Professional Documents
Culture Documents
Chicago Pneumatic CPE 100-150 CPE 125-250 Instruction Book en 2205601002
Chicago Pneumatic CPE 100-150 CPE 125-250 Instruction Book en 2205601002
2205 6010 02
Edition 07/2013
CPE125-180
CPVS125-180
I
Instruction Book
Instruction Book
Table of Content
2 Introduction .......................................................... 7
1 Safety Precautions
1.1 Safety Icons
Interpretation
Caution
Warning
Important note
All responsibility for any damage or injury resulting from neglecting these precautions, or non observance
of the normal caution and care required for installation, operation, maintenance and repair, even if not
expressly stated, will be disclaimed by the manufacturer.
P a g e |1
Instruction Book
P a g e |2
Instruction Book
The following safety measures, i.e. safety measures during operation process and safety measures
during maintenance process may also be referred to.
These preventive measures apply to machining, air consumed or inert gases.
The treatment of any other gases shall follow the additional safety measures generally applied to other
products uncovered here.
Some preventive measures are universal to a certain degree and cover a number of machine types and
equipment; thus, some instructions may not apply to your machine.
General precautions
1. The operator must employ safe working practices and observe all related work safety requirements and
regulations.
2. If any of the following statements does not comply with the applicable legislation, the stricter of the two shall
apply.
3. Installation, operation, maintenance and repair work must only be performed by authorised, trained, specialised
personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality, the
compressed air must be adequately purified according to the applicable legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor, press
the emergency stop button, switch off the voltage and depressurise the compressor. In addition, the power
isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never use
the air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme caution and
wear eye protection.
P a g e |3
Instruction Book
P a g e |4
Instruction Book
3. Installation, operation, maintenance and repair work must only be performed by authorised, trained, specialised
personnel.
4. The compressor is not considered capable of producing air of breathing quality. For air of breathing quality, the
compressed air must be adequately purified according to local legislation and standards.
5. Before any maintenance, repair work, adjustment or any other non-routine checks, stop the compressor, press
the emergency stop button, switch off the voltage and depressurise the compressor. In addition, the power
isolating switch must be opened and locked.
6. Never play with compressed air. Do not apply the air to your skin or direct an air stream at people. Never use the
air to clean dirt from your clothes. When using the air to clean equipment, do so with extreme caution and wear
eye protection.
Precautions during maintenance or repair
1. Please always use appropriate protective articles (e.g. safety glasses, gloves and safety shoes, etc.).
2. Use only the correct tools for maintenance and repair work.
3. Use only genuine spare parts.
4. All maintenance work shall only be undertaken when the machine has cooled down.
5. A warning sign bearing a legend such as "work in progress; do not start" shall be attached to the starting
equipment.
6. Persons switching on remotely controlled machines shall take adequate precautions to ensure that there is no
one checking or working on the machine. To this end, a suitable notice shall be affixed to the remote start
equipment.
7. Close the compressor air outlet valve before connecting or disconnecting a pipe.
8. Before removing any pressurized component, effectively isolate the machine from all sources of pressure and
relieve the entire system of pressure.
9. Never use flammable solvents or carbon tetrachloride for cleaning parts. Take safety precautions against toxic
vapours of cleaning liquids.
10. Observe cleanliness during maintenance and repair. Keep dirt away by covering the parts and exposed
openings with a clean cloth, paper or tape.
11. Never weld or perform any operation involving heat near the oil system. Vessels must be completely purged,
e.g. by steam-cleaning, before carrying out such operations. Never weld on, or in any way modify, pressure
vessels.
12. Whenever there is an indication or any suspicion that an internal part of a machine is overheated, the machine
shall be stopped but no inspection covers shall be opened before sufficient cooling time has elapsed; this to
avoid the risk of spontaneous ignition of the oil vapour when air is entering.
13. Never use a light source with open flame for inspecting the interior of a machine, pressure vessel, etc.
14. Make sure that no tools, loose parts or rags are left in or on the machine.
15. All regulating and safety devices shall be maintained with due care to ensure that they function properly. They
may not be put out of action.
16. Before clearing the machine for use after maintenance or overhaul, check that operating pressures,
temperatures and time settings are correct. Check that all control and shut-down devices are fitted and that they
function correctly. If removed, check that the coupling guard of the compressor drive shaft has been reinstalled.
17. Every time the separator element is renewed, examine the discharge pipe and the inside of the oil separator
vessel for carbon deposits; if excessive, the deposits should be removed.
18. Protect the motor, air filter, electrical and regulating components, etc. to prevent moisture from entering them,
e.g. when steam-cleaning.
19. Make sure that all sound-damping material and vibration dampers, e.g. damping material on the bodywork and
in the air inlet and outlet systems of the compressor, are in good condition. If damaged, replace it by genuine
P a g e |5
Instruction Book
material from the manufacturer to prevent the sound pressure level from increasing.
20. Never use caustic solvents which can damage materials of the air net, e.g. polycarbonate base.
21. The following safety precautions are stressed when handling refrigerant:
z Never inhale refrigerant vapours. Check that the working area is adequately ventilated; if required, use
breathing protection.
z Always wear special gloves. In case of refrigerant contact with the skin, rinse the skin with water. If liquid
refrigerant contacts the skin through clothing, never tear off or remove the latter; flush abundantly with
fresh water over the clothing until all refrigerant is flushed away; then seek medical first aid.
22. Protect hands to avoid injury from hot machine parts, e.g. during draining of oil.
The following safety measures, i.e. safety measures in operation process and safety measures in
maintenance process may also be referred to.
These preventive measures apply to machining, air consumed or inert gases.
The treatment of any other gases shall follow the additional safety measures generally applied to other
products uncovered here.
Some preventive measures are universal to a certain degree and cover a number of machine types and
equipment; thus, some instructions may not apply to your machine.
P a g e |6
Instruction Book
2 Introduction
1 2 3 4 5 6 7
Safety Valve Danger! Irrespirable High-tempera Noise With Internal The Fan May
Electric High ture Parts Pressure Injure Your
Voltage! Hands
P a g e |7
Instruction Book
P a g e |8
Instruction Book
safety valve The safety valve installed on the vessel, in case the capacity controlling is failure or the separator
clogged, the pressure in the vessel will rise continuously, when reaches to the safety valve set point, the valve will
open and releases the vessel pressure to the safe pressure. The safety valve will be closed automatically when the
pressure drops to the closing pressure of safety valve.
High pressure protection When working pressure goes beyond the setting value (rated working
pressure+0.12MPa), the controller will cut off the power source automatically to enable the compressor will
emergency stop. A message will be displayed on the display.
High temperature protection when Element discharge temperature reaches to the set point (115℃), the
compressor will be stopped automatically.
Low cooling water flow protection When there is a shortfall of water cooling or water flow, the water flow
switch will act. If the water flow fails to come back to normal in 20 seconds and the exhuast temperature has risen to
110℃, then the power source of motor will be cut off automatically and the compressor will stop.
Oil filter, oil separator and air filter blocked warning When the oil filter, oil separator or air filter is blocked
and the differential pressure goes beyond the setting value, the differential pressure indicator will act and there will be
a prompt of "replacing new parts" on the display screen of the control panel.
Electric protection functions: Phase sequence protection (preventing the inversion of compressor) and open
phase function as well as motor's thermal overload protection function.
P a g e |9
Instruction Book
14
6
7
12 10
13 8
20
Cooling water 11
Inlet
21
Cooling water
Outlet 9
18 17 15
16
22
23
19
P a g e | 10
Instruction Book
6
7
22 20
10
8
18 14 13 12
11
9
17 15
21 16
19
P a g e | 11
Instruction Book
14
6
7
12 10
13 8
20
Cooling water 11
Inlet
21
Cooling water
Outlet 9
18 17 15
16
22
23
19
P a g e | 12
Instruction Book
To achieve superior pre-separation effect, detaching of the end cover of filter and dust remover
during the running of machine is forbidden.
z Unloader
Unloader is composed of valve housing, piston, piston rod, upper cover, valve, solenoid valve and sealing ring,
etc. The functions of unloader are: load and unload compressor. During compressor starting, the unloader closed to
reduce starting load of compressor, after starting, unloader opening completely, compressor is fully loading, if the air
consumption is less than the capacity of the compressor, the pressure of the net will go up, when it reaches the upper
limit pressure, the solenoid valve on the unloader is de-energized by the PLC, the unloader closed and the
compressor is unloading, the pressure in the vessel is blown down to 0.07-0.09Mpa, if air consumption continue, the
pressure of the net will go down, when it reaches the lower limit pressure, the solenoid valve on the unloader is
energized by the PLC, the unloader open and the compressor is loading again. When the compressor stop, the
unloader will vent the compressed air in the vessel.
The flexibility of the starting/closing action of unloader valve is vital to the reliability of compressor. Therefore,
unloader should subject to scheduled maintenance (once per 8000 hours, at least once per year) to keep it in good
working condition.
P a g e | 13
Instruction Book
P a g e | 14
Instruction Book
z Cooler
Cooler is designed to cool down the compressed air exhausted from compressor and the lubricating oil.
plate-fin cooler, completely made up of aluminium alloy materials by welding, is used in air-cooled unit; oil cooler and
after-cooler used in water-cooled unit are both shell and tube high-efficiency coolers, the helical structure inside of
which improves the heat exchange effect of cooler.
A large quantity of heat produced by the compressor is taken away by lubricating oil and then by the cooling air
through forced convection in oil cooler (cooling water for water-cooled machine type). Thermal resistance in the air is
dominant in the heat exchange process of air-cooled machine type, thus the cooling fin and tube sheet surface shall
always be kept clean. Large quantity of oil stain and dirt (scale for water-cooled unit) shall be cleared up on a regular
basis, if any.
z Water separator
The condensate water is separated in the water separator and then is drained out by the solenoid valve.
Y-type strainer at the front end of blowoff valve needs regular maintenance. The first running-in
of a new machine lasts for 300 hours and regular cleaning is required at an interval of 2000
hours afterwards.
P a g e | 15
Instruction Book
z Thermostatic valve
The thermostatic valve controls the Element outlet
temperature not lower than the dew point to protect the
condensate forming in vessel. The condensate water will
short lifetime of the oil. The thermostatic valve keeps the
Element outlet temperature always higher than dew point.
The operating principle is as follows:oil from the
separation vessel enters into t thermostatic valve. All
bypass orifices of thermostatic valve will open when the
temperature is below 70℃ and part of the hot oil directly
enters into the elememt; when the temperature is above
70℃, the thermostatic valve element will stretch out to push the piston forward and begin to close bypass oil
gradually. The amount being closed depends on the oil inlet temperature. When the oil inlet temperature is higher, all
bypass oil will be closed and all the oil will enter into the cooler and be cooled down. Temperature control valve
should subject to scheduled maintenance (once per 8000 hours, at least once per year) to keep it in good working
condition.
z Oil filter
Oil filter functions to filter the particles, dust and other foreign matters in
lubricating oil during its circulation to guarantee the operation of compressor. It
should be replaced after 300 hours' running of new machine and be replaced
regularly at an interval of 2000 hours afterwards. Or, it should be replaced when the
pressure drop between the pressure before filtering and the oil injection pressure is
above 0.13Mpa (warning will be displayed on PLC) to guarantee the oil supply and
cooling effect of the machine.
P a g e | 16
Instruction Book
P a g e | 17
Instruction Book
3.Installation
150mm
Concrete plane
100mm
100mm
Foundation
1. Standard, flat and industrial floor able to afford the weight of machine must be used (referring to the Ground Plot
for the details).
2. Compressor must be mounted at the 150mm high cement platform (see the drawing below) so as to connect
inlet and outlet piping system.
Ventilation
1. When the machine is working, the temperature at machine room should be kept within 1~46℃.
2. Machine room space: refer to (3.4 Installtion Propose)
3. Two air vents must be provided for air-cooled machine room, the minimum area of air vents shall be no less
than 1.5 ㎡.
The first air vent is overhead for exhausting hot air; the second air vent is in the lower for intaking cold air from
the outside. If there is too much dust in the environment, the mounting of filter plate shall be recommended;
4. Hot air exhausted by air-cooled machine type should be exhausted with pipe;
The minimum area of pipe shall be no less than 1.5 ㎡, and the pressure drop at outlet airduct shall be no more
than 3mm water column, or the cooling effect of the cooler will be affected. Pressure drop at outlet airduct may
be reduced by the installation of exhaust fan. The exhaust fan capacity shall not be lower than that specified
below.
Compressor Cooling fan
power (kw) capacity (m³/h)
90-132 20000
P a g e | 18
Instruction Book
OOBA
Check carefully for damage after unpacking the machine. If there is any doubt, please do not use the machine
and please contact with the Service Department of manufacturer or the supplier. Packing materials (plastic bag,
cystosepiment, iron nail and woods, etc.) shall be properly disposed so as to avoid environmental pollution or
personal injury.
P a g e | 19
Instruction Book
(Variable Speed)
Hot air out
1300
Cooling air in
925
2120
Outlet DN65 PN1.6
1025
645
80
80
80
40
510
1600 58
620 980
30
2400
330
φ1
00
4-φ
20 1930
Cable inlet
1390
1550
00
φ1
310
739 310
Technical specification
TYPE CPE125(CPVS125) CPE150(CPVS150) CPE180(CPVS180)
Pressure (Mpa) 0.5 0.7 0.8 1.0 1.3 0.5 0.7 0.8 1.0 1.3 0.7 0.8 1.0 1.3
3
FAD (m /min) 21.1 17.2 17.0 14.2 12.5 24.4 21.0 20.6 17.0 14.0 24.2 24.0 20.5 17.0
Noise dB(A) 76 76 76
P a g e | 20
Instruction Book
(Variable Speed)
330 646
Cooling air in
367
2120
1280
80
80
80
40
510
1600 58
620 980
2400
φ100
330
1930
4-φ
20 750 435
Cable inlet
570
460 470
1550
460
0
φ 10
310
Technical specificationN
TYPE CPE125W(CPVS125W) CPE150W(CPVS150W) CPE180W(CPVS180W)
Pressure (Mpa) 0.7 0.8 1.0 1.3 0.7 0.8 1.0 1.3 0.7 0.8 1.0 1.3
FAD (m3/min) 17.2 17.0 14.2 12.5 21.0 20.6 17.0 14.0 24.2 24.0 20.5 17.0
Noise . dB(A) 76 76 76
Note1: Cooling water temp. <=35℃, pressure 0.2Mpa-0.6Mpa, with min flow, temp. diff 24℃; with max flow,
temp. diff 8℃. Water flow shall be determined according to the water quality.
Note2: Voltage Supply 380V/50Hz
Important interpretation
The measurement of sound pressure level shall be conducted according to PNEUROP
PN8NTC2.2 and in free field 1m away (3.281 ft). Tolerance of 3dB is acceptable.
P a g e | 21
Instruction Book
R1
45
R7
0
00
1450
〉2500
200
250 Canvas
750
804
Air intake
150
Concrete plane
Cable inlet(φ100)
00
15
150
0
150
0
00
15
Spare cable inlet(φ100)
Air intake
Concrete plane
P a g e | 22
Instruction Book
Description
1. Install the compressor on level floor suit for bearing its weight.
2. The recommended minimum distance between the top of compressor and the ceiling is 1.5m (58.5 inch) for the
convenience of ventilation and lifting.
3. While piping, all pipes and pipe joints should fit to the rated pressure, use of elbows and various valve banks
should be reduced as far as possible to reduce the pressure loss.
The pressure drop of delivery pipe can be calculated by the following formula:
dp = (L×450×Qc1.85)/(d5×P)
z dp = pressure drop (recommended maximum value= 0.1 bar)
z L = length of delivery pipe in the unit of m
z d = internal diameter of delivery pipe in the unit of mm
z P = absolute pressure at the outlet of compressor in the unit of bar (a)
z Qc = air displacement of compressor in the unit of 1/s
4. Air outlet grid and ventilation fan mounting should always avoid hot air goes into the compressor.
Ventilation air speed should be lower 5 m/s (16.5 inch/s).
Ventilation air flow can calculation by :
For water cooled unit: Qv = 0.1N/dT
For air cooled unit: Qv = 0.9N/dT
z Qv = ventilation air flow m3/s
z N = shaft power kW
z dT = compressor room temperature rise ℃
5. The blow-off pipe can not be soaked in the water of collector so as to observe the flow of condensed water.
6. Check the electrical connection for the compliance with local regulations. The installation must be connected to
the earth and fuse must be mounted in each phase to prevent short circuit. Isolating switch must be installed
around the compressor.
7. For water-cooled unit, the water supply pressure of cooling water should be 0.2-0.6MPa. Valves should be
mounted at both the inlet and outlet (see the drawing). It is recommended that a strainer should be provided at
the water inlet to filter particles greater than 0.1mm. The water supply shall not be lower than:
z For once-through water supply whose quality is in keeping with the regulation, the water supply= the quantity
specified in the Technical specification Table.
z For circulating water, the water supply= the quantity specified in 24x Technical specification/temperature
difference of cooling tower.
z If the quality of cooling water can not meet the specified requirements, water supply shall be increased to keep
the discharge temperature within 50℃.
Water inlet Manometer
z Water supply= quantity specified in 24x
Technical specification /temperature Water outlet Thermometer
Ball valve G1/2
difference between water inlet and
Ball valve G1/2
outlet Ball valve G1/2
Drain
P a g e | 23
Instruction Book
System type
First, you must consider the system you treat. Is it closed or open? This is very important.
In closed system, the same cooling water circulates in the system without contacting the air.
Symbol Interpretation
pHs Actual pH value of water sample (at room temperature)
pHs Saturated pH value
P a g e | 24
Instruction Book
P a g e | 25
Instruction Book
This table suggests that distilled water and softened water can never be used, for their RSI is above 11.
RSI only indicates the balance between scaling and descaling. RSI conditions indicate that good cooling water may
still be unacceptable due to other factors.
According to the table above, the RSI index should be in between 5.6 and 7.5. Otherwise, please contact with the
relevant expert.
pH
pH results have been counted in Ryznar indices. Moreover, pH itself has some additional restrictions: 6.8<pH<8.5
Chloride (CL-)
Chloride ion will lead to pitting corrosion on stainless steel. Its concentration should be defined as:
Closed cooling system: chloride <500ppm
Open cooling system: chloride <150ppm
However, if the water is scaling, then lower restriction should be adopted. (Please refer to "Ryznar stability index
(RSI)").
Free chlorine(Cl2)
The content shall not exceed 0.5ppm for a long time.
In case of short-time treatment, the time shall be limited at 30 minutes each day and the maximum content of free
chlorine shall be 2ppm.
Sulphate(SO4-)
Closed cooling system: sulphate <400ppm
Open cooling system: sulphate <150ppm
P a g e | 26
Instruction Book
Hardness of carbonate
losed cooling system: 50-1000ppm CaCO3
Open cooling system: 50-500ppm CaCO3
HCO3-/SO42- should be >1
Ammonia
<0.5ppm
Copper
<1ppm
Organic matter
Algae-free category
Oil-free category
Suspended particles
The size of insoluble particles <1mm
<10ppm
Remarks
Chemical reaction may occur between chlorides and sulphate.
In open system, the quadratic sum of the value of chlorides and sulphate shall not exceed
85,000.
The quadratic sum of recirculation system with proper control and treatment measures may be
as high as 520,000.
Please note that the value of sulphate must include any sulfite contained in water.
P a g e | 27
Instruction Book
3.6 Identify
Water system
1 2 3
Electrial system
1 2 3 4
Other location
1 2 3 4 5 6 7
8 9 11
Please cut off
the power and
depressurize the
compressor
Please read the Instruction before Special lubricating oil for compressor
Manual before starting the maintenance
compressor
P a g e | 28
P a g e | 29
C146 series service tag and service kit
12
Instruction Book
Instruction Book
4 Operation
Operators must implement all the relevant safety measures, including those covered in this
Manual.
Electrical safety
To keep the protection level of electric room and prevent the components from being affected by
dust in the environment, please make sure that correct cable coupling sleeve will be used when
connecting the cable to compressor.
Protection level of frequency converter
Compressor under the control of frequency converter (VSD) can be mounted indoor only, and
must be equipped with sufficient ventilation and filtration conditions to prevent dust from being
deposit in the environment. If such compressor is going to be mounted at places with
conductive dust, then corresponding measures should be taken in the mounting or
commissioning process. Please contact with the manufacturer. Optional parts for rain
protection are not provided for frequency converter-driven compressor.
Environmental condition
Action must be taken if the ambient or air inlet temperature is below 1℃ or above 46℃.
Please contact with the manufacturer. if the machine is operated altitude above 1000m (3300 feet).
P a g e | 30
Instruction Book
11 Before start up,make sure that transport red pads have been effectively removed.
Under unloader condition, the oil pressure must be kept within 0.07~0.09MPa, or system
lubrication will be affected. In case of defficient oil pressure, the machine should be stopped
immediately to check the leakage of the system.
P a g e | 31
Instruction Book
Generally speaking, power switched shall not be pulled down until 2~5 minutes after the
shutdown in a bid to guarantee that the compressed air in the vessel is emptied through
blow-off solenoid valve, so that there will be no load during the next start-up.
In winter, cooling water valve (water-cooled unit) shall be closed and cooling water in oil
cooler (see the drawing below) shall be drained off, lest freezing should damage the cooler
due to swelling.
P a g e | 32
Instruction Book
4. In case of excessively high exhaust temperature (or pressure) and warning displayed on the controller screen,
the compressor will stop automatically and the display screen will display over-temperature (over-pressure)
prompt, please restart after finding out the reason and troubleshooting.
Please perform the following operations when the service life of compressor expires:
Step Operation
1 Close the air outlet valve and stop the compressor.
2 Cut off the power supply and disconnect the main power.
3 Close the air oulet valve and depressurize the parts of air pipe network.
Disconnect the air outlet pipe of the compressor.
4 Discharge water, oil and condensed water circuit.
5 Disconnect the condensed water pipe of compressor and condensed water blow-off pipe network.
6 Disconnect cooling water inlet and outlet piping.
Warning
5 Maintenance
Guarantee that the operate can see the whole machine at the operation panel and that no irrelevant
staff stays beside the machine.
5.1 General
Daily maintenance must be performed pursuant to the specified maintenance forms.
Prior to any maintenance or repairing, please press down the stop button. After the compressor being
stopped, press down the emergency stop button, cut off power supply and depressurize the compressor.
Prevent accidental power-on.
Please comply with all the relevant descriptions in the "safety measures" part.
P a g e | 33
Instruction Book
Air filter element Clean the dust on the ★ According to the ambient
condition to long or short the
surface period.
Replacement must be
performed at least once per
year.
Oil filter Change a new one ★ Oil filter Change a new one after
300 hours for the first time and
replace at an interval of 2000
hours afterwards.
Oil separator Change a new one ★ The max. service time is 4000
hours.
Oil stop valve Check and Maintain ★ At least once per year
quality
tools
P a g e | 34
Instruction Book
connection
Administration of Quality
Thermostat Valve Change the maintenance kit ★ At least once per year
Min. pressure valve Change the maintenance kit ★ At least once per year
Piping Check/Change ★
Change ★
regreasing dateplate
P a g e | 35
Instruction Book
Check the seal ring of filter element for the intactness before assembly to guarantee the sealing
performance.
P a g e | 36
Instruction Book
P a g e | 37
Instruction Book
Oil volume for water-cooled unit Oil volume for air-cooled unit
90/110kW 46 57
132kW 63 60
P a g e | 38
Instruction Book
While mounting the oil pumping pipe, ensure that the pipe is about 3mm away from the bottom of
olein separator.
Appropriately extend or shorten the cleaning time according to the water quality.
P a g e | 39
Instruction Book
In case of serious scaling on oil cooler which can not be satisfactorily cleaned with the said
method, you may dismount the oil cooler separately, open the end covers at both ends and remove
scales with dedicate wire brush or other tools.
If the cleaning of medium side of cooler can not lower the temperature effectively, then the oil side should be cleaned.
Cleaning procedures of oil side of water cooler:
Step Operation
1 Stop the compressor.
2 Cut off the power supply and disconnect the compressor main power.
3 Turn off air outlet valve and depressurize.
Disconnect the air outlet pipe of compressor. Ensure that there is no pressure in the machine.
4 Take the inlet and outlet oil pipes apart.
5 Soak with cleaning solution or wash out through pump circulation (the effect of backflushing will be better).
6 Flush with clear water.
7 Dry it with dry gas or remove the water with dehydrated oil.
8 Mount the inlet and outlet oil pipes properly.
Solvent tank
Pump >50 liters
P a g e | 40
Instruction Book
Condensed Water Discharge Schedule should be formulated according to the humidity. The time
interval for the discharge of condensed water shall not exceed 300 hours.
Condensed water should be discharged upon stoppage or sufficient cooling of the machine and after
complete deposit of condensed water, such as before startup on morning.
P a g e | 41
Instruction Book
The opening pressure of the safety valve must lower than the vessel design pressure
P a g e | 42
Instruction Book
6 Problem solving
Warning
Before carrying out any maintenance, repair work or adjustment, stop the compressor, press the
emergency stop button and switch off the voltage. Close the air outlet valve and open the manual
condensate drain valves. Open and lock the isolating switch.
Prevent accidental power-on.
The operator must apply all relevant Safety precautions.
z The alarm LED will light up indicating that the temperature at the outlet of the compressor element is too high.
P a g e | 43
Instruction Book
z Choked airfilter lead to a reduced airflow. Check the cleanliness of the filter and the pressure drop over the
filters. Change if necessary.
7 Principal Data
7.4 Limit
Pressure limit
Max. setting pressure bar(e) Refer to the performance parameters of compressor
Max. cooling water pressure bar(e) 6
Min. cooling water pressure bar(e) 2
Temperature limit
Max. air inlet temperature ℃ 46
Min. air inlet temperature ℃ 0
Max. ambient temperature ℃ 40
Min. ambient temperature ℃ 0
Max. cooling water inlet temperature (open cooling system) ℃ 35
Min. water inlet temperature ℃ 1
Temperature difference between inlet and outlet with min. water flow ℃ 24
Temperature difference between inlet and outlet with max. water flow ℃ 8
Max. outlet temperature of element ℃ 115
P a g e | 45
Instruction Book
Details for maintenance: the item of air filter: cleaning, replacement; the item of lubricating oil: filling xx
liters, replace xx brand; other items: replacement.
P a g e | 46
Instruction Book
P a g e | 47