Cooling Tower Evaporation Heat and Mass

Balance Calculation
Unit
UOM
Specification
Ambient 26.25
Load % 100% 50%
1 Generation MW 18.00 27.04
2 Oil Used Turbinol-46 SERVO PRIME 46

3 Specific Heat KJ/KG ◦C 2.001 2.001


4 Oil cooler Inlet oil temp. DegrC 59.7 52.56
5 Oil cooler outlet oil temp. DegrC 41.74 46
6 Delta T of Oil DegrC 18.0 6.6
7 Density @ 75 Deg C kg/M3 886 886
8 Lube oil flow LPM 1000 1083
10 Heat rejection by oil Kcal/Hr 456945 180755
11 Specific heat rejection Kcal/Kwh 25.39 6.7
12 Oil cooler inlet water temp. DegrC 25.96 26.25
13 Oil cooler outlet water temp. DegrC 34.67 34.87
14 Delta T of water DegrC 8.7 8.6
15 Water flow TPH 52.5 22.95
16 Heat gained By Water MKcal 457275 197829
17 Evaporation Loss KL/Day 20.32 8.79
18 Sp CT Evaporation KL/Day 0.05 0.01
Generator Air Cooler
1 Generator cold air temp. TE-703A DegrC 34.59 40.92
2 Generator Hot air temp. TE-704A DegrC 49.77 45.64
3 Delta T Air DegrC 15.18 4.72
4 Water I/L temp DegrC 25.8 26.53
5 Water O/L temp DegrC 27.2 28.75
6 Delta T across Gen Cooler DegrC 1.4 2.22
7 Water Flow TPH 55.0 133.3
8 Heat in Water Kcal 77000 295926
9 Evaoration Loss KL/Day 3.42 13.15
10 Sp Evaporation Loss Ltr/Kwh 0.01 0.02
11 Total Evaporation (calculated) KL/Day 23.74 21.94
12 Total Sp Evaporation (calculated) Ltr/Kwh 0.05 0.03
13 Total Evaporation Loss (Actual) KL/Day 24.50 23.00