1MRG033422 A en KEMA Type Test Certificate of Complete Type Tests 670 and 650 Series Version 2.2
1MRG033422 A en KEMA Type Test Certificate of Complete Type Tests 670 and 650 Series Version 2.2
Type Relion® 670 and 650 series, version 2.2 Serial No. See 2.2
Product(s) REB670, REC670, RED670, REG670, REL670, RER670, RES670 and RET670
REB650, REC650, RED650, REL650, RET650 and REQ650
ABB India Limited, Plot no. 4A, 5 & 6, Peenya 2nd Phase, Peenya Industrial
Estate, Bangalore - 560058. India *)
The object, constructed in accordance with the description, drawings and photographs incorporated in
this Certificate, has been subjected to the series of proving tests in accordance with the complete type
test requirements of
IEC 60255-1:2009
The results are shown in the record of proving tests and the oscillograms attached hereto. The values
obtained and the general performance are considered to comply with the above standard(s) and to
justify the ratings assigned by the manufacturer as listed on pages 5 and 6.
This Certificate applies only to the object tested. The responsibility for
conformity of any object having the same type references as that tested
rests with the Manufacturer.
*) as declared by the manufacturer
J.P. Fonteijne
Executive Vice President
KEMA Laboratories
Copyright: Only integral reproduction of this Certificate is permitted without written permission from DNV GL. Electronic copies as PDF or scan of this
Certificate may be available and have the status “for information only”. The sealed and bound version of the Certificate is the only valid version.
-2- 1418-18
INFORMATION SHEET
1 KEMA Type Test Certificate
A KEMA Type Test Certificate contains a record of a series of (type) tests carried out in accordance
with a recognized standard. The object tested has fulfilled the requirements of this standard and the
relevant ratings assigned by the manufacturer are endorsed by DNV GL. In addition, the object’s
technical drawings have been verified and the condition of the object after the tests is assessed and
recorded. The Certificate contains the essential drawings and a description of the object tested. A
KEMA Type Test Certificate signifies that the object meets all the requirements of the named
subclauses of the standard. It can be identified by gold-embossed lettering on the cover and a gold
seal on its front sheet.
The Certificate is applicable to the object tested only. DNV GL is responsible for the validity and the
contents of the Certificate. The responsibility for conformity of any object having the same type
references as the one tested rests with the manufacturer.
Detailed rules on types of certification are given in DNV GL’s Certification procedure applicable to
KEMA Laboratories.
TABLE OF CONTENTS
1 Summary ................................................................................................................... 4
4 Test arrangement...................................................................................................... 11
7 Photographs of printboards......................................................................................... 15
1 SUMMARY
By order of the client type tests according to IEC 60255-1 have been performed on the product family
of protection relays, Relion 670 and 650 series, version 2.2.
A risk assessment has been performed for the complete Relion 670 and 650 series, version 2.2. The
risk assessment shows what test on which IED need to be conducted to cover compliance to the
requirements for the whole product family as stated on page 1 of this certificate.
Therefore, type tests were done on various test objects of various IED types, all belonging to the
Relion 670 and 650 series, version 2.2. The required tests and the corresponding results of these type
tests are described in the following documents/reports:
Classification
IP-class, front side (with sealing strip) IP 54
IP-class, front side (without sealing strip) IP 40
IP-class sides IP 40
IP-class rear side (compression terminal) IP 20
IP-class ring lug terminal IP 10
Mechanical class 1
EMC emission class A
EMC immunity zone A
Overvoltage category II & III
Pollution degree 2
Version: 2
-6- 1418-18
1) Manufacturer declares that ZMFPDIS and ZMFCPDIS are fundamentally the same functions.
2) Manufacturer declares that T2WPDIF and T3WPDIF are fundamentally the same functions.
Version: 2
-7- 1418-18
The table underneath gives an overview of the test objects. More detailed information concerning the
individual test objects is present in the respective Reports of performance.
The client has submitted files containing drawings and documents of the IEDs and their modules.
These files are kept in the KEMA Laboratories project file.
KEMA Laboratories has made use of these drawings / documents during the execution of the tests.
KEMA Laboratories has not verified in detail that these drawings and documents represent the object
tested.
Version: 2
-9- 1418-18
Photographs of the objects tested are presented in the respective reports of performance.
Version: 2
-10- 1418-18
3 GENERAL INFORMATION
The tests were carried out without a representative of the client present.
Name Company
Martijn Dallinga DNV GL Netherlands B.V.,
Herman Koerts Arnhem, the Netherlands
Mihai Bivolaru
3.4 Subcontracting
The following tests were subcontracted to DEKRA Certification B.V., Arnhem, the Netherlands:
• measurement of radiated emission in accordance with IEC 60255-26 and CISPR22
• measurement of conducted emission in accordance with IEC 60255-26 and CISPR22
• radiated, radio-frequency and electromagnetic field immunity test in accordance with
IEC 60255-26 and IEC 61000-4-3
• contact performance tests in accordance with IEC 61810-1.
The following tests were subcontracted to Sebert Trillingstechniek, Bergschenhoek, the Netherlands:
• vibration response and endurance in accordance with IEC 60255-21-1
• shock response and withstand in accordance with IEC 60255-21-2
• bump test in accordance with IEC 60255-21-2
• seismic test in accordance with IEC 60255-21-3.
A table with measurement uncertainties is enclosed in this Certificate. Unless otherwise stated, the
measurement uncertainties of the results presented in this Certificate are as indicated in that table.
A detailed list with instruments used is enclosed in the respective Reports of performance.
Version: 2
-11- 1418-18
4 TEST ARRANGEMENT
A general test set-up is made by connecting the protective relay to a relay test set. The protective
relay is powered with rated auxiliary voltage. Currents and/or voltages are applied to the analogue
input module(s). If required status signals are applied to the binary input module(s). The operation
and resetting is monitored with the binary output modules operated with 24 VDC. The protective relay
is parameterized and monitored by means of the human machine interface and interface on the
display and LED's. Settings of the IED under test and information from the IED is handled by PCM600
software from ABB. Communication between IED and parameterizing and monitoring device is via
Ethernet communication.
Protective relay
Parameterizing and
Analog Binary monitoring device
input I/O
Current/voltage
amplifier
Analog Binary
output I/O
Monitoring device
Relay test set
Version: 2
-12- 1418-18
5 RISK ASSESSMENT
Clause 7.3 in IEC 60255-1 describes that testing a product which is part of a product family shall be
considered sufficient to cover the entire product family provided a documented risk assessment is
carried out to determine which type tests are valid and which tests need to be repeated on the rest of
the product family.
A detailed risk assessment for Relion 670 and 650 series, version 2.2 is enclosed in the Excel
document with file name 72126077 ABB_650_670 V2.2_risk_assessment dated 29 August 2018.
The risk assessment revealed that not all product variants of the Relion 670 and 650 series,
version 2.2 was required to be tested to still certify all product variants of the family and as stated on
page 1 of this certificate.
The table below gives an condensed overview of which test was done on what IED type.
Note
1: Only on RJ45 SFP port.
2: Test results of 670-series v 2.0 are re-used.
Version: 2
-14- 1418-18
6 COMMUNICATION PROTOCOLS
The communication protocols and the type of communication media, used for communication
with the equipment, shall be stated by the manufacturer. Protocols preferred are those with an
IEC standard. Conformance testing shall be performed to ensure that they comply with the
relevant standard or specification. See IEC 60255-1 subclause 6.6.
The results of communication protocol testing have been enclosed in the reports;
7 PHOTOGRAPHS OF PRINTBOARDS
PSM
BIM
Version: 2
-16- 1418-18
BOM
IOM
Version: 2
-17- 1418-18
SOM
MIM
Version: 2
-18- 1418-18
TRM
At the top ADM board with GTM, IRIG-B and SLM. NUM at the bottom.
Version: 2
-19- 1418-18
Version: 2
-20- 1418-18
CBM
UBM
Version: 2
-21- 1418-18
UBM
LHMI
Version: 2
-22- 1418-18
8 MEASUREMENT UNCERTAINTY
The measurement uncertainties in the results presented are as specified below unless otherwise
indicated.
The used EMC test generators are calibrated on an annual base and comply with the tolerances
mentioned in the applicable test standard.
Version: 2