Environmental Health and Safety Electrical Safety Program and Permit
Environmental Health and Safety Electrical Safety Program and Permit
September 2016
Table of Contents
1.0 Purpose ................................................................................................................................................ 1
2.0 Scope ................................................................................................................................................... 1
3.0 Definitions ............................................................................................................................................ 2
4.0 Responsibilities ..................................................................................................................................... 7
5.0 Requirements ....................................................................................................................................... 8
6.0 Personal Protective Equipment .......................................................................................................... 13
7.0 Training ............................................................................................................................................... 21
8.0 Labeling ............................................................................................................................................... 22
9.0 Storage ............................................................................................................................................... 22
Appendix A Energized Electrical Work Permit ........................................................................................... 23
1.1 Purpose
The purpose of this program is to define the electrical safety requirements that are
necessary for the practical safeguarding of employees in their workplaces and is
divided into five major divisions as follows:
2.1 Scope
The scope of this program is to establish safety precautions for individuals working
on or near electrical circuits of 50 to 600 volts that are not building electrical service
entrance panels.
The safety-related work practices covered include persons working on, near, or with
the following Davidson College installations:
This procedure complies with OSHA Part 1910 Subpart S – Electrical, and NFPA
70E (2015) – Standard for Electrical Safety in the Workplace.
Arc Flash – the expanding arc or fireball emanating from the source of the arc. It
may be from a fraction of an inch to ten feet or more in size. It involves extremely
intense heat and may ignite anything combustible in its path. The duration is
usually a fraction of a second. An arc flash can reach temperatures of 35,000
degrees and can produce a concussive force of expanding gases and metal
plasma.
Arc Flash Boundary – When an arc flash exists, an approach limit at a distance from
a prospective arc source within which a person could receive a second degree burn if
an electrical arc flash were to occur.
Conductor – the physical elements that allow electricity to flow along a path, there
are three types:
(NFPA fine print note): Flame resistance can be an inherent property of a material,
or it can be imparted by a specific treatment applied to the material.
Ground Fault Circuit Interrupter (GFCI) – A device intended for the protection of
personnel that functions to de-energize a circuit or portion thereof within an
established period of time when a current to ground exceeds the values established
for a Class A device.
(NFPA Fine Print Note): Class A ground-fault circuit-interrupter trips when the
current to ground has a value in the range of 4 mA to 6 mA. For further
information, see UL 943, Standard for Ground-Fault Circuit Interrupters.
Insulated Tools – Tools tested and approved by the manufacturer for the rated
voltage or tools that are covered, surrounded or separated with a nonconductive
material in order to prevent or reduce the transfer of electricity. Insulated tools are
rated to a specific voltage.
Load- is any device that converts electrical energy to motion, light, heat, or sound.
Panelboard – a single panel or group of panel units designed for assembly in the
form of a single panel, including buses and automatic overcurrent devices, and
equipped with or without switches for the control of light, heat, or power circuits;
designed to be placed in a cabinet or cutout box placed in or against a wall, partition,
or other support; and accessible only from the front.
Power – is the rate of doing work or using energy and is represented by the letter P.
Power can be best described as the rate at which electrical energy is transferred by
an electrical circuit. It is measured in watts or kilowatts.
(a) Such persons shall also be familiar with the proper use of the special
precautionary techniques, personal protective equipment, including
arc-flash, insulating and shielding materials, insulated tools and
Single-Phase Power - single phase power refers to two wire Alternating Current
(AC) power circuits, typically with one power (leg) conductor and one neutral
conductor. In the US, 120VAC is the standard single phase voltage with one 120V
power (leg) conductor and one neutral conductor.
Voltage – is the electromotive force (EMF) or “push” that moves electrons along a
conductor. It is the amount of electrical pressure in a circuit and can be either
direct current (DC) or alternating current (AC). On an electrical schematic or
drawing, or in calculations, voltage is represented by the letter E.
4.1 Responsibilities
Supervisors – Supervisors will ensure that their Technicians have been trained in
the details of this procedure. When hazardous or unsafe conditions are brought
forward by Technicians, the Supervisor will address these deficiencies to the
appropriate individuals to correct them.
Supervisors are also responsible for completing the Davidson College - Energized
Electrical Work Permit, if work is performed on exposed electrical parts. (See
Appendix A). The supervisors should retain a copy of the permit on file for a period
of one year.
Qualified Persons – When electrical equipment is open and energized parts are
exposed, only qualified persons with the proper PPE are allowed to cross the Arc
Flash Protection Boundary and the Limited Approach Boundary. It is the
responsibility of the qualified person to prevent any unqualified or qualified person
without proper PPE from entering the work area.
Contractors- contractors must comply with the Contractor Safety Program and
determine any site specific information from their designated Project Manager.
5.1 Requirements
Work Procedures – If live exposed electrical parts are not placed in an electrically
safe work condition (i.e., for the reasons of increased or additional hazards or
infeasibility), work to be performed under this procedure shall be considered
energized electrical work and shall be performed by a Qualified Person. The
Qualified Person shall complete the Davidson College – Energized Electrical
Work Permit (See Appendix A). This permit must be completed by the
qualified employee and authorized by their supervisor.
In addition, safe work practices and PPE shall be used to protect employees who
might be exposed to the electrical hazards. Such work practices and PPE shall
protect employees from arc flash and from direct contact with live body parts, or
indirectly through some other conductive object. The work practices used shall be
suitable for the conditions under which the work is to be performed and for the
voltage level of the live parts.
(a) The Qualified Person is insulated or guarded from the live parts
(Insulating gloves compliant with Table 2), arc-face shield and
protective clothing are considered insulation only with regard to the
energized parts upon which work is being performed), OR
(b) The live part is insulated from the employee and from any other
conductive object at a different potential.
Limited Approach Boundary
Restricted
Nominal Exposable Exposed Fixed Approach
System Voltage Movable Circuit Part Boundary
Range Phase to Conductor
Phase Voltage
Overhead Lines – if work is to be performed near overhead lines, the lines shall be
de-energized and grounded, or other protective measures shall be provided before
work commences. If the lines are to be de-energized, arrangements shall be made
with the person or organization that operates or controls the electric circuits involved
to de-energize and ground them. If protective measures, such as guarding,
isolating, or insulating are provided, these precautions shall prevent employees from
contacting such lines directly with any part of their body or indirectly through
conductive materials, tools, or equipment.
Portable Ladders – Portable ladders shall have nonconductive side rails if they are
used where the employee or the ladder could contact exposed energized parts.
Insulated Tools and Equipment – Employees shall use insulated tools and
equipment when working inside the limited approach boundary. The insulated tools
shall be protected from damage and inspected prior to use. Fuse or fuse holder
handling equipment, insulated for the circuit voltage, shall be used to remove or
install a fuse if either of the fuse terminals are energized.
Test instruments/equipment and all associated test leads, cables, power cords,
probes and connectors shall be visually inspected for external defects and damage
before each time the equipment is used. If there is a defect or evidence of damage
that might expose an employee to injury, the defective or damaged item shall be
immediately removed from service, and no employee may use it until repairs and
tests necessary to render the equipment safe have been made.
Test instruments/equipment and their accessories shall be rated for the circuits and
equipment to which they will be connected and shall be designed for the
environment in which they will be used.
(1) Approved GFCI protection shall be provided and used for all 125 volt (nominal)
single phase 15, 20 and 30 amp receptacle outlets that are not part of the
permanent wiring of the building or structure. GFCIs shall be used whenever
employees are working on a construction project, working with temporary wiring
or working in wet areas. Extension cords used for construction or used in wet
applications shall be equipped with Ground Fault Circuit Interrupters (GFCI)
protection, unless a breaker, receptacle, or portable GFCI unit provides GFCI
protection.
Employees working in areas where energized exposed live parts and/or equipment
are within the Limited Approach Boundary shall wear protective clothing and other
personal protective equipment in accordance with this procedure and as indicated by
PPE Categories in Table 3. The PPE and clothing requirements may be determined
by conducting a Flash Hazard Analysis or by using the requirements presented in
the following table:
Table 130.7 (C)(15)(A)(a) Arc Flash Hazard Identification for Alternating Current (ac)
and Direct Current (dc) System
Task Equipment Condition* Arc Flash
PPE
Required
Reading a panel meter while operating Any No
a meter switch.
Normal operation of a circuit breaker All of following: No
(CB), switch, contactor or starter.
The equipment is properly installed.
The equipment is properly maintained.
All equipment doors arc closed and
secured.
All equipment covers are in place and
secured.
There is no evidence of impending failure.
*The phrase properly installed, as used in this table, means that the equipment is installed in accordance with
applicable industry codes and standards and the manufacturer’s recommendations. The phrase properly
maintained, as used in this table, means that the equipment has been maintained in accordance with the
manufacturer’s recommendations and applicable industry codes and standards. The phrase evidence of
impending failure, as used in this table, means that there is evidence of arcing, overheating, loose or bound
equipment parts, visible damage, deterioration, or other damage.
Parameter: Maximum of 25 kA
short circuit current available;
maximum of 0.03 sec (2 cycles)
fault clearing time; working
distance 455 mm (18 in.)
Panelboards or other 2 900 mm
equipment rated >240 V and up (3 ft.)
to 600 V.
Parameter: Maximum of 25 kA
short circuit current available:
maximum of 0.03 sec (2 cycles)
fault clearing time; working
distance 455 mm (18 in.)
600-V class motor control 2 1.5 mm
centers (MCC’s) (5 ft.)
Parameter: Maximum of 65 kA
short circuit current available;
maximum of 0.03 sec (2 cycles)
fault clearing time; working
distance 455 mm (18 in.)
600-V class motor control 4 5.1 m
centers (MCC’s) (14 ft)
Parameter: Maximum of 42 kA
short circuit current available:
maximum of 0.03 sec (20
cycles) fault clearing time;
working distance 455 mm (18
in.)
600-V switchgear (with power 4 6m
circuit breakers or fused (20 ft.)
switches) and 600 V class
switchboards
Parameter: Maximum of 35 kA
short circuit current available;
maximum of up to 0.5 sec (30
cycles) fault clearing time;
working distance 455 mm (18
in.)
Other 600-V class (277 V 2 1.5 m
through 600 V, nominal) (5 ft.)
equipment.
Parameters: Maximum of 35 kA
short circuit current available;
maximum of up to 0.24 sec (15
cycles) fault clearing time;
working distance 910 mm (36
in.)
Parameters: Maximum of 35 kA
short circuit current available;
maximum of up to 0.24 sec (15
cycles) fault clearing time;
working distance 910 mm (36
in.).
Other equipment 1 kV through 4 12 m
15 kV (40 ft)
Parameters: Maximum of 35 kA
short circuit current available;
maximum of up to .24 sec (15
cycles) fault clearing time;
working distance 910 mm (36
in)
Note: For equipment rated 600 volts and below, and protected by upstream current limiting fuses or current
limiting circuit breakers sized at 200 amperes, the arc flash PPE category can be reduced by one number but
not below arc flash PPE category 1.
Note: Apparel that can be expected to be exposed to electrolyte must meet both of the following conditions:
(1) Be evaluated for electrolyte protection in accordance with ASTM F1296, Standard Guide for Evaluating
Chemical Protective Clothing
(2) Be arc-rated accordance with ASTM F1891, Standard Specification for Arc Rated and Flame Resistant,
Rainwear, Or equivalent.
Using Flame Resistant Clothing - Where it has been determined that work will be
performed in areas where there are electrical hazards, Flame Resistant (FR)
clothing and PPE, shall be used by employees working within the Arc Flash
Protection Boundary. Clothing made from synthetic materials such as acetate,
nylon, polyester, rayon, or cotton blends containing these materials are prohibited.
Logos and labels shall not be affixed to clothing.
NOTE: The PPE requirements contained in this section are designed to protect an
employee from arc-flash and shock hazards. Electrical PPE will limit a burn to the
skin to a curable burn (second degree or less). Because of the explosive nature of
some catastrophic electric failures, physical trauma may occur. The potential for
physical trauma injuries should be considered prior to the start of the project.
Objects that could cause injury in an explosive arc flash should be removed or
padded.
7.1 Training
This training should include the identification of electrical hazards, potential injuries
and special precautionary measures that should be taken in order to minimize the
possibility for injury. Training shall consist of classroom training, on the job training,
or a combination of both. The degree of training shall be determined by the risk to
the employee and the job task assigned. Retraining shall be provided anytime there
is a change in the process and when an audit or incident investigation indicates a
need. Retraining shall be performed at intervals not to exceed three years. All
training shall be documented and retained for the duration of employment.
8.1 Labeling
9.0 Storage
Working space in front of electrical equipment shall be free from storage. The
space should be kept clear to permit safe operation and maintenance of electrical
equipment.
Description of Circuit/Equipment:
Workers must be
Ensure Shock trained, Boundary
Protection qualified, and
of athave
leastfull
10 knowledge
feet unless of equipment.
specified on electrical equipment.
Ensure Arc Flash Protection Boundary of at least 4 feet unless specified on electrical equipment.
All Natural Fiber Outerwear is being worn
Fire Retardant Clothing is being worn
Required Additional PPE:
Use
YES safetyNO
signs,Doattendants, or other
you agree the means
work can of barricading
be completed safely?to restrict the access of unqualified persons from the work area
AUTHORIZED WORKERS that understand and agree to the above:
Printed or Signature(s) Printed or Signature(s) & Date(s):
typed & Date(s): typed
name(s): name(s):
APPROVAL(S) TO PERFORM THE WORK WHILE ELECTRICALLY ENERGIZED:
Departmental Supervisor: Date:
Departmental Manager: Date:
Forward a completed copy of this form to the EH&S Office.