CLIENT: Axis CONTRACTOR: Pan Engineering (North) S/B

PROJECT: DHL Penang Logistics Hub TESTER: Freddie Bin Henry Foad
SYSTEM: Fire Sprinkler Pump (Diesel) DATE: 04-Feb-21
LOCATION: Batu Maung, Penang

Wire Insulation Test Sheet (Duty Pump)


Wire Reference
Marking No. Description Marking No. Description
1 Energize to Start Solenoid 10 Start Contactor 2
2 Engine Run 11A Ground
3 Overspeed 11B Ground
4 Low Oil Pressure 12 Energize to Stop Solenoid
5 High Engine Temperature 310 High Raw Water Temperature
6 Battery 1 311 Low Raw Water Flow
8 Battery 2 312 Low Engine Temperature
9 Start Contactor 1

Test Cable No. Insulation Resistance Value (Mega Ω)


Cable 1 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 2 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 3 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 4 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 5 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 6 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 8 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 9 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 10 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 11A to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 11B to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 12 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 310 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 311 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 312 to Earth 2.2 GigaΩ (2,200 MΩ)

Test Voltage Pressure Setting (Volt DC) 1,000


Instrument Use Brand / Model FLUKE / 1587 Insulation Multimeter

Name Signature Date


Tested By
Verified By
Witnessed By
Cable Number Photo

Cable No. 1
(Duty)

Cable No. 2
(Duty)

Cable No. 3
(Duty)

Cable No. 4
(Duty)
Cable Number Photo

Cable No. 5
(Duty)

Cable No. 6
(Duty)

Cable No. 8
(Duty)

Cable No. 9
(Duty)
Cable Number Photo

Cable No. 10
(Duty)

Cable No. 11A


(Duty)

Cable No. 11B


(Duty)

Cable No. 12
(Duty)
Cable Number Photo

Cable No. 310


(Duty)

Cable No. 311


(Duty)

Cable No. 312


(Duty)

Cable
Termination
(Duty)
CLIENT: Axis CONTRACTOR: Pan Engineering (North) S/B
PROJECT: DHL Penang Logistics Hub TESTER: Freddie Bin Henry Foad
SYSTEM: Fire Sprinkler Pump (Diesel) DATE: 21-Feb-21
LOCATION: Batu Maung, Penang

Wire Insulation Test Sheet (Standby Pump)


Wire Reference
Marking No. Description Marking No. Description
1 Energize to Start Solenoid 10 Start Contactor 2
2 Engine Run 11A Ground
3 Overspeed 11B Ground
4 Low Oil Pressure 12 Energize to Stop Solenoid
5 High Engine Temperature 310 High Raw Water Temperature
6 Battery 1 311 Low Raw Water Flow
8 Battery 2 312 Low Engine Temperature
9 Start Contactor 1

Test Cable No. Insulation Resistance Value (Mega Ω)


Cable 1 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 2 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 3 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 4 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 5 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 6 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 8 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 9 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 10 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 11A to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 11B to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 12 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 310 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 311 to Earth 2.2 GigaΩ (2,200 MΩ)
Cable 312 to Earth 2.2 GigaΩ (2,200 MΩ)

Test Voltage Pressure Setting (Volt DC) 1,000


Instrument Use Brand / Model FLUKE / 1587 Insulation Multimeter

Name Signature Date


Tested By
Verified By
Witnessed By
Cable Number Photo

Cable No. 1
(Standby)

Cable No. 2
(Standby)

Cable No. 3
(Standby)

Cable No. 4
(Standby)
Cable Number Photo

Cable No. 5
(Standby)

Cable No. 6
(Standby)

Cable No. 8
(Standby)

Cable No. 9
(Standby)
Cable Number Photo

Cable No. 10
(Standby)

Cable No. 11A


(Standby)

Cable No. 11B


(Standby)

Cable No. 12
(Standby)
Cable Number Photo

Cable No. 310


(Standby)

Cable No. 311


(Standby)

Cable No. 312


(Standby)

Cable
Termination
(Standby)