Installation Guide
Trademark Notices
GE, Hydran and are trademarks and service marks of General Electric Company.
Customer Service
For information on Grid Solution products, please contact:
GE Grid Solutions (UK) Ltd
Lissue Industrial Estate East
Unit 1, 7 Lissue Walk, Lisburn, United Kingdom BT28 2LU
Web: www.gegridsolutions.com/MD.htm
For help and support for your Hydran* M2-X, please contact the GE Customer Service
Center. Open 24 hours a day, 365 days a year.
Tel: +44 1785-250-070 (United Kingdom)
Tel: 1-800-361-3652 (United States and Canada)
Tel: +1 514-420-7460 (worldwide)
Email: GA.support@ge.com
Contents
Copyright Notice and Proprietary Rights ..................................................................... 2
Trademark Notices ....................................................................................................... 2
Customer Service ......................................................................................................... 2
3 INSTALLATION ...................................................................................... 17
General .............................................................................................................. 53
1 PRELIMINARY INFORMATION
Safety Warnings In Six Languages
[EN] (in English) WARNINGS:
• All procedures in this manual must be strictly adhered to.
• Any deviation from these could cause irreversible damage to the transformer being
monitored and/or the Hydran M2-X, and could lead to property damage, personal
injury and/or death.
• Installation and maintenance of the Hydran M2-X must be carried out by qualified
personnel only. Please advise station operator prior to maintenance. Working inside
the Hydran M2-X may trigger unwanted alarms due to parameter changes, power
shutdown, system rebooting or electrostatic discharge.
• For a maximum distance of 15 m (50 ft) from the power source, use a 2.08 mm2 (14-
AWG) cable and an overcurrent protection.
antes del mantenimiento. El trabajo dentro del Hydran M2-X puede accionar alarmas
indeseadas debido a los cambios del parámetro, parada de la energía, sistema que
reanuda o descarga electrostática.
• Para una distancia máxima de 15 m (50 pies) de la fuente de alimentación, utilice un
cable de 2,08 mm2 (14-AWG) y una protección contra las sobrecargas de corriente.
• Installation och underhåll av Hydran M2-X måste utföras av behörig personal. Råd var
god posterar operatören före underhåll. Funktionsduglig insida Hydran M2-X kan
starta oönskade parameterändringar för larm tack vare, driver avstängning,
systemomstart eller elektrostatisk urladdning.
• För ett maximalt avstånd på 15 m från kraftuttaget, använd 2,08 mm2 kabel (14-AWG)
och ett överströmsskydd.
1.3 Preface
This manual provides an overview of the installation for the Hydran M2-X. For
complete explanations on the installation process, see Chapter 5 in the Hydran M2-X
Instruction Manual.
− An installer
− An electrician
Please keep all documentation (model number, manuals, etc.) for reference and
warranty purposes.
A Table of Contents and a List of Figures are present at the beginning of the manual.
The Hydran M2-X Installation Guide (this manual) and the Hydran M2-X Instruction
Manual are in PDF format in the English/Manuals folder of the Hydran M2-X installation
CD. Hard copies of each manual can be purchased from GE.
1
The referenced paragraph covers the standard warranty period for Hydran M2-X devices. All other
elements of warranty and all other terms and conditions shall be governed under the relevant contract
of sale between GE and its direct customer. Specifically, in GE’s terms and conditions “Form EM104
(Global) Grid Solutions 28Oct2015” the warranty periods stated in Clause 5.2 for “Products” shall be
replaced by the above statement All other elements of Clause 5.2 and all other elements of “Form
EM104 (Global) Grid Solutions 28Oct2015” shall remain unaffected.
Software is warranted for ninety (90) days from delivery. GE represents and warrants
that any software and firmware covered by this manual is free from functional
deficiencies. If any functional deficiencies are discovered and are reported to GE within
the Warranty Period, GE agrees to use due diligence to correct such deficiencies within
30 days after receipt of such notification. Upon receiving such notice, GE may lend
telephone support or patches. If the reported deficiencies cannot be eliminated within
30 days, the Buyer may request, and GE shall then furnish, monthly status reports to the
Buyer regarding the progress of GE’s efforts to correct such functional deficiencies.
If Products covered by this manual do not meet the above warranties during the
applicable Warranty Period, the Buyer shall promptly notify GE in writing but not later
than 30 days and make the Products available promptly for correction. GE shall
thereupon correct any defect by, at its option, repairing the defective Products or
making available necessary replacement parts.
Any failure which is the basis for a warranty claim shall not be cause for extension of
the duration of the applicable Warranty Period. GE shall not be responsible for removal
or replacement of systems, structures or other parts of the Buyer’s facility. If a defect in
Products or part thereof cannot be corrected by GE’s reasonable efforts, the parties
shall negotiate an equitable adjustment in price with respect to such Products or part
thereof. All decontamination work necessary for the correction of defects shall be
performed by the Buyer at the Buyer’s expense. The condition of any tests shall be
mutually agreed upon and GE shall be notified of and may be represented at all tests
that may be made.
GE does not warrant Products or any repaired or replacement parts against normal
wear and tear, including that due to environment or operation, including excessive
operation at peak capability, frequent starting, type of fuel, detrimental air inlet
conditions, or erosion, corrosion or material deposits from fluids, or which have been
involved in an accident. The warranties and remedies set forth herein are further
conditioned upon:
• Proper storage, installation, operation and maintenance of the Buyer’s
equipment and conformance with the instruction manuals (including revisions thereto)
provided by GE and/or its subcontractors, as applicable
• Repair or modification pursuant to GE’s instructions or approval
The Buyer shall keep proper records of operation and maintenance during the
applicable Warranty Period. These records shall be kept in the form of log sheets and
copies shall be submitted to GE upon its request in connection with a warranty claim by
the Buyer. GE does not warrant any products or services of others designated by the
Buyer where such products or services are not normally supplied by GE.
The preceding paragraphs set forth the exclusive remedies for all claims based on
failure of or defect in Products covered by this manual, whether the failure or defect
arises before or during the applicable Warranty Period and whether a claim, however
instituted, is based on contract, indemnity, warranty, tort (including negligence) or civil
liability, strict liability or otherwise. The foregoing warranties are exclusive and are in
lieu of all other warranties and guarantees whether written, oral, implied or statutory.
NO IMPLIED STATUTORY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A
PARTICULAR PURPOSE SHALL APPLY.
Hazardous location (HazLoc) certification pertains to units with part number M2-
X-HZ only. The Hydran M2-X carrying the “HZ” designation is certified for use in
hazardous locations as identified by the branding on the product casing including the
serial number label as shown in Figure 1 and Figure 2. Once a HazLoc product is in
location, do not:
Note: In the case of a HazLoc certified product, please ignore additional appendices in
this document as they relate to a standard Hydran M2-X regarding servicing of parts, and
therefore are not applicable for a HazLoc certified product.
Suitable for use in Class I, Division II, Groups A, B, C and D Hazardous Locations, or
Nonhazardous Locations only.
For any servicing needs, the unit must be removed from the transformer and returned
to a GE service centre.
Table 1 lists other HazLoc relevant materials for the Hydran M2-X / Hydran M2-X H2
that are in contact with oil under normal-use operations.
Table 1: List of product materials in oil contact
Material Description
Free Machining Brass This is the constituent material of the sensor body.
VITON® 75 SHORE TYPE GLT Constituent material in V023, V029 & V030 O-rings
Glass to metal seal Glass to metal seal formed between sensor brass and
Humidity-in-oil sensor
DOW CORNING ® high vacuum grease Greased O-rings create appropriate seals
Teflon Chemfilm® DF100 PTFE This forms the outer layer of the oil-gas membrane in the
standard composite-gas sensor
Figure 3: Plastic Cap Must Remain in Place Until the Sensor Is Installed on the Valve
Figure 5: Do Not Block the Sensor’s Breathing Hole or Puncture the Breathing Hole’s Membrane
Figure 6: Do Not Install the Hydran M2-X at an Angle, Vertically or Using an Elbow
Figure 8: Do Not Install the Hydran M2-X on the Inlet Side of the Radiator Pump
Figure 9: Do Not Subject the Hydran M2-X or Its Sensor to High-Pressure Water Streams
Figure 10: Do Not Paint the Sensor or Clean It with Any Solvent
3 INSTALLATION
The Hydran M2-X is typically installed on a full-bore gate or ball valve of a
transformer. There are two cables:
• The Hydran M2-X’s power supply cable is passed in a flexible (recommended) or
rigid steel conduit toward a supervisory control and data acquisition (SCADA)
system.
• The alarm cable is passed in a flexible (recommended) or rigid steel conduit
toward a SCADA system.
Figure 11 illustrates some typical valve locations that can be found on a transformer.
These locations vary between transformers, but there are some valve locations on a
transformer where the oil circulation is much better due to the nature of a transformer’s
operation.
The circulation of oil is generally the same in all transformers — the natural
convection of the oil circulates from warm to cool as the transformer warms up. The
oil at the bottom is usually cooler than the top as it returns from the cooling system, as
illustrated in Figure 11.
circulation and is easily accessible for installation and taking oil samples
directly from the Hydran M2-X.
Location #D: Upper Filling Valve
Most transformers are equipped with an upper filling valve. This location
offers excellent oil circulation, but is not easily accessible and may require an
outage to install the Hydran M2-X.
Location #E: Top of Cooling System
Some transformers may have a valve that is mounted on the pipe that joins
the top tank of the transformer to the top of the cooling system. This location
offers an excellent circulation of oil; but is not easily accessible and may require
an outage to install the Hydran M2-X.
6 mm 84 mm
(0.25 in)
3/16-in Hex Key with 9-in 1/16-in and 5-32-in Spanner wrench
Blade & Cushion Grip T- Handle standard Hex (Allen) L-
Keys
#2 Phillips Screwdriver
Adjustable Pliers
or Wrench
Wire Stripper
Wire Cutter
CAUTION
Oil on sensor
CAUTION
Sensor cable
Figure 17: Mount the Sensor Manually onto the Valve and Tighten it, Using an Adjustable Wrench
O-ring
Figure 18: The Bleed Screw Must Be on Top, at the 12 O’clock Position
Note: Prior to installing the Hydran M2-X onto the transformer valve, it is
recommended to drain approximately 2-4 liters of oil from the valve. This clears any
contaminants and moisture that may have accumulated.
Figure 19: Opening the Valve and Purging the Air from the Sensor
WARNING
Active 2-wire
4-20mA Sensor
2-wire 4-20mA
Loop-powered
Sensor
3-wire, 4-20mA
Loop-powered
Sensor
SCADA
4-20 mA
Input
L = LINE
=
N
NEUTRAL Fuse Holder
= GROUND
Figure 30: Wiring of the AC Power Supply Terminal Block
4 SOFTWARE CONFIGURATION
User Interface Overview
For more information on the Hydran M2-X’s user interface, see Chapter 4 in the
Hydran M2-X Instruction Manual.
3 Context keys:
Purpose can change
according to the
screen content.
Purpose is displayed
on the bottom line of
LCD Display the display.
Context
Selected item: Key Messages
Use arrow keys to
select another item
on the screen.
Scrolling
Indicators
Select Setup
Press Enter
Press Enter
Select Services
Press Enter
Press Enter
Press OK
Note: After a Sensor Test, the sensor readings will not be available for two (2)
minutes.
Go to Main Menu
Select Setup
Press Enter
Press Enter
Press Enter
Press Enter
To next
page
Press Enter
Go to Main Menu
Select Setup
Press Enter
Press Enter
Select Identification
Press Enter
Change, as required:
Monitor ID
Power Station ID
Press Enter
Change, as required:
RS232 Baud Rate
RS485 Baud Rate
Notes:
• Each Hydran M2-X unit in the local network must be set to the same Power
Station ID and RS485 Baud Rate.
• Each Hydran M2-X in the local network must be set to a unique Monitor ID.
Go to Main Menu
Select Setup
Press Enter
Press Enter
Press Enter
Press Enter
To next
page
Select Configuration
Press Enter
Select Identification
Press Enter
Press Enter
Notes:
• Input Min is the lowest possible reading for this signal; this value corresponds
to 4 mA.
• Input Max is the highest possible reading for this signal; this value
corresponds to 20 mA.
• Repeat the above procedure for each analog input that is installed.
Go to Main Menu
Select Setup
Press Enter
Press Enter
Press Enter
Press Enter
To next
page
Select Configuration
Press Enter
Notes:
• Input Min is the lowest possible reading for this signal; this value will deliver a
current output corresponding to 4 mA.
• Input Max is the highest possible reading for this signal; this value will deliver
a current output corresponding to 20 mA.
• Repeat the above procedure for each analog output.
CAUTION
Gasket must be
properly in place
Commissioning
= DGA
To host computer
using Perception
software via either:
• Ethernet (wire
or fiber optic)
• Modem
interface.
• Or RS-485 link
to Hydran 201Ci
controller
CAUTION: The LEDs used for the fiber optic transmitter are
classified as IEC 60825-1 Accessible Emission Limit (AEL) Class
1. Class 1 devices are considered eye safe to the naked eye. Do
not view directly with optical instruments.
Figure 37: Local Communications with a Laptop Computer (for service only)
Figure 40: Wiring Details of the RS-485 between 2 or more Hydran M2-Xs
Figure 41: Wiring of the Supervisory Link between a Hydran M2-X and a Hydran 201Ci-1 Controller
Note: The Hydran 201Ci-1 Controller can only display the gas level measured by the
Hydran M2-X, not the moisture level.
Figure 42: Wiring of the Supervisory Link between a Hydran M2-X and a Hydran 201Ci-C Controller
Figure 43: Wiring of the RS-485 Link between a Hydran M2-X and a D25
General
GENERAL
ANALYTICAL PERFORMANCE
ELECTRONIC UNIT
MISCELLANEOUS
ENVIRONMENTAL CONDITIONS
Note: General Electric has made every reasonable attempt to ensure the completeness and
accuracy of these technical specifications. However, the information contained in these technical
specifications is subject to change without notice, and does not represent a commitment on the
part of General Electric.