residential Supply, Installation, Testing & Commisioning Fire Pump, wet
29 Commercial Shannon AEB sprinkler system, FM-200 System, Aerosol Fire Supression system.
Apartment)
Dukhan Tower (B+G+36) Red Line Supply, Installation, Testing & Commisioning of Fire Alarm system,
30 Hotel Apartment AEB Fire Pump, wet sprinkler system.
Dafna Area beside W Hotel Contractor
12 Building each Supply, Installation, Testing & Commisioning of Fire Pump, wet
31 Awqaf Building – Bin Mahmoud Hassanesco ECG
B+G+8 sprinkler system & Fire Alarm system.
Barahaa Tower – Lusail Area Supply of Hose Reel cabinets & Testing Commisioning of Fire
32 Commercial CRC EHAF Pump.
(4B+G+18)
James Cubit & Supply, Installation, Testing & Commisioning of Fire Pump, wet
40 5 Star Hotel (B+G+7) Hilton Commercial Atlantic sprinkler system & Fire Alarm system.
Partners
Jasrah Twin Tower - LUSAIL Supply of Hose Reel cabinets & Testing Commisioning of Fire
41 Commercial CRC EHAF
AREA (3B+G+16) Pump.
45 Muntazah Plaza Commercial How United AEB Supply, Installation, Testing & Commisioning Fire Alarm system.
PARSONS
o Eng. Ahmed Qassim – Senior Mechanical Engineer - 66499303
AEB Consultant :
o Eng. Nazir Ahmed – Senior Project Manager – 55379562
o Eng. Balvant Jhavarie – Fire and Safety Design Engineer – 66468016
ECG Consultant
o Eng. Walid – Projects Manager (Executions) – 66087698
o Eng. Raman – Senior Mechanical Engineer – 33651220
United Consultant
o Eng. Rames – Senior Mechanical Engineer – 66952413
Shaheen Consultant
o Eng. Hesham – Head of Projects - 33929870
Hassanesco
o Eng. Hatem – Head of Mechanical - 70246674
Water Control Valves (Gongs & Bells) / Pre-action System/Deluge system ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ :
ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ
.ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ /ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ
ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ
ﻣﻼﺣﻈﺎﺕ :
-ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ .
-ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ.
-ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ .
2019-01-02 ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ : 2017-01-02 ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ :
ﻉ/
ﺍﻟﻮﺻﻒ ﺍﻟﻤﻮﺩﻳﻞ
ALARM VALVES, 3,4,6,8 INCH SIZES, 175 AND 300 PSIG RATED PRESSURE, WITH
NECESSARY TRIM ACCESSORIES, FOR HORIZONTAL OR VERTICAL INSTALLATION AS H-2
INDICATED IN THE CERTIFICATE.
3RD PARTY
Underwriters ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ
CERTIFICATE / - VPLX.EX3148 - Laboratories (UL)
: ( )ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ
APPROVAL :
RECOMMENDATIONS ﺍﻟﺘﻮﺻﻴﺎﺕ
NOTES/STANDARD:
/ﻉ
VPLX.EX3148
Valves, Alarm
Page Bottom
Valves, Alarm
See General Information for Valves, Alarm
GLOBE FIRE SPRINKLER CORP EX3148
4077 AIRPARK DR
STANDISH, MI 486589447 USA
Models H1, H2, H3, 3 (80) and 4 (100) in. (mm) size and Models H1, H2, H3, 6 (150) in. (mm) size, rated pressure 175 psig. For
horizontal or vertical installation.
Models H2, 3 (80) and 4 (100), 6 (150) in. (mm) size, rated pressure 300 psig. For horizontal or vertical installation.
Model H1, 4 in. size with DIN Class 2633 end flanges, rated 16 Bar (232 psig) for vertical and horizontal installation. For use with Model B or
Model H retard chamber and Model F, WM or WM2 water motor alarm.
Models H, H1, H2, H3, 8 in. size, rated pressure 175 psig, for use with Model B or Model H retard chamber and Model F, WM or WM2 water
motor alarm for variable pressure service. For vertical installation only.
Models H2, 8 in. size, rated pressure 300 psig, for use with Model B or Model H retard chamber and Model F, WM or WM2 water motor alarm
for variable pressure service. For vertical installation only.
Model G provided with retarding chamber.
Last Updated on 20120423
© 2015 UL LLC
When the UL Leaf Mark is on the product, or when the word "Environment" is included in the UL Mark, please search the UL Environment
database for additional information regarding this product's certification.
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's FollowUp Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's FollowUp
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2015 UL LLC".
http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=VPLX.EX3148&ccnshorttitle=Valves,+Alarm&objid=1074306796&cfgid=1… 1/1
EZ01-CW04-QBEC-MEC-MAS-000010 Rev 2 74/87
Waterflow Alarm Valves
Waterflow alarm valves (alarm check valves) are installed in either vertical or horizontal positions in wetpipe sprinkler systems to
sound a fire alarm gong when a flow of water from the system equals or exceeds that of a single sprinkler. They are designed for use
with hydraulic or electric gongs or both.
There are two designs, the differential type and the pilot valve type. The differential type has a rubber-faced clapper with an annular
groove in the seat; the pilot valve type has a metal-faced clapper with a pilot valve attached to the clapper arm.
A retard chamber, which minimizes false alarms due to surges and fluctuations in water supply pressure, may be supplied with the
alarm valve. If a retard chamber is supplied,
only the listed chamber for a specific manufacturer and valve model shall be used. Alarm
valves are FM Approved with specific trim, and no substitutes or omissions in part or in full are allowed.
Alarms are tested by flowing water through the system test pipe. Pilot valves may be field-adjusted to assure alarm reliability. Unless
otherwise noted in the listing, these valves have 175 psi (1205 kPa) rated working pressure.
Remarks:
a. Resilient seat.
b. With Model H retard chamber.
c. Vertical installation only
d. Cast Iron.
e. Ductile Iron.
Model WM
Model WM. Single gong.
Water Control Valves (Gongs & Bells) / Pre-action System/Deluge system ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ :
ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ
ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ /ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ
ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ .
ﻣﻼﺣﻈﺎﺕ :
-ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ .
-ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ.
-ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ .
2017-10-04 ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ : 2015-10-05 ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ :
ﻉ/
3RD PARTY
Underwriters ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ
CERTIFICATE / - VPLX.EX3148 - Laboratories (UL)
: ( )ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ
APPROVAL :
RECOMMENDATIONS ﺍﻟﺘﻮﺻﻴﺎﺕ
Investigated to Standard ANSI/UL 193, "Alarm Valves for Fire-Protection Service," and UL 753, "Alarm Accessories for
Automatic Water-Supply Control Valves for Fire Protection Service."
/ﻉ
VPLX.EX3148
Valves, Alarm
Page Bottom
Valves, Alarm
See General Information for Valves, Alarm
GLOBE FIRE SPRINKLER CORP EX3148
4077 AIRPARK DR
STANDISH, MI 486589447 USA
Models H1, H2, H3, 3 (80) and 4 (100) in. (mm) size and Models H1, H2, H3, 6 (150) in. (mm) size, rated pressure 175 psig. For
horizontal or vertical installation.
Models H2, 3 (80) and 4 (100), 6 (150) in. (mm) size, rated pressure 300 psig. For horizontal or vertical installation.
Model H1, 4 in. size with DIN Class 2633 end flanges, rated 16 Bar (232 psig) for vertical and horizontal installation. For use with Model B or
Model H retard chamber and Model F, WM or WM2 water motor alarm.
Models H, H1, H2, H3, 8 in. size, rated pressure 175 psig, for use with Model B or Model H retard chamber and Model F, WM or WM2 water
motor alarm for variable pressure service. For vertical installation only.
Models H2, 8 in. size, rated pressure 300 psig, for use with Model B or Model H retard chamber and Model F, WM or WM2 water motor alarm
for variable pressure service. For vertical installation only.
Model G provided with retarding chamber.
Last Updated on 20120423
© 2015 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's FollowUp Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's FollowUp
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2015 UL LLC".
http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=VPLX.EX3148&ccnshorttitle=Valves,+Alarm&objid=1074306796&cfgid=1… 1/1
EZ01-CW04-QBEC-MEC-MAS-000010 Rev 2 79/87
2015-10-05 :ﺗﺎﺭﻳﺦ ﺍﻟﻄﺒﺎﻋﺔ ﻭﺯﺍﺭﺓ ﺍﻟﺪﺍﺧﻠﻴــــﺔ
ﻭﻗـﺖ ﺍﻟﻄﺒﺎﻋﺔ AM 9:03 : ﺍﻻﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﻪ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ
ﺭﻗــﻢ ﺍﻟﻄﻠـﺐ PAC15002207 : ﺇﺩﺍﺭﺓ ﺍﻟﻮﻗﺎﻳﺔ
Water Control Valves (Gongs & Bells) / Pre-action System/Deluge system ﺇﺳﻢ ﺍﻟﻤﻨﺘﺞ :
ﺗﻔﺎﺻﻴﻞ ﺍﻟﺸﻬﺎﺩﺓ
ﺗﻢ ﻣﺮﺍﺟﻌﺔ ﺍﻟﻄﻠﺐ ﺍﻟﻤﻘﺪﻡ ﻭﺍﺗﻀﺢ ﺑﺄﻧﻪ ﻻ ﻣﺎﻧﻊ ﻣﻦ ﺍﻋﺘﻤﺎﺩ ﺍﻟﻤﻨﺘﺞ /ﺍﻟﻤﻨﺘﺠﺎﺕ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻰ ﺍﻟﻤﺮﻓﻖ ﺑﻨﺎﺀ ﻋﻠﻰ ﺍﻋﺘﻤﺎﺩﻩ ﻣﻦ ﻗﺒﻞ ﺍﻟﻬﻴﺌﻪ
ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻮﺿﺤﻪ ﻓﻰ ﺍﻟﺘﻘﺮﺭ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ .
ﻣﻼﺣﻈﺎﺕ :
-ﻳﺠﺐ ﻋﻠﻰ ﺍﻟﺸﺮﻛﻪ ﺍﻻﻟﺘﺰﺍﻡ ﻭﺍﻟﻌﻤﻞ ﺑﻤﺎ ﺟﺎﺀ ﻓﻲ ﺍﺷﺘﺮﺍﻃﺎﺕ ﻗﺴﻢ ﺃﻧﻈﻤﺔ ﺍﻟﺴﻼﻣﻪ ﺍﻟﺘﻲ ﺗﻢ ﺍﻻﻃﻼﻉ ﻭﺍﻟﻤﻮﺍﻓﻘﺔ ﻋﻠﻴﻬﺎ ﻣﻦ ﺧﻼﻝ ﺍﻟﻤﻮﻗﻊ .
-ﻳﺠﺐ ﺍﻥ ﻳﻘﻮﻡ ﺑﺘﺮﻛﻴﺐ ﻫﺬﺍ ﺍﻟﻤﻨﺘﺞ ﻣﻦ ﻗﺒﻞ ﻣﻬﻨﺪﺳﻴﻦ ﻭﻓﻨﻴﻴﻦ ﻣﻌﺘﻤﺪﻳﻦ ﻣﻦ ﺍﻹﺩﺍﺭﺓ ﺍﻟﻌﺎﻣﺔ ﻟﻠﺪﻓﺎﻉ ﺍﻟﻤﺪﻧﻲ.
-ﻳﺠﺐ ﺍﻥ ﻳﺤﻤﻞ ﺍﻟﻤﻨﺘﺞ ﺍﻟﻌﻼﻣﺔ ﺍﻟﺘﺠﺎﺭﻳﺔ ﻟﻠﻬﻴﺌﻪ ﺍﻟﻤﺨﺘﺒﺮﻳﺔ ﺍﻟﻤﻌﺘﻤﺪﺓ ﻭﺍﻟﻤﻮﺿﺤﻪ ﻓﻲ ﺍﻟﺘﻘﺮﻳﺮ ﺍﻟﻔﻨﻲ ﺍﻟﻤﺮﻓﻖ .
2017-10-04 ﺗﺎﺭﻳﺦ ﺍﻹﻧﺘﻬﺎﺀ : 2015-10-05 ﺗﺎﺭﻳﺦ ﺍﻻﻋﺘﻤﺎﺩ :
ﻉ/
3RD PARTY
Underwriters ﺷﻬﺎﺩﺓ ﺍﻟﻤﺨﺘﺒﺮﺍﺕ ﺍﻟﻤﺴﺎﻧﺪﺓ
CERTIFICATE / - VPLX.EX3148 - Laboratories (UL)
: ( )ﻣﻦ ﻫﻴﺌﺎﺕ ﻣﻌﺘﻤﺪﺓ
APPROVAL :
RECOMMENDATIONS ﺍﻟﺘﻮﺻﻴﺎﺕ
NOTE: The basic standards used to investigate products in this category are ANSI/UL 193, "Alarm Valves for Fire-Protection
Service," and UL 753, "Alarm Accessories for Automatic Water-Supply Control Valves for Fire Protection Service."
/ﻉ
VPLX.EX3148
Valves, Alarm
Page Bottom
Valves, Alarm
See General Information for Valves, Alarm
GLOBE FIRE SPRINKLER CORP EX3148
4077 AIRPARK DR
STANDISH, MI 486589447 USA
Models H1, H2, H3, 3 (80) and 4 (100) in. (mm) size and Models H1, H2, H3, 6 (150) in. (mm) size, rated pressure 175 psig. For
horizontal or vertical installation.
Models H2, 3 (80) and 4 (100), 6 (150) in. (mm) size, rated pressure 300 psig. For horizontal or vertical installation.
Model H1, 4 in. size with DIN Class 2633 end flanges, rated 16 Bar (232 psig) for vertical and horizontal installation. For use with Model B or
Model H retard chamber and Model F, WM or WM2 water motor alarm.
Models H, H1, H2, H3, 8 in. size, rated pressure 175 psig, for use with Model B or Model H retard chamber and Model F, WM or WM2 water
motor alarm for variable pressure service. For vertical installation only.
Models H2, 8 in. size, rated pressure 300 psig, for use with Model B or Model H retard chamber and Model F, WM or WM2 water motor alarm
for variable pressure service. For vertical installation only.
Model G provided with retarding chamber.
Last Updated on 20120423
© 2015 UL LLC
The appearance of a company's name or product in this database does not in itself assure that products so identified have been manufactured
under UL's FollowUp Service. Only those products bearing the UL Mark should be considered to be Certified and covered under UL's FollowUp
Service. Always look for the Mark on the product.
UL permits the reproduction of the material contained in the Online Certification Directory subject to the following conditions: 1. The Guide
Information, Assemblies, Constructions, Designs, Systems, and/or Certifications (files) must be presented in their entirety and in a non
misleading manner, without any manipulation of the data (or drawings). 2. The statement "Reprinted from the Online Certifications Directory
with permission from UL" must appear adjacent to the extracted material. In addition, the reprinted material must include a copyright notice in
the following format: "© 2015 UL LLC".
http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/showpage.html?name=VPLX.EX3148&ccnshorttitle=Valves,+Alarm&objid=1074306796&cfgid=1… 1/1
EZ01-CW04-QBEC-MEC-MAS-000010 Rev 2 82/87
Water Motor Gongs
Water motor gongs give a locally audible alarm signal when the automatic sprinkler system operates. They may be used with
waterflow alarm, dry pipe, or automatic water control valves.
Model WM
Model WM. Single gong.
Ishield Security and safety Warrants to the extent hereinafter set forth, each equipment as per the
below list to be free from defects in materials and workmanship under the normal use and service
for which it was intended if and only if it was serviced by Ishield.
Ishield’s Obligation under this warranty is limited to replacing or repairing free of charge, any
defective part of parts that supplied by Ishield Security and Safety for the above project.
This warranty shall not apply to any item/equipment was repaired or altered by other party other
than Ishield without Ishield Written approval, or which have been subject to misuse, negligence
or accident or which have been operated under conditions more serve than, or otherwise
exceeding, those set forth in the specification for such equipment.
Ishield shall not be liable for any loss or damage resulting directly or indirectly from the use or
loss of the equipment without limiting the generality of the foregoing, this execution from
liability embraces the purchaser’s expenses for down time or for making up downtime, and/or
damage for which the purchaser may be liable to other party, and/or damage to property, and/or
injury or death of any persons.
Ishield neither assumes nor authorizes any person to assume for it any other liability in
connection with the sale, or use of the above mentioned equipment.
SIGNATURE :
-
-
( Additional parameters can be added as Applicable to the project Application)
NUMBER OF STOREYS:
THE BUILDING COMPRISES OF GROUND FLOOR AND MEZZANINE FLOOR. 1
·
· (Officer's Signature)
·
CONSULTANT SIGNATURE:
UPDA REG.NO: 2616 QID NO: 27160808616
FROM 27/04/2011 TO 26/04/2021
CONSULTANT:
QUANTITY LOCATION
1
DESIGN & BUILD OF LIGHT INDUSTRIAL
AND LOGISTICS UNITS AT RAS BUFONTAS
SPECIAL ECONOMIC ZONE (PORTION 1)
1
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-01
DATE:02-07-2020 SHEET: 01 OF 13 SCALE: NTS
PLOT CO-ORDINATES PLOT CO-ORDINATES
PA-UT-04
EASTING NORTHING EASTING NORTHING 244990.0508
SS-01 1891718.5423
PA-HQ-01
23299.10
8 238511.132 386486.995 18 238484.092 386464.033
SS-19
SS-25
2 LOCATION PLAN
SCALE 1:2000
+0.65 ASSEMBLY
APPLICATION NO: NN/2018/0090
Road F.L. Road F.L. POINT C
(+ 0.877) (+ 0.443) (Reviewing Engineer's Signature / Date)
R Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. R
(+ 1.179) (+ 1.070) (+ 0.906) (+ 0.797) (+ 0.688) (+ 0.579) (+ 0.470)
+13.20
TOP
5010
5010
ROOF DRAIN
Road F.L.
(+ 1.288) 14 15 16 17 18 19 20 21 22 23 24 25
9 10 11 12 13
3'' 01 02 03 04 05 06 07 08
GF
Q Q
G.F. LINE
2''
ASSEMBLY
15 CS CS CS CS
32 POINT B
3300
3300
G.R.C. +5.65
ASSEMBLY TOP E:238516.152
POINT A
+13.20 +13.20 +13.20 RD N:386552.275
1'' 60 SLOPE 1%
E 1%
E 1%
ROOF DRAIN TOP GROUND GROUND GROUND OP
N:386526.493 TOP TOP TOP SL
3500
3500
SLOP
FLOOR LINE FLOOR LINE +11.00 +10.80 FLOOR LINE
+13.20 F.F.L. S.S.L. Road F.L. SUBSTATION
+11.00 +10.80 +11.00 +10.80
TOP ( 5.289)
N F.F.L. S.S.L. ROOF DRAIN F.F.L. S.S.L. ROOF DRAIN ROOF DRAIN +4.25 +5.65 N
G.F
ROOF DRAIN
2600
2600
GF S.S.L. TOP
.L
+4.45
IN
Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. Road F.L.
F.F.L.
E
Road F.L.
M (+ 1.354)
(6.025) (5.916) (5.752) (5.643) (5.534) (5.425) (5.316) M
3250
3250
(5 +15.65
L +15.65 )
17
.8
+15.65 +15.65 +15.65 +15.65 +15.65 TOP L
+15.65 G.R.C.
2845
2845
TOP TOP TOP TOP TOP TOP
SLOP
+12.20 TOP +12.20 +12.20 +12.20 +12.20 +12.20 +12.20 +12.20
E 1%
K
lower lower lower lower lower lower lower lower
K CONSULTANT SIGNATURE:
SLO
PE
1%
Road F.L. SLOP
E 1%
RD
(+ 1.398)
UPDA REG.NO: 2616 QID NO: 27160808616
5800
5800
GF GF
J GF J
FROM 27/04/2011 TO 26/04/2021
300
300
+12.20 +12.20 +12.20 +12.20 +12.20 +12.20 +12.20 +12.20
H TOP TOP TOP G TOP TOP TOP TOP TOP
H
.F
3940
3940
+6.65
F.F.L
+6.65
F.F.L
.L
IN
E
CONSULTANT:
+12.10 +12.10 +12.10 +12.10 +12.10 +12.10 +12.10
G lower lower lower lower lower lower lower G
FENCE LOCATION
A.2
A.2
E.M
E.M
E.M
E.M
E.M
E.M
E.M
E.M
A.2
A.2
A.2
A.2
A.2
A.2
R
R
R
R
+1.15
R
+0.35
R
R
+5.31 +1.50 +1.35 +1.05 +0.80 +0.65
PAV. 20%(1:5-L=2.25) PAV. 20%(1:5-L=2.74) PAV. 20%1:5-L=2.06) PAV. 20%(1:5-L=2.50) 20%(1:5-L=2.06) 20%(1:5-L=2.75) PAV.
TOP PAV. PAV. +0.45 20%(1:5-L=2.00)
PAV. 20%(1:5-L=2.60)
3945 3950 3940 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 365 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 7890 7890
ASSEMBLY E:238513.744
POINT E
20
13
E:238362.524
N:386497.454
SECURITY KIOSK
CC. TV.
RoadS*3
F.L.
(+ 1.357)
Road F.L. S*5
S*4
(+ 1.257)
WHEEL S*6
GUIDES
S*7Road F.L. S*8
(+ 1.042)
S*9 S*10Road F.L. S*11
(+ 0.937)
S*12 S*13Road F.L. S*14
(+ 0.686)
S*15 S*16Road F.L. S*17
(+ 0.537)
WHEEL S*18
GUIDES
S*19 Road F.L.S*20
(+ 0.352)
S*21 S*22 RoadS*23
F.L. S*24
(+ 0.237)
S*25 N:386521.002
ASSOCIATED CONSULTING ENGINEERS
ASSEMBLY
TRUCK TRUCK
15800
POINT D 15775 15780 15780 15780 ROAD15780
LINE 15775 15785
Road F.L. FIRE TRUCK HARD STAND FIRE TRUCK HARD STAND FIRE TRUCK HARD STAND
(+ 1.520)
1* S*1 S*2 2* 3* 4* 5* 6* 7* 8* 9* 10* P.O. Box 39304
ENTRANCE
RA
+0.80
20%(1:5-L=2.74)
RA
+0.60
20%(1:5-L=2.00)
R
+0.45
PAV.
20%(1:5-L=2.75) F UPDA REG. NO: 25 COMPANY REG. GRADE: INT'L
PAV. RA PAV. RA PAV. RA PAV. RA PAV. PAV. PAV. A.2 RA
.2 .2
3950
3950
.2 .2 .2 .2 .2 SECURITY KIOSK
E.M
E.M
E.M
E.M
E.M
E.M
E.M
E.M
E* E*
& Q.TELROOM FENCE LOCATION
VALIDITY: 29-10-2020 QID NO.11762100
300
295
+6.45 +6.10 +0.90
F.F.L F.F.L F.F.L
E +12.25 +12.25 +12.25 +12.25 +12.25 +12.25 +12.25 E
Road F.L. +12.35 lower +12.35 lower lower +12.35 lower +12.35 lower +12.35 lower +12.35 lower +12.35 E:238494.014
10
5800
5805
(6.435) TOP TOP TOP TOP TOP TOP TOP
N:386499.498
E:238512.312
Road F.L. Road F.L. Road F.L. Road F.L. Road F.L.
N:386502.341 11
(6.095) (5.993) (5.788) (5.482)
Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. (5.175) Road F.L.
D (5.686) (5.584) (5.379) (5.072)
D Road F.L.
(6.198) (5.891) (5.277) (4.970)
2845
2845
+15.80 +15.80 +15.80 +15.80 +15.80 +15.80 +15.80 +15.80
TOP TOP TOP TOP TOP TOP TOP TOP
C* C*
+12.35 +12.35 +12.35 +12.35 +12.35 +12.35 +12.35 +12.35
3250
3250
lower lower lower lower lower lower lower lower
CS
C C
3095
3095
E:238496.335
N:386484.680 09
B* CS
B*
2950
2950
FENCE LOCATION
ROOF DRAIN ROOF DRAIN ROOF DRAIN ROOF DRAIN
B +11.15 +10.95 +11.15 +10.95 +11.15 +10.95 +11.15 +10.95 B E:238511.132
08
F.F.L. S.S.L. F.F.L. S.S.L. F.F.L. S.S.L. F.F.L. S.S.L. N:386486.995
3400
CS
+6.60
GROUND GROUND GROUND
FLOOR LINE FLOOR LINE FLOOR LINE
+12.75 +12.75 +12.75 +12.75
A*
ROOF DRAIN
TOP +13.35
TOP
TOP +13.35
TOP
TOP +13.35
TOP
TOP
A* AND LOGISTICS UNITS AT RAS BUFONTAS
SPECIAL ECONOMIC ZONE (PORTION 1)
4570
4570
E:238358.774 CS
04
ROOF DRAIN
N:386460.622
ASSEMBLY
1'
POINT G
A GF
A E:238510.520
26 27 28 29 30 31 47 07
2'
N:386478.934
3'
+13.35
GF
ROOF DRAIN
+13.35
TOP LOCATION: Ras Bufontas Special Economic Zone PIN NO: 90042229
TOP
ASSEMBLY
POINT F
ASSEMBLY
POINT H
GF GF
275
4885 2765 1300 3870 3330 1475 3960 3340 3395 3400 3340 3960 1475 3600 3650 1475 3960 3340 3355 365 3350 3340 3960 1475 3650 3600 1475 3960 3340 3345 245 3425 3340 3960 1475 3330 1620 950 2750 1725 1800 3625 3310 1210 7800
MEZZANINE
OUTLINE
CAR PARKING
CAR PARKING SHADE
R SHADE R
RA.1
LIGHT INDUSTRIAL UNIT NO.08 ENTRANCE
5010
5010
3'' SHAFT
Q +0.65 Q
2'' 15 +1.25 PAV.
(Officer's Signature)
32 +1.00 MEZZANINE
3300
3300
+0.90 +0.65 ENTRANCE
+1.4 PAV. PAV. PAV. OUTLINE
UP UP UP UP UP PAV.
RA.1
RA.1
V.C.B-11kv SWITCH GEAR ROOM
+1.20
UP
1'' 60
PAV.
+0.55
P 32 F.F.L
P
FHC
RA.1
RA.1
RA.1
SHAFT
ENT. ENT. ENT. ENT. ENT.
FHC
.50 LIGHT INDUSTRIAL UNIT FHC
3500
3500
SEC-A +1 AV. FHCLIGHT INDUSTRIAL LIGHT INDUSTRIAL UNIT LIGHT INDUSTRIAL +0.65 +0.75 F.F.L.
P T2 T1 LIGHT INDUSTRIAL UNIT NO.04 ENTRANCE S.S.L. +0.55 S.S.L.
LIGHT INDUSTRIAL UNIT UNIT NO.05 ENTRANCE NO.06 ENTRANCE FHC UNIT NO.07 ENTRANCE
NO.02 ENTRANCE +1.70 +1.35 NO.03 ENTRANCE +1.35 +1.00 +1.00 +0.65
N N
FHC S.S.L. S.S.L.
FHC S.S.L. S.S.L. S.S.L. S.S.L.
SEC-A APPLICATION NO: NN/2018/0090
2600
2600
LIGHT INDUSTRIAL UNIT SHAFT SHAFT SHAFT SHAFT
M
NO.01 ENTRANCE
2HR fire rated wall T ROOM M
(Reviewing Engineer's Signature / Date)
2HR fire rated wall 400x200x200mm 2HR fire rated wall 2HR fire rated wall
+1.70 2HR fire rated wall 2HR fire rated wall
3250
3250
RA.1 concrete block
S.S.L. +0.55
ENT. FHC flush jointed. 400x200x200mm concrete F.F.L
2845
SEC-B SEC-B
MV-415V ROOM
+0.55
F.F.L
K K
2800 mm H. block work
sandwich panel partition
100 mm thickness
LIGHT INDUSTRIAL UNIT NO.01 LIGHT INDUSTRIAL UNIT NO.02 LIGHT INDUSTRIAL UNIT NO.03 LIGHT INDUSTRIAL UNIT NO.04 LIGHT INDUSTRIAL UNIT NO.05 LIGHT INDUSTRIAL UNIT NO.06 LIGHT INDUSTRIAL UNIT NO.07 LIGHT INDUSTRIAL UNIT NO.08
5800
5800
2800 mm H. block work
+1.80 F.F.L. +1.80 F.F.L. +1.45 F.F.L. +1.45 F.F.L. +1.10 F.F.L. sandwich panel partition +1.10 F.F.L. +0.75 F.F.L. +0.75 F.F.L.
2800 mm height insulation +1.60 S.S.L. 2800 mm H. block work +1.60 S.S.L. +1.25 S.S.L. +1.25 S.S.L. +0.90 S.S.L. 100 mm thickness +0.90 S.S.L. +0.55 S.S.L. +0.55 S.S.L.
block work sandwich panel partition
100 mm thickness 100 mm thickness
J J
300
300
00 FHC FHC FHC
H 34 FHC FHC FHC FHC FHC H
sk S-2
3940
3940
Kio nd +1.80
OH
rity ma +1.353 +1.80 F.F.L +1.038 +1.45 +0.933 +1.45 +0.682 +1.10 +0.533 +0.348 +0.233
cu m +1.253
Se . Co ROAD F.L F.F.L
ROAD F.L ROAD F.L F.F.L ROAD F.L F.F.L ROAD F.L F.F.L ROAD F.L ROAD F.L ROAD F.L
F
F.F .65 ent
G G
+1 ipm
Eq Ro
.L
u om
Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. Road F.L. Road F.L.
+0.75
.2
.2
+1.10 +0.75
RA
RA
(+ 1.357) (+ 1.257) (+ 1.042) (+ 0.937) (+ 0.686) (+ 0.537) (+ 0.352) (+ 0.237)
.2
.2
.2
.2
F.F.L
.2
PA
+1
F.F.L
RA
F.F.L
.2
RA
RA
RA
+1.50
RA
+1.15
RA
.50
430
0
3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 365 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 7890 7890
S*3 S*4 S*5 S*6 S*7 S*8 S*9 S*10 S*11 S*12 S*13 S*14 S*15 S*16 S*17 S*18 S*19 S*20 S*21 S*22 S*23 S*24 S*25
CONSULTANT SIGNATURE:
15800 15775 15780 15780
ELV-3 365
15780 15780 15775 15785
UPDA REG.NO: 2616 QID NO: 27160808616
000038
1* S*1 S*2 2* 3* 4* 5* 6* 7* 8* 9* 10*
ELV-4
FROM 27/04/2011 TO 26/04/2021
1 2 3 4 5 6 000038 7 8 9 10
CONSULTANT:
15775 15780 Road F.L. Road F.L. 15780 Road F.L. 15780 Road F.L. 15780 Road F.L. 15780 Road F.L. 15780 Road F.L. 15780 Road F.L.
(+ 1.357) (+ 1.257) (+ 1.042) 365 (+ 0.937) (+ 0.686) (+ 0.537) (+ 0.352) (+ 0.237)
S1 S2 S3 S4 S5 S6 S7 S8 S9 S10 S11 S12 S13 S14 S15 S16 S17 S18 S19 S20 S21 S22 S23 S24 S25 S26 20%(1:5-L=2.75) Security
+1.45 +0.352 Kiosk
14%(1:7-L=3.45) 19%(1:5.3-L=3.45) +1.30 13%(1:7.7-L=3.45) +1.30 16%(1:6.2-L=3.70) 12%(1:8.2-L=3.45) 16%(1:6.3-L=3.45) +0.45
+1.55 RA PAV. RA PAV. RA +0.95 RA +0.80 RA +0.60 RA ROAD F.L
3945 3615 7890 3945 3945 7890 RA 3945 3945 PAV. 7890 3945 3945 .2 3945 3945 7890 3945 3945 PAV. 3945 3945 3560 3945 PAV.
330 PAV. .2 .2 .2 8255 PAV. .2 7890 .2 PAV. 7890 385 .2
Telecom
Room
F +1.30 +1.15 +0.702 +0.502
F
+0.832
+1.95
+1.458
ROAD F.L +1.95
ROAD F.L
+1.60
ROAD F.L
+1.60
+1.002
ROAD F.L +1.25 ROAD F.L
+1.25
ROAD F.L
+0.90
ROAD F.L
+0.90
F.F.L ASSOCIATED CONSULTING ENGINEERS
3950
3950
F.F.L F.F.L F.F.L F.F.L F.F.L F.F.L F.F.L
E* FHC FHC FHC FHC
FHC FHC FHC FHC E*
300
295
+1.60
F.F.L
+1.25
F.F.L +0.90 P.O. Box 39304
E 4 WAY-BREECHING INLET F.F.L E
FOR SPRINKLER SYSTEM 5/F Office No. 503 Behzad Business Center
5800
5805
LIGHT INDUSTRIAL UNIT NO.13
LIGHT INDUSTRIAL UNIT NO.09 LIGHT INDUSTRIAL UNIT NO.10 LIGHT INDUSTRIAL UNIT NO.11 LIGHT INDUSTRIAL UNIT NO.12
+1.25 F.F.L.
LIGHT INDUSTRIAL UNIT NO.14
+1.25 F.F.L.
LIGHT INDUSTRIAL UNIT NO.15
+0.90 F.F.L.
LIGHT INDUSTRIAL UNIT NO.16
+0.90 F.F.L.
Building No. 57, Zone 23, Street 342
+1.95 F.F.L. +1.95 F.F.L. +1.60 F.F.L. +1.60 F.F.L. +1.05 S.S.L. +1.05 S.S.L. +0.70 S.S.L. +0.70 S.S.L.
+1.75 S.S.L. +1.75 S.S.L. +1.40 S.S.L. +1.40 S.S.L. Al Jazeera Street, Fareej Bin Mahmoud, Doha, Qatar
D D
Tel: +974-4435-0858 Fax: +974-4421-0720
2845
2845
C* C*
2800 mm height insulation HEAD OFFICE SIGNATURE:
3250
3250
block work
100 mm thickness
3095
LIGHT INDUSTRIAL UNIT NO.13 ENTRANCE
UP +1.85 +1.50 +1.50 +1.15 +1.15 +0.80 UP
VALIDITY: 29-10-2020 QID NO.11762100
FHC
2950
LIGHT INDUSTRIAL LIGHT INDUSTRIAL UNIT
LIGHT INDUSTRIAL UNIT NO.15 ENTRANCE
RA.1
RA.1
LIGHT INDUSTRIAL UNIT NO.12 ENTRANCE
RA.1
ENT. ENT. ENT. ENT. UNIT NO.14 ENTRANCE ENT. ENT. NO.16 ENTRANCE
NO.09 ENTRANCE
B B
RA.1
RA.1
RA.1
+1.55 +1.40
ENTRANCE
UP +1.05
ENTR.
PAV. UP PAV. MEZZANINE UP MEZZANINE UP +0.80
3400
3400
SHAFT
T1 +1.15 PAV. +0.85 UP +0.90 F.F.L.
UP OUTLINE PAV. OUTLINE PAV. +0.70 S.S.L. +0.70 S.S.L.
PAV.
A* +1.85 RA.1 SHAFT
A*
T2 S.S.L.
4570
4570
68
RA.1
5
1'
29
40
A SHAFT
A
2'
3'
+0.70
+1.55 PAV.
PAV.
3345 3960 1475 7250 1475 3960 3345 7070 3345 3960 1475 4950 950 2505 1970 1800 3625
2825 2640 3250 5175 750 1475 3960 3345 3400 270 3430 8725 1475 3960 3340 3255 3395 3345 3960
415
1A 1B 1C 1D 2A 2B 2C 2D 2E 3A 3B 3C 3D 3E 4A 4B 4C 4D 6A 6B 6C 6D 7A 7B 7C 7D 7E 8A 8B 8C 8D 8E 9A 9B 9C 9D 9E 9F
LOCATION: Ras Bufontas Special Economic Zone PIN NO: 90042229
15780 365 15780 15780
15775 15780 15780 15780 15780
AREA:QEZ-1 STREET: N/A PLOT: WH-04
1 2 3 4 5 6 7 8 9 10
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-03
DATE:02-07-2020 SHEET: 03 OF 13 SCALE: 1:200
2*E 3*A 7*E 8*A
1*C 1*D 2*A 2*B 3*D 3*E 4*A 4*B 5* 6* 6*C 6*D 7*A 7*B 8*D 8*E 9*A 10*A
3*
1* 1*A 1*B 2* 2*C 2*D 3*B 3*C 4* 4*C 4*D 6*A 6*B 7* 7*C 7*D 8* 8*B 8*C 9* 9*B 9*C 9*D 9*E 9*F 10* 10*B
1300 950
2975 4885 2765 3870 3330 1475 3960 3340 3395 3400 3340 3960 1475 3600 3650 1475 3960 3340 3355 3350 3340 3960 1475 3650 3600 1475 3960 3340 3345 300 3425 3340 3960 1475 3330 1620 1725 1800 3625 3310 1210 7800
275 365
R R
LIU 08
5010
5010
SINGLE TENANT
OFFICE SPACE
3'' R.A. SHAFT
Q Q
15
2'' 32
3300
3300
60
1'' 32
P SHAFT LIU 03 LIU 05 LIU 06 LIU 07 P
SINGLE TENANT SINGLE TENANT SINGLE TENANT SINGLE TENANT +0.75 +4.45 (Officer's Signature)
3500
3500
SEC-A LIU 01 LIU 02 OFFICE SPACE OFFICE SPACE OFFICE SPACE OFFICE SPACE F.F.L F.F.L.
FE-1
LIU 04
FE-2
SINGLE TENANT SINGLE TENANT
OFFICE SPACE OFFICE SPACE SINGLE TENANT 3000
N N
FE-1
FE-1
FE-1
FE-1
FE-1
FE-1
FE-2
FE-2
FE-2
FE-2
FE-2
FE-2
OFFICE SPACE 41
SEC-A
2600
2600
SHAFT SHAFT
FE-1
SHAFT
FE-2
SHAFT 1296 3100 3100 1400
R.A. R.A.
FZV-2 R.A. R.A. R.A. R.A. R.A.
M 3000
M
FZV-3 2hr. Fire Rated Wall / FZV-4 1504
FZV-5 1504 1504
FZV-6 1504
FZV-7 1504 FZV-8 1504
NIARD OT
11
NIARD OT
NIARD OT
NIARD OT
NIARD OT
NIARD OT
NIARD OT
CV CV CV CV CV CV CV
8
3250
3250
9 10
Cement board.
7
L 1315 3100 3100 3100 3100 1805 1315 3100 3100 3100 3100 1805 1315 3100
3000
3100 3100 3100 1805 1315 3100
3000
3100 3100
3000
3100 1805 1315 3100
3000
3100 3100 3100 1805 1315 3100
3000
3100 3100 3100 1805 1685
3000
3100 3100 3100 3100 1800 L (Reviewing Engineer's Signature / Date)
FZV-1 1100
2800 MM H. BLOCK WORK/. 13 14 15 16 17
FIRE SCENARIO - MOST REMOTE / MOST DEMAND
2845
2845
TO DRAIN
CV
5800
3000 3000 3000 3000 3000 3000 3000
No.01 No.02 No.03 No.04 No.05 No.06 No.07 No.08
25 27 28 29 30
J J
300
300
3000 3000 3000 3000 3000 3000 3000
3940
1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000
G SLO
G
PE 1%
SL
OPE
1%
+5.05
T.O.P.
SL
OPE 3945 3950 3940 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 365 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 3945 7890 7890
1%
SLO
PE 1%
S*3 S*4 S*5 S*6 S*7 S*8 S*9 S*10 S*11 S*12 S*13 S*14 S*15 S*16 S*17 S*18 S*19 S*20 S*21 S*22 S*23 S*24 S*25
1%
PE
SLO
1%
PE
SLO
F F
2950 2950 2950 2950 2950 2950 2950 2950 2950
3950
3950
1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000 1000 3100 1000
295
3000 3000 3000 3000 3000 3000 3000 3000 3000
5805
3000 3000 3000 3000 3000 3000 3000 3000 3000
2845
OPEN BELOW OPEN BELOW OPEN BELOW OPEN BELOW
+1.95 +1.95 +1.60 +1.60 +1.25 +1.25 +0.90 +0.90
F.F.L 3100 F.F.L 3100 F.F.L 3100 F.F.L F.F.L 3100 F.F.L3100 F.F.L
C*
1750 3100
3000
3100
3250
FZV-12
TO DRAIN
TO DRAIN
TO DRAIN
TO DRAIN
TO DRAIN
TO DRAIN
FZV-16
CV CV CV CV CV CV CV
FZV-14
TO DRAIN
1504
3000 3000
C C
HEAD OFFICE SIGNATURE:
FZV-10 FZV-11
1750 3100 2700
SHAFT
R.A. R.A. SHAFT R.A. FZV-13 R.A. SHAFT R.A. FZV-15 R.A. SHAFT 1296 3100 3100 1400
3095
3095
3000 LIU 10 LIU 11 LIU 13 3000
B* B*
SINGLE TENANT
OFFICE SPACE
SINGLE TENANT
OFFICE SPACE LIU 12
SINGLE TENANT
OFFICE SPACE LIU 14 LIU 15
+0.90 UPDA REG. NO: 25 COMPANY REG. GRADE: INT'L
2950
2950
SINGLE TENANT SINGLE TENANT SINGLE TENANT F.F.L
TO DRAIN
CV
QID NO.11762100
3000
B FZV-9
R.A.
B
VALIDITY: 29-10-2020
3400
3400
SHAFT
A* SHAFT
A*
R.A.
LIU 09
SINGLE TENANT LIU 16
4570
4570
OFFICE SPACE SINGLE TENANT
OFFICE SPACE
1'
A SHAFT A
2'
3'
950
2825 2640 3250 5175 7501475 3960 3345 3400 270 3430 3345 3960 1475 7250 1475 3960 3345 7070 3345 3960 8725 1475 3960 3340 3255 3395 3345 3960 1475 4950 2505 1970 1800 3625
415
1A 1B 1C 1D 2A 2B 2C 2D 2E 3A 3B 3C 3D 3E 4A 4B 4C 4D 6A 6B 6C 6D 7A 7B 7C 7D 7E 8A 8B 8C 8D 8E 9A 9B 9C 9D 9E 9F
1
1 FIRE FIGHTING SYSTEM MEZZANINE FLOOR PLAN LOCATION: Ras Bufontas Special Economic Zone PIN NO: 90042229
- SCALE 1:200
AREA:QEZ-1 STREET: N/A PLOT: WH-04
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-04
DATE:02-07-2020 SHEET: 04 OF 13 SCALE: 1:200
1 2 3 4
7000
1100 1500 4200
FE-1
FE-2
G.R.C.
A A
D3
+1.20
FE-1
APPLICATION NO: NN/2018/0090
+0.55 FE-2 (Reviewing Engineer's Signature / Date)
F.F.L
FIRE EXTINGUISHER
ENLARGED DETAILS
8000
8000
CONSULTANT SIGNATURE:
UPDA REG.NO: 2616 QID NO: 27160808616
FROM 27/04/2011 TO 26/04/2021
15452
15452
CONSULTANT:
B B
4000
Building No. 57, Zone 23, Street 342
Al Jazeera Street, Fareej Bin Mahmoud, Doha, Qatar
Tel: +974-4435-0858 Fax: +974-4421-0720
3252
MV (415V) ROOM
G.R.C. +0.55
F.F.L DESIGN & BUILD OF LIGHT INDUSTRIAL
AND LOGISTICS UNITS AT RAS BUFONTAS
D D SPECIAL ECONOMIC ZONE (PORTION 1)
1 2 3 4 SUBSTATION
FIRE FIGHTING LAYOUT
SHEET PROPERTIES
1 SUBSTATION FIRE FIGHTING LAYOUT REVISION: 1 SHEET SIZE: A0 SETTING: DWF
- SCALE 1:25 FF-05
DATE:02-07-2020 SHEET: 05 OF 13 SCALE: 1:25
+0.55 +0.55
F.F.L F.F.L
EOL
EOL
C C
EOL
EOL
EOL
EOL From ceiling void
3252
3252
From ceiling void
To trench void To trench void
MV (415V) ROOM MV (415V) ROOM
G.R.C. +0.55 G.R.C. +0.55
F.F.L F.F.L
D D
(Officer's Signature)
1100 1500 4200 1100 1500 4200
7000 7000 APPLICATION NO: NN/2018/0090
(Reviewing Engineer's Signature / Date)
1 2 3 4 1 2 3 4
1 MV ROOM AEROSOL SYSTEM LAYOUT 1 MV ROOM TRENCH LEVEL AEROSOL SYSTEM LAYOUT
- SCALE 1:25 - SCALE 1:25
SCHEMATIC DIAGRAM
EOL
Scale: NTS
DSPA 8-1-60
EOL
CONSULTANT SIGNATURE:
EOL
CONSULTANT:
WARNING
EOL
DONOT ENTER
EOL
DSPA
WARNING
SIGN
EOL
Design Calculation
LOCATION: Ras Bufontas Special Economic Zone PIN NO: 90042229
AREA:QEZ-1 STREET: N/A PLOT: WH-04
MV ROOM
AEROSOL SYSTEM LAYOUT
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-06
DATE:02-07-2020 SHEET: 06 OF 13 SCALE: 1:25
01 02 03 04
100 100
1915 3140 5680
FIRE EXTINGUISHER APPLICATION NO: NN/2018/0090
(Reviewing Engineer's Signature / Date)
ENLARGED DETAILS
B B
FE-1
FE-1
CONSULTANT SIGNATURE:
SECURITY KIOSK EQUIPMENT ROOM CC.TV CONTROL ROOM UPDA REG.NO: 2616 QID NO: 27160808616
FE-1
3200
01 02 03 04
1 GROUND FLOOR PLAN FIRE FIGHTING LAYOUT LOCATION: Ras Bufontas Special Economic Zone PIN NO: 90042229
- SCALE 1:25
AREA:QEZ-1 STREET: N/A PLOT: WH-04
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-07
DATE:02-07-2020 SHEET: 07 OF 13 SCALE: 1:20
01 02 03 01 02 03
MONITOR MODULE
CONNECT TO
MAIN FIRE ALARM SYSTEM
3170 1915 3170 1915
FECP
CAUTION ! ARABIC !
M
DOOR
A
SECURITY KIOSK SECURITY KIOSK
+0.50 +0.50
S
F.F.L S S F.F.L
GAS DISCHARGE
GAS DISCHARGE
EVACUATE NOW
DO NOT ENTER
3195
S S
3195
A
B B (Officer's Signature)
3170 1910 M
SA
FM200 FLOW CALCULATION DESIGN DATA
S
S S
CONSULTANT SIGNATURE:
S S UPDA REG.NO: 2616 QID NO: 27160808616
FROM 27/04/2011 TO 26/04/2021
CONSULTANT:
•
•
• ASSOCIATED CONSULTING ENGINEERS
•
•
Remote Auto/Manual
Releasing Solenoid
Extinguishant Low
Extinguishant Released
Pressure Switch
Pressure Switch
1st Stage 2nd Stage
Remote Manual
Release Switch
VALIDITY: 29-10-2020 QID NO.11762100
Select Switch
Notification Notification
Disablement Switch
Releasing
Detectors
•
470R
470R
470R
470R
470R
DIODE
Stop Air Conditioning
Shutdown Power
•
01 02 03 •
6K8
6K8
3165 1910 S
6K8
6K8
6K8
6K8
6K8
To Status O
( +4.90 ) Units S S L
+4.90 •
TOP LEVEL TOP S S
S S
•
( +4.40 )
500
+4.40 •
F.F.L. F.F.L.
E +R0V SIL AL FLT RST NC C NO NC C NO NO C NC C NO NC C NO NC C NO
200
AUX REMOTE DATA POWER NAC 1 NAC 2 ZONE 1ZONE 2 ZONE 3 2ND 1ST 2ND MODE MAN. ABORT REL EXTING. LOW EXTRACT TROUBLE LOCAL FIRE
24V CONTROL STATUS UNITS SOUNDER STAGE STAGE SELECT RELEASE PRESS. PRES. RELAY FIRE RELAY
SWITCH SWITCH
( +4.20 ) LEGEND
S.S.L. GENERAL SYSTEM STATUS
SOUNDER FAULT/
DISABLEMENT FIRE IN ZONE DISABLEMENTS EXTINGUISHANT STATUS
TEST MODE ON SYSTEM FAULT ZONE FAULT/TEST/ 2ND STAGE CONTACT HOLD
ACTIVATED
A DUSABLEMENT
M/R
+ - + -
TELECOM ROOM SECURITY KIOSK
3700
3500
3500
S EXTINGUISHING CONTROL
AREA:QEZ-1 STREET: N/A PLOT: WH-04
2 5 2 2 5 2 2 5
+13.20 +13.20
+12.60 TOP 2 +12.60 TOP 2
600
TOP 1 TOP 1
400
+12.20 6 +12.20
6 6
TOP 3 TOP 3
200
13850
100 4200
4000
4000
4000
4000
4000
4000
4000
4000
+6.60 +6.60 +6.60
F.F.L F.F.L F.F.L
450.00
ENTRANCE
LOBBY LOBBY
4700
4700
4500
4500
LOBBY
4850
4850
MAIN
OFFICE
5205
5205
+2.10 (Officer's Signature)
+1.78 +1.80
+1.45
+1.70 +1.70 +1.35 +1.35
S.S.L S.S.L +1.00
S.S.L S.S.L
S.S.L
485
APPLICATION NO: NN/2018/0090
PLOT BOUNDARY
6300
SET BACK
PLOT BOUNDARY
UPDA REG. NO: 25 COMPANY REG. GRADE: INT'L
1200 2450
5 2 2 5 2 3
+13.20 ( +13.20 )
( +12.60 )
600
+12.60 TOP 2 TOP 2
VALIDITY: 29-10-2020 QID NO.11762100
400
7
TOP 1 TOP 1
SET BACK
(+11.00 )
F.F.L(ROOF) ( +15.65 )
+12.20
200
6 6 S.S.L(ROOF)
TOP 3
4200
4000
4000
4000
4000
4000
4000
14905
( +6.60 )
+6.60 S.F.L ( +6.50 )
300
F.F.L S.S.L
100
4
5205
5205
5755
5555
5555
+1.50
+6.30 +6.05 DESIGN & BUILD OF LIGHT INDUSTRIAL
2800
PLOT BOUNDARY
1
1 1
SET BACK
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-09
DATE:02-07-2020 SHEET: 09 OF 13 SCALE: 1:100
PART -1
1* 2* 3* 4* 5* 6* 7*
15775 15780 15780 365 15780
15780 126595
( ) +15.65 +15.65
TOP 4 TOP 4 TOP 4
PLOT BOUNDARY
PLOT SETBACK
3590
4255
4255
4270
4270
4270
( )
300
300
300
300
300
LIGHT INDUSTRIAL UNIT NO.01 LIGHT INDUSTRIAL UNIT NO.02 LIGHT INDUSTRIAL UNIT NO.03 LIGHT INDUSTRIAL UNIT NO.04 LIGHT INDUSTRIAL UNIT NO.05
13915
10325
9325
9325
9690
10040
10040
(Officer's Signature)
2800
2200
400
( ) +1.80 +1.80
2200
2200
D1 D1
+1.45 +1.45
2200
F.F.L. F.F.L. D1 D1
+1.10 (Reviewing Engineer's Signature / Date)
F.F.L F.F.L. F.F.L. D1
F.F.L.
210
PLOT BOUNDARY
PLOT SETBACK
+15.65 +15.65
TOP 4 TOP 4 TOP 4
QID NO.11762100
PLOT BOUNDARY
VALIDITY: 29-10-2020
PLOT SETBACK
3590
SLOPE SLOPE SLOPE
4270
4270
4270
( )
TOP 3
300
300
300
LIGHT INDUSTRIAL UNIT NO.06 LIGHT INDUSTRIAL UNIT NO.07 LIGHT INDUSTRIAL UNIT NO.08
14965
11375
10040
10040
10390
2800
+1.10
2200
400
D1
D1 +0.75 ( )
F.F.L.
F.F.L. F.F.L
510
PLOT BOUNDARY
FIRE FIGHTING
SECTION B-B
(Officer's Signature)
ITV
CONSULTANT SIGNATURE:
UPDA REG.NO: 2616 QID NO: 27160808616
FROM 27/04/2011 TO 26/04/2021
CONSULTANT:
FIRE FIGHTING
1 SCHEMATIC RISER DIAGRAM
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-11
DATE:02-07-2020 SHEET: 11 OF 13 SCALE: NTS
07 DETAIL
SCALE:
OF PIPE SUPPORT THR'U WALL
NTS
0.09 M
SCALE: NTS
02 MECHANICAL
SCALE:
TEE
NTS
04 4-WAY
SCALE:
BREECHING INLET
NTS 05 WATER FLOW SWITCH MOUNTING DETAIL
SCALE: NTS
08 PIPE
SCALE:
HANGER THR'U SLAB
NTS
12 SCALE: NTS
WALL
4" 6"
CHANNEL
6" 8"
MIN.25mm
PENDENT SPRINKLER
16.8 / 22.4 K.FACTOR
15 PIPE
SCALE:
SLLEEVES
NTS
PIPE CLIP
ALARM CHECK VALVE DETAIL
17 SCALE: NTS
Ø40 Ø40 ELBOW
ANCHOR BOLT
ANCHOR BOLT
SPRINKLER
ANCHOR BOLT
SPRINKLER
RISER
FLEXIBLE CONDUITS
FLEXIBLE CONDUITS
PIN NO: 90042229
BV
PRV BV AREA:QEZ-1 STREET: N/A PLOT: WH-04
.50
TO SPRINKLER SYSTEM
.50
TO SPRINKLER SYSTEM
FS
PG
DRAIN RISER
FS
25mmØ
PG
DRAIN RISER
25mmØ
TO FHR
.50
21 SCALE: NTS
SCALE: NTS
BV
BV
TO DRAIN PIPE RISER
TO DRAIN PIPE RISER FIRE FIGHTING
INSPECTOR'S TEST & DRAIN INSTALLATION DETAILS SHEET-1
24 VALVE CONNECTION ZONE CONTROL VALVE ASSEMBLY (NFPA-13 REF.NO:8.16.1.5)
SCALE: NTS 25 ZONE CONTROL VALVE WITH PRV
SCALE: NTS 26 SCALE: NTS
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-12
DATE:02-07-2020 SHEET: 12 OF 13 SCALE: NTS
Extinguishant Released
Remote Auto/Manual
Releasing Solenoid
Extinguishant Low
Pressure Switch
Pressure Switch
Remote Manual
1st Stage 2nd Stage
Release Switch
Select Switch
Notification Notification
CAUTION !
Disablement Switch
Releasing
Detectors
DO NOT ENTER
470R
470R
470R
470R
470R
DIODE
Stop Air Conditioning
Shutdown Power
This area is protected مﺎظ ﺒ ط ﻤﺤﻤ طﻘطﻨﻤ ا ﻩذﻫ
with FM 200 CLEAN AGENT
GAS DISCHARGED
٢٠٠ ﻫﺒ ﺌﺒ ﻏذز افذام
fire extinguishing system
6K8
6K8
قﻤرذﻟ ﺒ ﻘﻔﻨﻻ
S
6K8
6K8
6K8
6K8
6K8
To Status O
Units S S L
S S
When alarm sounds ﺒﻔم ﺨذءط ﺒ ﻟﺎنﺒ ورﻨ
or on gas discharge
evacuate hazard area اطرﻔﻻ طذﺼ عمﻤ ﺒق ﺎﺒﻔ S S
immediately زم ﻟ ﻻ ﻴرﻔﻨ ﺒ ذﻏ
After discharge do
NOT re-enter until
اﻟﻻ ﻴرﻔﻨ ﺒ ذﻏ ق ﻴﻻنﺘ ﺒ ﺒ
قﺒ ﻤﻨ ذﺜ ﺨذءط ﺒ
EVACUATE NOW E +R0V
AUX
24V
SIL AL FLT RST
REMOTE DATA POWER NAC 1 NAC 2 ZONE 1ZONE 2 ZONE 3 2ND 1ST
NC C NO NC C NO
2ND MODE MAN. ABORT REL EXTING. LOW EXTRACT TROUBLE
NO C NC C NO NC C NO NC C NO
LOCAL FIRE
CONTROL STATUS UNITS SOUNDER STAGE STAGE SELECT RELEASE PRESS. PRES. RELAY FIRE RELAY
thoroughly ventilated
ذطذطﻴ ﻤﻴﻨم ﻴ ﻻﻟا
GAS DISCHARGE SWITCH SWITCH
SOUNDER FAULT/
Security and Safety Solutions DISABLEMENT FIRE IN ZONE DISABLEMENTS EXTINGUISHANT STATUS
GENERAL SYSTEM STATUS
TEST MODE ON SYSTEM FAULT ZONE FAULT/TEST/ 2ND STAGE CONTACT HOLD
ACTIVATED
DUSABLEMENT
GENERAL ALARM/FAULT
DISABLEMENT WARNING SILENCED EXTRACT FAN FLOODING
ZONE FAULT
SILENCE SOUND ALARM/FAULT LAMPTEST MODE SELEST ENTER SYSTEM MODE ENABLE CONTROL
ALARM WARNING SILENCE RESET (+100) (+10) (+1)
(Officer's Signature)
+ - + -
SA
S
S S
CONSULTANT SIGNATURE:
S S UPDA REG.NO: 2616 QID NO: 27160808616
CL CL
FROM 27/04/2011 TO 26/04/2021
CONSULTANT:
CL CL
MONITOR MODULE
CONNECT TO MAIN FIRE ALARM SYSTEM
FECP
CAUTION ! ARABIC !
PULL LOCATION: Ras Bufontas Special Economic Zone PIN NO: 90042229
AREA:QEZ-1 STREET: N/A PLOT: WH-04
FIRE FIGHTING
INSTALLATION DETAILS SHEET-2
SHEET PROPERTIES
REVISION: 1 SHEET SIZE: A0 SETTING: DWF
FF-13
DATE:02-07-2020 SHEET: 13 OF 13 SCALE: NTS
GENERAL DESCRIPTION:
DESIGN PHILOSOPHY:
·
(Officer's Signature)
·
CONSULTANT SIGNATURE:
UPDA REG.NO: 2616 QID NO: 27160808616
FROM 27/04/2011 TO 26/04/2021
CONSULTANT:
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-01
DATE:09-08-2020 SHEET: 01 OF 13 SCALE: NTS
PA-WH-07
PLOT AREA= 13033.17 SQ.M.
1 LOCATION PLAN
LS-02 SCALE NTS
1 2 3 4 5 6 7 8 9 10
APPLICATION NO:NN/2018/0000089
ENT. EXIT (Reviewing Engineer's Signature / Date)
+5.60
E:238367.365 E:238395.5543 R.L. E:238401.1301 E:238494.4944 E:238499.7265 E:238516.238
11 16 17 18 +5.50 19 12
N:386190.670 N:386195.0869 N:386195.9605 N:386210.5881 N:386211.4079 N:386213.995
R.L.
TANK LOCATION
+5.80 +5.85
+17.55
TOP
+17.55 +5.70 +5.70
GF
TOP R.L. R.L. +16.95
TOP
ASSEMBLY ASSEMBLY
4000
POINT C
4 m ACCESS ROAD POINT D
5300 5300
G.F.L. 1990 3350 2650 2650 +5.85
+5.85 PAV.
G.F.L.
PAV.
+17.55 +17.55 E:238529.478 1
TOP TOP N:386205.182
5615
6351
6351
+16.95 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 +16.95
+16.95 TOP
TOP TOP G.F.L.
G.F.L.
R.A.H R.A.H
13001
+5.85 +5.85 +5.85
11950
11950
+17.55 PAV. +16.95 +5.85 +16.95 PAV. +17.55 PAV.
10850
10800
TOP TOP PAV. TOP TOP
G GF
+15.35 +15.15 +16.95 RD.
E:238352.231 +16.95 +16.95 +16.95 +16.95
10 F.F.L. S.S.L TOP
N:386170.785 TOP G.F.L. TOP G.F.L. TOP G.F.L. G.F.L. TOP
+15.35 +15.15
5000
+15.35 +15.15
F.F.L. S.S.L
ALUMINIUM COVER CAP +15.35 +15.15 F.F.L. S.S.L
R.A.H ALUMINIUM COVER CAP
FIXED AT ONE SIDE AT +15.55 F.F.L. S.S.L R.A.H
RD. RD. FIXED AT ONE SIDE AT +15.55 RD.
RD.
CONSULTANT SIGNATURE:
R.A.H R.A.H R.A.H R.A.H RD.
F
SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE
UPDA REG.NO: 2616 QID NO: 27160808616
FROM 27/04/2011 TO 26/04/2021
R O A D
R O A D
GF
CONSULTANT:
22105
ROOF
PANEL
+16.55 +20.45 +20.45 +20.45 +20.45 +20.45 +20.45 +20.45 70 +20.45
LOWER TOP TOP TOP TOP TOP TOP TOP MM TOP
+16.55 +16.55 +16.55 +16.55 +16.55 +16.55 +16.55
THICKNESS
LOWER LOWER LOWER LOWER LOWER LOWER LOWER
GF
SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE SLOPE
ASSOCIATED CONSULTING ENGINEERS
C
+6.15 +6.15 +6.15 +6.15 +6.15 +6.15
GF
F.F.L F.F.L F.F.L F.F.L F.F.L F.F.L
E.M E.M E.M E.M E.M E.M
E.M +5.75 P.O. Box 39304
R.L. +6.15
+6.15
F.F.L
F.F.L
E.M
5/F Office No. 503 Behzad Business Center
Building No. 57, Zone 23, Street 342
14700
+5.75
R.L.
Ø200 SPRINKLER RISER F/B Ø200 SPRINKLER RISER F/B Al Jazeera Street, Fareej Bin Mahmoud, Doha, Qatar
(1:12-L=5.00)
(1:12-L=5.00)
(1:12-L=5.00)
(1:12-L=5.00)
(1:12-L=5.00)
(1:12-L=5.00)
Z2-ACV-02 Z1-ACV-01
SLOPE
Tel: +974-4435-0858 Fax: +974-4421-0720
(1:1
0)
GF
5.0
SLOPE
2-L
=
SLOPE SLOPE 200Ø TO SYSTEM SLOPE
2-L
=5
(1:1
+5.85 R.L. SLOPE R.L. R.L. R.L.
)
E 1% 5
OP
N:386155.2155
SLOPE
SL
R.L. 113996 R.L.
6000
EL:-900M
+9.85 FIRE TRUCK HARD STAND FIRE TRUCK HARD STAND 114 x 6 m FIRE TRUCK HARD STAND 114 x 6 m FIRE TRUCK HARD STAND +5.85
QID NO.11762100
150Ø
VALIDITY: 29-10-2020
TOP PAV.
INDOOR SUBSTATION E:238543.820
ASSEMBLY 2
POINT B N:386155.372
SLO
PE
SECURITY KIOSK
1%
SL
Telecom Room
4 m ACCESS ROAD KAHRAMAA SUBSTATION
O
PE
&
1%
800
RD & CCTV.
+9.20
TOP +5.60 FIRE HYDRANT
FIRE HYDRANT
3500
ENT.
200Ø
DONE BY KAHRAMAA
DEMAND
FLOW RATE 1587 GPM
PRESSURE 117.3 PSI
AVAILABLE
R O A D FLOW RATE 2500 GPM
PRESSURE 124.80 PSI
TAPPING POINT 200 MM
TIE-IN FROM PUBLIC NETWORK
FIRE FIGHTING SYSTEM
COORDINATES
DESIGN & BUILD OF LIGHT INDUSTRIAL
E 238455.0018
N 386128.9959
AND LOGISTICS UNITS AT RAS BUFONTAS
SPECIAL ECONOMIC ZONE (PORTION 1)
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-02
DATE:09-08-2020 SHEET: 02 OF 13 SCALE: 1:250@A0
SEC-A
1 2 3 4 4C 5 6 7 7C 8 9 10
300
20850 21250 21350 9850 11320 21150 9900 11400 21300 29800
1B 1C 2D 2E 8B 8C 9C 9D
1A 2A 2B 2C 2F 3A 3B 3C 3D 3E 4A 4B 4D 4E 4F 6A 6B 6C 6D 6E 7A 7B 7D 7E 7F 8A 8D 8E 8F 9A 9B 9E 9F
2885 1380 5225 3600 3575 3650 1200 8970 3625 4540 2660 3600 7200 3600 3575 3625 3625 6570 3625 3625 3575 3600 7200 3600 3575 3625 3625 6495 2475 1200 3650 3575 3600 4775 5310 4735 515 6945 3735
D
8'
1''
E
36
FIRE
00
+5.85
PAV.
BLANKET
65
7'
38
F
15
36
75
00
2''
GF RA. TANK
RA.
LOCATION
FROM MEZZANINE FLOOR
FE-03
Ø40 FHC RISER
0
36 3''
5
6'
43
00
UP
Ø40 FHC RISER Single Tenant FROM MEZZANINE FLOOR
+
T2 PA 5.85
+5.85 +5.85 Office Space
FE-1 23 (Officer's Signature)
4'
75 FROM MEZZANINE FLOOR Ø40 FHC RISER V. 50
5'
PAV. PAV.
'
32 FIRE
Single Tenant FHC FE-2
Office Space FIRE FIRE H
ENT.
106.41
UP
MEZZANINE
106.41
ENT.
BLANKET BLANKET BLANKET
4'
3'
RA.
35
28 +6.05
FE E-1
5175
S.S.L
-2
5
F
76
2'
FE-03
ENT. ENT.
0
91
Office Space
+6.05
APPLICATION NO:NN/2018/0000089
FE-1
FE-2
G'
FE
2025
FROM MEZZANINE FLOOR S.S.L BLANKET OUTLINE PAV. BLANKET FROM MEZZANINE PAV. BLANKET
OUTLINE S.S.L
RA. RA. 250.00
FE-03
FE-03
FE-03
FE-03
ENT. ENT. ENT. ENT.
+6.15 F.F.L FHC Ø40 FHC RISER
FROM MEZZANINE FLOOR FE-2 +6.15 F.F.L +6.15 F.F.L
5000
Single Tenant
+5.95 S.S.L Single Tenant Single Tenant Single Tenant +5.95 S.S.L FROM MEZZANINE FLOOR +5.95 S.S.L
Ø40 FHC RISER FE-1 +6.05 Office Space +6.05 Office Space Office Space FE-2
FE-2
FE-1
+6.05 +6.05
FE-2
FE-1
FHC FE-2 Office Space
FE-1
FE-2
FE-2
FE-1
S.S.L S.S.L S.S.L FIRE S.S.L FE-1
FE-1 BLANKET
Ø40 FHC RISER
F
FROM MEZZANINE FLOOR FHC FHC
E.M
Ø40 FHC RISER Ø40 FHC RISER Ø40 FHC RISER
FROM MEZZANINE FLOOR
FHC FE-2 FROM MEZZANINE FLOOR FROM MEZZANINE FLOOR FE-2 FE-2 FROM MEZZANINE FLOOR Ø40 FHC RISER
7405
FE-1 FE-1 FE-1 Ø40 FHC RISER FE-2 FROM MEZZANINE FLOOR
FE-1
E.M
FE-1
FE-2 E
FE-1 FE-1 FE-1 FE-1 FE-1 FE-1 FE-1
PAV.
+5.85
GF
FE-2 FE-2 FE-2 FE-2 FE-2 FE-2 FE-2
LIGHT INDUSTRIAL UNIT NO.01 LIGHT INDUSTRIAL UNIT NO.02 LIGHT INDUSTRIAL UNIT NO.03 LIGHT INDUSTRIAL UNIT NO.04 LIGHT INDUSTRIAL UNIT NO.05 LIGHT INDUSTRIAL UNIT NO.06 LIGHT INDUSTRIAL UNIT NO.07 LIGHT INDUSTRIAL UNIT NO.08
7350
+6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L
+5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L
Ø40 FHC RISER Ø40 FHC RISER Ø40 FHC RISER Ø40 FHC RISER Ø40 FHC RISER Ø40 FHC RISER
FROM MEZZANINE FLOOR FROM MEZZANINE FLOOR FROM MEZZANINE FLOOR FROM MEZZANINE FLOOR FROM MEZZANINE FLOOR FROM MEZZANINE FLOOR CONSULTANT SIGNATURE:
7350
GF Ø40 FHC RISER
FROM MEZZANINE FLOOR
UPDA REG.NO: 2616 QID NO: 27160808616
FE-1
FE-2
FE-2
FE-1
FE-1
FE-2
FE-2
FE-1
FE-1
FE-2
FE-2
FE-1
C
GF
+6.15 F.F.L
+5.95 S.S.L
FHC
+6.15 +6.15
FHC FHC
+6.15
+6.15
FHC
W.G.T
FHC
+6.15 +6.15
FHC
W.G.T
+6.15 F.F.L
+5.95 S.S.L Ø40 FHC RISER FROM 27/04/2011 TO 26/04/2021
SEC-B FHC F.F.L F.F.L F.F.L
F.F.L F.F.L F.F.L W.G.T
FHC FE-2 FROM MEZZANINE FLOOR SEC-B
+6.15 F.F.L +6.15 F.F.L FE-1
CONSULTANT:
7350
+5.95 S.S.L +6.15 F.F.L
+6.15 F.F.L +5.95 S.S.L +5.95 S.S.L +6.15 F.F.L
+5.95 S.S.L (1:12-L=5.00) +5.95 S.S.L
(1:12-L=5.00) (1:12-L=5.00) (1:12-L=5.00) (1:12-L=5.00) (1:12-L=5.00)
+6.15 W.G.T +6.15
F.F.L F.F.L
B
(1:12-L=5.00) +5.750 +5.750 +5.750
ROAD F.L RA. RA. ROAD F.L RA. RA. +5.750 RA. RA. ROAD F.L
PAV.
+5.85
ROAD F.L
7350
(1:12-L=5.00) RA
RA. .
GF +5.85
PAV. ASSOCIATED CONSULTING ENGINEERS
FE-1 FE-1 FE-1 FE-1
FE-2 E.M
FE-2 FE-2 E.M
FE-2 E.M
A
GS GS GS
D4
5200 16400 5600 5600
5600 Building No. 57, Zone 23, Street 342
D5
Al Jazeera Street, Fareej Bin Mahmoud, Doha, Qatar
MV-415V ROOM
W W TELECOM
ROOM
W D3 SECURITY
KIOSK SECURITY KIOSK
+5.90
EQUIPMENT ROOM
+5.90
CC.TV CONTROL ROOM
+5.90
UPDA REG. NO: 25 COMPANY REG. GRADE: INT'L
F.F.L F.F.L F.F.L
1 2 3 4 SEC-A 7 8 9 10
5 6
1 FIRE FIGHTING SYSTEM GROUND FLOOR PLAN AREA:QEZ-1 STREET: N/A PLOT: 07
- SCALE 1:200
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-03
DATE:09-08-2020 SHEET: 03 OF 13 SCALE: 1:200
SEC-A
1 2 3 4 4C 5 6 7 7C 8 9 10
20850 21250 21350 9850 11320 300 21150 9900 11400 21300 29800
1B 1C 2D 2E 8B 8C 9C 9D
1A 2A 2B 2C 2F 3A 3B 3C 3D 3E 4A 4B 4D 4E 4F 6A 6B 6C 6D 6E 7A 7B 7D 7E 7F 8A 8D 8E 8F 9A 9B 9E 9F
2885 1380 5225 3600 3575 3650 1200 8970 3625 4540 2660 3600 7200 3600 3575 3625 3625 6570 3625 3625 3575 3600 7200 3600 3575 3625 3625 6495 2475 3650 3575 3600 4775 5310 4735 515 6945 3735
(Officer's Signature)
1200
D
8'
36
1''
00
65
APPLICATION NO:NN/2018/0000089
7'
38
F
15
36 2''
75
00
S.S.L 00
3''
DN
FE-1
FE-2
23
4'
75 1340Single2500
Tenant 50
5'
'
H 32 Ø40 FHC RISER
Office Space
FIRE Ø40
TO GROUND FLOOR
PS-F5
+10.85
4'
BLANKET
3'
VRP
DN
TO DRAIN
2'
Single Tenant
PS-F5
PS-F5
Ø40 Ø40
FE-03
Ø150
0 Office Space
91 Ø40 FHC RISER T/B +10.85 Single Tenant ZCV-8
+10.85 Single Tenant
Ø40 FHC RISER S.S.L Office Space 1340 3400 3400 1240
Office Space
S.S.L
G' 10 Ø40 FHC RISER FIRE
TO GROUND FLOOR
PS-F5
PS-F5
1'
Ø65 Ø40 Ø40
51 R.A.
2025
FE-2
FE-1
Ø150
TO GROUND FLOOR
3050
Ø200 Ø200 EL: 9.60 Meter 1410 STEEL BEAM
G 1495
1325 Ø200 EL: 9.60 Meter Ø200
1350
3100 3100 3100 3100 3100 1420
1345
Ø40 FHC RISER
1400
995 3100 3100 3100 3100 1450 815 3200 3200 3200 3200
ZCV-1 ∅40 ∅40 DN DN
1346995
FE-03
Single Tenant TO GROUND FLOOR Single Tenant Ø40 FHC RISER Ø65 Ø65 Ø65
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
3100 3100 995 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
+10.85 Ø40 FHC RISER Office
T/B Space Single Tenant Single Tenant Office Space
Ø150
TO GROUND FLOOR 495 3100 3100
5000
Ø150
TO GROUND FLOOR +10.85
Ø200
PRV
VRP
S.S.L Ø40 FHC RISER T/B +10.85 +10.85 Ø40 FHC RISER F/A
Ø200
2550
2355
Ø40 FHC RISER
TO DRAIN
TO DRAIN
Ø40 FHC RISER T/B
2350
PS-F5
PS-F5
FE-2
FE-1
∅40 ∅40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
FE-2
FE-1
∅65
FE-2
FE-1
FE-1
FE-2
FE-1
FE-1
Ø40 FHC RISER T/B
FE-2
FE-2
1100
1100
1100
1100
Ø40 FHC RISER T/B
∅150
3000
Ø150
Ø65 Ø65 Ø65 Ø65 Ø65
PS-F5
Ø65 Ø65 Ø65 Ø40 Ø40 DN DN DN DN
PS-F5
PS-F5
PS-F5
PS-F5
Ø200
1245 1245
3535
STEEL BEAM STEEL BEAM STEEL BEAM
3550
1065 1220 1220
3850
1215 1065
1445
1445
1450
695 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 1410
3100 3100 3100 1195 695 3100 3100 3100 3100 3100 3100 1220 695 3100 3100 3100 3100 3100 3100 1220 1230
1030
Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø40 Ø40 720 3100 3100 3100 3100 3100 3100 3300 3300 3300 3300 1320
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
795 3100 3100 3100 3100 3100 3100 1405 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 3100 3100 3100 1230
Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø40 Ø65 Ø65 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø40 Ø65 Ø65 Ø65 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
VRP
VRP
VRP
VRP
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
TO DRAIN
TO DRAIN
TO DRAIN
TO DRAIN
Ø150
Ø150
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 ZCV-3 Ø40 FHC RISER
Ø150
Ø150
3105
3105
3100
TO GROUND FLOOR
Ø150
3105
3100
Ø40 FHC RISER 1065 1220 1220
3045
TO GROUND FLOOR
3050
1215 695 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 1065 1410
3100
695 3100 3100 3100 3100 3100 3100 1195 TO GROUND FLOOR 695 1220 695 1220 1230
1300
9133260
3104970
3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 495
Ø65 Ø65 Ø65 Ø65 720 3100 3100 3100 3300 3300 3300 3300 3300 3300 3300 1220
Ø65 Ø40 Ø40 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
795 3100 3100 3100 3100 3100 3100 1405 Ø65 Ø65 Ø65 Ø65 3100 3100 3100 1230
Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65
Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø150
CONSULTANT SIGNATURE:
Ø150
3700
3700
3700
3350
3070
3050
1215 STEEL BEAM 1410
2700
STEEL BEAM 1300 STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM
E 695 3100 3100 3100 3100 3100 3100
1195
795 3100 3100
3105015
3100 3100 3100 3100 1405 695 3100 3100 3100 3100 3100 3100 1065 695 3100 3100 3100 3100 3100 3100 1220 695 3100 3100 3100 3100 3100 3100 1065 695 3100 3100 3100 3100 3100 3100 1220
1230
495 3300 3400 3400 3400 3400 3400 3100 1220
1100
1100
720
1100
1100
1100
1100
1100
1100
1100
1100
3100 3100 3100 3100 3100 3100 1230
Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
Ø150
Ø150
OPEN BELOW OPEN BELOW OPEN BELOW OPEN BELOW OPEN BELOW OPEN BELOW OPEN BELOW OPEN BELOW
UPDA REG.NO: 2616 QID NO: 27160808616
18448245
Ø150
2525
2510
2510
2525
Ø150
2550
2500
2550
2550
1300 1245 1245 1230
1215 1065 1220 1065 1220 1410
495
695 3100 3100 3100 3100 3100 3100 795 3100 3100 3100 3100 3100 3100 1405 695 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 720 3100 3100 3100 3300 3400 3400 3400 3400 3400 3400 1220
LIGHT INDUSTRIAL UNIT NO.01 1195 LIGHT INDUSTRIAL UNIT NO.02 LIGHT INDUSTRIAL UNIT NO.03 LIGHT INDUSTRIAL UNIT NO.04 1220 LIGHT INDUSTRIAL UNIT NO.05 LIGHT INDUSTRIAL UNIT NO.06 1220 LIGHT 3100
INDUSTRIAL 3100
UNIT NO.07 3100 1230 LIGHT INDUSTRIAL UNIT NO.08
7350
Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
+6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L +6.15 F.F.L
FROM 27/04/2011 TO 26/04/2021
Ø150
2525
2525
2550
2550
2550
2550
+5.95 S.S.L 1300 +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L +5.95 S.S.L
3105
3105
1230
Ø150
695 3100 3100 3100 3100 3100 3100 1195 795 3100 3100 3100 3100 3100 3100 1405 695
1245 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 1220 695
1245 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 1220 495
1410 3400 3400 3400 3400 3400 3500 3700 1220
720 3100 3100 3100 3100 3100 3100 1230
1215 1065 1220 1065 1220
Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
1100
D
Ø150
Ø150
STEEL BEAM
CONSULTANT:
3400
STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM
3800
3800
3800
3800
3800
3800
3800
Ø150
1245 1245 495
1285 1300 1065 1220 1065 1220 1230 1410 3100 3100 3100 3100 3100 3100 3100 3100 1090
Ø150
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
Ø65 Ø65 Ø40 Ø65 Ø65 Ø40 Ø65 Ø65 Ø40 Ø65 Ø65 Ø40 Ø65 Ø65 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø40 Ø65 Ø65 Ø65 Ø40 Ø65 Ø65 Ø65 Ø40 Ø65 Ø65 Ø65 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
7350
Ø150
Ø150
Ø150
3700
3100
3275
3295
3295
3300
3300
3300
Ø150
Ø150
1245 1245 1410
1215 1300 1220 1220 1230
1065 1220 1065 1220 720 495
695 3100 3100 3100 3100 3100 3100 1130 795 3100 3100 3100 3100 3100 3100 1405 695 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 695 3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 3100 3200 3300 1090
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø40 Ø40 Ø40 Ø40 Ø40 Ø40 Ø40 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
1350
∅150
1350
ITC ITC
Ø150
Ø150
1600
Ø150 Ø150
STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM
2785
2785
STEEL BEAM
2800
713230
C
3100
3100
3050
1310
3200 3200 3200 820 3200 3200 3200 820
1350
Ø32
945 945
1600
1650
1065 3100 3100 3100 885 1065 3100 3100 3100 885 645
1650
Ø32
795 3200 3200 3200 3200 1265 FLUSHING VALVE
Ø40 FHC RISER Ø40 FHC RISER Ø40 FHC RISER FLUSHING VALVE Ø40 FHC RISER 3400 3400 3400 3400 3400 3400
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
∅65 ∅65 ∅65 ∅40 ∅40 TO GROUND FLOOR TO GROUND FLOOR TO GROUND FLOOR Ø65 Ø40 Ø40 TO GROUND FLOOR TO GROUND FLOOR Ø65 Ø40 Ø40
TO GROUND FLOOR
Ø40 FHC RISER Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
SEC-B
Ø200
TO GROUND FLOOR
Ø150
Ø150
SEC-B
3105
3105
3100
Ø200
Ø40 FHC RISER
3105
3050
3100
7350
Ø150
1310 TO GROUND FLOOR
945 3200 3200 3200 820 1065 3100 3100 3100 885 945 3200 3200 3200 820 1065 3100 3100 3100 885 645
795 3200 3200 3200 3200 1265 3400 3400 3400 3400 3400 3600
∅65 ∅65 ∅40 ∅40 ∅65 ∅65 ∅40 ∅40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
∅65 ∅65 ∅65 ∅40 ∅40 Ø65 Ø40 Ø40 Ø65 Ø40 Ø40 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
P.O. Box 39304
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø150
5/F Office No. 503 Behzad Business Center
4015
4015
4000
3715
3800
3700
1310 STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM STEEL BEAM
B 945 3200 3200 3200 820 1065 3100 3100 3100 885 945 3200 3200 3200 820 1065 3100 3100 3100 885 645
795 3200 3200 3200 3200 1265 3400 3400 3400 3400 3600 3600
Building No. 57, Zone 23, Street 342
1100
1100
1100
1100
1100
∅65 ∅65 ∅65 ∅40 ∅40 ∅65 ∅65 ∅40 ∅40 Ø65 Ø40 Ø40 ∅65 ∅65 ∅40 ∅40 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø150
Ø150
Al Jazeera Street, Fareej Bin Mahmoud, Doha, Qatar
Ø150
Ø150
2510
2510
2510
2500
2500
2500
1310
3200 3200 3200 3200 1265 945 3200 3200 3200 820 1065 3100 3100 3100 885 945 3200 3200 3200 820 1065 3100 3100 3100 885 645 3400 3600 3600 3600 3600 3600
795
7350
∅65 ∅40 ∅65 ∅65 ∅40 ∅40 Ø65 Ø40 Ø40 ∅65 ∅65 ∅40 ∅40 Ø65 Ø40 Ø40
PS-F5
∅65 ∅65
PS-F5
∅40
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
∅150
Ø150
3000
3000
3000
3000
3000
3000
1315 820 1065 3100 3100 3100 885 820 1065 3100 3100 3100 885 645
3200 3200 3200 3200 1265 945 3200 3200 3200 945 3200 3200 3200 3200 3200 3200 3200 3200 3200 3300
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
PS-F5
ITC ITC 200∅ TO SYSTEM Ø65 Ø65 Ø65 Ø65 Ø65 Ø65 Ø40 Ø40
850
940
940
900
900
Ø32
A Ø32
FLUSHING VALVE
FLUSHING VALVE
E 1%
OP
SLOPE
A2 SLOP
E 1%
RD
+9.20
T.O.P. +9.20
TOP
A3
1 2 3 4 7 8 9 10
DESIGN & BUILD OF LIGHT INDUSTRIAL
SEC-A
AND LOGISTICS UNITS AT RAS BUFONTAS
5 6
SPECIAL ECONOMIC ZONE (PORTION 1)
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-04
DATE:09-08-2020 SHEET: 04 OF 13 SCALE: 1:200
1 2 3 4
11400
100
100
A A
4300
(Officer's Signature)
3500
Transformer
APPLICATION NO:NN/2018/0000089
(Reviewing Engineer's Signature / Date)
FE-1
FE-2
MV (415V) ROOM
B B
+6.00
3000
3000
F.F.L
CONSULTANT SIGNATURE:
UPDA REG.NO: 2616 QID NO: 27160808616
VCB (11KV) ROOM FROM 27/04/2011 TO 26/04/2021
CONSULTANT:
13700
C C
11250
FE-1 ASSOCIATED CONSULTING ENGINEERS
3748
Al Jazeera Street, Fareej Bin Mahmoud, Doha, Qatar
+1.20
6000
D D
100
100
FE-2
FE-1
DESIGN & BUILD OF LIGHT INDUSTRIAL
AND LOGISTICS UNITS AT RAS BUFONTAS
SPECIAL ECONOMIC ZONE (PORTION 1)
100
100 4200
3200 3800
LOCATION: RAS BUFONTAS SEZ PORTION 1 PIN NO:49030018
AREA:QEZ-1 STREET: N/A PLOT: 07
11400
1 2 3 4 SUBSTATION
FIRE FIGHTING LAYOUT
FP-1200
FP-3000
3500
(Officer's Signature)
R
APPLICATION NO:NN/2018/0000089
FP-3000 (Reviewing Engineer's Signature / Date)
MV (415V) ROOM
MV (415V) ROOM
MV (415V) ROOM
MV (415V) ROOM
B
FP-3000
3000
CONSULTANT SIGNATURE:
UPDA REG.NO: 2616 QID NO: 27160808616
FP-1200
R
13700
GAS DISCHARGE
SA SA SA SA SA EVACUATE NOW
C CONSULTANT:
GAS DISCHARGE
DO NOT ENTER
W
FACP FACP FACP
MOUNTING BRACKET
AEROSOL UNIT
DISCHARGE HOLES
500
WALL MOUNTED FP-3000 UNIT
FFL
FECP MOUNTING DETAIL LOCATION: RAS BUFONTAS SEZ PORTION 1 PIN NO:49030018
240V 5AMF POWER SUPPLY
AREA:QEZ-1 STREET: N/A PLOT: 07
DOOR
MV (415V) ROOM
AEROSOL SYSTEM LAYOUT
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
3 TYPICAL DEVICES MOUNTING HEIGHTS & DETAILS FF-06
DATE:09-08-2020 SHEET: 06 OF 13 SCALE: AS SHOWN
(Officer's Signature)
APPLICATION NO:NN/2018/0000089
FIRE EXTINGUISHER (Reviewing Engineer's Signature / Date)
ENLARGED DETAILS 01 02 03 04
1915 3140 5680
B B
FE-1
FE-1
SECURITY KIOSK CONSULTANT SIGNATURE:
FIRE COMMAND CENTER EQUIPMENT ROOM CC.TV CONTROL ROOM
UPDA REG.NO: 2616 QID NO: 27160808616
FE-1 FROM 27/04/2011 TO 26/04/2021
3200
FE-1
+5.90 +5.90 +5.90 CONSULTANT:
F.F.L F.F.L F.F.L
FE-1
ASSOCIATED CONSULTING ENGINEERS
01 02 03 04
1 GROUND FLOOR PLAN FIRE FIGHTING LAYOUT DESIGN & BUILD OF LIGHT INDUSTRIAL
- SCALE 1:25
AND LOGISTICS UNITS AT RAS BUFONTAS
SPECIAL ECONOMIC ZONE (PORTION 1)
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-07
DATE:09-08-2020 SHEET: 07 OF 13 SCALE: 1:20
01 02 03
LEGEND
5280
100 A
3170 1915
M
S
M/R
S
TELECOM ROOM SECURITY KIOSK
+5.90 +5.90
3195
F.F.L F.F.L
A TELECOM ROOM
ISOMETRIC VIEW
4 FM200 SYSTEM LAYOUT
SCALE NTS
TELECOM ROOM
FM200 SYSTEM LAYOUT APPLICATION NO:NN/2018/0000089
SCALE: 1:25
(Reviewing Engineer's Signature / Date)
3170 1910
Extinguishant Released
Remote Auto/Manual
Releasing Solenoid
Extinguishant Low
Pressure Switch
Pressure Switch
1st Stage 2nd Stage
Remote Manual
Release Switch
Select Switch
Notification Notification
Disablement Switch
Releasing
Detectors
470R
470R
470R
470R
470R
DIODE
Stop Air Conditioning
M
Shutdown Power
5280
6K8
6K8
S
SA
6K8
6K8
6K8
6K8
6K8
To Status O
Units S S L
100 S S
3170 1915 S S
CONSULTANT SIGNATURE:
E +R0V SIL AL FLT RST NC C NO NC C NO NO C NC C NO NC C NO NC C NO
AUX REMOTE DATA POWER NAC 1 NAC 2 ZONE 1ZONE 2 ZONE 3 2ND 1ST 2ND MODE MAN. ABORT REL EXTING. LOW EXTRACT TROUBLE LOCAL FIRE
S
24V CONTROL STATUS UNITS SOUNDER STAGE STAGE SELECT RELEASE PRESS. PRES. RELAY FIRE RELAY
SWITCH SWITCH
FIRE
SOUNDER FAULT/
DISABLEMENT
POWER FAULT
SOUNDER FAULT/
FIRE IN ZONE DISABLEMENTS
EXTINGUISHANT
EXTINGUISHANT STATUS
EXTINGUISHANT
RELEASED
RELEASE
LOW
PRESSURE
UPDA REG.NO: 2616 QID NO: 27160808616
POWER ON MANUAL RELEASE
DISABLEMENT IMMINENT AUTO MANUAL EXTINGUISHANTS
1 2 3 MANUAL ONLY RELEASE
A
FROM 27/04/2011 TO 26/04/2021
DELAY ON GENERAL FAULT STAGE CONTACT FIRST STAGE PULL DOWN - PUSH BOTTON
ACTIVATED
S
ACTIVATED
DUSABLEMENT
GENERAL ALARM/FAULT
DISABLEMENT EXTRACT FAN FLOODING
WARNING SILENCED
ZONE FAULT
SILENCE SOUND ALARM/FAULT LAMPTEST MODE SELEST ENTER SYSTEM MODE ENABLE CONTROL
ALARM WARNING SILENCE RESET (+100) (+10) (+1)
CONSULTANT:
TELECOM ROOM SECURITY KIOSK + - + -
S
R
•
S 24V 7 A/H BATTERY 24V 7 A/H BATTERY
•
•
EXTINGUISHING CONTROL
S
•
+5.90 +5.90 ASSOCIATED CONSULTING ENGINEERS
•
3195
F.F.L F.F.L
M
GAS DISCHARGE
EVACUATE NOW
DO NOT ENTER
S
R
01 02 03 •
3165 1910 •
( +4.90 )
+4.90
TOP LEVEL TOP
•
( +4.40 )
500
+4.40
F.F.L. F.F.L. 11 INSTALLATION DETAIL OF FIRE ALARM PANEL •
SCALE NTS
200
•
( +4.20 )
S.S.L. DESIGN & BUILD OF LIGHT INDUSTRIAL
MONITOR MODULE
CONNECT TO MAIN FIRE ALARM SYSTEM
AND LOGISTICS UNITS AT RAS BUFONTAS
SPECIAL ECONOMIC ZONE (PORTION 1)
4050
3000
FECP
CAUTION ! ARABIC !
DOOR
(Officer's Signature)
APPLICATION NO:NN/2018/0000089
(Reviewing Engineer's Signature / Date)
ENLARGED DETAIL
SCALE: 1:50
H G F E D C B A
49005
7200 5000 7405 7350 7350 7350 7350
2900
SET BACK
(+17.55 )
TOP +17.55 (+17.55 )
TOP TOP
600
(+16.95 ) (+16.95 )
CONSULTANT SIGNATURE:
6000
UPDA REG.NO: 2616 QID NO: 27160808616
1200
(+15.35 ) (+15.35 )
350
200
9800
F.F.L F.F.L
FROM 27/04/2011 TO 26/04/2021
11500
(+15.15 ) (+15.15 )
200
S.S.L S.S.L
CONSULTANT:
FIRE ENGINE
14300
14300
14300
14300
4200
4200
HARDSTAND
4000
4000
3350
5800
300
(+10.95 ) (+10.95 )
+10.85
300
100
100
F.F.L S.S.L F.F.L ASSOCIATED CONSULTING ENGINEERS
(+10.85 ) (+10.85 ) ( +9.95 )
800 400
4700
4500
4500
4500
Al Jazeera Street, Fareej Bin Mahmoud, Doha, Qatar
4050
3300
3000
3000
2800
2800
Tel: +974-4435-0858 Fax: +974-4421-0720
2200
2400
3600
( +5.90 )
( +6.15 ) +6.15 +6.15 ( +6.15 )
+5.90 F.F.L +5.80
+6.05
S.S.L F.F.L F.F.L
SLOPE
+5.75 +5.70 F.F.L
F.F.L
+5.65 HEAD OFFICE SIGNATURE:
R.F.L R.F.L SLOPE R.F.L R.F.L
( ±0.00 )
FIRE FIGHTING
SECTION A-A
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-09
DATE:09-08-2020 SHEET: 09 OF 13 SCALE: 1:75
10
+20.45
TOP
ENLARGED DETAIL
SCALE: 1:50
(Officer's Signature)
3900
APPLICATION NO:NN/2018/0000089
(Reviewing Engineer's Signature / Date)
14300
10400
CONSULTANT SIGNATURE:
UPDA REG.NO: 2616 QID NO: 27160808616
1 FIRE FIGHTING SYSTEM SECTION B-B PART-1 FROM 27/04/2011 TO 26/04/2021
- SCALE 1:100
CONSULTANT:
ENLARGED DETAIL
SCALE: 1:50
VALIDITY: 29-10-2020 QID NO.11762100
6 5 4C 4 3 2 1
SHEET PROPERTIES
2 FIRE FIGHTING SYSTEM SECTION B-B PART-2 REVISION: 2 SHEET SIZE: A0 SETTING: DWF
- SCALE 1:100 FF-10
DATE:09-08-2020 SHEET: 10 OF 13 SCALE: 1:100
LIGHT WAREHOUSE 01 LIGHT WAREHOUSE 02 LIGHT WAREHOUSE 03 LIGHT WAREHOUSE 04 LIGHT WAREHOUSE 05 LIGHT WAREHOUSE 06 LIGHT WAREHOUSE 07 LIGHT WAREHOUSE 08
(Officer's Signature)
APPLICATION NO:NN/2018/0000089
(Reviewing Engineer's Signature / Date)
CONSULTANT SIGNATURE:
UPDA REG.NO: 2616 QID NO: 27160808616
FROM 27/04/2011 TO 26/04/2021
CONSULTANT:
PG PRESSURE GUAGE
DV DRAIN VALVE
WFS WATER FLOW SWITCH
TV TEST VALVE
SG SIGHT GLASS
SV STRAINER VALVE DESIGN & BUILD OF LIGHT INDUSTRIAL
GV GATE VALVE AND LOGISTICS UNITS AT RAS BUFONTAS
DV DRAIN VALVE SPECIAL ECONOMIC ZONE (PORTION 1)
AAV AUTOMATIC AIR VALVE
FHR FIRE HOSE REEL
LOCATION: RAS BUFONTAS SEZ PORTION 1 PIN NO:49030018
FH FIRE HYDRANT
FD FLOOR DRAIN AREA:QEZ-1 STREET: N/A PLOT: 07
VB VALVE BOX
PRV PRESSURE REDUCING VALVE
FIRE FIGHTING SYSTEM
SCHEMATIC DIAGRAM
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-11
DATE:09-08-2020 SHEET: 11 OF 13 SCALE: NTS
07 DETAIL
SCALE:
OF PIPE SUPPORT THR'U WALL
NTS
0.09 M
SCALE: NTS
02 MECHANICAL
SCALE:
TEE
NTS
04 4-WAY
SCALE:
BREECHING INLET
NTS 05 WATER FLOW SWITCH MOUNTING DETAIL
SCALE: NTS
08 PIPE
SCALE:
HANGER THR'U SLAB
NTS
(Officer's Signature)
APPLICATION NO:NN/2018/0000089
(Reviewing Engineer's Signature / Date)
01 TYPICAL
SCALE: NTS
CONCRETE THRUST BLOCKS
WALL
4" 6"
19 TYPICAL
SCALE:
UPRIGHT SPRINKLER
NTS
M
ROOF INSULATED PANEL
M003 . XAM
M
DESIGN & BUILD OF LIGHT INDUSTRIAL
M52 . N IM
TO FACP (BY OTHERS)
WATER FLOW ALARM SWITCH
AND LOGISTICS UNITS AT RAS BUFONTAS
ROOF CEILING SPECIAL ECONOMIC ZONE (PORTION 1)
PENDENT SPRINKLER
ANCHOR BOLT
ANCHOR BOLT
CHANNEL
SPRINKLER
RISER
TO SPRINKLER SYSTEM
FS PIPE CLIP
PG
DRAIN RISER
25mmØ
SCALE: NTS
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-12
DATE:09-08-2020 SHEET: 12 OF 13 SCALE: NTS
Extinguishant Released
Remote Auto/Manual
Releasing Solenoid
Extinguishant Low
Pressure Switch
Pressure Switch
Remote Manual
1st Stage 2nd Stage
Release Switch
Select Switch
Notification Notification
CAUTION !
Disablement Switch
Releasing
Detectors
DO NOT ENTER
470R
470R
470R
470R
470R
DIODE
Stop Air Conditioning
Shutdown Power
This area is protected مﺎظ ﺒ ط ﻤﺤﻤ طﻘطﻨﻤ ا ﻩذﻫ
with FM 200 CLEAN AGENT
GAS DISCHARGED
٢٠٠ ﻫﺒ ﺌﺒ ﻏذز افذام
fire extinguishing system
6K8
6K8
قﻤرذﻟ ﺒ ﻘﻔﻨﻻ
S
6K8
6K8
6K8
6K8
6K8
To Status O
Units S S L
S S
When alarm sounds ﺒﻔم ﺨذءط ﺒ ﻟﺎنﺒ ورﻨ
or on gas discharge
evacuate hazard area اطرﻔﻻ طذﺼ عمﻤ ﺒق ﺎﺒﻔ S S
immediately زم ﻟ ﻻ ﻴرﻔﻨ ﺒ ذﻏ
After discharge do
NOT re-enter until
اﻟﻻ ﻴرﻔﻨ ﺒ ذﻏ ق ﻴﻻنﺘ ﺒ ﺒ
قﺒ ﻤﻨ ذﺜ ﺨذءط ﺒ
EVACUATE NOW E +R0V
AUX
24V
SIL AL FLT RST
REMOTE DATA POWER NAC 1 NAC 2 ZONE 1ZONE 2 ZONE 3 2ND 1ST
NC C NO NC C NO
2ND MODE MAN. ABORT REL EXTING. LOW EXTRACT TROUBLE
NO C NC C NO NC C NO NC C NO
LOCAL FIRE
CONTROL STATUS UNITS SOUNDER STAGE STAGE SELECT RELEASE PRESS. PRES. RELAY FIRE RELAY
thoroughly ventilated
ذطذطﻴ ﻤﻴﻨم ﻴ ﻻﻟا
GAS DISCHARGE SWITCH SWITCH
SOUNDER FAULT/
Security and Safety Solutions DISABLEMENT FIRE IN ZONE DISABLEMENTS EXTINGUISHANT STATUS
GENERAL SYSTEM STATUS
TEST MODE ON SYSTEM FAULT ZONE FAULT/TEST/ 2ND STAGE CONTACT HOLD
ACTIVATED
DUSABLEMENT
GENERAL ALARM/FAULT
DISABLEMENT WARNING SILENCED EXTRACT FAN FLOODING
ZONE FAULT
SILENCE SOUND ALARM/FAULT LAMPTEST MODE SELEST ENTER SYSTEM MODE ENABLE CONTROL
ALARM WARNING SILENCE RESET (+100) (+10) (+1)
(Officer's Signature)
+ - + -
SA
S
S S
CONSULTANT SIGNATURE:
S S UPDA REG.NO: 2616 QID NO: 27160808616
CL CL
FROM 27/04/2011 TO 26/04/2021
CONSULTANT:
CL CL
MONITOR MODULE
CONNECT TO MAIN FIRE ALARM SYSTEM
FECP
CAUTION ! ARABIC !
FIRE FIGHTING
INSTALLATION DETAILS SHEET-2
SHEET PROPERTIES
REVISION: 2 SHEET SIZE: A0 SETTING: DWF
FF-13
DATE:09-08-2020 SHEET: 13 OF 13 SCALE: NTS