Generator set data sheet

Model: C1000 D6B


Frequency: 60
Fuel type: Diesel

Spec sheet: SS15-CPGK


Noise data sheet (open/enclosed): MSP-2082
Airflow data sheet: MCP-1082

Standby Prime
Fuel consumption kW (kVA) kW (kVA)
Ratings 1020 (1276) 928 (1160)
Load 1/4 1/2 3/4 Full 1/4 1/2 3/4 Full
US gph 27 37 49 65 20 31 49 60
L/hr 104 138 185 246 76 117 185 246

Standby Rating Prime Rating


Engine
Engine manufacturer Cummins
Engine model KTA38-G14
Configuration Cast iron, 60º V12 cylinder
Aspiration Turbocharged and after-cooled
Gross engine power output, kWm 1112 1007
BMEP at set rated load, kPa 1965 1779
Bore, mm 159
Stroke, mm 159
Rated speed, rpm 1800
Piston speed, m/s 9.5
Compression ratio 13.9:1
Lube oil capacity, L 161
Overspeed limit, rpm 2100 ±50
Regenerative power, kW 127
Governor type Electronic
Starting voltage 24 Volts DC

Fuel flow
Maximum fuel flow, L/hr 507
Maximum fuel inlet restriction, mm Hg 102
Maximum fuel inlet temperature, °C 61

©2015 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS370d-CPGK (4/15)
Air Standby Rating Prime Rating
3
Combustion air, m /min 86.10 81.54
Maximum air cleaner restriction, kPa 6.2

Exhaust
Exhaust gas flow at set rated load, m3/min 238.0 218.4
Exhaust gas temperature, °C 524 499
Maximum exhaust back pressure, kPa 10.1

Standard set-mounted radiator cooling


Ambient design, °C 40
Fan load, kWm 33.8
Coolant capacity (with radiator), L 275
Cooling system air flow, m3/sec @ 12.7 mmH2O 17.7
Total heat rejection, Btu/min 38740 35100
Maximum cooling air flow static restriction mm H2O 25.4

Weights* Open Enclosed


Unit dry weight kgs 7990 RTF
Unit wet weight kgs 8380 RTF
* Weights represent a set with standard features. See outline drawing for weights of other configurations.

Dimensions Length Width Height


Standard open set dimensions mm 4470 1785 2229
Enclosed set standard dimensions mm RTF RTF RTF

Genset outline
Open set

Outlines are for illustrative purposes only. Please refer to the genset outline drawing for an exact representation of this model.

©2015 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS370d-CPGK (4/15)
Alternator data
Connection Temp rise ºC Duty Alternator Voltage
Wye, 3-phase 125/150 C S/P HC6K 380-480V

Ratings definitions
Emergency standby power Limited-time running power Base load (continuous)
(ESP): (LTP): Prime power (PRP): power (COP):

Applicable for supplying power to Applicable for supplying power Applicable for supplying power Applicable for supplying
varying electrical load for the to a constant electrical load for to varying electrical load for power continuously to a
duration of power interruption of a limited hours. Limited Time unlimited hours. Prime Power constant electrical load for
reliable utility source. Emergency Running Power (LTP) is in (PRP) is in accordance with unlimited hours. Continuous
Standby Power (ESP) is in accordance with ISO 8528. ISO 8528. Ten percent overload Power (COP) is in accordance
accordance with ISO 8528. Fuel capability is available in with ISO 8528, ISO 3046,
Stop power in accordance with accordance with ISO 3046, AS 2789, DIN 6271 and
ISO 3046, AS 2789, DIN 6271 and AS 2789, DIN 6271 and BS 5514.
BS 5514. BS 5514.

Formulas for calculating full load currents:


Three phase output Single phase output

kW x 1000 kW x SinglePhaseFactor x 1000


Voltage x 1.73 x 0.8 Voltage

See your distributor for more information.


Cummins Power Generation
Manston Park, Columbus Avenue
Manston, Ramsgate
Kent CT12 5BF, UK
Telephone: +44 (0) 1843 255000
Fax +44 (0) 1843 255902
E-mail: cpg.uk@cummins.com
Web: www.cumminspower.com

©2015 | Cummins Power Generation Inc. | All rights reserved | Specifications subject to change without notice | Cummins Power Generation and Cummins are registered trademarks of Cummins Inc.
PowerCommand and “Our energy working for you.” are trademarks of Cummins Power Generation. Other company, product, or service names may be trademarks or service marks of others.
DS370d-CPGK (4/15)

You might also like