Outdoor Power System

TP48200A-H15A3

Introduction
TP48200A-H15A3 is an AC/DC outdoor power system that
configures 48V/50A rectifier modules to supply rated of 200A
output current, with heat exchange cooling. The system has
excellent performance such as wide range of AC input voltage, high
power efficiency, surge protection, intelligent temperature and
battery management, and remote management. The TP48200A-
H15A3 is used in class C environment for various outdoor scenarios.

Features
 High protection level, equipment cabin: IP55, battery cabin:
IP45
 High efficiency of rectifier module: >96%
 Super temperature performance for rectifiers with range from
-40℃ to 75℃
 The power module supports hot-swapping, easy to install and
maintain
 Temperature control system built-in door, easy to maintain,
clean, replace
 Strong anti-theft design: Door embedded, hinge hidden, 3-
point lock, door sensor, support padlock
 Intelligent battery management, prolong battery lifespan
 Support battery anti-reverse function, reducing operating risk
 Support remote management, reducing customer operating
cost

Application Scenarios
 Outdoor wireless site
 Outdoor enterprise communication network

enterprise.huawei.com
Specifications
Dimension 650mm(W)×650mm(D)×1500mm(H) (excluding base)
Weight ≤110kg (without rectifier module and battery)
Cooling mode Equipment cabin: heat exchanger(850W), battery cabin: direct ventilation
Installation mode On ground\on roof\against wall
Cabling mode At the bottom, inlet/outlet downwards
System Maintenance mode In front
Noise level Satisfied GR487, noise≤65dBA@1.5m
Protection level Equipment cabin: IP55, battery cabin: IP45
Battery space 16U(2×150Ah)
User space 8U
MTBF 200,000 hours
Input mode Three phase, single phase
Input voltage 85VAC~300VAC, rated: 220VAC;
Input frequency 45~65Hz, rated value: 50Hz/60Hz
AC Input capacity 1×63A/3P

Distribution SPD 20kA/40kA, 8/20μs

Maintenance socket(AC output) Universal


Three phase/single phase:
AC output 1×16A/1P(maintenance socket)
1×16A/1P
Output voltage 42~58VDC, rated value: 53.5VDC

Maximum capacity 12kW(4×3000W)

DC Battery branch 2x125A MCB


Distribution LLVD branch 2×63A MCB, 2×32A MCB

BLVD branch 2×16A MCB

SPD 10kA/20kA, 8/20μs

Input voltage 85VAC~300VAC, rated 220VAC

Rated power 3000W

Working temperature -40℃~+75℃

Rectifier Dimensions 103mm(W)×243mm(D)×88.9mm(H)

Weight <2.8kg

Power factor ≥0.99

THD ≤5%

3 AI(battery temp., ambient temp., ambient humidity)


Signal input
9 DI(water, smoke, gate, 6 common DI)
Alarm output 8 dry contact
Controller
Communication port RS232, RS485, SNMP
Storage capacity Up to 50000 historical records
Display mode LCD
Operating temperature -10℃~+45℃ (+ solar radiation)
Storage temperature -40℃~+70℃
Environment
Operating humidity 5%~95%(non-condensing)
Altitude 0~4000m

Remark: Normal efficiency(>92%) rectifier is optional

Copyright © Huawei Technologies Co., Ltd. 2013. All rights reserved. HUAWEI TECHNOLOGIES CO., LTD.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.
Huawei Industrial Base
General Disclaimer Bantian Longgang
The information in this document may contain predictive statements including,without limitation, statements regarding the future Shenzhen 518129, P.R. China
financial and operating results, future product portfolio, new technology, etc. There are a number of factors that could cause actual Tel: +86-755-28780808
enterprise.huawei.com
results and developments to differ materially from those expressed or implied in the predictive statements. Therefore,
enterprise.huawei.com
such information is provided for reference purpose only and constitutes neither an offer nor an acceptance.
Huawei may change the information at any time without notice.

You might also like