Harduaganj Thermal Power Station

Extension- II (1x660 MW)


Harduaganj, Distt. Aligarh, Uttar Pradesh

EPC PACKAGE
UTTAR PRADESH RAJYA VIDYUT UTPADAN
OWNER NIGAM LIMITED,
Lucknow, Uttar Pradesh

DESEIN PRIVATE LIMITED,


OWNER’S ENGINEER CONSULTING ENGINEERS
New Delhi

TOSHIBA JSW POWER SYSTEMS PRIVATE


CONTRACTOR
LIMITED

ARCHITECT ENGINEER

SUB - CONTRACTOR TOSHIBA TRANSMISSION AND DISTRIBUTION SYSTEMS


(INDIA) PRIVATE LIMITED

DISTRIBUTION TRANSFORMERS DIVISION

PACKAGE NAME Service Transformer

OWNER’S DWG. NO. HAE2-TEB-SPC-BFT-0002 REV. 03

NTPC’s DWG. NO. REV. 03

CONTRACTOR’S DWG. NO. HAU2-TEB-SPC-BFT-0002 REV. 03

SUB – CONTRACTOR’S DWG.


04DTA17-TM-7410-H-8011 REV. 03
NO.

DWG./DOC. TITLE GTP for 11/0.433kV, 800kVA Oil Type transformer

PURPOSE FOR APPROVAL / FOR INFORMATION

[Revision Status for Owner’s Submission]

R3 5.11.2018 GTP for 11/0.433 kV, 800kVA Oil Type transformer Kalyani Raamesh Sreesan

R2 10.09.2018 GTP for 11/0.433 kV, 800kVA Oil Type transformer Kalyani Raamesh Sreesan

R1 05.02.2018 GTP for 11/0.433 kV, 800kVA Oil Type transformer Raamesh
Pradeep Sreesan

R0 25.07.2017 GTP for 11/0.433 kV, 800kVA Oil Type transformer Raamesh Pradeep Sreesan

REV. NO. DATE DESCRIPTION PREPARED BY CHECKED BY APPROVED BY


Toshiba Transmission & Distribution Systems (India) Pvt. Ltd. Engineering
Distribution Transformers Division
Unit-10
Technical Particulars
Data Sheet of Service Transformer
Work CUSTOMER : UTTAR PRADESH RAJYA VIDYUT UTPADAN NIGAM LIMITED(UPRVUNL)
Order:6809B CONTRACTOR:TOSHIBA JSW POWER SYSTEMS PRIVATE LIMITED
LOI No: TJPSG/17-18/37069 DATED 29 JUNE 2017
kVA:800 kV:11/0.433 Phases:3 Freq.: 50Hz Cooling:ONAN Doc.No.EGT 30653 R5

S. No. Description Unit Bidder Detail Remarks

1.00.00 General
1.01.00 Make TTDI
1.02.00 Type Outdoor;ONAN
1.03.00 Reference Standard IS 1180(PART 1)-2014
2.00.00 Rating
2.01.00 Rated output kVA 800
2.02.00 Type of cooling ONAN
2.03.00 Rated voltage Volt
H.V 11000
L.V 433
2.04.00 Rated Current Amps
H.V 41.989 Line current
L.V 1066.698
2.05.00 No. of phases 3
2.06.00 Rated Frequency Hz 50
2.07.00 Vector group reference Dyn1
3.00.00 Temperature
3.01.00 Reference ambient temp. 50 deg C Deg. C 50
3.02.00 Temp. rise over reference ambient
a. On enclosure by thermometer Deg. C 40 Oil by Thermometer
b. In winding by Resistance Deg. C 45
4.00.00 Tappings
4.01.00 Type OCTC
4.02.00 Capacity 11kV, 50A
-5% to +5% in steps of
4.03.00 Taps provided on HV winding 2.5%
5.00.00 Insulation level kV/kVp
5.01.00 H.V 28/75
5.02.00 L.V 3/--
5.03.00 L.V Neutral 3/--
Impedance at principal tap
6.00.00 rated current & frequency %
6.01.00 Impedance 5 IS tolerance applicable
6.02.00 Reactance 4.95 Approx
6.03.00 Resistance at 75 Deg. C
a) H.V Winding 1.338 Approx
b) L.V Winding 0.00072 Approx
80% to 110% of Positive
6.04.00 Zero sequence impedance :
sequence Impedance
Zero sequence capacitance of H.V
6.05.00 winding
pf/ph 1681 Normal capacitance :LV-HV
Guaranteed losses at Principal
7.00.00 tap, full load and 75 deg.
7.01.00 No load losses Watts 917 Maximum
7.02.00 Load losses Watts 5480 Maximum
Efficiency at 75 deg. C and 0.8
8.00.00 power factor lag %
8.01.00 At full load 99.01
8.02.00 At ¾ full load 99.17
8.03.00 At ½ full load 99.29
8.04.00 Maximum efficiency 99.44
8.05.00 Load and power factor at which it occurs 0.41 Load factor & UPF
9.00.00 Regulation at full load and 75 deg.C
%
9.01.00 At unity power factor 0.81
9.02.00 At 0.8 power factor lagging : 3.58
10.00.00 No load current referred to HV Amps
10.01.00 At 90% rated voltage 0.63
10.02.00 At 100% rated voltage 0.84

ALL INFORMATION CONTAINED IN THIS DOCUMENT IS CONFIDENTIAL AND THE PROPERTY OF TOSHIBA TRANSMISSION DISTRIBUTION SYSTEMS (INDIA) PVT. LTD., REPRODUCTION OF
THIS IN ANY FORM IS TO BE DONE WITH THE SPECIFIC PERMISSION OF THE ORGANIZATION”
S. No. Description Unit Bidder Detail Remarks
10.03.00 At 110% rated voltage 2.1
11.00.00 Maximum current density Amps/sq.mm
11.01.00 At 90% rated voltage 3
11.02.00 At 100% rated voltage 3
11.03.00 At 110% rated voltage 3
12.00.00 Maximum current density Amps/sq.mm
12.01.00 H.V Winding 3
12.02.00 L.V Winding 3
13.00.00 Withstand time without injury forSec.
Three phase dead short-circuit at
Terminal with rated voltage 3 Seconds(Thermal)
13.01.00 maintained on other side
Single phase short circuit at
terminal with rated voltage 3 Seconds(Thermal)
13.02.00 maintained on other side

Tank details mentioned


in sl.no.23.00.00
14.00.00 Details of Enclosure
14.01.00 Material NOT APPLICABLE
14.02.00 Thickness mm NOT APPLICABLE
14.03.00 Degree of protection NOT APPLICABLE
14.04.00 Padlocking provisions NOT APPLICABLE
15.00.00 Core
15.01.00 Type-core or shell Core
15.02.00 Core material CRGO
15.03.00 Thickness of lamination mm 0.23 Approx
15.04.00 Insulation of lamination Carlite
15.05.00 Maximum flux density (Web/M2)
at 90% of rated voltage. 1.52
at 100% of rated voltage. 1.69
at 110% of rated voltage. 1.86
16.00.00 Coils
16.01.00 Type of coil
a. H.V Spiral
b. L.V Foil
16.02.00 Conductor material Copper
16.03.00 Insulation material Kraft Paper
17.00.00 Bushings

17.01.00 Make JAIPUR Glass/ GENESIS


17.02.00 Type Porcelain
17.03.00 Reference standard IS - 2099 / 7421 HV/LV & LVN
17.04.00 Voltage class Kv 24 / 1 HV/LV & LVN
17.05.00 Current rating A 1000 / 2000 HV/LV & LVN
17.06.00 Creepage distance mm/KV 25
Power frequency (HV/LV &
17.07.00 50KV rms / 5 KV rms
Dry flashover voltage at 50 c/s LVN)
Power frequency (HV/LV &
17.08.00 50KV rms / 5 KV rms
Wet flashover voltage at 50 c/s LVN)
Approx per 1no (HV/LV &
17.09.00 20 / 11.5
Weight LVN)
Free space required for bushing
700
17.10.00 removal
18.00.00 Minimum clearance
HV:130, LV:25 Air clearances in
18.01.00 Between phase mm
cableboxes(As per
18.02.00 Between phase & earth mm HV:80, LV:20 IS:1180:2014)
19.00.00 Terminal connections
19.01.00 H.V CABLE BOX
19.02.00 L.V CABLE BOX
19.03.00 L.V Neutral BARE BUSHING
19.04.00 H.V Neutral NOT APPLICABLE
20.00.00 Marshalling box
Provided with removable gland
20.01.00 Plate/conduit knock out’ Removable gland Plate
20.02.00 Degree of protection IP 55
21.00.00 Terminal Blocks
21.01.00 Make ELEMEX
21.02.00 Type STUD
21.03.00 10% spare terminals furnished : YES
22.00.00 Tests
Routine test as per IS and other
Yes
22.01.00 tests as per specification

ALL INFORMATION CONTAINED IN THIS DOCUMENT IS CONFIDENTIAL AND THE PROPERTY OF TOSHIBA TRANSMISSION DISTRIBUTION SYSTEMS (INDIA) PVT. LTD., REPRODUCTION OF
THIS IN ANY FORM IS TO BE DONE WITH THE SPECIFIC PERMISSION OF THE ORGANIZATION”
S. No. Description Unit Bidder Detail Remarks
Core bolts are not
applicable.Core
insulation test will be
performed for 1 min.
22.02.00 Core bolt withstand voltage for 1 min.
23.00.00 Details of the tank
23.01.00 Type of tank Rectangular
23.02.00 Material Mild steel
Nominal thickness as per
5
23.03.00 Thickness of sides mm IS:1852
Nominal thickness as per
6
23.04.00 Thickness of bottom mm IS:1852
Nominal thickness as per
6
23.05.00 Thickness of cover mm IS:1852
Stainless steel for size
M12 & below and Hot
dip galvanized for size
above M12 size
23.06.00 Material of Nut & Bolt
24.00.00 Details of insulating oil
24.01.00 Approx. volume litres 1070
24.02.00 10% excess oil furnished Yes/No Yes
24.03.00 Oil conforms to Latest version of IS:335
24.04.00 Oil preservation system provided Yes,conservator provided
25.00.00 Details of wiring
25.01.00 Cable type PVC
25.02.00 Voltage grade V 1100
25.03.00 Conductor size Sq.mm 1.5 Minimum
Details of Trip & Alarm Contact
26.00.00 Ratings of OTI and WTI
26.01.00 Voltage Volt DC/AC V 220V DC / 250V AC
26.02.00 Rated/Making Current A 0.5 / 5.0 WTICT ratio 1067/2 A
27.00.00 Details of Conservator
27.01.00 Volume of Conservator litres 100 Approx total volume
Volume of oil between the highest
27.02.00 & lowest levels litres 80 Approx
Details of Approximate Overall
28.00.00 Dimension
28.01.00 Length mm 2285
28.02.00 Breadth mm 2750
28.03.00 Height mm 2365
Crane lift for un tanking core and
28.04.00 core assembly (including slings) mm 5200
29.00.00 Details of Approximate Weights
29.01.00 Core and coil kg 1875 Core & Coil assembly
29.02.00 Tank & fittings kg 1920
29.03.00 Oil kg 870
29.03.01 Oil L 1070
29.04.00 Total weight kg 4665
30.00.00 Details of Shipping Data
30.01.00 Weight of the heaviest package kg 4050
Dimension of the largest package 2300 x 2060 x 2250
30.02.00 (LxBxH) mm
30.03.00 Thickness of the radiator mm 1
31.00.00 Details of Radiators
31.01.00 Nos.of Radiatos No. 4
31.02.00 Nos.of fins per radiator No. 7
31.03.00 size of fin mm 520W x 900H
58 dB
32.00.00 Noise level (As per NEMA TR1)

NOTE :
1. All weights and Dimensions are subject to ±10% tolerance.
2. All the efficiencies and regulations are calculated at the nominal values of NLL, LL & %Z @ 75C.
3. Neutral CT ratio :1250/1-1A
Date: Prepared: Checked: Approved: