TC4 Series: Temperature Controller

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Specifications Dimensions

TC4 Series TC4S Series TC4SP Series 6 TC4W Series


Series 72.2
TEMPERATURE CONTROLLER Power AC power
TC4S TC4SP
100-240VAC 50/60Hz
TC4Y TC4M TC4W TC4H TC4L
48 6 64.5 48 58.5 45 96 6 64.5

TC4 Series
supply AC/DC Power 24VAC 50/60Hz, 24-48VDC
Allowable voltage range 90 to 110% of rated voltage
Power AC power Max. 5VA(100-240VAC 50/60Hz)

44.7
M A N U A L

45

48
consumption AC/DC Power Max. 5VA (24VAC 50/60Hz), Max. 3W(24-48VDC)
Display method 7Segment(Red), Other display(Green, Yellow, Red LED)
Character size(W×H) 7.0×15.0mm 7.4×15.0mm 9.5×20.0mm 9.5×20.0mm 7.0×14.6mm 11.0×22.0mm
Input RTD DPt100Ω, Cu50Ω (Allowable line resistance max.5Ω per a wire)
type TC K(CA), J(IC), L(IC) TC4Y Series 84
At room temperature(23℃±5℃): (PV ±0.5% or ±1℃, select the higher one) ±1digit 72 7 77
Display RTD
Out of room temperature range: (PV ±0.5% or ±2℃, select the higher one) ±1digit
accuracy※1
TC ※ For TC4SP, add ±1℃ by accuracy standard.
Control Relay 250VAC 3A 1a

36

30
output SSR 12VDC ± 2V 20mA Max. TC4H Series TC4L Series
Alarm output AL1, AL2 Relay: 250VAC 1A 1a(※TC4SP, TC4Y have AL1 only.) 48 6 64.5 96 6 64.5
Control method ON/OFF and P, PI, PD, PID control
Hysteresis 1 to100℃/℉(0.1 to 50.0℃/℉) variable TC4M Series
Proportional band(P) 0.1 to 999.9℃/℉ 72 6 64.5
Integral time(I) 0 to 9999 sec.
Derivative time(D) 0 to 9999 sec.
Thank you very much for selecting Autonics products. Control period(T) 0.5 to 120.0 sec.
Manual reset 0.0 to 100.0%

91.5

91.5
For your safety, please read the following before using.

96
Sampling period 100ms

67.5
Dielectric AC power 2,000VAC 50/60Hz for 1min.(Between input terminal and power terminal)
Caution for your safety strength AC/DC Power 1,000VAC 50/60Hz for 1min.(Between input terminal and power terminal)
Vibration 0.75mm amplitude at frequency of 5 to 55Hz in each of X, Y, Z directions for 2 hours
※Please keep these instructions and review them before using this unit. Mechanical OUT: Min. 5,000,000 operations, AL1/2: Min. 5,000,000 operations
Relay
※Please observe the cautions that follow; OUT: Min. 200,000 operations(250VAC 3A resistive load),
life cycle Electrical
AL1/2: Min. 300,000 operations (250VAC 1A resistive load)
Warning Serious injury may result if instructions are not followed. Insulation resistance Min. 100MΩ(at 500VDC megger) Bracket Panel cut-out Terminal cover(sold separately)
Caution Product may be damaged, or injury may result if instructions are not followed. Noise immunity
Memory retention
Square-wave noise by noise simulator(pulse width 1㎲) ± 2KV R-phase and S-phase
Approx. 10 years (When using non-volatile semiconductor memory type)
TC4S/TC4SP Series TC4Y Series RSA-COVER(48×48mm) RMA-COVER(72×72mm)
31 30 48.4 3 70 3
※The following is an explanation of the symbols used in the operation manual. A
Environ Ambient temp. -10 to 50℃, Storage: -20 to 60℃ 48.6 20
Caution:Injury or danger may occur under special conditions. -ment Ambient humi. 35 to 85%RH, Storage: 35 to 85%RH

12
10
45 5
Double insulation or reinforced insulation (mark: , Dielectric strength between the

41.5
Insulation type 60

68.5
Warning measuring input part and the power part: AC power 2kV, AC/DC Power 1kV)

64
Approval

B
1. In case of using this unit with machinery (Ex: nuclear power control, medical equipment, ship,

10
Approx. 141g Approx. 123g Approx. 174g Approx. 204g Approx. 194g Approx. 194g Approx. 254g C

44.9
vehicle, train, airplane, combustion apparatus, safety device, crime/disaster prevention equipment, Weight※2

36

16

18
(approx. 94g) (approx. 76g) (approx. 85g) (approx. 133g) (approx. 122g) (approx. 122g) (approx. 155g)

22
4.4
etc) which may cause damages to human life or property, it is required to install fail-safe device.

3.5
※1: Thermocouple L(IC) type, RTD Cu50Ω 9.8

13
It may cause a fire, human injury or damage to property.
2. Install the unit on a panel. At room temperature (23℃ ±5℃): (PV ±0.5% or ±2℃, select the higher one) ±1digit
Out of room temperature range: (PV ±0.5% or ±3℃, select the higher one) ±1digit 22.5
It may cause electric shock. 55 15 TC4M, TC4W, TC4H, TC4L Series Size
3. Do not connect, inspect or repair this unit when power is on. In case of TC4SP Series, ±1℃ will be added. A B C D
※2: The weight with packaging and the weight in parentheses is only unit weight. Model
It may cause electric shock. 21 RHA-COVER RLA-COVER(96×96mm )

3.3
4. Wire properly after checking terminal number. ※Environment resistance is rated at no freezing or condensation. TC4S Min. 65 Min. 65 45+0.6
0 45+0.6
0 (48×96mm, 96×48mm )
It may cause a fire. 47.2 4 94 3
Parts description TC4SP Min. 65 Min. 65 45 45
+0.6 +0.6
0 0
5. Do not disassemble the case. Please contact us if it is required.

4
It may cause electric shock or a fire. 56 46 TC4Y Min. 91 Min. 40 68+0.7
0 31.5+0.5
0

1
TC4M Min. 90 Min. 90 68+0.7 68+0.7
Caution
0 0

91.5

91.5
1 TC4H Min. 65 Min. 115 45+0.6 92+0.8

86

86
37.5
40.5
0 0

1. This unit shall not be used outdoors. 2 6 7, 8


It may shorten the life cycle of the product or cause electric shock.
3 4 TC4W Min. 115 Min. 65 92+0.8
0 45+0.6
0
2 5
2. When connect wire, AWG 20(0.50mm2) should be used and screw bolt on terminal block with 0.74N·m 8 TC4L Min. 115 Min. 115 92+0.8
0 92+0.8
0
to 0.90N·m strength. 6
7 12
It may cause a malfunction or fire due to contact failure.
3. Please observe the rated specifications.
3 5 4

13

13
23.9
It may shorten the life cycle of the product and cause a fire. 1. Present temperature (PV) display 5. Control/alarm output indicator
4. Do not use beyond of the rated switching capacity of relay contact. RUN mode: Present temperature (PV) display. OUT: It will turn ON when control output(Main Control
It may cause insulation failure, contact melt, contact failure, relay broken and fire etc.
5. In cleaning unit, do not use water or organic solvent. And use dry cloth.
Parameter setting mode: Parameter or
parameter setting valuedisplay.
Output) is ON.
※In case of CYCLE/PHASE control of SSR drive
Connections SSR drive output selection function(SSRP function)[ SSrM ]
It may cause electric shock or a fire. 2. Deviation indicator, Auto-tuning indicator
output, it will turn ON when MV is over 3.0%. ※TC4 Series has selectable control output; Relay output, and SSR drive output. ● Realizing high accuracy and cost effective temperature control with both current output (4-20mA)
6. Do not use this unit in place where there are flammable or explosive gas, humidity, direct ray of the (only for AC power type) AC/DC power type does not have SSRP function. and linear output(cycle control and phase control)
It shows current temperature(PV) deviation
light, radiant heat, vibration and impact etc. AL1/AL2: It will light up when alarm output Alarm1/ ● SSRP function is selectable one of standard ON/OFF control, cycle control, phase control by utilizing
based on set temperature(SV) by LED. TC4S Series TC4SP Series
It may cause a fire or an explosion. Alarm2 are on.
No. PV deviation temp. Deviation display standard SSR drive output.
7. Do not inflow dust or wire dregs into the unit. 6. key SSR OUT: 6 ● Select one of standard ON/OFF control [ STND], cycle control[ CYCL] , phase control[ PHAS] at
1 Over 2℃ indicator ON 1 AL1 OUT: 7 -
It may cause a fire or a malfunction. Used when entering into parameter group, returning 12VDC ±2V 5 7 AL1 OUT:
20mA Max
250VAC 1A 1a Relay OUT 250VAC 1A 1a SSrM parameter of parameter 2 group. For cycle control, connect a zero cross turn-on SSR (a
8. Please wire properly after checking the terminal polarity when connecting temperature sensor. 2 Below ±2℃ indicator ON to RUN mode, moving parameter, and saving setting 2 8 250VAC 3A 1a
AL2 OUT:
4 8
+ random turn-on SSR is also available). For phase control, connect a random turn-on SSR.
It may cause a fire or an explosion. 3 Under -2℃ indicator ON values. 250VAC 1A 1a SSR OUT:
3 9 Temperature controller SSR voltage output
9. In order to install the units with reinforced insulation, use the power supply unit which basic Relay OUT: TC RTD B' 12VDC ±2V SSR module
The deviation indicators ( , , ) flash by 7. Adjustment B' RTD TC 3 9 (TC4Series) (12VDC)
insulation level is ensured. 4 250VAC 3A 1a
10 - 20mA Max
Load
(TC4SP is basic insulation only.) every 1 sec. when operating auto tuning. Used when entering into set value change mode, digit -
+ B
moving and digit up/down. B + 2 10 -
3. Set temperature(SV) indicator -
5 11
A +
Ordering information 1 11
8. FUNCTION key ※1
Press any front key once to check or ※1 +
6 12
A
SENSOR SOURCE
SOURCE SENSOR
change current set temperature(SV), the set Press + keys for 3 sec. to operate function(RUN/ 100-240VAC 5VA 50/60Hz 100-240VAC 5VA 50/60Hz
24VAC 5VA 50/60Hz
T C 4 S 1 4 R temperature(SV) indicator is ON and preset set STOP, alarm output cancel, auto-tunning) set in inner 24VAC 5VA 50/60Hz
24-48VDC 3W
24-48VDC 3W
value is flashed. parameter [DI-K].
TC4Y Series TC4H, TC4W, TC4L Series Power
Control output N Indicator - Without control output 4. Temperature unit(℃/℉) indicator ※Press + keys at the same time in set value
100-240VAC
R Relay output+SSR drive output※1 It shows current temperature unit. operation to move digit. 50/60Hz
AL1 OUT: Relay OUT: 1 13
250VAC 1A 1a 250VAC 3A 1a ※When selecting cycle or phase control mode, the power supply for a load and a temperature
Power supply 2 24VAC 50/60Hz, 24-48VDC Input sensor and temperature range[ IN-T] 2 14 controller must be the same.
4 100-240VAC 50/60Hz 1 2 3 4 5 6 7 8 9 10 11 ※In case of selecting cycle [ CYCL] or phase [ PHAS] control mode for PID control, control cycle [ T] is
Input sensor Display Input range (℃) Input range (℉) 3 15
N No alarm output A B B' -+ not allowed to set.
K(CA) KCA -50 to 1200 -58 to 2192
Sub output SSR OUT: 4 16 ※For AC/DC power model (TC4 - 2R), this parameter [SSrM] is not displayed and it is available only
1 Alarm1 output Thermocouple J(IC) JIC -30 to 500 -22 to 932 SENSOR RTD
12VDC ±2V
SOURCE ※1
standard control by relay or SSR.
2 Alarm1 + Alarm2 output※2 L(IC) LIC -40 to 800 -40 to 1472 20mA Max 100-240VAC 5VA 50/60Hz 5 17
TC 24VAC 5VA 50/60Hz 1)Standard ON/OFF control [ STND]
DPtH -100 to 400 -148 to 752 24-48VDC 3W
S DIN W48 H48mm(terminal block type) DPt100Ω 6 18 A mode to control the load in the AC
DPtL -100.0 to 400.0 -148.0 to 752.0 same way as Relay output type.
SP DIN W48 H48mm(11pin plug type) ※3 RTD
CUsH -50 to 200 -58 to 392 TC4M Series SSR OUT: 7 AL1 OUT: 19
(ON: output level 100%, OUT
Y DIN W72 H36mm Cu50Ω 12VDC ±2V 250VAC 1A 1a ON OFF ON OFF
Size CUsL -50.0 to 200.0 -58.0 to 392.0 20mA Max 8 20 OFF: output level 0%)
1 10 AL2 OUT:
M DIN W72 H72mm
Installation
250VAC 1A 1a
H DIN W48 H96mm 9 21 2)Cycle control [ CYCL]
2 11 Relay OUT:
●TC4S/SP(48 48mm) Series ●TC4Y(72 36mm) Series ●Other Series 250VAC 3A 1a B' RTD TC A mode to control the load by AC
W DIN W96 H48mm 10 22
3 12 - repeating output ON / OFF
L DIN W96 H96mm B + according to the rate of output
11 23
Digit SSR OUT: 4 AL1 OUT: 13 - within setting cycle. OUT
4 9999(4 Digit) 12VDC ±2V 250VAC 1A 1a +
12 24
A
Having improved ON / OFF noise
50Cycle 50Cycle
20mA Max ※1
Setting type 5 AL2 OUT: 14 SOURCE SENSOR
100-240VAC 5VA 50/60Hz feature by Zero Cross type. 50% 80%
C Set by touch switch 250VAC 1A 1a 24VAC 5VA 50/60Hz
Item 6 15 24-48VDC 3W
Relay OUT:
T Temperature controller B' RTD TC
3)Phase control [ PHAS]
250VAC 3A 1a
7 16 A mode to control the load by
※1: In case of the AC voltage model, SSR drive output method (standard ON/OFF control, cycle control, -

phase control) is available to select. 8 17 B + controlling the phase within


AC
※2: It is unavailable for TC4SP, TC4Y. ※1: AC power: 100-240VAC 5VA 50/60Hz AC half cycle. Serial control is
A available.
※3: Socket for TC4SP (PG-11, PS-11) is sold separately. SOURCE 9 18 SENSOR
AC/DC power: 24VAC 5VA 50/60Hz
100-240VAC 5VA 50/60Hz Random turn-on SSR must be OUT
※The above specifications are subject to change without notice. ※Mount the product on the panel, fasten bracket by pushing with tools as 24VAC 5VA 50/60Hz 24-48VDC 3W
24-48VDC 3W used for this mode. 10% 50%
shown above.(In case of TC4Y, fasten bolts for bracket.)
Flow chart for setting group Parameter 2 group ※1: S : Press any key among , , .
Alarm[ AL-1/ AL-2 ] Input correction[ IN-B ]
Controller itself does not have errors but there may be error by external input temperature sensor. This function
RUN mode

※2: After checking/changing set value at each parameter, and press
key, set value flashes twice and it moves to next parameter
AM!A There are two alarms which operate individually. You can set combined alarm
operation and alarm option.
is for correcting this error.
Alarm Alarm Ex) If actual temperature is 80℃ but controller displays 78℃, set input correction value [IN-B] as '002' and
Press any key among Run mode automatically. operation option Use digital input key(set as AlRE) or turn OFF power and re-start this unit to
① ② 2sec. ③ 4sec. controller displays 80℃.
, , , . 4 sec. ※Press key for 3 sec. to return RUN mode at any parameter. 1)Alarm operation release alarm operation. ※As the result of input correction, if current temperature value (PV) is over each temperature range of input
3 sec. ※ This parameter might not be displayed depending on other sensor, it displays 'HHHH' or 'LLLL'.
PAR2 Mode Name Alarm operation Description
SV setting Parameter 1 group[PAR1] Parameter 2 group[PAR2] parameter settings.

3sec. 3sec. Input type ※1


AM)_ - - No alarm output
Input digital filter [ MAvF]
OFF H ON OFF H If deviation between PV and SV
ON
If current temperature(PV) is fluctuating repeatedly by rapid change of input signal, it refl ects to MV and stable
IN-T Deviation
④ KCA JIC LIC DPtH DPtL CU%H CU%L as high-limit is higher than set control is impossible. Therefore, digital filter function stabilizes current temperature value.
AM! high-limit
AL1 AL1 alarm temperature IN-Tㄴㄴ Input type
alarm
SV
100℃
PV
110℃
PV
90℃
SV
100℃
value of deviation temperature, For example, set input digital filter value as 0.4 sec, and it applies digital filter to input values during 0.4 sec and
※2 ※When changing input type, SV, IN-B, H-SV, L-SV, AL1, AL2, LBaT,
High deviation: Set as 10℃ High deviation: Set as -10℃ the alarm output will be ON. displays this values. Current temperature may be different by actual input value.
AL2 AL2 alarm temperature UNITㄴㄴ Temperature unit LBaB, AHYS parameters are initialized.

AT Auto tuning IN-Bㄴㄴ Input correction


Temperature unit ※Front temperature unit indicator will flash when
selecting the unit. Deviation
ON H OFF ON H OFF
If deviation between PV and SV Hysteresis [ HYS]
UNIT ?C ?F PV SV SV PV as low-limit is higher than set ●● If Hysteresis is too narrow, hunting(oscillation, chattering)
※When changing temperature unit, SV, IN-B, H-SV, AM@ low-limit
Pㄴㄴ Proportional band MAvFㄴㄴ Input digital filter
alarm
90℃ 100℃ 100℃ 110℃ value of deviation temperature, could occur due to external noise.
L-SV, AL1, AL2, LBaT, LBaB, AHYS parameters Lower deviation: Set as Lower deviation: Set as the alarm output will be ON.
Input correction ●● In case of ON / OFF control mode, even if PV reaches Heating operation
I Integral time L-SV SV low-limit value are initialized. 10℃ -10℃ stable status, there still occurs hunting. It could be due
IN-Bㄴㄴ 000 Set range: -999 to 999 (DPtL / CUsL: -199.9 to 999.9) Control
D Derivative time H-SV SV high-limit value Deviation ON H OFF H ON If deviation between PV and SV to Hysteresis [ HYS] SV, load’s response characteristics output
or sensor’s location. In order to reduce hunting to a ON OFF
high/low- as high/low-limit is higher than set
Manual reset (Normal Input digital filter AM#
REST deviation correction)
O-FTㄴㄴ Control output operation Set range: 0.1 to 120.0 sec. limit PV
90℃
SV
100℃
PV
110℃
value of deviation temperature, minimum, it is required to take into following factors Hysteresis
MAvF )1 ※Set input digital filter time for average input value affected control, alarm High/Lower deviation: Set as 10℃ the alarm output will be ON. consideration when designing temp. controlling; (HYS)
HYS ON/OFFcontrol hysteresis C-MD Control type
and display value. proper Hysteresis [ HYS], heater’s capacity, thermal Temp.
Deviation characteristics, sensor’s response and location. SV
OUTㄴㄴ Control output SV low-limit value Set range: Within the rated temperature If deviation between PV and SV
※1: It is not displayed for AC/DC power model(TC4 - 2R). high/low- OFF H ON H OFF
※If no key entered for 30 sec., it returns to RUN mode
SSrMㄴㄴ SSR drive output method※1
L-SV -050 range by input sensor [ L-SV ≤ ( H-SV-1digit)] ※In case of [IN-T]
input sensor type, AM$ limit
PV SV PV
as high/low-limit is higher than set
value of deviation temperature,
Manual reset[ REST ] ●Manual reset [REST] by control result
When changing SV low-limit value, reserve Set below 50.0 as reset value
automatically and the set value of parameter is not be saved. low/high-limit setting 90℃ 100℃ 110℃ the alarm output will be OFF. When selecting P/PD control mode, certain temperature difference
if SV < L-SV, SV is initialized as L-SV. alarm
※ This parameter might not be displayed depending on T Control cycle
SV high-limit value Set range: Within the rated temperature
temperature(SV) is High/Lower deviation: Set as 10℃ exists even after PV reaches stable status because heater's rising
Offset
other parameter settings. also set as max./min. and falling time is inconsistent due to thermal characteristics of SV
AL-1ㄴㄴ AL1 alarm operation mode H-SV 1200 range by input sensor [ H-SV ≥ ( L-SV+1digit)] temperature range of
OFF H ON OFF H ON
controlled objects, such as heat capacity, heater capacity. This Offset
①P  ress any key once in RUN mode, it advances to set value When changing SV high-limit value, Absolute
input sensor. If PV is higher than the absolute temperature difference is called offset and manual reset [ REST]
setting group. AL-2ㄴㄴ AL2 alarm operation mode
Control output operation
if SV > H-SV, SV is initialized as H-SV. AM% value high PV
90℃
SV
100℃
SV
100℃
PV
110℃ value, the output will be ON. function is to set/correct offset.
limit alarm Set over 50.0 as reset value
②P  ress key over 2sec. in RUN mode, it advances to Absolute-value Alarm: Absolute-value Alarm: When PV and SV are equal, reset value is 50.0%. After control
AHYSㄴㄴ Alarm output hysteresis O-FT HEAT COOL ※When changing control output operation, ErMU is Set as 90℃ Set as 110℃
parameter 1 group. initialized. is stable, PV is lower than SV, reset value is over 50.0% or PV is
③P  ress key over 4sec. in RUN mode, it advances to LBaTㄴㄴ LBA monitoring time ON H OFF ON H OFF higher than SV, reset value is below 50.0%.
Absolute
④F
parameter 2 group.
 irst parameter will be displayed on viewer when it
LBaBㄴㄴ LBA detection range Control type AM^ value low PV SV SV
100℃
PV
110℃
If PV is lower than the absolute
value, the output will be ON.
Digital input key( + 3sec.) [ DI-K]
90℃ 100℃
advances to the setting group. DI-Kㄴㄴ Digital input key C-MD PID ONOF ※When changing control type, ErMU is initialized(control limit alarm
Absolute-value Alarm: Absolute-value Alarm: Parameter Operation
output MV is below 100%) and DI-K turns OFF Set as 90℃ Set as 110℃
⑤P  ress key over 3sec. in the setting group, it returns Control output MV in case OFF OFF It does not use digital input key function.
to RUN mode.
ErMVㄴㄴ of input break error
automatically. Sensor It will be ON when it detects
SBa - It is available to pause on control output and auxiliary output (except loop break alarm,
break alarm sensor disconnection.
※Exception: Press key once in SV setting group it LOCㄴㄴ Lock Control output sensor break alarm) except control output operates normally as set. Press digital input
Loop break It will be ON when it detects loop key for 3sec to re-start the operation.
returns to RUN mode. OUT RLY SSR ※Operates only selected output between Relay or SSR. LBa
alarm
-
break. RUN/STOP ㄴ썌ㅖSTOP t t t t Digital input key
※Press key again within a sec after return to RUN mode by press key over 3sec., it ※ H: Alarm output hysteresis[AHYS] (t: over 3sec.)
advances to the first parameter of previous setting group. 2)Alarm opetion
SSR dirve RUN STOP RUN STOP RUN
※Parameter setup Parameter 2 group → Parameter 1 group → SV setting ※It is displayed when selecting control Option Name Description
output method
output [ OUT] as SSR. For AC/ It is available to clear alarm output by force. (It is only when alarm option is alarm latch,
• Set parameter as the above considering parameter relation of each setting group. SSrM STND CYCL PHAS Standard If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output
DC power type (TC4 - 2R), this ㅁㅆAM .A standby sequence.)
• Check parameter set value after change parameter of parameter 2 group. alarm is OFF. Clear alarm AlRE
parameter [SSrM] is not displayed. Clear alarm is able to only for out of alarm operation range. Alarm operates normally
※Indicator model (TC4 -N N)displays shaded parameter( ) of parameter 2 group. If it is an alarm condition, alarm output is ON and maintains ON status. right after clear alarm.
※AL-1, AL-2 parameters of parameter 2 group is decided whether to display according by alarm output type. AM ㅁ.ㅜㅜㅠㅠㅠㄱㅠㅠㅠㅁB Alarm latch
Control cycle Set range:0.5 to 120.0 sec. (Alarm output HOLD) Auto tuning function, it is same as auto tuning function [AT] of parameter 1 group.
※If alarm operation mode[ AL-1, AL-2] of parameter 2 group is set to AM)_/ SBa / LBa , AHYS 02)0 ※If control output [ OUT] is set as RLY, factory default is 20.0 sec, or First alarm condition is ignored and from second alarm condition, standard alarm (You can execute auto tuning from parameter 1group, and finish it by digital input key.)
T Standby Auto tunning AT
parameter is not displayed. set as SSR, factory default is 2.0 sec. AM .C operates. When power is supplied and it is an alarm condition, this first alarm condition When control type [C-MD] is set as PID, AT is displayed. When it is set as ONOF,
sequence 1 digital input key [DI-T] is changed as OFF.
※This T will not be displayed when SSR drive output method [ SSrM] is ignored and from the second alarm condition, standard alarm operates.
Flow chart for SV setting group is set as CYCL, PHAS. Alarm latch If it is an alarm condition, it operates both alarm latch and standby sequence. When
Control output MV when input sensor line is broken [ ErMV ]
※In case of changing set temperature from 210℃ to 250℃ AL1 alarm operation ※Press key to AM .D and standby power is supplied and it is an alarm condition, this first alarm condition is ignored and
sequence 1 from the second alarm condition, alarm latch operates. The function to set control output MV in case of open error. Users are able to set by ON/OFF setting or MV
AL-1 AM!A LBaA AM!Aㄴ AM!B convert alarm setting. It executes control output by set MV regardless of ON/OFF or PID control output.
①RUN mode(display current temperature)
operation mode First alarm condition is ignored and from second alarm condition, standard alarm
Standby
※Alarm operation mode ※Alarm option into alarm option. AM .E
sequence 2
operates. When re-applied standby sequence and if it is alarm condition, alarm output
does not turn ON. After clearing alarm condition, standard alarm operates.
Lock setting[ LOC ] Display Description
AL2 alarm operation
A function to prevent changing SV and parameters of Lock off
※Same with the above [ AL-1]. Basic operation is same as alarm latch and standby sequence1. It operates not only by
OFF
③Finish the setup. AL-2 AM@A Alarm latch each setting group. Parameter setting values are still LOC1 Lock parameter group 2
Press any key among , , , . ※When changing alarm operation AL1, AL2, alarm temperature of power ON/OFF, but also alarm setting value, or alarm option changing. When re-applied
AM .F and standby possible to check while Lock mode is ON. LOC2 Lock parameter group 1, 2
AL1, AL2 is initialized. standby sequence and if it is alarm condition, alarm output does not turn ON. After
②Set value change mode sequence 2 ※ OFF, LOC1 are available only for indicator(TC4 -N N). LOC3 Lock parameter group 1, 2, SV setting
Alarm output hysteresis Set range: 1 to 100℃/℉(DPtL/ CYsL: 0.1 to 50.0℃) clearing alarm condition, alarm latch operates.
Change set value
by , , keys. AHYS 001 ※If alarm operation mode [ AL-1, AL-2] is set to AM)_, SBa ,
LBA , AHYS parameter is not displayed.
Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON Error
Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, Display Description Troubleshooting
changing set temperature, alarm temperature [AL1, AL2] or alarm operation [AL-1, AL-2], switching STOP mode Flashes if input sensor is disconnected or sensor
LBA monitoring time Set range: 0 to 9999sec. (Automatically setting with Auto-tunning) OPEN Check input sensor state.
④Check SV to RUN mode. is not connected.
※LBaT parameter is displayed when alarm operation mode [ AL-1,
LBaT 0 3)Sensor break alarm Flashes if measured sensor input is higher than
AL-2] is set as LBA . HHHH
The function that alarm output will be ON when sensor is not connected or when sensor's disconnection is temperature range. When input is within the rated temperature
Parameter 1 group ※1: S : Press any key among , , . Set range: 0 to 999℃/℉ (DPtL/ CUs: 0.0 to 999.9℃/℉) detected during temperature controlling. You can check whether the sensor is connected with buzzer or other LLLL
Flashes if measured sensor input is lower than range, this display disappears.
LBA detection band (Automatically setting with Auto-tunning) temperature range.
※2: After checking/changing set value at each parameter, and press units using alarm output contact. It is selectable between standard alarm [SBaA] or alarm latch [SBaB].
LBaB 002 ※When alarm operation mode [ AL-1, AL-2] is set as loop break
3 sec.
Run mode key, set value flashes twice and it moves to next parameter
automatically.
alarm(LBA) [ LBA ], and LBaT parameter does not set as 0,
4)Loop break alarm(LBA)
It checks control loop and outputs alarm by temperature change of the subject. For heating control(cooling
Caution for using
2 sec. LBaB parameter is displayed. 1. The connection wire of this unit should be separated from the power line and high voltage line in order to
※3: It is displayed when control type parameter [ C-MD] of parameter control), when control output MV is 100%(0% for cooling control) and PV is not increased over than LBA prevent from inductive noise.
PAR1 2group is set PID. Digital input key
detection band [LBaB] during LBA monitoring time [LBaT], or when control output MV is 0%(100% for cooling 2. For crimp terminal, select following shaped terminal (M3).
※Press key for 3 sec. to return RUN mode at any parameter. DI-K OFF STOP AlRE AT control) and PV is not decreased below than LBA detection band
※ This parameter might not be displayed depending on other [LBaB] during LBA monitoring time [LBaT], alarm output turns ON. Max. 5.8mm Max. 5.8mm
※1 ※AlRE is not displayed for not alarm output model.
AL1 alarm temperature parameter settings. ※AT is not displayed when control type parameter [ C-MD] is set ONOF.
AL1 1250 3. Please install power switch or circuit-breaker in order to cut power supply off.
Control output MV in case Set range: 0.0 to 100.0% 4. Switch or circuit-breaker should be installed near by users for convenient control.
Set range: Deviation alarm(-[F.S] to [F.S], Absolute value of input break error ※0.0/100.0% is displayed when control type parameter [ C-MD] is
※2
5. Do not use this product as Volt-meter or Ampere-meter, this is a temperature controller.
alarm(temperature range) ErMV 00)0 set ONOF. 6. In case of using RTD sensor, 3 wire type must be used. If you need to extend the line, 3 wires must be used
AL2 alarm temperature ※In case alarm operation mode [ AL-1, AL-2], AM)_/ SBa ※When changing PID control to ON/OFF control, if MV is below with the same thickness as the line. It might cause the deviation of temperature if the resistance of line is
AL2 1250 / LBa of parameter 2 group is set to [ AL-1, AL-2], no 100.0%, it is initialized as 0.0%. different.
parameters is displayed. Lock ※For indicator model 7. In case of making power line and input signal line closely, line filter for noise protection should be installed at
※3 LOC OFF LOC1 LOC2 LOC3 (TC4 -N N), only OFF, power line and input signal line should be shielded.
※It starts to operate auto-tuning when it is ON and LOC1 are available. 8. Keep away from the high frequency instruments.(High frequency welding machine & sewing machine, large
Auto-tuning capacity SCR controller)
set as OFF automatically after finish the operation.
AT OFF ON 9. When supplying measuring input, if 'HHHH' or 'LLLL' is displayed, measuring input may have problem.
※Deviation indicators(▲, , ▼) flash (cycle:1
sec.) during auto tuning function. Factory default Turn off the power and check the line.
10. Installation environment
Time ①It shall be used indoor.
Proportional band ● SV setting ● Parameter 2 group
②Altitude Max. 2000m.
P 01)0 Set range: 0.1 to 999.9℃/℉ Parameter Factory default ③Pollution Degree 2.
Parameter Factory default Parameter Factory default
④Installation Category II.
- 0 IN-T ㅏKCA T 02)0 Start control When control output MV is 100%, PV is increased over than LBA detection band [LBaB] during ※It may cause malfunction if above instructions are not followed.
Integral time UNIT ?C to LBA monitoring time [LBaT].
I 0000
Set range: 0 to 9999 sec. ● Parameter 1 group
IN-B 0000
AL-1 AM!A to The status of changing control output MV (LBA monitoring time is reset.) Major product
※Integral operation will be OFF when set value is "0". Photoelectric sensors Temperature controllers
Parameter Factory default When control output MV is 0% and PV is not decreased below than LBA detection band [LBaB]
MAvF 00)1 AL-2 AM@A to
during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.
Fiber optic sensors Temperature/Humidity transducers
Derivation time
AL1 Door sensors SSR/Power controllers http://www.autonics.com
Set range: 0 to 9999 sec.
1250 L-SV -050 AHYS 0001 to Control output MV is 0% and loop break alarm (LBA) turns and maintains ON. Door side sensors Counters
D 0000 AL2 Area sensors Timers
Satisfiable Partner For Factory Automation
※Derivative operation will be OFF when set value is "0". H-SV 1200 LBaT 0000 to The status of changing control output MV (LBA monitoring time is reset.) Proximity sensors Panel meters HEAD QUARTERS:
AT OFF Pressure sensors Tachometer/Pulse(Rate) meters 116, Ungbigongdan-gil, Yangsan-si, Gyeongsangnam-do,
O-FT HEAT LBaB 002 When control output MV is 100% and PV is not increased over than LBA detection band [LBaB] Korea
Manual reset P 01)0 to
during LBA monitoring time [LBaT], loop break alarm (LBA) turns ON after LBA monitoring time.
Rotary encoders Display units
OVERSEAS SALES:
Set range: 0.0 to 100.0% C-MD PID DI-K STOP Connector/Sockets Sensor controllers
#402-404, Bucheon Techno Park, 655, Pyeongcheon-ro,
REST 05)0 I When control output MV is 100% and PV is increased over than LBA detection band [LBaB] Switching mode power supplies Wonmi-gu, Bucheon, Gyeonggi-do, Korea
※It is displayed in P/PD control. 0000 OUT RLY ErMV 00)0 to Control switches/Lamps/Buzzers
D during LBA monitoring time [LBaT], loop break alarm (LBA) turns OFF after LBA monitoring time. TEL: 82-32-610-2730 / FAX: 82-32-329-0728
I/O Terminal Blocks & Cables E-mail: sales@autonics.com
SSrM STND LOC OFF to The status of changing control output MV (LBA monitoring time is reset.) Stepper motors/drivers/motion controllers
ON/OFFcontrol
Set range: 1 to 100℃/℉ (For DPtL/CUsL: 0.1 to 50.0℃/℉)
REST 05)0 The proposal of a product improvement and
※AC/DC power type has no SSR drive output method [ SSrM] and Graphic/Logic panels
hysteresis  hen executing auto-tuning, LBA detection band[LBaB] and LBA monitoring time are automatically set based
W development: product@autonics.com
※It is displayed when control type parameter [ C-MD] of parameter HYS 002 supports only ON/OFF output when selecting SSR in control output on auto tuning value. When alarm operation mode [AL-1, AL-2] is set as loop break alarm(LBA)[LBa ], LBA
Field network devices
HYS 002 Laser marking system(Fiber, CO₂, Nd:YAG)
2 group is set ONOF. [ OUT]. detection band [LBaB] and LBA monitoring time [LBaT] parameter is displayed. Laser welding/soldering system
EP-KE-03-0320F