Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

Nicotine & Tobacco Research, Volume 12, Number 6 (June 2010) 665–668

Brief Report

Air quality in and around airport enclosed


smoking rooms
Kiyoung Lee, Sc.D., C.I.H.,1,2 Ellen J. Hahn, Ph.D., R.N.,2 Heather E. Robertson, M.P.A.,2 Laura Whitten, B.A.,2
Laura K. Jones, M.S., M.A.,2 & Brendan Zahn, B.S.N.2
1
Graduate School of Public Health and Institute of Health and Environment, Seoul National University, Seoul, Korea
2
Tobacco Policy Research Program, College of Nursing, University of Kentucky, Lexington, KY
Corresponding Author: Kiyoung Lee, Sc.D., C.I.H., Graduate School of Public Health, Seoul National University, 599 Gwanak-ro,
Gwanak-gu, Seoul 151-742, Korea. Telephone: +82-2-880-2735; Fax: +82-2-762-2888; E-mail: cleanair@snu.ac.kr
Received December 31, 2009; accepted March 14, 2010

Downloaded from http://ntr.oxfordjournals.org/ at Pennsylvania State University on May 8, 2016


Abstract all the poisons, toxins, gases, and particles found in SHS (U.S.
Department of Health and Human Services). Scientific evidence
Introduction: Smoking rooms have been installed in some suggests that the only means of effectively eliminating health
airports to allow indoor smoking. There have been few field risks associated with indoor exposure to SHS is to prohibit
studies to measure fine particle leakage in operational smoking indoor smoking even in smoking rooms that are enclosed and
rooms. The objective of the research was to assess air quality ventilated (American Society of Heating, Refrigerating and
inside and outside the 4 smoking rooms located within a medium- Air-Conditioning Engineers [ASHRAE], 2005; U.S. Department
sized, regional commercial airport. of Health and Human Services).

Methods: Particulate matter less than 2.5-mm (PM2.5) concen- Several European countries have implemented nationwide
trations were simultaneously measured inside and outside the 4 smoke-free policies, and effectiveness of such policies has
smoking rooms in the airport and in the public lobby. The been well documented (Fong et al., 2006; Haw & Gruer, 2007;
monitoring was conducted during normal hours of operation. Hyland et al., 2008). Comprehensive public smoke-free policies
Numbers of people and smokers were counted. The airport had have been adopted beyond Europe, including Africa, Asia, and
separate ventilation systems for all 4 rooms checked by the Central and South Americas. Currently in the United States,
airport prior to monitoring, and they were operating properly. 19 states, along with Puerto Rico and Washington, DC, have
100% smoke-free laws in workplaces, restaurants, and bars
Results: Although there were few smokers in each room, (Americans for Nonsmokers’ Rights, 2010), covering 41% of the
average PM2.5 concentrations inside the smoking rooms were U.S. population. Comprehensive smoke-free policy covering all
significantly higher than the National Ambient Air Quality workplaces with no exceptions is the best way to protect all
Standard for 24 hr (35 mg/m3). Fine particles from secondhand workers and the public from the dangers of SHS (Lee et al.,
smoke (SHS) leaked to the outside in 3 of the 4 smoking rooms, 2009). However, there are many local ordinances or regulations
exposing workers and the public. that restrict smoking in only some workplaces with exceptions
across the United States and Washington, DC (Americans for
Discussion: Although the ventilation systems in the smoking Nonsmokers’ Rights).
rooms were operating properly, fine particles from SHS leaked
to the surrounding smoke-free areas in the airport. Indoor space Installation of enclosed smoking rooms is allowed by some
inside airports should be completely nonsmoking, and enclosed local and state laws, although comprehensive smoke-free policy
smoking rooms are not recommended. is more effective. More convincing research is needed to examine
the effectiveness of these smoking rooms in protecting the air
quality in adjacent nonsmoking areas from smoke contami-
nants. Despite efforts by airport personnel and ventilation
Introduction companies to minimize leakage from enclosed smoking rooms,
significant levels of nicotine were perceptible at 35 feet from an
Secondhand smoke (SHS) exposure is the third leading cause of enclosed smoking area that had direct ventilation to the outside
preventable death in the United States (U.S. National Cancer of the airport buildings (Pion & Givel, 2004). Leakage of an en-
Institute, 1999). The U.S. Surgeon General recommends total closed smoking area was demonstrated by much higher airborne
elimination of smoking indoors to reduce exposure to SHS nicotine levels in adjacent nonsmoking areas of California office
(U.S. Department of Health and Human Services, 2006). Fur- buildings (Liu, Alevantis, & Offermann, 2001).
thermore, separating smokers from nonsmokers, air cleaning
technologies, and ventilating buildings cannot eliminate SHS Airports are used by millions of people every day, and travel-
exposure, and conventional air cleaning systems cannot remove ers and airport employees are at risk for being exposed to SHS
doi: 10.1093/ntr/ntq054
Advance Access published on April 21, 2010
© The Author 2010. Published by Oxford University Press on behalf of the Society for Research on Nicotine and Tobacco.
All rights reserved. For permissions, please e-mail: journals.permissions@oxfordjournals.org

665
Air quality in smoking room

if airport buildings are not completely smoke free. In 2002, people inside and smokers every 5 min during the data collection
38.1% of 198 randomly selected U.S. airports did not have a period. Any additional activities that could generate fine parti-
smoke-free policy (Pevzner et al., 2004). There have been few cles were noted (i.e., vacuum cleaner use, aerosol cleaners). As a
field studies to measure fine particle leakage in operational control condition, fine particle concentration was measured for
smoking rooms. The purposes of this study were to assess the air 4 hr in a public lobby at a distance from the smoking rooms.
quality inside and outside the four smoking rooms located within
a medium-sized, regional commercial airport and compare the
fine particulate levels inside and outside the smoking rooms with Results
control areas within the airport that do not allow smoking.
Fine particle concentrations inside and outside the smoking
rooms were simultaneously measured on four different days.
Methods There was a range of 0–6 patrons present in the smoking rooms
and 0–4 burning cigarettes observed, as shown in the Table 1. In
Between August 11 and 22, 2008, indoor air quality was assessed Room A, the average number of burning cigarettes was 0.39.
in five indoor locations including four enclosed smoking rooms The average indoor PM2.5 concentration was 55 mg/m3, and
and one public nonsmoking area located outside of security in a maximum concentration was 952 mg/m3. In Room B, the average
medium-sized (defined as serving 1–5 million passengers per number of burning cigarettes was 0.73. The average indoor
year), regional commercial airport in the United States. The air- PM2.5 concentration was 102 mg/m3, and maximum concentra-

Downloaded from http://ntr.oxfordjournals.org/ at Pennsylvania State University on May 8, 2016


port serves over one million passengers each year and occupies tion was 640 mg/m3. In Room C (lounge with air curtain), the
approximately 1,000 acres. The four smoking rooms had an average number of burning cigarettes was only 0.08. The aver-
average volume of 57.5 ± 4.8 m3, and all except one had a swing age indoor PM2.5 concentration was 13 mg/m3, and maximum
door at the entry to the room. One room was open to another concentration was 325 mg/m3. In Room D, the average number
space and had an air curtain system with a motion sensor. of burning cigarettes was 0.13. The average indoor PM2.5 con-
centration was 68 mg/m3, and maximum concentration was
Indoor air quality was monitored using an aerosol spec- 697 mg/m3. All enclosed smoking rooms had average PM2.5 concen-
trometer (Sidepak Model AM510; TSI Inc., St. Paul, MN). The trations higher than the National Ambient Air Quality Standard
Sidepak is a portable battery operated aerosol monitor that mea- (NAAQS; 35 mg/m3) for 24 hr, except Room C. In the smoke-
sures mass concentration of certain size, including particulate free airport area (control), the average PM2.5 level was 10 mg/m3.
matter less than 2.5 mm (PM2.5). The device was used with a
2.5-mm impactor to measure PM2.5. Prior to each experiment, the In Rooms C and D (Room C with air curtain and Room D
device was zero calibrated with a high efficiency particulate air with swing door), temporal profiles of outside PM2.5 levels
filter according to manufacturer’s specifications. The flow rate showed substantial leakage of PM2.5. The Figure 1 shows the
was set to 1.7 L/min and calibrated before the experiment. The levels of PM2.5 measured inside and outside the two smoking
devices were set to record the average PM2.5 concentration every rooms. Whenever there were smokers inside, the inside PM2.5
minute. The measurement was corrected by a conversion factor level increased substantially. Since the room was ventilated at its
of 0.295 obtained from calibration against gravimetric measure- maximum capacity, the level decreased as soon as the cigarette
ment (Lee et al., 2008). was extinguished. The PM2.5 levels outside the smoking rooms
had a similar temporal profile of the inside PM2.5, as shown in
Two aerosol spectrometers were simultaneously used to the Figure 1. The temporal profile of outside PM2.5 levels in
sample and record PM2.5 levels. One monitor was placed inside Room A showed leakage of PM2.5, although the peak was associ-
the smoking rooms in a corner location away from the seats. ated with opening doors rather than smoking inside the room.
The other monitor was placed outside each smoking room. The In Room B, the outside PM2.5 was stable at 10 mg/m3 and was not
outside monitor was attached to the wall and approximately associated with inside PM2.5.
12 inches from the door and 30 inches from the floor.

The smoking rooms were assessed on separate days, for an Discussion


average of 15.2 hr inside and outside each room (range 13.3–16.1
hr) simultaneously. Data collection occurred from about 5 a.m. Measurement of fine particle levels inside and outside enclosed
to about 9 p.m., the full operation hours of the airport. Research smoking rooms in one medium-sized, regional commercial
assistants sat outside the smoking rooms to record numbers of airport demonstrated that leakage of fine particles is a potential

Table 1. Indoor air quality by airport smoking room


Range of PM2.5 (mg/m3) Range of PM2.5 (mg/m3) Average number of Room Average number Air exchange
Smoking room inside room (mean) outside room (mean) burning cigarettes size (m3) of people rate (ACH)
A 1–952 (55) 1–39 (3) 0.39 57 0.54 5.6
B 3–640 (102) 2–22 (5) 0.73 54 0.96 5.2
C 2–325 (13) 2–34 (7) 0.08 54 0.22 17.3
D 9–697 (68) 5–80 (13) 0.13 64 0.17 1.7
Smoke-free area 8–24 (10)

Note. Room C had an air curtain.

666
Nicotine & Tobacco Research, Volume 12, Number 6 (June 2010)

Downloaded from http://ntr.oxfordjournals.org/ at Pennsylvania State University on May 8, 2016


Figure 1.  Fine particulate levels inside and outside two smoking rooms. (a) Room C with air curtain. (b) Room D with swing door.

threat to patrons outside the smoking rooms but also the workers This is the first scientific report of simultaneous measurement
who enter the rooms on a regular basis. Fine particle concentra- of fine particle air pollution in smoking rooms by continuous moni-
tions in three smoking rooms (A, B, and D) were significantly tors inside and outside the rooms. When airborne nicotine was
higher than the NAAQS of 35 mg/m3. Although one room (C) measured adjacent to a smoking room in an airport, the concentra-
did not exceed the NAAQS, it is likely because very few smokers tion was 3–4.8 times higher than the level in a smoke-free airport
used the smoking room during the study period. However, the (Pion & Givel, 2004). In our study, temporal profiles of fine parti-
indoor fine particle level of Room C was as high as 325 mg/m3, cles inside and outside smoking rooms clearly demonstrated the
when smokers presented in the room. leakage of fine particles from three of the four smoking rooms.

High PM2.5 concentration inside the smoking rooms may Prior to measurement inside and outside the smoking rooms,
be obvious. Although the smoking rooms are mainly used by the ventilation systems were evaluated by the airport and found
smokers, impact of such high levels can affect more than those to be functioning properly. Based on the air exchange rate equa-
who visit the rooms to smoke. Airport workers have to enter tion of smoking density and respirable particle concentration (air
these rooms to clean them and can have significant occupational exchange rate = 650 × smoking density/respirable particle by
exposure to SHS. In addition, parents may take their children SHS; Repace, 2004), ventilation rates in the four smoking rooms
with them inside the smoking rooms or leave them directly out- were estimated to be 5.6, 5.2, 17.3, and 1.7 air exchange rate
side the rooms. (ACH). There is no ASHRAE standard for ventilation rate in

667
Air quality in smoking room

smoking areas. The ASHRAE (2007) standard recommends an Americans for Nonsmokers’ Rights. (2010). Berkeley, CA:
air exchange rate of 7.5 cfm/person + 0.06 cfm/ft2 at a default oc- Americans for Nonsmokers’ Rights. Retrieved 31 January
cupancy of 100 persons/1000 ft2 for transportation waiting rooms. 2010, from http://www.no-smoke.org/
Although the standard is for nonsmoking facilities, the ventila-
tion rate should be about 1.5 ACH, considering the maximum Fong, G. T., Hyland, A., Borland, R., Hammond, D., Hastings, G.,
number of people in the smoking room and average area of the McNeill, A., et al. (2006). Reductions in tobacco smoke pol-
rooms. Despite high ventilation rates, three smoking rooms mea- lution and increases in support for smoke-free public places
sured in this study showed leakage of fine particles. following the implementation of comprehensive smoke-free
workplace legislation in the Republic of Ireland: Findings from
The study has several limitations. Although many studies the ITC Ireland/UK Survey. Tobacco Control, 15, 51–58.
measure PM2.5 for SHS, PM2.5 is not specific to SHS. There are
many potential sources of PM2.5. During the monitoring, addi- Haw, S. J., & Gruer, L. (2007). Changes in exposure of adult
tional potential sources of PM2.5 were observed and the airport non-smokers to secondhand smoke after implementation of
building did not have obvious indoor sources (i.e., airport smoke-free legislation in Scotland: National cross sectional
shuttles inside the terminal). Although temporal profiles of survey. British Medical Journal, 335, 549–552.
PM2.5 levels outside and inside the smoking rooms were gener-
ally similar, the data showed some unexplained and relatively Hyland, A., Higbee, C., Hassan, L., Fong, G. T., Borland, R.,
small peaks. For example, a marked increase in outside PM2.5 Cummings, K. M., et al. (2008). Does smoke-free Ireland have

Downloaded from http://ntr.oxfordjournals.org/ at Pennsylvania State University on May 8, 2016


was observed in Room D at 1.30 p.m., but the increase was not more smoking inside the home and less in pubs than the United
associated with inside smoking, and we could not explain the Kingdom? Findings from the international tobacco control policy
peak from our observation data. evaluation project. European Journal of Public Health, 18, 63–65.

The U.S. Surgeon General recommends complete non- Lee, K., Hahn, E. J., Pieper, N., Okoli, C. T. C., Repace, J., &
smoking in indoor spaces and does not recommend enclosed Troutman, A. (2008). Differential impacts of smoke-free laws
smoking rooms at all (U.S. Department of Health and Human on indoor air quality. Journal of Environmental Health, 70(8),
Services, 2006). Our findings support this recommendation. 24–30.
Neither dilution ventilation nor air cleaning technologies can
Lee, K., Hahn, E. J., Robertson, H. E., Lee, S., Vogel, S. L., &
mitigate health risks from SHS exposure in spaces where smoking
Travers, M. J. (2009). Strength of smoke-free air laws and
occurs (ASHRAE, 2005). Even if the room is separately venti-
indoor air quality. Nicotine & Tobacco Research, 11, 381–386.
lated, the pumping action of swing doors as they are opened and
closed further exacerbates contaminant leakage from smoking Liu, K. S., Alevantis, L. E., & Offermann, F. J. (2001). A survey
rooms (Wagner et al., 2004). As much as 10% of smoking room of environmental tobacco smoke controls in California office
air can enter nonsmoking areas when a swing type entry door is buildings. Indoor Air, 11, 26–34.
opened and closed (Wagner et al.).
Pevzner, E., Davis, R., Pan, W., Husten, C., Pechacek, T., &
Malarcher, A. (2004). Survey of airport smoking policies-
Funding United States 2002. Morbidity and Mortality Weekly Report, 53,
1175–1178.
There was no extramural funding for this project.
Pion, M., & Givel, M. S. (2004). Airport smoking rooms don’t
work. Tobacco Control, 13, 37–40.
Declaration of Interests Repace, J. (2004). Respirable particles and carcinogens in the air
None declared. of Delaware hospitality venues before and after a smoking ban.
Journal of Occupational and Environmental Medicine, 46, 887–905.

U.S. National Cancer Institute. (1999). Health effects of exposure


Acknowledgments to environment tobacco smoke. Smoking and Tobacco Control
Authors appreciate Mark Day whose assistance was critical to Volume Monograph No. 10. Bethesda, MD: U.S. Department of
collect the data from airport. Health and Human Services, National Institutes of Health,
National Cancer Institute.

References U.S. Department of Health and Human Services. (2006). The


health consequences of involuntary exposure to tobacco smoke: A
American Society of Heating, Refrigerating and Air-Conditioning report of the Surgeon General. Atlanta, GA: Department of Health
Engineers. (2005). ASHRAE position document on environmen- and Human Services, Public Health Service, Centers for Disease
tal tobacco smoke. Retrieved 6 April 2010, from http://www Control and Prevention, National Center for Chronic Disease
.ashrae.org/doclib/20058211239_347.pdf and Prevention and Promotion, Office of Smoking and Health.

American Society of Heating, Refrigerating and Air-Conditioning Wagner, J., Sullivan, D. P., Faulkner, D., Fisk, W. J., Alevantis, L. E.,
Engineers. (2007). Standard 62.1-2007, ventilation for acceptable Dod, R. L., et al. (2004). Environmental tobacco smoke leakage
indoor air quality. Retrieved 6 April 2010, from http://www from smoking rooms. Journal of Occupational and Environmental
.ashrae.org/doclib/20058211239_347.pdf Hygiene, 1, 110–118.

668

You might also like