Professional Documents
Culture Documents
SECTION 4.15: Break-In Procedure After Rebuild
SECTION 4.15: Break-In Procedure After Rebuild
15
BREAK-IN PROCEDURE AFTER REBUILD
All new engines are test run at the factory before 4. Verify protective guards and shields on engine and
shipment and therefore do not require break-in. Howev- driven equipment are secure (see Figure 4.15-1).
er, after an on-site overhaul, certain break-in proce- Remove tools, rags, fittings or any other objects that
dures must be followed to allow critical engine parts to may get caught by rotating parts.
seat properly.
5. Examine engine foundation for condition of grout,
PRESTART INSPECTION tightness of hold down bolts and general alignment of
driven equipment.
Always wear protective clothing when checking or Figure 4.15-1. Engine Guards
venting the cooling system on a heated engine.
Slowly loosen the air bleed petcock to relieve any 6. Check air cleaner restriction indicator. If indicator
excess pressure. Use the vent on the pressure cap shows red, clean pre-cleaner and/or air cleaner ele-
to allow pressure to escape. Escaping steam ments (see Figure 4.15-2).
and/or hot water can result in severe burns or
death.
BARRING DEVICE
C
O M
M A
P
E X
N
S
A
T M
I I
O N
N
COMPENSATION
POINTER
OIL DRAIN
Figure 4.15-3. Engine Barring Device PLUG
LOW FULL
IGNITION
STEP SPEED ± 10 RPM BMEP PSI ± 10% TIME (MINUTES) TORQUE POWER
MINIMUM FT--LB ± 3% HP ± 3%
1 800 Minimum 10 Check for leaks, unusual noise or vibration
2 900 50 15 3113 533
3 Rated 100 30 6225 --
4 Rated ++ 130 60 8093 --
5 Rated ++ 160 60 9961 --
6 Rated ** 60 ** **
NOTE: ++If the BMEP listed exceeds the rated BMEP (as specified in the engine build package or nameplate for field break-- in), run that Step at
rated BMEP and end break-- in.
**Engine set at rated load per the appropriate “Performance Data for Production Test” S-- sheet or at rated load on the engine nameplate for field
break-- in.
Alarm and shutdown values are based on dry natural gas (900 Btu/cu. ft. SLHV).
Refer to Gaseous Fuel Specification Sheet S7884-7, Oil Recommendations Sheet
S1015-30, Service Bulletins 9-2702B and 12-1880Z or latest revisions for typical changes in operation
temperatures for jacket water and oil when running on landfill or digester gas fuels. Disregarding this
information could result in product damage.
NOTE: 1 Waukesha Power Systems Code 1105, 1105A, or equivalent shutdown system is recommended when jacket water temperature exceeds
210° F (99° C).
2 Waukesha Power Systems Code 1106, 1106A, or equivalent shutdown system is recommended for ebulliently cooled engines.
BREAK-IN PROCEDURE 6. Press and hold down PRELUBE button for 5 min-
utes (see Figure 4.15-7). Check oil pressure gauge for a
Proper engine break--in is required after installation of
minimum of 5 psi (35 kPa).
new piston rings. Table 4.15-4 lists the correct break--in
schedule for VHP Series Four engines. See
Table 4.15-1 additional break--in schedules. START PRELUBE
3. Make sure all controls are set properly for the water
and oil systems. Prelube the engine for 5 minutes prior
to starting.
SYNCHRONIZER
Turbocharged engines
should not be idled for
extended periods. Accumulated carbon may dam-
age turbocharger. Shut down and restart when
needed.
GOVERNOR SPEED
CONTROL LEVER 13. Warm engine by running with little or no load until oil
pressure is normal and the coolant temperature reach-
Figure 4.15-10. Governor Speed Control Lever es 100° F(38° C). Refer to Table 4.15-2 for complete
information.
9. Open the fuel shutoff valve(s) (see Figure 4.15-11).
14. Gradually apply load to engine. Do not overload.
Observe all gauges Always verify fuel gas valve(s) are closed after
continuously for the engine shutdown. Failure to close valve(s) could
duration of the break-in. Shut engine down if safe cause severe personal injury or death.
temperatures are exceeded or if pressure falls to
unsafe levels. Failure to shut down automatically 30. Close fuel valves to shut engine down.
indicates a problem with the engine protection
shutdown system. Determine the cause of failure 31. Post lube engine for 5 minutes.
before starting engine. Failure to comply may
result in severe equipment damage and/or 32. Check and adjust intake and exhaust valves for
personal injury. each cylinder head. See Section 4.10 Valve Adjustment
And Web Deflection.
NOTE: Crankcase pressure could be up to 1 in. of
water maximum during break-in. Higher pressure is a
good indication of a power cylinder problem and should
be investigated. After break-in it should be 0 to --2 in. of
vacuum.
21. Start engine and run at 900 rpm (1000 or 1200 rpm
for high rpm engines) under 25% (50 BMEP) load until
oil reaches 130° F (54° C).
OPERATING AT LIGHT LOADS Engine oil and coolant temperatures should be main-
The following information gives recommendations for tained within the standard operating ranges. Always
special operation and maintenance procedures when check thermostats for proper operation. General guide-
operating Waukesha natural gas engines at light loads lines are as follows:
or no loads for extended periods of time. · Maintain engine jacket water outlet coolant in
Light load operation is typically defined as power levels standard range of 180° F to 190° F (82° C to 89° C).
less than 50% of the maximum continuous power rating.
· Oil header temperature should be above 160° F
Gas engines usually have unstable combustion at light (71° C) to assure proper lubrication of the engine and
loads because combustion chamber pressures are minimize oil nitration rates.
lower which increases blow--by past the piston rings.
Refer to “General Data” Technical Data Book, under
This can lead to contamination of the engine oil
Control Systems see Number S8382 “Alarm And
including an increase in oil nitration rates and carboning
Shutdown Setpoints” and in the Fuels And Lubrication
of the piston ring grooves. Oil analysis is recommended
Section, Number S1015--27 “Waukesha Oil Recom-
to determine proper oil change intervals. Refer to
mendations.”
Section 5.30 Lubrication System “Oil Specifications” for
Waukesha oil recommendations. Change intervals are The crankcase breather system should be checked for
usually not affected by periodic light loading. proper operation, which will ensure that blow--by gases
are properly vented from the crankcase. The breather
If the engine is operated at less than 30% load for long
system should be adjusted to operate at a slight
periods (> 300 hours), it is recommended that the
vacuum. Refer to VHP Series Four Operation and
engine be exercised at full load for 2 hours every
Maintenance Manual, Form 6287, Section 4.40
400 hours.
“Crankcase Breather System Maintenance” for
Single electrode iridium platinum spark plugs are specifications.
recommended by Waukesha Engine and are available
from Waukesha Engine Distributors. Refer to Service
Bulletin No. 11--1895G (or latest revision) for spark plug
recommendations for all Waukesha production
engines. These spark plugs have superior corrosion
resistance and will significantly improve the engine
stability at part and full load operation compared to the
multi--electrode spark plugs.