6MB Telecontrol System: 6MB552 Compact Remote Terminal Unit
6MB Telecontrol System: 6MB552 Compact Remote Terminal Unit
6MB Telecontrol System: 6MB552 Compact Remote Terminal Unit
Application range
The 6MB552 compact remote terminal
unit is a member of the SINAUT LSA
substation control and protection product
range. It is dimensioned for medium
volumes of process data.
For telecontrol applications with smaller
or larger volumes of process data, the
following SINAUT LSA products are avail-
able:
6MB551 station control unit for
medium to high volumes of process
data
6MB553 minicompact remote terminal
unit for low volumes of process data.
The central link to the switchyard is
parallel. A terminal block can be
interposed. Numerical protection units
and the distributed input/output units of
the 6MB system can also be connected
via fibre optic cable (see Fig. 2).
Design and operation (cont’d) Analog measured values are acquired Functions
with the AE and AR analog input The standard version of the compact re-
Via the MD modem module the compact modules. The AE module has 32 analog mote terminal unit performs the typical
unit can be connected in a simple and inputs connected to common potential functions of the station control level:
compact way to the higher and lower via multiplexer and the AR module has 16
telecontrol levels. Additional external Communication with the higher
galvanically isolated inputs. These inputs
data transmission equipment is not are applied to 4 independent analog–to– telecontrol level with adaptation to the
required. The MD module uses the digital converters via relay multiplexer. various communication procedures
optional second telecontrol interface of Thus, the AR module is capable to and message structures
the FP processor module and isolates it sample up to 4 analog input quantities Indication acquisition and processing
to 2 kV. simultaneously. For both modules, Analog value acquisition and
The MD module can be equipped with a various current and voltage measuring processing
receiver for the DCF77 radio time signal ranges from 1.5 to 24 mA DC or 1 to
Metered value acquisition and
receiver (Mainflingen) that ensures 10 V DC and a 1–V–AC measuring range
with true rms value calculation are processing
precise time synchronization throughout
available (see ”Technical data”). The Communication with distributed
the system.
standard measuring range of the modules input/output units and numerical
Input/output modules is 0 to 2.5/5/10/20 mA. Analog values protection devices of the 6MB system
are acquired with 11 significant bits and via serial interfaces.
The central link with the process makes one sign bit.
use of several input and output modules The functions are described in detail in
each with its own microcontroller. All Commands are output to the process separate catalog sheets (see ”User
input and output lines of these modules using the BA command output module. functions” in the index of Siemens
are isolated to 2 kV. The BA module is able to output thirty– catalogs on page 6).
two 1–pole commands or sixteen 2–pole Some other tasks are:
The DE digital input module acquires up commands. As an alternative, bit pattern
to 32 single indications from the process Continuous and complete self– and
output is also possible. Then, the number
or an equivalent number of double system–monitoring
of commands is lower. By using the BF
indications, transformer tap positions, bit command enable module already con- Support of test and diagnostics
patterns or metered values. The module tained in the basic version it is possible functions
itself performs some pre–processing, to output thirty–two 1 –pole commands
such as real–time assignment with 1–ms (2–pole A) or sixteen 2–pole commands Configuration
resolution and detection of contract (2–pole B) with a BA module.
chattering. The 32 single digital inputs In the configuration phase, inputs,
consist of 4 isolated groups with 8 digital Parameterizable, the command output equipment and module requirements
inputs each. Each group has its own circuit of the BF module can be checked must be defined.
input to which the indication voltage is by a switching current check and the The following table gives an overview of
applied as a reference. Due to dynamic circuit can be tested for signal isolation the number of inputs and outputs that
adjustment to varying signal voltages, the before command output. This check and can be achieved with various I/O mod-
reference voltage input allows very the distribution of command output and ules.
reliable indication acquisition. enabling over two different modules
Signalling–circuit voltage failure is ensures much greater protection from
incorrect output. The check function on Type Single Indica- Analog
detected. Using optocouplers, the circuit com- tions inputs
for indication acquisition is isolated from the modules also detects wire–breaks mands
the other modules to 2 kV. Malfunctions and wiring errors that might otherwise
in the input circuits (incl. optocouplers) lead to serious switching errors. In case 6MB552/A 32 + 81) 64 + 81) 32
are detected reliably and can be of errors, the associated switching
operations are suppressed and the 6MB552/B 32 + 81) 32 + 81) 162)
transmitted to the central processor
module. incorrect operating state is signalled to 6MB552/C 32 + 81) 96 + 81) –
the higher level.
The BF module also has eight 1–pole 6MB552/D 81) 128 + 81) –
inputs and outputs with which local
operating states, such as the position of 1) Limited functionality (for local indications +
commands)
the remote/local switch can be moni-
2) Without grouping of inputs with common
tored. Local commands for LEDs or potential
acoustic signals, for example, can be out-
put as well. The possible combinations of I/O
modules are given in the ”Selection and
ordering data” table on page 5.
Requirements not specified here can also
be implemented as long as the total
permissible power loss is observed.
Further technical details, in particular for
the interfaces and inputs/outputs
(number, isolation) are given in the
”Technical data”.
Parameterization components and units in the switchyard, All telecontrol message assignments
The parameter set is created using the the system is ready for operation. To and transmission procedures.
LSATOOLS PC program package. The use make changes and expansions is easy The parameter lists for each function and
of LSATOOLS ensures data consistency with LSATOOLS. their setting options are given in the
throughout planning, configuration, para- The parameterization data includes: catalog sheets ”User functions”
meterization to automatic documentation Switchyard configuration and topology
and subsequent changes and expansions. Diagnostics
Configuration of the compact unit
The entire switchyard–specific configura- The user–friendly PC program LSADIAG
Connection to the switchyard:
tion of the compact remote terminal unit can be used for system diagnostics. It is
is stored as a parameter set in a non–vol- acquisition, processing and output used to read out lists (event list, alarm
atile memory of the FP processor mod- parameters for each switchyard list, protection alarm list, system
ule. Entering the data adapts the com- information item and command messages), run a trace, set metered
pact unit to the specific characteristics Specification of the numerical protec- values and time and date and display the
and requirements of the switchyard. tion devices connected via serial inter- module configuration. To run LSADIAG on
Parameter loading is efficiently supported face a PC, the OS/2 operating system and a
by the CB communication module in the Configuration of the telecontrol CB communication module are required.
PC. After system boot with autonomous connections to and from the compact
distribution of the parameters to all unit
Technical data
Telecontrol interfaces Number of network control centres or substations 1
that can be connected
Interface type Interface 1: V.24/V.28 (RS 232 C), isolated, up to
19.2 baud
Interface 2: MDV21 modem, 300 baud
Interfaces for bay unit connection Number of bay units that can be connected Up to 7 (via MD module)
Interface type Fibre optic
Transmission rate 9.6 or 19.2 kbaud
Transmission protocol IEC 870–5, parts 1 and 2
Input and output modules for central process link DE digital input module
Number of inputs 32, in groups of 8 with common ground
Time resolution for indication acquisition 1 ms
Hardware filter time 2 to 64 ms
Indication voltage 19.2 to 75 V DC or 88 to 275 V DC
Input current 0.4 to 1.56 mA
Electrical tests Isolation according to IEC 255–5 or DIN VDE 0435 part 303, 2 kV AC, for 1 min
(100% test/type test)
Surge voltage according to IEC 255–5 DIN VDE 0435 part 303, 5 kV, 1.2 / 50 s
(type test)
EMC tests HF interference test according to DIN IEC 255–22–1, 1 MHz attenuated, rate 400/s
test class III, (type test) 2.5 kV longitudinal voltage
1 kV transverse voltage
Transient interference / burst according to IEC 801–4, 2 kV, for power connections
test class III (type test) 1 kV for I/O lines
5/50 ns, burst 15 ms, 15 kHz
Electromagnetic fields according to DIN IEC 255–22–3, at least 15 V/m at 27, 68.05, 164.87 and
test class III (type test) 459.55 MHz
Documentation
Manual for the 6MB552 compact unit C73000–G1876–C7
Function description of the IEC 870–5–101 telecontrol profile for the network control centre link E50400–U0491–U500–A2–7600
Network control – telecontrol system SINAUT 8–FW message formats description E50400–U0055–U500–A2–7600
Supply
We supply the unit from the factory in a
7XP20 housing. It contains an FP module
and the SV power supply with an
integrated line filter and fuse. Four
predefined standard module
complements can be ordered using the
order numbers given above. If you
require a different module complement,
you must order the I/O modules
separately.
MD module and FO modules are supplied
as specified in the order number.
1) 5 standard plug–in stations (SPS) are free: Not all combinations of modules are permissible (observe power loss). Clarify each case with EV S E.
2) One telecontrol interface is assigned for the field link. Only in conjunction with 2 telecontrol interfaces V.24/V.28 (RS 232 C) and MD V.21 modem (11th
position = 4). Software functionality ”field link” requires software version V9 (16th position = 5).
3) Only in conjunction with 2 telecontrol interfaces V.24/V.28 (RS 232 C) and MDV21 modem (11th position = 4).
Index of Siemens catalogs for SINAUT LSA substation control and protection
Title of catalog expected Catalog Order No.
publishing date abbreviations
6MB station control system 6MB522 Input/output unit LSA 1.1.1 E50001–K5701–A111–A2–7600
6MB523 Input/output unit LSA 1.1.2 E50001–K5701–A121–A1–7600
6MB511/512 Substation control master unit and LSA 1.1.3 E50001–K5701–A131–A2–7600
7SW511/512 Relay data concentrator
6MB520 and 6MB521 Input/output units LSA 1.1.4 E50001–K5701–A141–A1–7600
6MB513/514 Compact control master unit 10/1995 LSA 1.1.6 E50001–K5701–A161–A1–7600
6MB524 Compact Input/Output Unit 02/1996 LSA 1.1.7 E50001–K5701–A171–A1–7600
6MB telecontrol system 6MB551 Station control unit LSA 1.2.1 E50001–K5701–A211–A1–7600
6MB552 Telecontrol compact unit 08/1995 LSA 1.2.2 E50001–K5701–A221–A1–7600
6MB5530–0 Minicompact remote terminal unit 08/1995 LSA 1.2.3 E50001–K5701–A231–A1–7600
6MB5530–1 Minicompact remote terminal unit 08/1995 LSA 1.2.4 E50001–K5701–A241–A1–7600
for cable shield communication
Telecontrol processor module SINAUT LSA system bus Digital input module
FP DE
RxD Test and diagnostics
TxD V.24 32 single indications
interface
per module
RxD
TxD Telecontrol interface for
CTS V.24
VFT/modem connection
RTS Command enable module
BF
8 local indications
8 local commands
Command enable
Switching current check
Modem module
MD
Command output module
DCF77 with time signal
BA
receiver module
a 32 single commands
b Modem
per module
RxD 1
TxD FO Analog input module
AE/AR
Fibre–optic bay link 32/16 analog values
7 per module
RxD
TxD FO
Fig. 3
Connection diagram and data flow for the 6MB552 compact remote terminal unit, overview
3
1
...
...
3
16
VM
V Ref
6
1
2
3
7 4
5
6
7
8 8
...
VC+
VC–
Command output
V Ref
EN+ and switching
EN– current check 25
26
27
28
29
SSK1 Switching current 30
SSK2 check for external 31
enable relay 32
Fig. 4
Connection diagram and data flow for the 6MB552 compact remote terminal unit, BF, BA, and DE modules
...
32 ...
CP
4
...
...
13
14
15
16
Fig. 5
Connection diagram and data flow for the 6MB552 compact remote terminal unit, modules AE and AR
Dimension drawings in mm
5.4
panel
Bus cover
0,3
+
245+1
1) 2)
266
244
255.8
Diam. 6
Fig. 6
6MB552 compact remote terminal unit in the 7XP20 housing (for switchboard and cabinet mounting)
Export Regulations
In accordance with present German and permissible without the approval of the Subject to change.
US export regulations export licences (da- relevant authorities except where current Relevant are the criteria stated in the
ted 07.95) are not required for the prod- German export regulations contain coun- delivery note and in the invoice.
ucts listed in this catalog. try–specific restrictions. An export licence may be required due
Export and re–export are therefore The following criteria for export apply: to country–specific application of the
Telecontrol compact unit: product.
AG: N, EC: D, ECCN: 3A96G
AD–modul:
AG: N, EC: D, ECCN: 4A96G
Other: AG: N, EC: N
Trademarks Dimensions
All product designations used are trade- All dimensions in this catalog are given in
marks or product names of Siemens AG mm.
or of suppliers.
Responsible for
Technical contents: Klaus–Dieter Scheffer,
Siemens AG, EV S T14, Nürnberg
General editing: Claudia Kühn–Sutiono,
Siemens AG, EV MK 2, Erlangen
Power
Transmission
and Distribution
12
Siemens Aktiengesellschaft Order No.: Siemens
E50001-K5701–A221-A1–7600
LSA 1.2.2 . August 1995
Printed in the Federal Republic of Germany
KG K 0895 3.0 SC 12 En 361 378