TECHNICAL SPECIFICATIONS

Supply voltage: 12 V - 24 V AC +/-10% ; 12 V - 35 V DC +/-10%


Power consumption: < 2.5 W
Mounting height: 6.5 ft to 11.5 ft (local regulations may have an impact on the acceptable mounting height)
Temperature range: Sensor: -31°F to +131°F Activation & safety sensor
LCD: 14°F to +131°F
0-95% relative humidity, non condensing
for automatic sliding doors
Degree of protection: IP54 (US Version)
Applicable directives: R&TTE 1999/5/EC; EMC 2004/108/EC; MD 2006/42/EC; RoHS 2002/95/EC
PLEASE KEEP FOR FURTHER USE - DESIGNED FOR COLOR PRINTING

Detection mode: Motion Presence


Min. detection speed: 2 in/s Typical response time: < 200 ms (max. 500 ms)

Technology: Microwave doppler radar Active infrared with background analysis


Transmitter frequency: 24.150 GHz Spot: 5 cm x 5 cm (typ) DESCRIPTION
Transmitter radiated power: < 20 dBm EIRP Number of spots: max. 24 per curtain
Transmitter power density: < 5 mW/cm2 Number of curtains: 2

Output: Solid-state-relay Solid-state-relay


(potential and polarity free) (potential and polarity free)
Max. contact current: 100 mA Max. contact current: 100 mA
Max. contact voltage: 42 V AC/DC Max. contact voltage: 42 V AC/DC
Adjustable Holdtime: 0.5 to 9 s Automatic Holdtime: 0.3 or 1 s

Sensitivity: Low: < 1 V; High: > 10 V (max. 30 V)


6
Test input *:
Specifi
p cations are subject
j to changes
g without prior notice.
Response time on test request: typical: < 5 ms 1
All values measured in specific conditions.
2
* SEE APPLICATION NOTES OR CONTACT BEA FOR TECHNICAL SUPPORT 3 7
4 8
©BEA |Originalinstructions|75.5736.0220130628IXIO-DT1

5 9

1. LCD 6. cover
2. radar antenna (narrow field) 7. main connector
3. radar antenna (wide field) 8. main adjustment knob
4. AIR-curtain width adjustment 9. AIR-curtain angle adjustment knob
5. AIR-lenses

ACCESSORIES

ANSI / AAADM Compliance


AAADM American Association of
Automatic Door Manufactures
Upon completion of the installation or service work, at a minimum, perform a daily safety check in accordance with the
minimum inspection guidelines provided by AAADM. Provide each equipment owner with an owner’s manual that
includes a daily safety checklist and contains, at a minimum, the information recommended by AAADM. Offer an
information session with the equipment owner explaining how to perform daily inspections and point out the location of
power/operation switches to disable the equipment if a compliance issue is noted. The equipment should be inspected
annually in accordance with the minimum inspection guidelines. A safety check that includes, at a minimum, the items
listed on the safety information label must be performed during each service call. If you are not an AAADM certified
inspector, BEA strongly recommends you have an AAADM certified inspector perform an AAADM inspection and place 10IDMB: Mounting Bracket 10IDCA: Ceiling Adapter 10WRC: Clear Rain Cover 35.1286: Black Cover
a valid inspection sticker below the safety information label prior to putting the equipment into operation. 35.1302: White Cover
35.1303: Silver Cover
24/7 Technical Support: Customer Service:
1-800-407-4545 1-800-523-2462

General Technical Questions: Technical Documentation:


Tech_Services@beainc.com www.beasensors.com

Page 8 of 8 75.5736.02 20130628 IXIO-DT1 75.5736.02 20130628 IXIO-DT1 Page 1 of 8


INSTALLATION
1 MOUNTING & WIRING
RED
12-24 V AC
12-35 V DC BLACK POWER SUPPLY

* WHITE
GREEN ACTIVATION INPUT

BROWN
*

SENSOR
BLUE SAFETY INPUT
PURPLE
2 in
max. YELLOW
TEST
OUTPUT **
Avoid extreme Do not cover the sensor. Avoid moving objects Avoid highly
vibrations. and light sources in reflective objects in
the detection field. the infrared field.

TIP! * Output status when sensor is operational


Mounting and wiring are compatible with the Wizard.

MAINTENANCE
** SEE APPLICATION NOTES OR CONTACT BEA FOR TECHNICAL SUPPORT

2 ACTIVATION ZONE

field size: 9 field size: 9


ANGLE

7 ft 7 ft
It is recommended to clean Do not use aggressive
the optical parts at least once products to clean
a year or more if required due the optical parts.
to environmental conditions.

15° to 45° -15° to 15°

SAFETY

field size: 9
WIDTH

field size: 9

7 ft 7 ft

The door control unit Only trained and Always test the proper The warranty is invalid if
13 ft x 6.5 ft (wide) 6.5 ft x 8 ft (narrow) and the door cover qualified personnel operation of the unauthorized repairs are
profile must be correctly may install and setup installation before made or attempted by
grounded. the sensor. leaving the premises. unauthorized personnel.

The size of the detection field varies according to the mounting height of the sensor.

• The device should not be used for purposes other than its intended use. All other uses cannot be
guaranteed by the manufacturer of the sensor.
• The installer of the door system is responsible for carrying out a risk assessment and installing the sensor and
the door system in compliance with applicable national and international regulations and standards on door
safety.
• The manufacturer of the sensor cannot be held responsible for incorrect installations or inappropriate
adjustments of the sensor.

Page 2 of 8 75.5736.02 20130628 IXIO-DT1 75.5736.02 20130628 IXIO-DT1 Page 7 of 8


TROUBLESHOOTING
3 SAFETY ZONE

ANGLE
DOOR
E1 The ORANGE LED The sensor signals 1 Cycle power supply.
1 flashes 1 x. an internal fault. 2 If orange LED flashes again, replace sensor. CLOSER

E2 The ORANGE LED The power supply voltage 1 Check power supply (in the diagnostics menu of the LCD).
2 flashes 2 x. is too low or too high. 2 Check wiring.

E4 The ORANGE LED The sensor does not receive 1 Check the angle of the AIR-curtains. max.
4 flashes 4 x. enough AIR-energy. 2 Increase AIR-immunity filter to value 2 (enhanced). 3.5**
OR AWAY
PUSH
The ORANGE LED The sensor receives 1 Check the angle of the AIR-curtains. 2X
E5
5 flashes 5 x. too much AIR-energy. 2 Decrease the AIR immunity filter to value 1 (normal).
Activate the visible spots.* If necessary, adjust the AIR-curtain
1 Replace sensor. angle (from -7° to 4°).
The ORANGE LED The AIR power emitter is
E8
8 flashes 8 x. faulty.
* Visibility depends on external conditions. When spots are not visible, use the Spotfinder to locate the curtains.
** The distance between the inner curtain of the inside door sensor and the inner
curtain of the outside door sensor should always be smaller than 8 inches.
The ORANGE LED The sensor encounters 1 Cycle power supply.
is on. a memory problem. 2 If orange LED turns on again, replace sensor.

WIDTH
TIP!
The RED LED flashes The sensor sees the door 1 Check the angle of the AIR-curtains. Always
quickly after an remember to
during the assisted setup. 2 Launch a new assisted setup.
also adjust the
assisted setup. Attention: Do not stand in the detection field!
width via the
LCD or remote
The RED LED The sensor vibrates. 1 Check if the sensor is mounted firmly. control
2 Check position of cable and cover. (see p. 5)
flashes
sporadically. The sensor sees the door. 1 Launch an assisted setup and adjust the AIR angle. The arrow position determines the width of the detection field. Always verify the actual detection field width
with this user’s guide and not the Spotfinder,
The sensor is disturbed 1 Increase the AIR-immunity filter to value 2 (enhanced). which detects the whole emitted field.
by external conditions. Mounting Detection The size of the detection field varies according to the mounting height of the sensor.
height width The full door width must be covered.

The GREEN LED The sensor is disturbed by 1 Increase radar-immunity filter. 6.6 ft 6.6 ft
7.2 ft 7.2 ft
flashes sporadically. rain and/or leaves. 8.2 ft 8.2 ft
9.8 ft 9.8 ft
Ghosting created by door 1 Change radar field angle. 11.5 ft 11.5 ft
movement.
The sensor vibrates. 1 Check if the sensor and door cover is mounted firmly. 4 SETTINGS
2 Check position of cable and cover.
The sensor sees the door 1 Remove the objects if possible. Adjust the sensor by LCD or remote control (see p. 4 and 5)
or other moving objects. 2 Change radar field size or angle.

The LED and the 1 Cycle power supply.


LCD-display are off. 2 Check wiring. OR

The reaction of 1 Check output configuration setting.


the door does not 2 Check wiring.
correspond to the
LED-signal.
5 SETUP
IMPORTANT! Step out of the detection field before launching a setup.

SETUP 1 (QUICK) = SETUP 2 (ASSISTED) = +


OPEN+CLOSE

OR OR
LONG PUSH (2 s) LONG PUSH (4 s)

Motion Presence LED flashes


LED flashes LED is off IMPORTANT! Walk test the proper operation of the installation before leaving the premises.
detection detection quickly
green red

Page 6 of 8 75.5736.02 20130628 IXIO-DT1 75.5736.02 20130628 IXIO-DT1 Page 3 of 8


OVERVIEW OF SETTINGS
HOW TO USE THE LCD?
0 1 2 3 4 5 6 7 8 9
DISPLAY DURING NORMAL OPERATION
Back
More
RAD: FIELDSIZE small > > > > > > > > large

AIR: WIDTH

BASIC
Always additionally adjust the
arrow position on the
Activation Safety Negative display = active output To adjust contrast, push and turn sensor with a screwdriver.
the grey button simultaneously.
During normal operation only. NO NC NC NO NO: normally
rmally open
AIR: OUTPUT * NC NO NC NO NC: norm
mally
m ally close
closed

FACTORY VALUE VS. SAVED VALUE TEST * off on

More
Back
displayed value = factory value displayed value = saved value
Back
More
RAD: FIELDSIZE small > > > > > > > > large
NAVIGATING IN MENUS
RAD: IMMUNITY low > > > > > > > high
bi: bi-directional detection (towards & away)
RAD: DIRECTION off bi uni MTF uni: unidirectional detection towards sensor
Select your language before entering MTF: uni with Motion Tracking g Feature
Push to enter the first LCD-menu.
the LCD-menu Scroll menu items RAD: HOLDTIME 0.5 s 1s 2s 3s 4s 5s 6s 7s 8s 9s
Available for the first 30 seconds after
power-on of the sensor .
RAD: REENTRY small > > > > > > > > large

NO NC NC NO NO: normally open


RAD: OUTPUT * NC NO NC NO NC: normally closed

RAD: EXTMON off on

Select Back to return Select More to go to next level: AIR: IMMUNITY normal enhanced
to previous menu or - basic settings
display. - all settings
AIR: WIDTH

ALL
- diagnostics Always remember to also adjust
the arrow position on the
sensor with a screwdriver.
+
service
AIR: NUMBER 1 2 Service Mode = no IR detection during 15 minutes (maintenance).
mode

CHANGING A VALUE AIR: PRESTIME 30 s 1 min 2 min 5 min 10 min 20 min 60 min ∞
AIR: FREQ A B Sensors mounted close to each other should have a different frequency.

NO NC NC NO NO: normally
rmally open
AIR: OUTPUT * NC NO NC NO NC: norm
mally
m ally close
closed

TEST * off on
current value is more values are new value is
displayed displayed displayed motion activation output is active in case of: 0 motion detection
REDIRECTION motion or
presence 1 motion orr presence detection

SCROLL PUSH SCROLL PUSH FACTORYRST restore to factory values


MENU TO SELECT VALUES TO SAVE
PARAMETER NEW VALUE More
UP-DOWN UP-DOWN
Back

Back
VALUE CHECK WITH REMOTE CONTROL ZIP all parameter settings in zipped format AIR: C2 ENERG signal amplitude received on curtain 2
DIAGNOSTICS

ID # unique ID-number POWERSUPPLY supply voltage at power connector


Pressing a parameter symbol on your CONFIG P/N configuration part number OPERATINGTIME power duration since first startup
remote control, displays the saved SOFT P/N software part number RESET LOG delete all saved errors
value directly on the LCD-screen. ERROR LOG the last 10 errors RC PASSWORD password for remotre control login
AIR: SPOTVIEW view of spot(s) that trigger detection ADMIN enter code to access admin mode
AIR: C1 ENERG signal amplitude received on curtain 1 BACK
* SEE APPLICATION NOTES OR CONTACT BEA FOR TECHNICAL SUPPORT