Professional Documents
Culture Documents
Smoking Rooms
Smoking Rooms
Brief Report
Methods: Particulate matter less than 2.5-mm (PM2.5) concen- Several European countries have implemented nationwide
trations were simultaneously measured inside and outside the 4 smoke-free policies, and effectiveness of such policies has
smoking rooms in the airport and in the public lobby. The been well documented (Fong et al., 2006; Haw & Gruer, 2007;
monitoring was conducted during normal hours of operation. Hyland et al., 2008). Comprehensive public smoke-free policies
Numbers of people and smokers were counted. The airport had have been adopted beyond Europe, including Africa, Asia, and
separate ventilation systems for all 4 rooms checked by the Central and South Americas. Currently in the United States,
airport prior to monitoring, and they were operating properly. 19 states, along with Puerto Rico and Washington, DC, have
100% smoke-free laws in workplaces, restaurants, and bars
Results: Although there were few smokers in each room, (Americans for Nonsmokers’ Rights, 2010), covering 41% of the
average PM2.5 concentrations inside the smoking rooms were U.S. population. Comprehensive smoke-free policy covering all
significantly higher than the National Ambient Air Quality workplaces with no exceptions is the best way to protect all
Standard for 24 hr (35 mg/m3). Fine particles from secondhand workers and the public from the dangers of SHS (Lee et al.,
smoke (SHS) leaked to the outside in 3 of the 4 smoking rooms, 2009). However, there are many local ordinances or regulations
exposing workers and the public. that restrict smoking in only some workplaces with exceptions
across the United States and Washington, DC (Americans for
Discussion: Although the ventilation systems in the smoking Nonsmokers’ Rights).
rooms were operating properly, fine particles from SHS leaked
to the surrounding smoke-free areas in the airport. Indoor space Installation of enclosed smoking rooms is allowed by some
inside airports should be completely nonsmoking, and enclosed local and state laws, although comprehensive smoke-free policy
smoking rooms are not recommended. is more effective. More convincing research is needed to examine
the effectiveness of these smoking rooms in protecting the air
quality in adjacent nonsmoking areas from smoke contami-
nants. Despite efforts by airport personnel and ventilation
Introduction companies to minimize leakage from enclosed smoking rooms,
significant levels of nicotine were perceptible at 35 feet from an
Secondhand smoke (SHS) exposure is the third leading cause of enclosed smoking area that had direct ventilation to the outside
preventable death in the United States (U.S. National Cancer of the airport buildings (Pion & Givel, 2004). Leakage of an en-
Institute, 1999). The U.S. Surgeon General recommends total closed smoking area was demonstrated by much higher airborne
elimination of smoking indoors to reduce exposure to SHS nicotine levels in adjacent nonsmoking areas of California office
(U.S. Department of Health and Human Services, 2006). Fur- buildings (Liu, Alevantis, & Offermann, 2001).
thermore, separating smokers from nonsmokers, air cleaning
technologies, and ventilating buildings cannot eliminate SHS Airports are used by millions of people every day, and travel-
exposure, and conventional air cleaning systems cannot remove ers and airport employees are at risk for being exposed to SHS
doi: 10.1093/ntr/ntq054
Advance Access published on April 21, 2010
© The Author 2010. Published by Oxford University Press on behalf of the Society for Research on Nicotine and Tobacco.
All rights reserved. For permissions, please e-mail: journals.permissions@oxfordjournals.org
665
Air quality in smoking room
if airport buildings are not completely smoke free. In 2002, people inside and smokers every 5 min during the data collection
38.1% of 198 randomly selected U.S. airports did not have a period. Any additional activities that could generate fine parti-
smoke-free policy (Pevzner et al., 2004). There have been few cles were noted (i.e., vacuum cleaner use, aerosol cleaners). As a
field studies to measure fine particle leakage in operational control condition, fine particle concentration was measured for
smoking rooms. The purposes of this study were to assess the air 4 hr in a public lobby at a distance from the smoking rooms.
quality inside and outside the four smoking rooms located within
a medium-sized, regional commercial airport and compare the
fine particulate levels inside and outside the smoking rooms with Results
control areas within the airport that do not allow smoking.
Fine particle concentrations inside and outside the smoking
rooms were simultaneously measured on four different days.
Methods There was a range of 0–6 patrons present in the smoking rooms
and 0–4 burning cigarettes observed, as shown in the Table 1. In
Between August 11 and 22, 2008, indoor air quality was assessed Room A, the average number of burning cigarettes was 0.39.
in five indoor locations including four enclosed smoking rooms The average indoor PM2.5 concentration was 55 mg/m3, and
and one public nonsmoking area located outside of security in a maximum concentration was 952 mg/m3. In Room B, the average
medium-sized (defined as serving 1–5 million passengers per number of burning cigarettes was 0.73. The average indoor
year), regional commercial airport in the United States. The air- PM2.5 concentration was 102 mg/m3, and maximum concentra-
666
Nicotine & Tobacco Research, Volume 12, Number 6 (June 2010)
threat to patrons outside the smoking rooms but also the workers This is the first scientific report of simultaneous measurement
who enter the rooms on a regular basis. Fine particle concentra- of fine particle air pollution in smoking rooms by continuous moni-
tions in three smoking rooms (A, B, and D) were significantly tors inside and outside the rooms. When airborne nicotine was
higher than the NAAQS of 35 mg/m3. Although one room (C) measured adjacent to a smoking room in an airport, the concentra-
did not exceed the NAAQS, it is likely because very few smokers tion was 3–4.8 times higher than the level in a smoke-free airport
used the smoking room during the study period. However, the (Pion & Givel, 2004). In our study, temporal profiles of fine parti-
indoor fine particle level of Room C was as high as 325 mg/m3, cles inside and outside smoking rooms clearly demonstrated the
when smokers presented in the room. leakage of fine particles from three of the four smoking rooms.
High PM2.5 concentration inside the smoking rooms may Prior to measurement inside and outside the smoking rooms,
be obvious. Although the smoking rooms are mainly used by the ventilation systems were evaluated by the airport and found
smokers, impact of such high levels can affect more than those to be functioning properly. Based on the air exchange rate equa-
who visit the rooms to smoke. Airport workers have to enter tion of smoking density and respirable particle concentration (air
these rooms to clean them and can have significant occupational exchange rate = 650 × smoking density/respirable particle by
exposure to SHS. In addition, parents may take their children SHS; Repace, 2004), ventilation rates in the four smoking rooms
with them inside the smoking rooms or leave them directly out- were estimated to be 5.6, 5.2, 17.3, and 1.7 air exchange rate
side the rooms. (ACH). There is no ASHRAE standard for ventilation rate in
667
Air quality in smoking room
smoking areas. The ASHRAE (2007) standard recommends an Americans for Nonsmokers’ Rights. (2010). Berkeley, CA:
air exchange rate of 7.5 cfm/person + 0.06 cfm/ft2 at a default oc- Americans for Nonsmokers’ Rights. Retrieved 31 January
cupancy of 100 persons/1000 ft2 for transportation waiting rooms. 2010, from http://www.no-smoke.org/
Although the standard is for nonsmoking facilities, the ventila-
tion rate should be about 1.5 ACH, considering the maximum Fong, G. T., Hyland, A., Borland, R., Hammond, D., Hastings, G.,
number of people in the smoking room and average area of the McNeill, A., et al. (2006). Reductions in tobacco smoke pol-
rooms. Despite high ventilation rates, three smoking rooms mea- lution and increases in support for smoke-free public places
sured in this study showed leakage of fine particles. following the implementation of comprehensive smoke-free
workplace legislation in the Republic of Ireland: Findings from
The study has several limitations. Although many studies the ITC Ireland/UK Survey. Tobacco Control, 15, 51–58.
measure PM2.5 for SHS, PM2.5 is not specific to SHS. There are
many potential sources of PM2.5. During the monitoring, addi- Haw, S. J., & Gruer, L. (2007). Changes in exposure of adult
tional potential sources of PM2.5 were observed and the airport non-smokers to secondhand smoke after implementation of
building did not have obvious indoor sources (i.e., airport smoke-free legislation in Scotland: National cross sectional
shuttles inside the terminal). Although temporal profiles of survey. British Medical Journal, 335, 549–552.
PM2.5 levels outside and inside the smoking rooms were gener-
ally similar, the data showed some unexplained and relatively Hyland, A., Higbee, C., Hassan, L., Fong, G. T., Borland, R.,
small peaks. For example, a marked increase in outside PM2.5 Cummings, K. M., et al. (2008). Does smoke-free Ireland have
The U.S. Surgeon General recommends complete non- Lee, K., Hahn, E. J., Pieper, N., Okoli, C. T. C., Repace, J., &
smoking in indoor spaces and does not recommend enclosed Troutman, A. (2008). Differential impacts of smoke-free laws
smoking rooms at all (U.S. Department of Health and Human on indoor air quality. Journal of Environmental Health, 70(8),
Services, 2006). Our findings support this recommendation. 24–30.
Neither dilution ventilation nor air cleaning technologies can
Lee, K., Hahn, E. J., Robertson, H. E., Lee, S., Vogel, S. L., &
mitigate health risks from SHS exposure in spaces where smoking
Travers, M. J. (2009). Strength of smoke-free air laws and
occurs (ASHRAE, 2005). Even if the room is separately venti-
indoor air quality. Nicotine & Tobacco Research, 11, 381–386.
lated, the pumping action of swing doors as they are opened and
closed further exacerbates contaminant leakage from smoking Liu, K. S., Alevantis, L. E., & Offermann, F. J. (2001). A survey
rooms (Wagner et al., 2004). As much as 10% of smoking room of environmental tobacco smoke controls in California office
air can enter nonsmoking areas when a swing type entry door is buildings. Indoor Air, 11, 26–34.
opened and closed (Wagner et al.).
Pevzner, E., Davis, R., Pan, W., Husten, C., Pechacek, T., &
Malarcher, A. (2004). Survey of airport smoking policies-
Funding United States 2002. Morbidity and Mortality Weekly Report, 53,
1175–1178.
There was no extramural funding for this project.
Pion, M., & Givel, M. S. (2004). Airport smoking rooms don’t
work. Tobacco Control, 13, 37–40.
Declaration of Interests Repace, J. (2004). Respirable particles and carcinogens in the air
None declared. of Delaware hospitality venues before and after a smoking ban.
Journal of Occupational and Environmental Medicine, 46, 887–905.
American Society of Heating, Refrigerating and Air-Conditioning Wagner, J., Sullivan, D. P., Faulkner, D., Fisk, W. J., Alevantis, L. E.,
Engineers. (2007). Standard 62.1-2007, ventilation for acceptable Dod, R. L., et al. (2004). Environmental tobacco smoke leakage
indoor air quality. Retrieved 6 April 2010, from http://www from smoking rooms. Journal of Occupational and Environmental
.ashrae.org/doclib/20058211239_347.pdf Hygiene, 1, 110–118.
668