Professional Documents
Culture Documents
XfrmDiffAnalysis R02
XfrmDiffAnalysis R02
By use of this program, the user agrees that Basler Electric disclaims all warranties of noninfringement of third party rights,
user assumes the entire risk as to the quality and performance of the software. In no event will Basler Electric be liable for a
regarding this software, the user agrees that the venue shall be the State of Illinois.
Instructions, Notes
=> See each sheet for instructions specific to that sheet.
=> The spreadsheets have data already entered in. This is for information only, so one can see the type of information expe
=> On common 1024x768 screens, most sheets are best viewed at 75% zoom. If one has a higher resolution monitor, one
=> See papers on the Basler Electric Web site for additioal information and transformer differential theory
=> Send comments on this spreadsheet to "info@basler.com"
Revision Notes:
Rev. D.1; 03/26/03; Request for comments
Rev. D.2; DDAB calc error fixed.
Rev. 0.1; Initial release, including a couple formating updates relative to rev 0 as used at Megger Conference, 06/27/05
Rev. 0.2; Fixed "Iop>MPU?" check, cells G31/G32, 87T-Diff Calcs-Isec sheet; revised disclaimer wording. 11/22/05
Basler Electric Company, P.O. Box 269, Highland, Illinois USA 62249
Phone: 618/654-2341 - Fax: 618/654-2351 - Website: http://www.basler.com
Current Differential Differential Relays, BE1-87T and BE1-CDS2x0
power transformers, but users should be aware the specific applications were intended, so the results cannot
attempted to develop accurate calculation methods, but Basler Electric does not warrant that the software is
ment with the results, and consult with a Basler Electric representative to determine the accuracy of the data
nfringement of third party rights, quality, performance, merchantability, or fitness for a particular purpose. The
will Basler Electric be liable for any indirect, special, or consequential damages. In the event of any litigation
ommissioning testing and post fault event analysis. The sheets and their puropose are:
ent.
. Includes CT connection and ratio effects.
ent.
see the type of information expected. Update all information and settings appropriately.
higher resolution monitor, one might raise the zoom control to 100% for clearer viewing.
erential theory
RELAY SETTINGS (Red range cell flags bad data) Range Current Inputs, Per Unit of Tap: Mag. Angle Intermediate Calculations
Nominal Amp Rating of Inputs 5 5 or 1 Input 1, Ph A 0.550 0 D1, D2 Jumper Compensation Equations:
% Slope 25 15-60, steps of 5 Input 1, Ph B 0.550 -120 Input 1, Rectangular format D1, D2 Equations
Minimum Pickup (MPU), per unit 0.35 See Cell Comment Input 1, Ph C 0.550 120 Real Imag Real Imag Mag Angle
Input 1 Tap 2 2.0-8.9 or 0.4-1.78 Input 2, Ph A 0.500 150 A 0.5500 0.0000 D1;1A-1C 0.8250 -0.4763 0.9526 -30.0
Input 1 Compensation Jumper Y Y, D1, D2 Input 2, Ph B 0.500 30 B -0.2750 -0.4763 D1;1B-1A -0.8250 -0.4763 0.9526 -150.0
Input 2 Tap 6 2.0-8.9 or 0.4-1.78 Input 2, Ph C 0.500 -90 C -0.2750 0.4763 D1;1C-1B 0.0000 0.9526 0.9526 90.0
Input 2 Compensation Jumper d2 Y, D1, D2 Restraint, with Compensation Jumper Effects D2;1A-1B 0.8250 0.4763 0.9526 30.0
Input 1, A Comparator 0.550 0 D2;1B-1C 0.0000 -0.9526 0.9526 -90.0
Input 1, B Comparator 0.550 -120 D2;1C-1A -0.8250 0.4763 0.9526 150.0
INJECTED CURRENT AT INPUT 1 Input 1, C Comparator 0.550 120 Input 2, Rectangular format D1, D2 Equations
(Single phase entry sufficient) Mag. Angle Input 2, A Comparator 0.866 180 A -0.4330 0.2500 D1;2A-2C -0.4330 0.7500 0.8660 120.0
Current @ Input 1, Ph A 1.1 0 Input 2, B Comparator 0.866 60 B 0.4330 0.2500 D1;2B-2A 0.8660 0.0000 0.8660 0.0
Current @ Input 1, Ph B 1.1 -120 Input 2, C Comparator 0.866 -60 C 0.0000 -0.5000 D1;2C-2B -0.4330 -0.7500 0.8660 -120.0
Current @ Input 1, Ph C 1.1 120 Effective Restraint (Largest Restraint x Slope) D2;2A-2B -0.8660 0.0000 0.8660 180.0
INJECTED CURRENTS AT INPUT 2 A Comparator 0.217 D2;2B-2C 0.4330 0.7500 0.8660 60.0
Mag. Angle B Comparator 0.217 D2;2C-2A 0.4330 -0.7500 0.8660 -60.0
Current @ Input 2, Ph A 3 150 C Comparator 0.217 Convert Restraint to Rectangular format
Current @ Input 2, Ph B 3 30 Mag. Operate Current (Restraint 1 - Restraint 2) X jY
Current @ Input 2, Ph C 3 -90 A Comparator 0.316 Input 1 A 0.5500 0.0000
B Comparator 0.316 B -0.2750 -0.4763
C Comparator 0.316 C -0.2750 0.4763
Trip? (I Op>MPU? & I Op>Restraint?) Input 2 A -0.8660 0.0000
A Comparator No B 0.4330 0.7500
B Comparator No C 0.4330 -0.7500
C Comparator No Sum Restraint to find Operate Current
X jY Mag Angle
Sum 1A+2A -0.3160 0.0000 0.3160 180.0
1B+2B 0.1580 0.2737 0.3160 60.0
1C+2C 0.1580 -0.2737 0.3160 -60.0
BE1-CDS, Testing With 2 Single Phase Current Sources
This sheet predicts targets on the BE1-CDS2x0 when testing with two single phase test sets, with the relay set at user's final settings.
-- Enter data in yellow fields only. Range cells become red if bad data is entered. Blue cells are calculated by the spreadsheet.
-- While most directly applicable to the CDS220, this spreadsheet can be used to analyze the CDS240 if one mentally compensates for the winding numbers and does not use the advanced compensation schemes in the CDS240.
-- The spreadsheet expects one to understand compensation that the relay is using and enter net compensation, not the Xfmr or CT configuration. See IM chapter 3.
RELAY SETTINGS (Red range cell flags bad data) Range CURRENTS AT INPUT 1 Current, Per Unit of Tap: Mag. Angle Effective Restraint (see cell
Nominal Amp Rating of Inputs 5 5 or 1 Mag. Angle Input 1, Ph A 1.400 180.0 notes)
Restr. = Max. or Avg. Mult. of Tap? m M or A Current @ Input 1, Ph A 7 180.0 Input 1, Ph B 1.400 60.0 A Comparator 0.490
No. of 87Ph inputs (see Range notes) 4 2,3,4 Current @ Input 1, Ph B 7 60.0 Input 1, Ph C 1.400 -60.0 B Comparator 0.490
87Phase Min Pickup (MPU), per unit 0.25 0.10-1.00 Current @ Input 1, Ph C 7 -60.0 Input 2, Ph A 0.400 0.0 C Comparator 0.490
Phase % Slope 35 15-60, steps of 1 CURRENTS AT INPUT 2 Input 2, Ph B 0.400 -120.0 Gnd Comparator 0.000
Input 1 Tap 5 2.0-20 or 0.4-4 Mag. Angle Input 2, Ph C 0.400 120.0
Input 1 Delta Comp. (see IM Chpt 3) y Y, DAB, DAC, DDAB Current @ Input 2, Ph A 1 0.0 Input 3, Ph A 0.400 0.0
Mag. Operate Current
Input 1 "Ground Source" selected? n Y, N Current @ Input 2, Ph B 1 -120.0 Input 3, Ph B 0.400 -120.0
(Rest. 1+2+3+4)
Input 1 Swap; A = ? a A, B, C Current @ Input 2, Ph C 1 120.0 Input 3, Ph C 0.400 120.0
Input 1 Polarity Reversal? n Y, N CURRENTS AT INPUT 3 Input 4, Ph A 0.600 0.0 A Comparator 0.000
Input 2 Tap 2.5 2.0-20 or 0.4-4 Mag. Angle Input 4, Ph B 0.600 -120.0 B Comparator 0.000
Input 2 Delta Comp. (see IM Chpt 3) y Y, DAB, DAC, DDAB Current @ Input 3, Ph A 1 0.0 Input 4, Ph C 0.600 120.0 C Comparator 0.000
Input 2 "Ground Source" selected? n Y, N Current @ Input 3, Ph B 1 -120.0 Input Ig / 87N Ig tap 0.000 180.0 Gnd Comparator 0.000
Input 2 Phase Swap; A = ? a A, B, C Current @ Input 3, Ph C 1 120.0 3Io, Input / 87N Ph tap 0.000 0.0
Input 2 Polarity Reversal? n Y, N CURRENTS AT INPUT 4 Phase Restraint, after compensation Trip? (Op>MPU? &
Input 3 Tap 2.5 2.0-20 or 0.4-4 Mag. Angle Input 1, A Comparator 1.400 180.0 Op>Restraint?)
Input 3 Delta Comp. (see IM Chpt 3) y Y, DAB, DAC, DDAB Current @ Input 4, Ph A 1.5 0.0 Input 1, B Comparator 1.400 60.0 A Comparator No
Input 3 "Ground Source" selected? n Y, N Current @ Input 4, Ph B 1.5 -120.0 Input 1, C Comparator 1.400 -60.0 B Comparator No
Input 3 Phase Swap; A = ? A A, B, C Current @ Input 4, Ph C 1.5 120.0 Input 2, A Comparator 0.400 0.0 C Comparator No
Input 4 Polarity Reversal? N Y, N CURRENT AT IG (GROUND INPUT) Input 2, B Comparator 0.400 -120.0 Ground Comparator No
Input 4 Tap 2.5 2.0-20 or 0.4-4 Mag. Angle Input 2, C Comparator 0.400 120.0
Input 4 Delta Comp. (see IM Chpt 3) y Y, DAB, DAC, DDAB Current @ Input Ig 0 180.0 Input 3, A Comparator 0.400 0.0
Input 4 "Ground Source" selected? n Y, N Input 3, B Comparator 0.400 -120.0
Input 4 Phase Swap; A = ? a A, B, C Input 3, C Comparator 0.400 120.0
Input 4 Polarity Reversal? n Y, N Input 4, A Comparator 0.600 0.0
87Gnd Min Pickup (MPU), per unit 0.2 0.10-1.00 Input 4, B Comparator 0.600 -120.0
87Gnd % Slope 20 15-60, steps of 1 Input 4, C Comparator 0.600 120.0
Which input # is Ig compared to? 4 1, 2. 3, 4
Phase CT Ratio for Input 4 400 N to 1
Ground CT Ratio 50 N to 1
87N Tap, Ig Input side 16.00 See cell notes
Blank Sheet for User Calculations