M E D I U M VO LTAG E P R O D U C T
TJC 7.1
Indoor voltage transformers
2 T J C 7. 1 I N D O O R V O LTA G E T R A N S F O R M E R S
Parameters Values
Insulation voltages different from the above are Rated secondary voltages
the subject of an agreement between the manu- 100/√3 V; 110/√3 V – accuracy classes 0.2; 0.5; 1
facturer and the customer. (measuring winding) or 3P; 6P (protection wind-
ing). Other secondary voltages can also be sup-
If no a different value is required, the transform- plied on request.
ers are manufactured with a overvoltage factor of
1.9 x Un/8 hrs. One outlet of the primary winding, Rated voltages for open-delta connection
including the respective terminal is insulated 100/3 V; 110/3 V - class 6P.
from the earth to a level which corresponds to the Other voltages for open-delta connection can
rated insulation value. The other outlet of primary also be supplied based on customer requirement.
winding with terminal is earthed during the oper-
ation. Most of the transformers are equipped Rated frequency
with two secondary windings, the first one for ei- 50 Hz; 60 Hz.
ther measuring or protection purposes, the other
for being connected into an open-delta connec- Based on a discussion with the manufacturer the
tion in a three-phase system. One terminal of transformer can also be designed for two primary
each secondary winding and one of the open- voltage levels (with change over secondary side).
delta connected terminals have to be earthed
during the transformer operation. The trans- The transformers are manufactured conformably
former can be mounted in any position. The trans- to the requirements and recommendations of the
formers are fixed by four screws. The secondary following standards and regulations: IEC, VDE,
terminal board is covered with sealable cover IEEE, BS, GOST and CSN.
made of plastic material.
For marking of the voltage transformer outlets
see picture 01 a-e.
3
—
01 Marking of the
voltage transformers
outlets
a Single-pole insulated
transformer
b Single-pole insulated
transformer with a tap
c Single-pole insulated
transformer with two
secondary windings
d Single-pole insulated a b
transformer with two
secondary windings,
with one of which being
the auxiliary (residual)
winding
e Single-pole insulated
transformer with two
secondary, tapped
windings, with one
which being the auxiliary c
(residual) winding d e
—
01
Dimensional Drawing
— Weight: appr. 48 kg
TJC
TJC 7.1 7.1 Creepage Distance: 48kg
WEIGHT: 398 mm
300 M10
14
324
314
Pg16
M8
70
38
28
26 55
4
20
225
225
250
107
4x
150 30 14
300
393
Drawing n.
44204010
6 T J C 7. 1 I N D O O R V O LTA G E T R A N S F O R M E R S
Dimensional Drawing
— Weight: appr. 48 kg
TJC 7.1
TJC 7.1 Creepage Distance: 48kg
WEIGHT: 398 mm
300
45 M10
°
60
°
60
45
324
314
308
14
Pg16
M8
R1
70
55
5
38
26
28
4
213 207
150
107
150
178
250
4x
192
14
45 360 15
420
Drawing n.
1VL4200515R0101
— —
C O N TA C T U S NOTE We reserve all rights in this document and in
1VLC000535 Rev.2, en 2017.06.28
ABB s.r.o. We reserve the right to make technical the subject matter and illustrations con-
EPDS Brno changes or modify the contents of this docu- tained therein. Any reproduction, disclosure
Videnska 117, 619 00 Brno, ment without prior notice. With regard to to third parties or utilization of its contents -
Czech Republic purchase orders, the agreed particulars shall in whole or in parts - is forbidden without
Tel.: +420 547 152 021 prevail. ABB does not accept any responsibil- prior written consent of ABB.
+420 547 152 854 ity whatsoever for potential errors or possi-
Fax: +420 547 152 626 ble lack of information in this document. Copyright© 2019 ABB
E-mail: kontakt@cz.abb.com All rights reserved
www.abb.com