Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

EMC’14/Tokyo 16A1-H1

Evaluation of Magnetic Field Generated by Power


Facilities in Accordance with IEC 62110

Yusuke Miyaji, Mitsuki Shimada and Yukio Mizuno Katsuhiko Naito


Nagoya Institute of Technology N. S. Co., Ltd.
Nagoya, Japan Nagoya, Japan

Abstract—This paper reports results of magnetic flux density


(denoted as magnetic field hereafter) measurements under power II. OUTLINE OF IEC 62110
transmission lines and around power distribution equipment.
Measurements were carried out in accordance with IEC 62110 A. Introduction
established in 2009, which prescribes measurement and This standard specifies fundamental procedures for
evaluation procedures of uniform and non-uniform magnetic
measurement of electric and magnetic fields, and, with regard
field generated by ac power systems with regard to human
to human exposure, in order to obtain a field value that
exposure. The average and the maximum exposure levels of
magnetic field generated such power facilities were evaluated and
corresponds to a spatial average over the entire human body.
found much lower than the reference level from the ICNIRP The standard is applied to measurement of fields generated
Guidelines. by AC power systems in areas accessible by the public. It
establishes a common measurement procedure to evaluate the
Keywords—magnetic field; power transmission lines; pad- exposure levels of the human body to electric and magnetic
mounted transformer; switchgear; vertical cable; average and
fields among the general public. It is not applicable to
maximum exposure levels; IEC 62110
occupational exposure.

I. INTRODUCTION The values obtained in accordance with this standard are


for use to determine whether the fields comply with exposure
Calculation results of power frequency magnetic field have limits by comparing them with the field limits for general
been reported, which are generated by power facilities such as public exposure such as the reference levels from the ICNIRP
transmission lines [1-3], substations [4-6] and so on [7-8]. Guidelines [15], MPE from the IEEE [16] or national
Reports of measurement results of magnetic field have also regulations. If the values obtained are higher than the reference
been published [9-13]. However, there seem little papers level or MPE, it does not necessarily mean that the basic
dealing with magnetic field near power distribution equipment restriction is exceeded, in which case other methods must be
such as pad-mounted transformers, switchgears and vertical used to ensure that the basic restriction is not exceeded.
cables, which are installed on sidewalks in urban areas.
Evaluation of magnetic field generated by such equipment is B. Fundamental Measurement Procedures
important from the standpoint of public exposure to magnetic
fields, because people passed by them closely in some cases. Three different measurement procedures are specified in
the standard depending on field characteristics; single-, three-
To evaluate magnetic field generated by ac power systems and five-point measurements.
with regard to human exposure, an international standard IEC
62110 [14] was established in 2009. The standard prescribes 1) Single-point measurement: Where the field is considered
measurement and evaluation procedures of uniform and non- to be uniform, the field level at the position of interest should
uniform magnetic field. be measured at 1.0 m above the ground or the floor in the
building.
In this paper, magnetic field generated by power facilities
was evaluated based on measurement results in accordance 2) Three-point measurement: Where the field is considered
with IEC 62110. Magnetic field generated by transmission to be non-uniform, the field levels at the position of interest
lines is considered almost uniform near the ground. On the should be measured at three heights, 0.5 m, 1.0 m and 1.5 m
other hand, non-uniform magnetic field is generated by power above the ground or the floor in a building.
distribution equipment such as pad-mounted transformers, Beside power equipment or in a building, measurement
switchgears and vertical cables. should be performed at a horizontal distance of 0.2 m from its
Evaluation results are also discussed by comparing the surface, boundary or a wall as shown in Fig. 1 (a). In situations
average and the maximum exposure levels with the reference where the equipment has a height less than 1.5 m, the three-
levels from the ICNIRP Guidelines [15]. point measurement must be performed at equidistant heights
with the highest being at the same height as the top of the
equipment as shown in Fig.1 (b).

Copyright 2014 IEICE


621
EMC’14/Tokyo 16A1-H1

0.2m Measuring points


0.2m
0.5m
H H/3 Top 0.2 m
0.5m surface
H H/3 1.0 m or
top height
0.5m H/3

H ≥ 1.5 m H < 1.5 m


Fig. 2. Procedure to obtain the maximum exposure level beside power
(a) (b) equipment.
Fig. 1. Three-point measurement beside power equipment [14].
measurement should be performed. When the position of the
3) Five-point measurement: Where there are sources of field maximum field within the area of interest is already known, the
below the ground or the floor and there is a reasonable three-point measurement should be performed at that position.
possibility that a person is likely to lie down above it, five-
point measurement should be performed as follows. III. EXPERIMENTAL
The field level should be scanned at a height of 0.2 m
A. Measurement under Ttransmission Lines
above the ground or the floor to find the value and the position
of the maximum field. The value and the position of the second A magnetic flux density meter with three coils (EMDEX II,
maximum field should be scanned on a circle with a radius of Enertech Consultants) was used. Resultant magnetic field in
0.5 m centered on the maximum position. Another root mean square was obtained.
measurement should be made at the point that is symmetric to Magnetic field was measured at 1 meter above the ground
the second maximum. A further two measurements should be following the single-point measurement procedure in seven
made, along the line perpendicular to the line passing the countries. Nominal voltages of transmission lines were 500-,
former three measurement points, at distances of 0.5 m on 400-, 275-, 220- and 115-kV. Measurement was carried out at
either side of the position of the maximum. every 1 meter along a path perpendicular to transmission lines
In cases where a person is not likely to lie on the ground or at the lowest clearance to draw magnetic field profile, from
the floor, the three-point measurement shall be used. which the maximum exposure level was obtained.

C. Average and Maximum Exposure Levels B. Measurement around Distribution Facilities


The average exposure level corresponds to a spatial average A magnetic flux density meter (Model 3470, HIOKI E. E.
of field over the entire human body to which the individual is Corporation) was used. The senor consists of three concentric
exposed to. It is defined as shown in Table 1 depending on coils and resultant magnetic flux density in root mean square
measurement procedures described above. can be obtained.
Magnetic field measurements were carried out five times in
TABLE I. AVERAGE EXPOSURE LEVEL different month of a year around six pad mounted transformers
(6,600V/105-210V), six switchgears (6,600V) and five vertical
Measurement
Procedure
Definition of Average Exposure Level cables (6,600V), which are installed on sidewalks in urban
areas and accessible by the public.
single-point measured field value

three-point arithmetic mean of the three field values


Since the height of any equipment was less than 1.5 m,
magnetic field was scanned at its top height and at a horizontal
five point arithmetic mean of the largest three field values distance of 0.2 m from its surface facing to pedestrian passage.
After finding the position of the maximum magnetic field, the
average exposure level was obtained by following the three-
The maximum exposure level is defined as the maximum of point measurement procedure.
the average exposure levels over the area of interest.
Then, magnetic field was scanned at its top height around
Beside power equipment, the maximum exposure level is equipment at a horizontal distance of 0.2 m from its surface at
obtained as follows: The magnetic field should be measured at appropriate intervals. After finding the position of the
a height of 1.0 m above the ground, around equipment at a maximum field, the maximum exposure level was obtained by
horizontal distance of 0.2 m from its surface, at appropriate performing the three-point measurement at the position.
intervals as shown in Fig. 2. In situations where the equipment
has a height less than 1.5 m, the field level should be scanned
at the top height of the equipment instead of 1.0 m. At the
position where the maximum field level is found, a three-point

Copyright 2014 IEICE


622
EMC’14/Tokyo 16A1-H1

IV. RESULTS AND DISCUSSION B. Around Distribution Facilities


The average and the maximum exposure levels of magnetic
A. Under Trasmission Lines field generated by six pad-mounted transformers are shown Fig.
Fig. 3 shows an example of magnetic field profile measured 5 (a) and (b), respectively. Fig. 6 (a) and (b) shows the average
at 1 m above the ground along a path perpendicular to 500 kV and the maximum exposure levels of magnetic field generated
transmission lines at the lowest clearance. From this figure, the by six switchgears, respectively. Vertical cables generate the
maximum exposure level of 2.02 μT can be obtained. maximum exposure level of magnetic fields shown in Fig. 7.
The maximum exposure levels of magnetic field under nine The average and the maximum exposure levels of magnetic
transmission lines are summarized in Fig. 4, where filled and field are much lower than the ICNIRP reference level of 200
unfilled bars indicate 60 Hz and 50 Hz in grid frequency, μT for any distribution equipment.
respectively. The maximum exposure level is less than 11 μT,
18
which is much lower than the reference level of 200 μT from
the ICNIRP Guidelines. 16

Average exposure level (μT)


14
12
2.5
10
8
2.0 a
6
Magnetic field (μT)

b
c

1.5 4
2
1.0 0
1 2 3 4 5 6

0.5 (a) Average exposure levels

18
0.0
16
Maximum exposure level (μT)

-25 -20 -15 -10 -5 0 5 10 15 20 25 30 35


Distance (m) 14
12
Fig. 3. Magnetic field profile along a path perpendicular to 500 kV
10
transmission lines at the lowest clearlance.
8
6
12
4
[μT]
level(μT)

10 2
exposure level

0
8 1 2 3 4 5 6
Maximumexposure

(b) Maximum exposure levels


6
Fig. 5. Average and Maximum exposure levels of magnetic field generated
4 by pad-mounted transformers.
Maximum

2 3.0

0 2.5
Average exposure level (μT)

500 500 500 500 400 400 275 220 115


2.0
Nominal voltage (kV)

Fig. 4. Maximum exposure levels of magnetic field generated by 1.5


transmission lines.
1.0

0.5

0.0
1 2 3 4 5 6

(a) Average exposure levels

Copyright 2014 IEICE


623
EMC’14/Tokyo 16A1-H1

3.5 [1] K. Isaka, N. Hayashi, Y. Yokoi and M. Okamoto, “Characteristics of


ground-level electric and magnetic fields generated by ac power
3.0 transmission lines”, International Symposium on Electromagnetic
Maximum exposure level (μT)

Compatibility, Vol. 2, pp. 511-514, 1989.


2.5 [2] A. E. Tzinevrakis, D. K. Tsanakas and E. I. Mimos, “Analytical
calculation of the electric field produced by single-circuit power lines”,
2.0 IEEE Trans. on Power Delivery, Vol. 23, No. 3, pp. 1495-1505, 2009.
[3] G. Mazzani, “The role played by current phase shift on magnetic field
1.5 established by ac double-circuit overhead transmission lines - Part I:
Static analysis”, IEEE Trans. on Power Delivery, Vol.32, No.2, pp. 939-
1.0 948, 2006.
[4] N. Hayashi, K. Isaka, H. Kume and Y. Yokoi, “Power frequency
0.5
magnetic field in a 187/66-kV electric power substation”, International
Symposium on Electromagnetic Compatibility, vol. 2, pp. 505-510,
0.0
1989.
1 2 3 4 5 6
[5] N. Goto, Y. Uga, K. Kato, M. Shimizu, A. Yoshida, H. Okubo,
(b) Maximum exposure levels “Investigation of magnetic field environment based on line current
condition in 77kV substation”, Trans. of IEE Japan, Vol. 121-B, No. 7,
pp. 874-880, 2001 (in Japanese).
Fig. 6. Average and maximum exposure levels of magnetic field generated
by switchgeras. [6] J. Lago, L. Skurcak, P. Bojda, M. Savcak, “Application of the
mathematical modeling on EHV substation’s electric and magnetic
fields at limit operating conditions”, CIGRE EMF-ELF, pp. 309-319,
4.0 Paris, 2011.
3.5 [7] Qingmin Li and Joseph D. Yan, “Computational investigation of the
Maximum exposure level (μT)

magnetic-field distribution in a 145-kV/40-kA rotary-arc circuit


3.0 breaker”, IEEE. Trans. on Power delivery, Vol. 21, No. 1, pp. 135-141,
2006.
2.5
[8] B.W. Jaekel, “General description and assessment concept for magnetic
2.0 field distributions caused by switchgear installation”, IEEE Trans. on
Power Delivery, Vol. 22, No. 1, pp. 167-177, 2007.
1.5 [9] I. Magne, F. Audran, E. Mayaudon, D. Clement, and F. Deschamps,
1.0 “50Hz electric and magnetic field measurements in high voltage
substations,” CIGRE EMF-ELF, Sarajevo, Paper 20, 2009.
0.5 [10] D. Clement, F. Deschamps, I. Magne, and M. Burceanu, “Inter-
laboratory 50 Hz EMF measurement,” presented at the BioEM, Davos,
0.0 Switzerland, P-194, 2009.
1 2 3 4 5
[11] K. Tanaka, Y. Mizuno, K. Naito, “Measurement of power frequency
electric and magnetic fields near power facilities in several countries”,
Fig. 7. Maximum exposure levels of magnetic field generated by vertical IEEE Trans. on Power Delivery, Vol. 26, No. 3, pp. 1508-1513, 2011.
cables. [12] S. Nuic, M. Veledar, E. Aganovic, Z. Bajamovic, S. Carsimanovcic, M.
Ljevak, “Electromagnetic fields and safety distances in the environment
of 400 kV overhead lines”, CIGRE EMF-ELF, pp. 89-94, Paris, 2011.
V. CONCLUSIONS
[13] L. Zhao, W. Gui-fang, J. Gio, J. Lu, “Measurement and analysis of
The average and the maximum exposure levels of magnetic electromagnetic environments of 1000kV UHV AC transmission project
field generated by transmission lines and power distribution in China”, CIGRE EMF-ELF, pp. 125-135, Paris, 2011.
equipment installed on sidewalks were evaluated in accordance [14] IEC 62110, “Electric and magnetic field levels generated by AC power
systems - Measurement procedures with regard to public exposure”,
with IEC 62110. They are much smaller than the reference 2009.
levels from the ICNIRP Guidelines.
[15] ICNIRP, “Guidelines for limiting exposure to time-varying electric and
Further measurements is planned to collect much data. A magnetic fields (1 Hz to 100 kHz), Health Physics, Vol. 99, No. 6, pp.
818-836, 2010.
method will be discussed to estimate the average and the
maximum exposure levels in the basis of current flowing into [16] IEEE Std C95.6, “IEEE standard for safety levels with respect to human
exposure to electromagnetic fields, 0-3 kHz”, 2002.
power distribution equipment.

REFERENCES

Copyright 2014 IEICE


624

You might also like