Shimla Site Report

1. 2 DG sets,910 KVA each to be proposed


2. DG-1 require acoustic room(L shape room)
3. DG-2 be proposed in the LT-Panel-2 room
4. Exhaust ventilation 1 no. extra required in DG-1 room
5. 8 no earth Pits to be proposed outside the building
6. Excavation and foundation for DGs
7. Gypsum partion dismantling 280sqft(LTpanel-2 room)
8. Wire,cables,conduits,cable trays,lights dismantling(LTpanel-2 room)
9. FM200 shifting-1nos.
10. Dismantling of MLTP-2
11. Existing MLTP-2 cable shifting to new MLTP(incomers and outgoings)
12. 2 nos DG placing,unloading manually
13. Brick work 230mm 280 Sqft
14. Fire door dismantling-1 nos
15. Revised floor alignment with tile 600mmx800mm.Need to change to 600mmx600mm
tiles.Existing pedestal availability less.( Proposed switch room). Room size:7.5mx11.5m
16. Old panels near toilet dismantling with cabling(Need to confirm)
17. (If new transformer proposed then 1no servo and LT kiosk not required)
18. Diesel storage yard -Location to be finalized in GF(990litres)
19. Water tanks with MS base to be sifted with lines
20. 2nos additional water tanks with fittings to be proposed(1000Lx2)
21. MS railing removing and refixing
22. Cement plaster on outer wall approx..700sqft.
23. MS Staircase with fittings approx..3 ton
24. 3HP motor for waterline with all fittings for PAC services-2nos
25. Waterline shifting in proposed panel room
26. Fire door opening-1nos
27. Fire door-double door(5ftx5ft)
28. Brick wall dismantling 200sqft(proposed MLTP-2 room)
29. MLTP-2 to be proposed in two parts considering space availability.
30. Glass door dismantling-2 nos(proposed MLTP-2 room)
31. Aluminium partition dismantling
32. Fire door supply and installation(5ftx8ft)
33. Fire door for proposed MLTP-1 room-(5ftx8ft)
34. Split ac dismantling,false ceiling dismantling,Gypsum partition with paint(150sqft),floor tile
dismantling(100sqft),Antistatic mat(700sqft),PCC for floor leveling(300sqft)
35. Light fixtures(2ftx2ft)-50 nos
36. Light points-50
37. Industrial sockets-20 nos
38. Paint interior-(5000sqft) or as per drawing
39. Paint exterior-(1000sqft) or as per drawing
40. 1nos. wash room renovation with required fittings
41. 1nos. new wash room with required fittings
42. PAC panel removal-2 nos
43. Existing 3DG dismantling with exhaust pipe
44. Approx.22m exhaust with 350mm dia pipe including all fittings and aluminium cladding(or
approx. 120m)
45. MS material for exhaust system-3ton
46. Hard soil(50 trolley)removal + earth pits