(m107 - Ele.2) - Pbtmz7546400 - Electrical Equipment List

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

00 30082018 FOR INFORMATION W. ZHENG YP. XUE XL.

ZHAO
DSGN CHKD APPD
REV. DATE DESCRIPTION
SIGNATURES
PROJECT NAME: PROJECT ID: IEP-000165 FORM SHEET
TERMOZIPA COAL-FIRED POWER PLANT NID-FF A4 1 of 1
TITLE: TZP/00/F/L1303600EI/LI/001_00_ELECTRICAL EQUIPMENT LIST

SUPERVISION OUTCOME

Esito Supervisione

00 PR

DATE Issue SUPERVISED CO-OPERATIONS APPROVED ISSUED


REV
Data Scope Esaminato COLLABORAZIONI Approvato Emesso

Document no. / Documento no. Security Index

Indice Sicurezza
PBTMZ75464
E&C submittal [ ] FOR APPROVAL [ X ] FOR INFORMATION [ ] NOT REQUESTED

Inoltra a E&C Per approvazione Per informazione Non richiesto

SYSTEM APPL. TO SECT. DOC. TYPE DISCIPLINE FILE

Sistema 530 Valido per sez. Tipo doc. EE Disciplina E File PBTMZ7546400

The Engineering and Construction approval refers to contractual requirements and L’approvazione di Ingegneria e Costruzioni è limitata agli aspetti relativi alle
clauses only. prescrizioni contrattuali. Rimangono pertanto a carico del Fornitore tutte le
All design responsibilities remain charged to the Supplier. responsabilità della progettazione.

PROJECT TERMOZIPA COAL-FIRED POWER PLANT


Progetto Life Extension and emissions improvement
CLIENT
ENEL GLOBAL THERMAL GENERATION
Cliente

JOB no : M107 Doc. no. …………………..

CLIENT SUBMITTAL [ ] FOR APPROVAL [ ] FOR INFORMATION [ ] NOT REQUESTED

Inoltro al Cliente Per approvazione Per informazione Non richiesto

ELECTRICAL EQUIPMENT LIST


No Equipment description Type Unit Quantity Remark
1 MCC
- 2 sets of incoming for MCC (NID 1 & 2)
Un=480V,60Hz, In=1250A,Ik=50kA,
- 2 sets of incoming for MCC (common part)
1.1 LV switchgear Form 3b,IP42 set 24
- 2 sets of bus coupling
- 18 sets of feeder

2 Distribution panel
2.1 DC sub distribution panel DC 125V, IP42 set 1 inside the Electrical buliding
2.2 UPS sub distribution panel AC 120V, 1Ph, 60Hz, IP42 set 1 inside the Electrical buliding
Lighting system sub distribution
2.3 Lighting & socket, IP42 set 1 inside the Electrical buliding
panel
Lighting system local distribution
2.4 Lighting & socket, IP55 set 3 For NID 1&2 area and common area
panel

3 MV motor VFD system


- inside the Electrical buliding
3.1 MV VFD system 4.16kV, 3Ph, 60Hz, IP31 set 2
- for booster fan motors (1800kW each)

* Note: all the above information is for prelimilary use only.