Professional Documents
Culture Documents
What Is A Medium-Voltage Transformer?
What Is A Medium-Voltage Transformer?
Practical levels of voltage are often referred to as medium voltage, meaning the
incoming voltage to the transformer is on the order of 5 kV to 35 kV. Some distribution
voltages may exceed 35 kV and would be considered high voltage, but most of the
distribution system is within the medium-voltage range. Modern distribution transformers
are manufactured in accordance with many standards, most notably by IEEE (Institute
of Electrical and Electronics Engineers) and IEC (International Electrotechnical
Commission).
In the United States, the features and functionality of most distribution transformers fall
under IEEE standard C57.12.00 (Standard General Requirements for Liquid-Immersed
Distribution Power and Regulating Transformers), however, there are a multitude of
standards that apply to specific types and applications of transformers including
substation type, compartmental padmount type, single-phase pole mounted
transformers, generator duty transformers, high-temperature transformers, and many
more.
The substation transformer is the heart of the electrical substation. This transformer
changes the relationship between the incoming voltage and current and the outgoing
voltage and current. Substation transformers are rated by their primary and secondary
voltage relationship and their power carrying capability. For example, a typical
substation transformer would be rated 15 kV, 25 kV, 35 kV or 46 kV on the primary at a
power rating of about 5-20 MVA. The secondary or low voltage can be 15 kV down to 5
kV or even less than 600 V. Substation-style transformer design and functionality is
dictated by IEEE standards C57.12.00 and C57.12.36. These type transformers consist
of a core and coils immersed in oil or dielectric fluid in a steel tank. The oil or fluid
serves both as an insulator and as a coolant to keep the core at reliable operating
temperatures. Substation units are easily identified by their exposed bushings, gauges,
panels or monitoring equipment and are typically located behind a fence or with a
restricted area.
Three-phase pad-mounted transformer
Standard ratings for types of distribution transformers are found in IEEE product
standards including the following:
Three-phase
• 12470Y/7200 V
• 12470GY/7200 V
• 7200 V Delta
Single-phase
• 7200/12470Y V
• 12470GY/7200 V
• 7200 V Delta
Temperature rise: A kVA rating is based on the current that the transformer can carry
without exceeding its temperature rise rating. The more heavily loaded a transformer
becomes, the higher its internal temperature gets. The maximum temperature rise that
the transformer can withstand without abnormal loss of life is governed by customer
specifications or by IEEE standards
Fluid: For over a century, transformers have utilized conventional mineral oil as a
dielectric coolant. It offers reasonable cost with proven, reliable, long-term
performance. Maintenance procedures are well established and used mineral oil can
usually be reconditioned for use by filtering and degassing. The fire point of mineral oil
is approx. 155 oC, while the fire point of a less-flammable fluid is above 300 oC. This
makes less flammable fluids, such as Envirotemp FR3, the better alternative for
installations indoors, on top of buildings or in high-pedestrian traffic areas. Use of less-
flammable fluids is recognized as a method of reducing fire hazard, indoors and
outdoors, by the National Electrical Cod (NFPA 70) and the National Electric Safety
Code
Key ratings
kilo-volt-amperes (kVA)
Primary voltage
Secondary voltage
Basic Insulation Level (BIL)
Impedance
Frequency
Cooling type
Temperature rise
Cooling: The heat that the core/coil assembly generates must be dissipated to the air
via the tank and cooling fins. The more surface area on the tank, the more heat that
may be dissipated. Adding cooling fins is an option for increasing surface area without a
significant increase in oil quantity, keeping costs lower than increasing the size of the
tank itself. Every liquid filled transformer is identified with a four-letter code describing
the transformer cooling method. IEEE C57.12.00 defines cooling methods, or the
cooling class, for distribution transformers.
Back to top
Deadfront connectors fall into two main categories: loadbreak and deadbreak.
Radial feed
Loop feed
Bushing layout options
ANSI/IEEE C57.12.34 defines bushing spacing, bushing
height, termination compartment size
Minimum
Specific
System configurations
• Radial system
• Loop system
These system configurations can be used alone or in combination with one another on
different portions of the distribution system. Complex combinations are sometimes
referred to as networks consisting of radial and loop branches with multiple sources of
supply.
Radial system
Loop system
A loop system is fed by two different feeders – one connected to each end of the loop.
Theoretically, the entire loop of transformers could be fed by either source, or the
transformers can be split up between the two sources, depending on where an “open
point” is created. In the event of a failed underground cable, this open point is “moved”
(by using load-break switches or elbows), so that no customers are out of power while
the cable is repaired. In the below example, the transformers are shown with fuses,
which would isolate a failed transformer, limiting the outages to those customers fed by
the failed transformer. Loop feed transformers have two high-voltage bushings per
phase line being connected, so current can loop through the transformer, downstream
to the next one.
IEEE standard C57.12.28 – Enclosure integrity (Tamper resistance)
The purpose of this standard is to describe the requirements for enclosure integrity of
pad mounted equipment that provides long field life with minimum maintenance and
resist tampering.
Enclosure security
• Enclosure mounting: The enclosure must allow for flush mounting on a flat
mounting surface
• Water resistant: The enclosure must resist the entry of water into the enclosure
(except under flood conditions), so that it does not impair the operation of the unit
• Resistant to foreign objects: The enclosure must prevent the entry of objects
such as sticks, wires and rods
• Sharp corners: The enclosure shall minimize projections and sharp corners
• Corrosion resistance: The hinges, hinge pins and pentahead bolts shall be made
of type 304 stainless steel or a material of equivalent corrosion resistance
• Locking devices: The enclosure must contain a locking device that resists
breaking and bending, and must comply with the enclosure access test, the fire
resistance test, the pry test, the push tool test, the pull tool test and the probe
wire test
Cooling types
Top view
There are many variations of these items that are tailored to different types of
transformer arrangements. These transformer protective devices, when coordinated
with up- and down-stream protections, can protect from a full range of events and help
to minimize outages caused by those occurrences by localizing the disruption or
shutting down the system for higher severity.
Overcurrent protection
Overcurrent protection from fault conditions and overloading can be accomplished with
various types of fuses and breakers. Sometimes these will be used in combination
together and they often need to be coordinated together as a system to get a proper
protection and functionality.
Overvoltage
• Gauges: Transformers have a multitude of gauges that allow for easy monitoring
or status checks of condition. Some of the most common types include liquid or
winding temperature gauges, liquid level gauge and pressure/vacuum gauges.
Most gauges come in one of two styles.
o Analog, non-contact type gauge: Used for local monitoring only of a
transformer diagnostic
o Contact gauge, or gauge with contacts: Includes internal conductive
contacts capable of closing or opening when a given condition arises,
relaying an electrical signal to an annunciator or control room as an alarm
signal
• Transducers: For more sophisticated monitoring schemes, the use of transducers
can be applied. A transducer is a type of gauge that records a real-time signal and
outputs the data in the form of an analog signal, typically a 4mA to 20mA signal,
for recording and tracking real-time data. New smart transformers are using
transducers to monitor real-time diagnostic data to help better predict the longevity
of the transformer.
• Sampling valve: Sampling valves are most often incorporated into a transformer
drain valve. The sampling valve is a crucial component of a liquid-filled transformer
as it gives the operator the ability to pull a portion of the transformer fluid to run
dissolved gas analysis, or other fluid testing, that may help determine the overall
health of the unit. Eaton and other manufacturers now offer the fluid sample valve
externally for safe access while the transformer is still energized.
• Visible break: Visible break is a term referring to a switch that allows visible
isolation of a single-phase or three-phase circuit. The purpose of including the
visible break switch is to allow an operator to quickly and effectively determine if a
transformer or line is truly de-energized. Eaton transformers can be provided with
external visible break on padmount transformers to allow safe de-energization
without the need to enter the primary or secondary cabinets.
• Relays/schemes: System protection is the art and science of detecting problems
with power system components and then isolating these components. Protective
relays, associated communication systems, voltage and current sensing devices,
station batteries and DC control circuitry make up the gambit of apparatuses in a
protection system. Ultimately these protective devices and sensors help keep
equipment such as transformers, reactors, generators, capacitors, buses and
transmission lines protected from the dangers of surges, faults and overcurrent
events.
Back to top
Routine tests
1. The purpose is to verify the correct high-voltage and low-voltage turns ratio (at all
tap positions and voltage settings)
2. This test verifies the unit is checked for open circuit conditions, short circuit (turn-
to-turn) conditions and proper polarity and phase relationship (start vs. finish
leads)
3. Test results are per IEEE standards C57.12.00 (+/-0.5% tolerance on test value
from design value). Results are reported as either pass or fail
Resistance test
1. The purpose is to verify coils resistance and wire size is as expected when
compared to design values, to obtain a resistance value to upgrade (correct)
winding losses and to perform heat run calculations
2. Procedure for substation units is to test on rated tap and tap extremes. Padmount
units are tested in nominal tap position only. In general, all readings are taken line-
to-line, and high-voltage and low-voltage windings are connected in-series
3. Test results for reporting are not required by IEEE standard C57.12.00 but are
available upon request. When used for heat run testing, the measurement is used
for calculating I2R values and separating stray losses from measured winding
losses
1. The purpose is to determine the ratio of the power dissipated in the insulation in
watts to the product of the effective voltage and current. (Is the insulation dry
enough?)
2. The procedure for power factor testing is to short all high-voltage terminals
together, and likewise with the low-voltage terminals. A 60 Hz, 120 V signal is
applied to the unit by the measurement bridge. The first measurement is taken
high-voltage to ground, the second high-voltage to low-voltage, and the final low-
voltage to ground.
3. Test results are pass or fail: Test results are compared to an empirically derived
curve of insulation factor power vs. temperature (typical pass value for a
distribution transformer would be 1.0% or less).
1. The purpose is to verify the insulation integrity and BIL rating of units
2. The procedure consists of applying one reduced wave (approximately 50% of
rated BIL) and one full wave (rated BIL) to each terminal. Non-impulsed terminals
are grounded. First an operator would monitor the voltage and current waves on a
DIMS 5 oscilloscope and then examine voltage and current waves for mismatch
between reduced and full waves.
Core loss (No Load Loss) and percent exciting current test
1. Winding loss (or load loss) testing is performed on all units during final testing
2. The purpose of the test is to check the test values against the design calculations,
check workmanship and materials and collect actual measured values for
customer use. Results may also be used in heat run calculations
3. The procedure for substation units is to test on rated tap and tap extremes.
Padmount units are tested at the nominal position only. The operator must short-
circuit the low-voltage winding and circulate rated current in the high-voltage
winding in order to measure the losses
4. Test results are compared to customer guarantees or design values for a pass /
fail status
Optional tests
IEEE Impulse Test (reduced wave, two chopped waves, full wave)
1. The IEEE impulse test is performed (60 kV BIL and above) upon request
2. This design test is performed because the application of two chopped waves
applies different stresses to the winding than the full wave and puts the unit under
similar stresses as a lightning strike or bushing flashover event. The test is meant
to simulate the violent surges a transformer may see throughout its lifetime
3. The procedure for this test is to apply in sequence one reduced wave, two
chopped waves and one full wave. The crest value of wave and time to chop is per
IEEE standard C57.12.00, Table 4, unless otherwise specified
4. Test results are examined, matching reduced wave, first full waves and second full
waves for variations in wave shape. Waveforms should overlay with minimal
deviations. Matching before and after traces will result in a pass for the test
Sound level test
1. Audible sound level testing is performed when purchased or for design verification
2. The purpose of this test is to determine the amount of audible noise generated by
the transformer
3. The specific procedure, including distance and sound sensor (microphone)
placement is dictated in IEEE standard C57.12.90. In order to conduct the test, the
unit to be tested is placed in a sound chamber and then energized at rated
voltage. Sound levels are measured at prescribed intervals around the perimeter
of the unit. The readings are then averaged to obtain the transformer sound level
4. Test results are reported and held per NEMA standards, specifically NEMA TR-1