6MB Telecontrol System: 6MB552 Compact Remote Terminal Unit

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 12

6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Application range
The 6MB552 compact remote terminal
unit is a member of the SINAUT LSA
substation control and protection product
range. It is dimensioned for medium
volumes of process data.
For telecontrol applications with smaller
or larger volumes of process data, the
following SINAUT LSA products are avail-
able:
 6MB551 station control unit for
medium to high volumes of process
data
 6MB553 minicompact remote terminal
unit for low volumes of process data.
The central link to the switchyard is
parallel. A terminal block can be
interposed. Numerical protection units
and the distributed input/output units of
the 6MB system can also be connected
via fibre optic cable (see Fig. 2).

Design and operation


The 6MB5520 compact unit is supplied in Fig. 1
a 7XP20 housing. The modules are 6MB552 compact remote terminal unit
plugged into slots behind a common front
panel, to ensure good EMC characteris-
tics. The modules are connected to the Network control centre
SINAUT LSA standard bus via their upper
backplane connector.
The functions of the compact unit are
distributed over several modules. The FP
telecontrol processor module contains
the 80386 processor, the memory for the WT
program code and parameters and the
following interfaces that are serviced by
Telecontrol channel
a separate, very powerful Motorola
68302 communication processor: Station
control level
 A V.24/V.28 (RS 232C) interface WT
isolated to 2 kV
 7 interfaces for connecting numerical
input/output and protection units via Fibre optic cable
fibre optic cables, with an alternative
Compact remote
use as second telecontrol interface
terminal units
 An interface for loading system
1 2 ....... 7
software, parameters and for test and
diagnostics functions.
The FP module performs the following Terminal block
tasks: Bay control Protection &
 Management of the 16 bit system bus level I/O devices
Interposing relays, transducers ...
 Communication via serial interface
with higher telecontrol level and bay
control units Existing switchyard Extended switchyard
 Input and management of the parame-
terization data
Fig. 2
 Loading all system modules and any Extension of the compact unit with input/output unit and protection devices
distributed bay control units with the
configuration data  Independent performance of system  Coordination and monitoring of all
boot function units of the compact unit
 Coordination of test and diagnostic  Management of the station and
functions between the PC program system image
LSADIAG and the system  Date and time keeping.
(Continued on page 2)

Siemens LSA 1.2.2 . August 1995  Siemens AG 19951


6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Design and operation (cont’d) Analog measured values are acquired Functions
with the AE and AR analog input The standard version of the compact re-
Via the MD modem module the compact modules. The AE module has 32 analog mote terminal unit performs the typical
unit can be connected in a simple and inputs connected to common potential functions of the station control level:
compact way to the higher and lower via multiplexer and the AR module has 16
telecontrol levels. Additional external  Communication with the higher
galvanically isolated inputs. These inputs
data transmission equipment is not are applied to 4 independent analog–to– telecontrol level with adaptation to the
required. The MD module uses the digital converters via relay multiplexer. various communication procedures
optional second telecontrol interface of Thus, the AR module is capable to and message structures
the FP processor module and isolates it sample up to 4 analog input quantities  Indication acquisition and processing
to 2 kV. simultaneously. For both modules,  Analog value acquisition and
The MD module can be equipped with a various current and voltage measuring processing
receiver for the DCF77 radio time signal ranges from 1.5 to 24 mA DC or 1 to
 Metered value acquisition and
receiver (Mainflingen) that ensures 10 V DC and a 1–V–AC measuring range
with true rms value calculation are processing
precise time synchronization throughout
available (see ”Technical data”). The  Communication with distributed
the system.
standard measuring range of the modules input/output units and numerical
Input/output modules is 0 to 2.5/5/10/20 mA. Analog values protection devices of the 6MB system
are acquired with 11 significant bits and via serial interfaces.
The central link with the process makes one sign bit.
use of several input and output modules The functions are described in detail in
each with its own microcontroller. All Commands are output to the process separate catalog sheets (see ”User
input and output lines of these modules using the BA command output module. functions” in the index of Siemens
are isolated to 2 kV. The BA module is able to output thirty– catalogs on page 6).
two 1–pole commands or sixteen 2–pole Some other tasks are:
The DE digital input module acquires up commands. As an alternative, bit pattern
to 32 single indications from the process  Continuous and complete self– and
output is also possible. Then, the number
or an equivalent number of double system–monitoring
of commands is lower. By using the BF
indications, transformer tap positions, bit command enable module already con-  Support of test and diagnostics
patterns or metered values. The module tained in the basic version it is possible functions
itself performs some pre–processing, to output thirty–two 1 –pole commands
such as real–time assignment with 1–ms (2–pole A) or sixteen 2–pole commands Configuration
resolution and detection of contract (2–pole B) with a BA module.
chattering. The 32 single digital inputs In the configuration phase, inputs,
consist of 4 isolated groups with 8 digital Parameterizable, the command output equipment and module requirements
inputs each. Each group has its own circuit of the BF module can be checked must be defined.
input to which the indication voltage is by a switching current check and the The following table gives an overview of
applied as a reference. Due to dynamic circuit can be tested for signal isolation the number of inputs and outputs that
adjustment to varying signal voltages, the before command output. This check and can be achieved with various I/O mod-
reference voltage input allows very the distribution of command output and ules.
reliable indication acquisition. enabling over two different modules
Signalling–circuit voltage failure is ensures much greater protection from
incorrect output. The check function on Type Single Indica- Analog
detected. Using optocouplers, the circuit com- tions inputs
for indication acquisition is isolated from the modules also detects wire–breaks mands
the other modules to 2 kV. Malfunctions and wiring errors that might otherwise
in the input circuits (incl. optocouplers) lead to serious switching errors. In case 6MB552/A 32 + 81) 64 + 81) 32
are detected reliably and can be of errors, the associated switching
operations are suppressed and the 6MB552/B 32 + 81) 32 + 81) 162)
transmitted to the central processor
module. incorrect operating state is signalled to 6MB552/C 32 + 81) 96 + 81) –
the higher level.
The BF module also has eight 1–pole 6MB552/D 81) 128 + 81) –
inputs and outputs with which local
operating states, such as the position of 1) Limited functionality (for local indications +
commands)
the remote/local switch can be moni-
2) Without grouping of inputs with common
tored. Local commands for LEDs or potential
acoustic signals, for example, can be out-
put as well. The possible combinations of I/O
modules are given in the ”Selection and
ordering data” table on page 5.
Requirements not specified here can also
be implemented as long as the total
permissible power loss is observed.
Further technical details, in particular for
the interfaces and inputs/outputs
(number, isolation) are given in the
”Technical data”.

2 Siemens LSA 1.2.2 . August 1995


6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Parameterization components and units in the switchyard,  All telecontrol message assignments
The parameter set is created using the the system is ready for operation. To and transmission procedures.
LSATOOLS PC program package. The use make changes and expansions is easy The parameter lists for each function and
of LSATOOLS ensures data consistency with LSATOOLS. their setting options are given in the
throughout planning, configuration, para- The parameterization data includes: catalog sheets ”User functions”
meterization to automatic documentation  Switchyard configuration and topology
and subsequent changes and expansions. Diagnostics
 Configuration of the compact unit
The entire switchyard–specific configura- The user–friendly PC program LSADIAG
 Connection to the switchyard:
tion of the compact remote terminal unit can be used for system diagnostics. It is
is stored as a parameter set in a non–vol- acquisition, processing and output used to read out lists (event list, alarm
atile memory of the FP processor mod- parameters for each switchyard list, protection alarm list, system
ule. Entering the data adapts the com- information item and command messages), run a trace, set metered
pact unit to the specific characteristics  Specification of the numerical protec- values and time and date and display the
and requirements of the switchyard. tion devices connected via serial inter- module configuration. To run LSADIAG on
Parameter loading is efficiently supported face a PC, the OS/2 operating system and a
by the CB communication module in the  Configuration of the telecontrol CB communication module are required.
PC. After system boot with autonomous connections to and from the compact
distribution of the parameters to all unit

Technical data
Telecontrol interfaces Number of network control centres or substations 1
that can be connected
Interface type Interface 1: V.24/V.28 (RS 232 C), isolated, up to
19.2 baud
Interface 2: MDV21 modem, 300 baud

Interfaces for bay unit connection Number of bay units that can be connected Up to 7 (via MD module)
Interface type Fibre optic
Transmission rate 9.6 or 19.2 kbaud
Transmission protocol IEC 870–5, parts 1 and 2

Test and diagnostics interface Interface type V.24/V.28 (RS 232 C)


Transmission rate Up to 64 kbaud
Transmission protocols IEC 870–5, parts 1 and 2

Inputs and outputs for local signals (on the BF Inputs


module) Number 8 single indications (common ground)
Isolation against supply voltage 2 kV AC rms or 2 850 V DC
Time resolution for indication acquisition 1 ms
Indication voltage 19.2 to 75 V DC, 88 to 275 V DC
Input current 0.4 to 1.56 mA
Outputs
Number 8 changeover switches
Switching voltage 19.2 to 75 V DC, 88 to 275 V DC on request
Max. break power (resistive load) VB = 24 V : 100 W, VB = 40 V : 65 W,
VB = 60 V : 55 W, VB = 75 V : 40 W,
Max. break power (inductive load, L/R <7 ms) VB = 24 V : 60 W, VB = 48 V : 30 W,
VB = 60 V : 20 W, VB = 75 V : 17 W
Contact life at max. resistive load >105 switching cycles
at min. resistive load 107 switching cycles

Input and output modules for central process link DE digital input module
Number of inputs 32, in groups of 8 with common ground
Time resolution for indication acquisition 1 ms
Hardware filter time 2 to 64 ms
Indication voltage 19.2 to 75 V DC or 88 to 275 V DC
Input current 0.4 to 1.56 mA

BA command output module


Number of command outputs (with enable 32 x 1–pole (2–pole A) or
via BF) 16 x 2–pole (2–pole B)
Switching voltage 19.2 to 75 V DC, 88 to 275 V DC
Max. break power (resistive load) 145 to 60 W
Max. break power (inductive load, L/R <20 ms) 75 to 50 W
Contact life at max. resistive load >105 switching cycles
at min. resistive load 107 switching cycles

Siemens LSA 1.2.2 . August 1995 3


6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Technical data (cont.)


Input and output modules for central AE analog input module
process link (cont.) Number of inputs 32, with common potential
Isolation against Vcc and GND with test voltage 2.5 kV AC rms or 3540 V DC (1 min.)
Measuring ranges 0 to 20 mA DC
0 to 24 mA DC
0 to 1 mA DC
0 to 10 V DC
0 to 6 V DC
0 to 1 V DC
optional 1 V AC (rms value measurement)
Resolution 11 significant bits + 1 sign bit
Maximum deviation 0.275 % of the measuring range
Measured value refresh time (50 Hz) 650 ms for 32 analog values
Interference suppression for 50, 60, 162/3 Hz
AR analog input module
Number of inputs 16, isolated to DIN VDE 0435, part 303
Isolation against Vcc and GND with test voltage 2 kV AC rms or 2850 V DC (1 min.)
Measuring ranges 0 to 24 mA (1.5, 3, 6, 12 mA ) standard
0 to 20 mA (2.5, 5, 10 mA ) option
0 to 1 mA, option
0 to 10 V (1.25, 2,5, 5 V ) option
0 to 6 V (1.5, 3 V ) option
0 to 1 V (option)
Resolution 11 significant bits + 1 sign bit
Maximum deviation 0.275 % of the measuring range
Measured value refresh time (50 Hz) 650 ms for 16 analog values
Interference suppression for 50, 60, 162/3 Hz
Contact life of the relay multiplexer >109 switching
Connecting method For fibre optic connections FSMA connector
For wire connections to modules Crimp connection to 48–pole socket
(DIN 41 612, type F)
For antenna connection BCD connector
Power supply Nominal auxiliary voltage +25/–20 % each 24 V DC, 48 to 60 V DC
110 to 125 V DC, 220 to 250 V DC
25 % 230/115 V AC switchover
Residual ripple of the input voltage 12 %
Back–up time during power failure 5 ms
50 ms with external back–up capacitor

Electrical tests Isolation according to IEC 255–5 or DIN VDE 0435 part 303, 2 kV AC, for 1 min
(100% test/type test)
Surge voltage according to IEC 255–5 DIN VDE 0435 part 303, 5 kV, 1.2 / 50 s
(type test)
EMC tests HF interference test according to DIN IEC 255–22–1, 1 MHz attenuated, rate 400/s
test class III, (type test) 2.5 kV longitudinal voltage
1 kV transverse voltage
Transient interference / burst according to IEC 801–4, 2 kV, for power connections
test class III (type test) 1 kV for I/O lines
5/50 ns, burst 15 ms, 15 kHz

Electromagnetic fields according to DIN IEC 255–22–3, at least 15 V/m at 27, 68.05, 164.87 and
test class III (type test) 459.55 MHz

Degree of protection According to EN 60 529 (DIN VDE 0470 part 1) IP20

Permissible ambient conditions Ambient temperature in the room (type test)


Operation in the rack (DIN 19 244 part 21, class B4) 0 to +55 C
Storage, transportation –25 to +70 C
Humidity according to DIN 19 244 part 21, class B3/B4 5 to 95 % rel. humidity
(type test) component rating according to former DIN 40 040, max. 28 g/m3 water in the air
class F

4 Siemens LSA 1.2.2 . August 1995


6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Selection and ordering data


Order No.
6MB552 compact remote terminal unit 6MB5520 – 0     – 0  A 
Process signal converters
1 BF, 1 BA, 2 DE, 1 AE (20 mA) A
1 BF, 1 BA, 1 DE, 1 AR (20 mA) B
1 BF, 1 BA, 3 DE C
1 BF, 4 DE D
without (order process signal converters separately)1) Y
Fibre optic cable interface modules (pairs) for field coupling
42) A
72) B
without Y
Telecontrol interface
1 telecontrol interface ( V.24/V.28 (RS 232 C) ) 0
2 telecontrol interfaces ( V.24/V.28 (RS 232 C) + MD V21 modem ) 4
Nominal auxiliary voltage
24 V DC 1
48/60 V DC 3
110/125 V DC 4
220/250 V DC 5
115/230 V AC, 50/60 Hz 6
Radio clock
with DCF77 (HOPF) without antenna3) A
without Y
Software
Version V8.1 0
Version V8.2 1
Version V8.3 3
Version V9.1 5

Documentation
Manual for the 6MB552 compact unit C73000–G1876–C7
Function description of the IEC 870–5–101 telecontrol profile for the network control centre link E50400–U0491–U500–A2–7600
Network control – telecontrol system SINAUT 8–FW message formats description E50400–U0055–U500–A2–7600

Supply
We supply the unit from the factory in a
7XP20 housing. It contains an FP module
and the SV power supply with an
integrated line filter and fuse. Four
predefined standard module
complements can be ordered using the
order numbers given above. If you
require a different module complement,
you must order the I/O modules
separately.
MD module and FO modules are supplied
as specified in the order number.

1) 5 standard plug–in stations (SPS) are free: Not all combinations of modules are permissible (observe power loss). Clarify each case with EV S E.
2) One telecontrol interface is assigned for the field link. Only in conjunction with 2 telecontrol interfaces V.24/V.28 (RS 232 C) and MD V.21 modem (11th
position = 4). Software functionality ”field link” requires software version V9 (16th position = 5).
3) Only in conjunction with 2 telecontrol interfaces V.24/V.28 (RS 232 C) and MDV21 modem (11th position = 4).

Siemens LSA 1.2.2 . August 1995 5


6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Index of Siemens catalogs for SINAUT LSA substation control and protection
Title of catalog expected Catalog Order No.
publishing date abbreviations

6MB station control system 6MB522 Input/output unit LSA 1.1.1 E50001–K5701–A111–A2–7600
6MB523 Input/output unit LSA 1.1.2 E50001–K5701–A121–A1–7600
6MB511/512 Substation control master unit and LSA 1.1.3 E50001–K5701–A131–A2–7600
7SW511/512 Relay data concentrator
6MB520 and 6MB521 Input/output units LSA 1.1.4 E50001–K5701–A141–A1–7600
6MB513/514 Compact control master unit 10/1995 LSA 1.1.6 E50001–K5701–A161–A1–7600
6MB524 Compact Input/Output Unit 02/1996 LSA 1.1.7 E50001–K5701–A171–A1–7600

6MB telecontrol system 6MB551 Station control unit LSA 1.2.1 E50001–K5701–A211–A1–7600
6MB552 Telecontrol compact unit 08/1995 LSA 1.2.2 E50001–K5701–A221–A1–7600
6MB5530–0 Minicompact remote terminal unit 08/1995 LSA 1.2.3 E50001–K5701–A231–A1–7600
6MB5530–1 Minicompact remote terminal unit 08/1995 LSA 1.2.4 E50001–K5701–A241–A1–7600
for cable shield communication

User functions Control LSA 1.4.1 E50001–K5701–A411–A1–7600


Status indications LSA 1.4.2 E50001–K5701–A421–A1–7600
Analog values LSA 1.4.3 E50001–K5701–A431–A1–7600
Metering LSA 1.4.4 E50001–K5701–A441–A1–7600
Voltage control in 6MB520 and 6MB521 I/O unit LSA 1.4.5 E50001–K5701–A451–A1–7600
Network synchronization with 6MB520 and LSA 1.4.6 E50001–K5701–A461–A1–7600
6MB521 I/O unit
Operation with two control master units 10/1995 LSA 1.4.7 E50001–K5701–A471–A1–7600
Node functions LSA 1.4.8 E50001–K5701–A481–A1–7600

Supporting Engineering and LSATOOLS planned LSA 1.5.1 E50001–K5701–A511–A1–7600


PC applications parameterization system
System diagnostics LSADIAG planned LSA 1.5.2 E50001–K5701–A521–A1–7600
Control and monitoring LSACONTROL 10/1995 LSA 1.5.3 E50001–K5701–A531–A1–7600
Communication diagnostics LSATEST planned LSA 1.5.4 E50001–K5701–A541–A1–7600
Process information analysis LSAPROCESS 11/1995 LSA 1.5.5 E50001–K5701–A551–A1–7600

Switchgear cubicle LSA678 Standard cubicle 10/1995 LSA 1.6.1 E50001–K5701–A611–A1–7600

6 Siemens LSA 1.2.2 . August 1995


6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Telecontrol processor module SINAUT LSA system bus Digital input module
FP DE
RxD Test and diagnostics
TxD V.24 32 single indications
interface
per module
RxD
TxD Telecontrol interface for
CTS V.24
VFT/modem connection
RTS Command enable module

BF
8 local indications
8 local commands
Command enable
Switching current check
Modem module
MD
Command output module
DCF77 with time signal
BA
receiver module
a 32 single commands
b Modem
per module

RxD 1
TxD FO Analog input module
AE/AR
Fibre–optic bay link 32/16 analog values
7 per module
RxD
TxD FO

Power supply module


SV
L+
=
L– =

Fig. 3
Connection diagram and data flow for the 6MB552 compact remote terminal unit, overview

Siemens LSA 1.2.2 . August 1995 7


6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Command output module Command output module


BF SINAUT LSA BA
system bus
Vm EN1
V Ref Command output
EN2
module
1
2
3
4
5 1
6
7
8 2
W

3
1

...

...
3
16

5 Digital input module


DE

VM
V Ref
6
1
2
3
7 4
5
6
7
8 8
...

VC+
VC–
Command output
V Ref
EN+ and switching
EN– current check 25
26
27
28
29
SSK1 Switching current 30
SSK2 check for external 31
enable relay 32

Fig. 4
Connection diagram and data flow for the 6MB552 compact remote terminal unit, BF, BA, and DE modules

8 Siemens LSA 1.2.2 . August 1995


6MB Telecontrol System

6MB552 Compact Remote Terminal Unit

Analog input module electronic

SINAUT LSA system bus


AE
1

...

32 ...

CP

Analog input module with relay


AR

4
...
...

13

14

15

16

Fig. 5
Connection diagram and data flow for the 6MB552 compact remote terminal unit, modules AE and AR

Siemens LSA 1.2.2 . August 1995 9


6MB Telecontrol System

Dimension drawings in mm

7,3 206.5 0.3


29.5 172 39 220
13,2 180 0.5
Mounting 8

5.4
panel

Bus cover

BNC socket Diam. 5 or M4


for antenna

0,3
+

245+1
1) 2)
266

244

255.8
Diam. 6

FO module block for 225 221+2


bay unit coupling 3)
Side view Rear view Panel cutout

Caution! If you are using an FO module an


extra 70 mm mounting depth is required.

Fig. 6
6MB552 compact remote terminal unit in the 7XP20 housing (for switchboard and cabinet mounting)

1) DIN 41 612 type F 48–way for signal converter and FP.


2) DIN 41 612 type H 15–way for SV power supply.
3) In the case of version with 2 x V.24/V.28 (RS 232 C) telecontrol interfaces, replaced by 48–way crimp connection as for 1).

10 Siemens LSA 1.2.2 . August 1995


6MB Telecontrol System

Conditions of Sale and Delivery S Export Regulations S Trademarks S Dimensions

Conditions of Sale and Delivery


Subject to the J
General Conditions of Supply and Delivery The technical data, dimensions and We reserve the right to adjust the prices
for Products and Services of the weights are subject to change unless and shall charge the price applying on
Electrical and Electronic Industry otherwise stated on the individual pages the date of delivery.
and to any other conditions agreed upon of this catalog.
with the recipients of catalogs.
The illustrations are for reference only.
A 9.91 a

Export Regulations
In accordance with present German and permissible without the approval of the Subject to change.
US export regulations export licences (da- relevant authorities except where current Relevant are the criteria stated in the
ted 07.95) are not required for the prod- German export regulations contain coun- delivery note and in the invoice.
ucts listed in this catalog. try–specific restrictions. An export licence may be required due
Export and re–export are therefore The following criteria for export apply: to country–specific application of the
Telecontrol compact unit: product.
AG: N, EC: D, ECCN: 3A96G
AD–modul:
AG: N, EC: D, ECCN: 4A96G
Other: AG: N, EC: N

Trademarks Dimensions
All product designations used are trade- All dimensions in this catalog are given in
marks or product names of Siemens AG mm.
or of suppliers.

Responsible for
Technical contents: Klaus–Dieter Scheffer,
Siemens AG, EV S T14, Nürnberg
General editing: Claudia Kühn–Sutiono,
Siemens AG, EV MK 2, Erlangen

Siemens LSA 1.2.2 . August 1995 11


6MB Telecontrol System

Power
Transmission
and Distribution
12
Siemens Aktiengesellschaft Order No.: Siemens
E50001-K5701–A221-A1–7600
LSA 1.2.2 . August 1995
Printed in the Federal Republic of Germany
KG K 0895 3.0 SC 12 En 361 378