Professional Documents
Culture Documents
IZE04002 HKGSG V2 01manual
IZE04002 HKGSG V2 01manual
DACCS-PC Series
DACCS-HKGSG
Ver. 2.01
IZE-04002 Page 1
Before using this software
This program is the revised version of the heat load calculation software, which is designed for the
use in Japan. Thus the values such as the overall heat transfer coefficient of outer wall assembly,
and the number of persons and personnel clarification according to the usage of building, which is
automatically set, are determined based on typical usage in Japan. Therefore, you need to check the
data input automatically and amend them if necessary.
Agreement
IZE-04002 Page 2
Table of Contents
IZE-04002 Page 3
1.Introduction
1.1 Outline
DACCS-HKGSG program uses a steady-state load calculation method to compute heat load over a 24-hour period
(1 day) on a summer day and a winter day. It also applies effective temperature differences in consideration of
the effect of heat accumulated in the walls, since the heat load received from strong sunlight in summer through
outer walls and roofs is substantial.
The program contains 24-hour weather condition data of major cities for summer and winter (TAC 5%). The
standard design data include weather data of 140 countries, and it is based on climate data of the British
Meteorological Office and Japan Meteorological Agency.
1.2 Features
IZE-04002 Page 4
2.Software Setup
IZE-04002 Page 5
3.Operation Flow
DACCS-HKGSG is designed to enable everyone to carry out an accurate* load calculation easily and
quickly. Users can operate it only by inputting data along with the functions from [1. Project Outline] to [4. Exit]
on its main menu.
*Though computers provide accurate calculation results normally, it can be unreliable if the input data itself is not
appropriate.
Main Menu
IZE-04002 Page 6
4.Starting the Software
As soon as program setup is completed, a "DACCS-PC" folder (B) will be created in "Program" folder (A) at the
start menu. Program short-cut menu (C) will also be created inside the "DACCS-PC" folder. Clicking on this
short-cut menu can start the application program.
B C
IZE-04002 Page 7
5.Data Input Method
IZE-04002 Page 8
5.2 Data Input
Concerning the following two points that sunlight and outside air temperature affects the outer wall and roof, and that
the heat storing capacity of the wall generates the time lag in heat transmission, the program adopts effective
.
temperature differences.
Depending on wall material and thickness, values of effective temperature difference are designated in Wall Type I, II,
III, IV and S. (See the Appendix (p.45).)
IZE-04002 Page 9
5.2.2 Change Design Data
You can change the default values of the weather
data and heat transfer coefficients, which are
categorized as a “ Standard Data”,with Design
Data function, if necessary.
*Revised data with this function is applicable
only to that relevant project.
Design Data = the default (initial) values for the weather data and heat transfer coefficients (= part of a
Standard Data) for each room.
Standard Data = the data which are automatically determined according to the room type. (= number of
persons, personnel calorific volume per person, number of infiltration ventilation, schedule, coefficient of internal
temperature difference, lighting and blind type)
5.3 Data Input [Room Data]
Following specification can be input.
- Room name
- Floor no.
[Flow of Room Data Input] - Number of rooms
- Usage of room
- Ventilation system
Room Specification Input - With or without ceiling board
- Floor area
- Ceiling height
Standard Data Change
- Non-conditioned ceiling area
- Non-conditioned floor area,
End of Add Room and Room Spec Change Input - Calorific volume from equipment
- Outer wall length
- Window area on outer wall
- Non-conditioned inner wall length
IZE-04002 Page 10
5.3.2 Add Room - Room Spec Input
You can input room data (= room specification) with Add function.
Clicking the Add button, the room data input screen will appear.
-Room Name
Input the room name within 20 characters.
(It will be printed on hardcopy.)
-Floor
Input a floor number from –5* to 99.
*Use a negative (-) value for underground floors.
-Qty
Input the number of same-type rooms* from 1 to 99.
(Heat loads of all same-type rooms are added in the heat load table.)
*"Same-type room" means a room having the same structure, same size, same purpose and same next room
conditions in the same building. (Ex. rooms in a hotel, classrooms in a school)
-System
Input the system number* from 1 to 999.
*It is used to calculate a system heat load. (If heat load is not calculated for individual systems, input "1.")
-Usage of Room
Select a type of room usage. If you select "Others", you can input any name within 10 characters.
Note: Once selecting room usage, some values such as the number of persons, personnel calorific volume per
person, number of infiltration ventilation, schedule, coefficient of internal temperature difference, lighting and
blind type will be automatically optimized according to the Usage of Room. These data are indicated as a
“Standard Data” . (See Appendixes for details (p.40).)
*If you select “ , the same standard data as for “
Others” Office”is optimized for this type.
IZE-04002 Page 11
-Ventilation System
Select a ventilation system from the following options:
Natural ventilation: Only an infiltration heat load is incorporated in calculation.
Ventilation Fan: An infiltration heat load and outside air heat load are incorporated in calculation.
Total heat exchanger: An infiltration heat load and outside air heat load minus a total heat exchanger
heat load are incorporated in calculation.
Note: Depending on the ventilation system, calculation method of the infiltration heat
load* and outdoor air heat load** are changed.
*Infiltration heat load A heat load of drafts coming through the doors and the gap
between the windows and outer walls.
**Outside air heat load A heat load of outside air circulated to the room artificially by
the mechanical ventilation systems.
-Ceiling Board
Select "Avail" (=available) or "No ceiling" depending on if the room has a ceiling board or not.
Note: Depending on whether the room has a ceiling board or not, heat transfer coefficients
of roof and ceiling are changed. (See the Appendixes in details. => p.41)
-Floor Area
Input the floor area of the room from 0 to 9999.9 (m2).
*It is used to calculate the heat load of the room per square
meter.
-Ceiling Height
ceiling board if the room has a ceiling board.
Input the floor height (=the distance between the
floor surfaces) if the room has no ceiling board.
*The value should be from 0 to 99.9.
*It is used to calculate the outer wall area.
IZE-04002 Page 12
. Non-Conditioned Floor Area
Input the ceiling area to each entering field 0 to 9999.9 (m2).
Each field is categorized depending on the situation under the ceiling.
-Earth Floor: Floor area faced on the earth (without underground)
-Air Layer Exist: Floor area where air conditioner is not used in the room below
-Air Layer No: Floor area where air conditioner is not used in the room below
-Pilotis: Floor area faced to the outside air (=pilotis)
Note: In the case of an underground wall (= when a negative (-) sign is attached in front of the outer wall length), total
"earth floor" area is calculated as an "underground earth" floor area.
(Due to different heat transfer coefficient and temperature difference value, the heat load of earth floor is changed.)
Pilotis 19.5
ATTENTION: Do not input the air-conditioned area since it is assumed that no heat transfer occurs with this area.
-Equipments
Input the calorific volume of the sensible heat and latent heat emitted from equipments, from -99999 to 300000
(kcal/h).
*It is possible to determine these values automatically with the Heat Source Input function (= input support
tool)shown below.
[Input Support Tool]
IZE-04002 Page 13
. Outer Wall Length Input the length of the wall that faces outside air or the underground earth (as in the
case of basement). (-999 to 999.9 m)
. Window Area on Outer Wall Input the area of windows which face outside air. (0 to 999.9 m2)
Example of input [Outer Wall Length / Window area / Inner Wall Length]
Note1: If the outer wall faces the underground earth, add a negative (-) sign to the length data.
Note2: Do not input the air-conditioned area since it is assumed that no heat transfer occurs with this area.
Note: By selecting "Usage of Room" as written above, the standard data corresponding to each usage will be
automatically determined. However, its initial values may not be applicable to some projects. In
this case, you need to change the condition of the standard data with this function
(See Appendixes for details of each initial value. => P.40)
IZE-04002 Page 14
5.3.3 Add Room –Other functional buttons
-Prev room / Next room button
Clicking these buttons, the room spec of the
previous room or next room will be displayed.
(These buttons are activated only when you
input more than two room specifications.)
-Add Room button *
Clicking this button, the original data is
automatically saved and the room spec screen
will be changed to input the new room data.
(This button is inactive when you open the
[Room spec] screen that has been already
saved.)
-OK button
Click to save the input data. Then the [Room spec] screen is closed and the input room is added to the list.
-Cancel button
Click it if you don’
t want to save the input data. The [Room spec] screen is closed and no room will be added to
the list.
IZE-04002 Page 15
5.3.4 Change Room
You can change the input room data with Change function.
1) Change the specific room data
Selecting the room you want to change the data from
the list (Section A) and clicking the Change button,
the following screen will appear.
Attention
Since changed data cannot be set back to original
settings anymore, be careful to use this function.
IZE-04002 Page 16
5.3.5 Delete Room
IZE-04002 Page 17
6.Data Change
There are two [Data Change] function in this program, [Change Design Data] and [Change Standard Data].
[Change Design Data]
You can change the initial values for the part of the standard data, which are applied to the whole project
[Change Standard Data]
You can change the values of the standard data for each room, which are applied to the relevant room
6.1 Standard Data Change in [Room Data]
Heat transfer coefficients for underground items can be changed only when the room is in the
underground floors. (The outer wall length is expressed in a negative value on a Room spec screen.)
IZE-04002 Page 18
The HKGSG uses effective temperature difference for outer
walls and roofs.
In effective temperature difference values, the solar heat
loads, outside air and the delay in heat transmissions caused
by the heat storing capacity of walls are taken into
consideration.
According to its material type and thickness, walls are generally categorized into Type I, II,
III and IV, as indicated in the wall type table (Appendix), and the specific effective
temperature difference is determined to each wall.
Furthermore, Type S is added to this program HKGSG, which is determined as having no
effective temperature difference value, and used for materials that do not store heat, such as slate roofs.
Clicking the Temp & Humid button, the screen shown below will appear. You can make necessary changes
within this screen.
IZE-04002 Page 19
6.1.4 Change of Schedule
Clicking the Schedule button, the screen shown at the
left will appear. You can make necessary changes within
this screen.
[Lighting / Persons (=Number of persons) / Equipment (=Operating rate of equipment with calorification
from internal equipment)]
You can set each operating rate for each hour of the day (24 hours) as you like. (0% to 100%)
*This rate is used in the heat load calculation.
*Though you can set it for the hour out of the operating time zone, it will not be used in heat load
calculation.
<Input Examples>
Situation Input
The equipment is always shut down at 4:00 => the calorification from internal equipment is 0% after 4:00.
Outside light is bright from 9:00 to 16:00 => 70% is used for the lighting setting during it.
Attention
Heat load calculation is performed to provide a safety margin (maximum load values) in its results.
Therefore, be sure to change the settings only when you confirm that the load reduction (setting change) occurs
without a fail.
IZE-04002 Page 20
6.1.5 Change of Others
Clicking the Others button, the screen shown below will appear. You can make necessary changes with it.
Note to change the settings in [Others]
Standard data in [Others] are greatly affected by the
room specification such as usage of room, floor
number, floor area, and ceiling height.
Thus, if you change them after changing the settings
in [Others], the standard data in [Others] are reset to
the initial values depending on the changed items.
*A caution message will appear to inform it.
IZE-04002 Page 21
[Infiltration]
Infiltration indicates the amount of outside air that comes into a room
through doors, gaps around window frames and gaps with outer walls. This
infiltration of outside air naturally occurs due to the temperature and
pressure difference between inside and outside or to wind pressure.
In this program, it is shown by the frequency (= number of times) that the room air is replaced by a ventilation
cycle method per hour. Though the initial value is different depending on the usage of room, you can manually
input it in this screen, referring to the table below.
[Safety Factor]
This setting is used to calculate the select heat load of air conditioner.
* The initial value is 1.05 for Cooling (in Summer) and 1.10 for Heating (in Winter).
* Select Heat Load (Required Capacity) = Total Heat Load x Safety Factor
[Lighting]
This data is used to calculate the heat load generated by lighting. Input the power
ratings (W) of the fluorescent lamps and the incandescent lamps.
*The initial value is different depending on the usage of room. (See Appendix.)
*Since lighting load is generally a positive factor in heating operation, it is not
added in calculation of the heating load.
[Internal Heat Gain in Heating (= Calorification from Internal Equipment in Heating Operation)]
Since the calorification from people, lighting and equipment offsets the external heat loss during heating
operation, it is not incorporated in conventional manual calculation in many cases. However, an excessive
safety margin can result in overrating of air conditioner capacity. This not only causes uneconomical operation
of air conditioners but also lowers the operating efficiency in normal condition.
To avoid them, you can incorporate a percentage of internal
calorification in heating operation into calculation of the heat load in
cooling operation in HKGSG. This setting can be made for each room..
*Initial setting is “
no consideration”.
<Example>
The following shows the cases that internal calorification may be
incorporated in heating.
(1) Extended air conditioner warming up time is acceptable.
(2) Steady internal calorification volume is expected.
(3) Calorification volume is excessively large.
* Note that heat load becomes smaller if internal heat gain is incorporated in heating.
IZE-04002 Page 22
[Window Type] and [Blind Type]
You can select the window type and blind type from the
list. Once you change them, the shading factor and heat
transfer coefficient used in the calculation of the heat load
from the glass area will be changed accordingly
.*The initial value for window type is “ Clear 5mm” . (= the normal glass: 5 mm)
*The initial value for blind type is different depending on the usage of room.
Selecting "Others" at the list of [Window Type], the screen at the left [Input Screen of Window Type Others]
will appear. You can input any settings as needed.
-Window Type Input the name of the window.
*It determines whether the latent heat load is added to the total heating load (= sensible heat load) or not.
Number of Persons]
You can change the number of persons in the room.
*Since the value of area per person is set according to the usage of room, the number of persons is changed if
the floor area is changed.
IZE-04002 Page 23
[Underground Wall Depth] *Only applicable when the room is in the underground
Input the under ground wall depth if the room is in the underground.
The HKGSG recognizes a wall as in underground if the outer wall
length has a negative (-) sign.
Since the external heat load of an underground wall (including semi-underground wall) is different
from that of a ground wall, HKGSG calculates it with a special calculation method.
*Another methods are used to calculate shallow underground wall and deep underground wall.
The initial value for shallow underground wall (-2.4 m or less)
= Floor height [ceiling height + attic height] x underground floor no.
(2) Deep underground walls (more than -2.4 m from ground surface)
For sections that are -2.4 m or more in depth, the heat load received from underground heat
(underground temperature) is obtained.
Underground wall heat load = Kb XAb X(Tr –Tg)
Kb: Heat transfer coefficient of underground wall (W/m2.K) / Ab: Underground wall area (m2)
Tx: Underground temperature at depth of x (m) / Ts: Highest outside air temperature in summer
To: Lowest outside air temperature in winter
IZE-04002 Page 24
6.1.6 Change of Canopy
Clicking on the Canopy button, the screen shown below will appear.
[Input Window and Canopy Screen]
After inputting the window and canopy dimensions, value of [Window area on Outer Wall] of the [Room spec]
screen becomes inactive as shown below.
IZE-04002 Page 25
6.1.7 Change of Material II
Clicking on the Material II button, the screen shown below will appear. Necessary change can be made with it.
On this screen, you can determine a maximum of two heat transfer coefficients and glass types for each
structure (outer wall, inner wall, window) in addition to the dimension and the heat transfer coefficient that is
determined on the [Room Spec] screen.
Input heat transfer coefficients (for both outer wall and inner wall) and window type in the same way as for the
dimension input on the "Room Spec" screen.
*Select necessary items from heat transfer coefficient, window type and dimension for data input.
<Example of use>
- The wall on the north side is different from the other walls in structure, and thus, different heat transfer
coefficient and wall type must be selected.
- Different heat transfer coefficient must be used for an entrance.
- Two window types must be used.
IZE-04002 Page 26
6.1.8 Change of Extension
Clicking the Extension button, the screen
shown at the right will appear. You can make
necessary changes within it.
IZE-04002 Page 27
6.2 Design Data Change in [Project Outline]
In the edit screen of [Project Outline], you can change the default value of weather data and heat coefficient.
-Change Shift
If you select this method, the boxes to input the temperature shift
for summer and winter will be activated. Input these values, which
should be different, and click the OK button. Then entire
temperature curve on [Change Design data (Weather Data)] screen
is shifted according to input values.
-Value Input
If you select this method, the temperature table on [Change Design
data (Weather Data)] screen will be activated, and you can directly
input numerical data.
Note: Humidity Data Display
It is not a problem that the relative humidity values (%) on the table remain the same even after you changed the
weather data by [Change Shift] function. This is because the relative humidity is automatically converted to the
absolute humidity on the program and its converted humidity is used to calculate the heat load of the outside air
temperature after the change. Thus, you don’
t need to care about it even if you can’
t see any change on the table.
IZE-04002 Page 28
6.2.2 Design Data Change [Heat Transfer Coefficient]
Selecting [Overall Heat Transfer Coeff] on the
[Design Data Change] screen shown above, the
screen at the left will appear.
You can change the initial values for heat transfer
coefficients applied for the project.
IZE-04002 Page 29
7.Sum and Print
To meet the diverse needs of users and to provide information in the most suitable arrangement, HKGSG
offers a variety of formats to output the calculation result.
7.1 Flowchart of Sum and Print Function
Calculation Result Display - - - You can see the result on the screen display.
IZE-04002 Page 30
Unit can be switched between W and kcal/h.
Clicking each button on the lower right, each corresponding table will appear as follows;
- Clicking Table of Room button, [Table of Room Heat Load] will appear.
[Room Load Table]
IZE-04002 Page 31
- Clicking Table of System button, [Table of System Heat Load Sum] will appear.
[Table of System Heat Load Sum]
- Clicking Print button, setup screen for the printing form will appear.
Print Setup
You can make various setting for printing form as
follows;
[Cover] Input the Messrs., company name,
attention, date and remarks, which are
printed on the cover.
Also, check the [Signature] box if you
want to print the signature on the cover.
*Message in remarks should be up to
130 characters.
[Header] Check the [Date] or [Project Name] box,
if you want to print the date and project
name on the header (= upper right corner
of each page excluding cover).
[Footer] Check the [Comments] box and input any
comments within 26 characters if you
want to print them on the footer (= lower
right corner of each page excluding
cover).
[Output Room] Select the starting number and ending
number of room to output.
The cover has a remarks section (up to 130 [Print Range] Check the boxes of items to print.
characters) and other pages have comments [Page] Select the print with or without page
section on the footer (up to 26 characters) so that number. You can also determine the page
information such as design number and estimate number to print on the first printed page for the case that
number can be indicated. data is not printed from
the beginning.
[With kcal/h value] Check the box if you want to have
Usually heat load calculation results are heatload tables
outputted horizontally on paper. However, include values in kcal/h
with some printers such as serial printers that unit in addition
use stack form, tables may not be printed in to W values.
proper direction. In this case,
check the [Use Strip Sheet] box , and the [Use Strip Sheet] Check the box if you use stack
output will become vertical. form (= output in vertical).
Heat load tables include values in
the kcal/h unit in addition to W values.
IZE-04002 Page 32
[Heat Load Sum Table]
IZE-04002 Page 33
[System Heat Load Sum Table]
[SystemTable]
IZE-04002 Page 34
[System Heat Load (Cooling)]
IZE-04002 Page 35
[Input Room Data]
IZE-04002 Page 36
[Room Heat Load Table]
IZE-04002 Page 37
[Peak Load Detail Table (Cooling)]
IZE-04002 Page 38
[Peak Load Detail Table (Heating)]
[Graphs]
IZE-04002 Page 39
8. Appendixes
Exothermic Coefficient
Area Outside
volume of Infiltration of Window
per Schedule Lighting air Blind
human volume Temperatu type
Person Intake
body re
difference
Kcal/h m3/h
m2/pers. times/h o’
clock with next W/m2
pers. person
room
Cooling
132
Cooling 0.2 0.4 Clear
Office 5 SH 56
Heating 0.3
8 to 18
Heating
20 20
5 mm
Neutral tint
LH 76
0.4
Cooling
145 Cooling 0.3
0.4 Clear
Store 2.5 SH 59 Heating 10 to 22
Heating
30 20
5 mm
Neutral tint
LH 86 0.45
0.4
Cooling Cooling
145
0.2 0.4 Clear
Hotel 5 SH 59
Heating
4 to 24
Heating
30 20
5 mm
Neutral tint
LH 86
0.3 0.4
Cooling
145 Cooling 0.3
0.4 Clear
Hospital 5 SH 59 Heating 4 to 24
Heating
20 20
5 mm
Neutral tint
LH 86 0.45
0.4
Cooling Cooling
264
0.2 0.4 Clear
Factory 10 SH 84
Heating
8 to 18
Heating
20 20
5 mm
Neutral tint
LH 180
0.3 0.4
Cooling Cooling
132
Condo 0.2 0.3 Clear
5 SH 56 6 to 24 20 20 Neutral tint
Heating Heating 5 mm
minium LH 76
0.3 0.3
Cooling
132 Cooling 0.5
0.9 Clear
House 5 SH 56 Heating 6 to 24
Heating
20 20
5 mm
Neutral tint
LH 76 0.75
0.6
Cooling Cooling
132
0.2 0.4 Clear Neutral tint
Others 5 SH 56
Heating
8 to 18
Heating
20 20
5mm
LH 76
0.3 0.4
IZE-04002 Page 40
[Overall Heat Transfer Coefficient 1]
The program contains specific heat transfer coefficient data for the roof, ceiling, earth floor, pilotis, outer wall,
underground wall and inner wall for each building structure type, as listed below.
* Roman numerals in parentheses ( ) indicate wall types.
(Note)
The heat transfer coefficient values indicated above are initial values set in the software at
the time of shipment.
When values are changed and registered by the "Change design data/heat transfer
coefficient" function, revised values become initial values in the next use.
The heat transfer coefficient of a wall is determined by the material type and thickness, as shown in [Heat transfer
coefficient 2] table.
The heat transfer coefficients of materials are based on the following.
-Heat conductivity coefficient of external surface = 23 (W/m2K)
-Heat conductivity coefficient of internal surface = 9 (W/m2K)
-Thermal resistance of enclosed air layer = 0.15 (m2K/W)
-Thermal resistance of open air layer = 0.07 (m2K/W)
IZE-04002 Page 41
[Overall Heat Transfer Coefficient 2] * Roman numerals in parentheses ( ) indicate wall types.
Normal concrete ALC plate Metallic curtain wall Wooden construction
Material Heat Material Heat Material Heat
and conductivity and conductivity and conductivity Material Heat
thickness coefficient thickness coefficient thickness coefficient and conductivity
thickness coefficient
Synthetic resin ALC Aluminum Mortar
Outer wall 10mm 0.190 100mm 0.17 1.5mm 210.0 15mm 1.5
Normal concrete Mortar Sprayed-on asbestos Plywood
200mm 1.4 20mm 1.5 20mm 0.051 10mm 0.19
Mortar Air layer - - Glass wool
20mm 1.5 Gypsum board 25mm 0.042
Plaster 5mm 0.17 Plaster
3m 0.79 1.33 (II) 1.55 (II) 3mm 0.79
2.72 (III) 1.23 (I)
Plaster Gypsum board 12mm 0.17 Plywood
Inner wall 25mm 0.79 Air layer - - 6mm 0.19
Normal concrete Gypsum board 12mm 0.17 Air layer -
150mm 1.4 Plywood
Mortar 2.30 6mm 0.19
19mm 1.5
Plaster 2.81
6mm 0.79
2.62
Roof (with No ceiling board+ Roofing tile
ceiling board) Air layer - - 22mm 1. 0
Gypsum board 12mm 0.17 Moisture
1.66 (IV) proof paper
Roof (without Mortar 20mm 1.5 10mm 0.21
ceiling board) Lightweight concrete 65mm 0.78 Plywood
Asphalt 10mm 0.11 9mm 0.19
Normal concrete 150mm 1.4 Glass wool
Mortar 15mm 1.5 25mm 0.042
Plaster 3mm 0.79 Air layer -
2.16 (IV) Plywood
6mm 0.19
1.03 (II)
Ceiling (with No ceiling board+ Flooring
ceiling board) Air layer - - 13mm 0.198
Gypsum board 12mm 0.17 Sub-slab board
1.95 18mm 0.14
Ceiling Synthetic resin 5mm 0.190 Air layer -
(without ceiling Mortar 5mm 1.5 Hardtex
Normal concrete 150mm 1.4 12mm 0.133
board)
Mortar 15mm 1.5
Plaster 3mm 0.79 1.73
2.69
Mezz floor Synthetic resin 5mm 0.19 Flooring
(with air layer) Mortar 5mm 1.5 13mm 0.198
Normal concrete 150mm 1.4 Sub-slab board
Air layer - - 18mm 0.14
Gypsum board 9mm 0.17 Air layer -
Asbestos sound-absorbing board 12mm 0.064 Hardtex
1.49 12mm 0.133
Mezz floor Synthetic resin 5mm 0.19
(without air Mortar 5mm 1.5 1.73
Normal concrete 150mm 1.4
layer)
Mortar 15mm 1.5
Plaster 3mm 0.79
2.69
IZE-04002 Page 42
Synthetic resin 5mm 0.19
Pilotis Mortar 5mm 1.5
Normal concrete 150mm 1.4
Mortar 15mm 1.5
Plaster 3mm 0.79
3.29
Mortar 20mm 1.5
Earth floor Normal concrete 150mm 1.4
Rubble 150mm 1.4
Concrete sub-slab 150mm 1.4
Soil 1000mm 1.5
0.90
Underground 1.56
wall (depth: (Value per unit ambient length)
less than 2.4 m)
Underground 0.45
wall (depth: 2.4
m or more)
Underground 0.28
earth floor
IZE-04002 Page 43
Wall
Without heat insulation Without heat insulation Normal concrete Aerated concrete
type
Normal concrete Aerated concrete plate
I d=0 to 5(*) to30 d=0 to30
Single-layer wall Single-layer wall
II d=30 to 100(*) to140 d=30 to 130
II d= 0 to 100 d= 0 to 90 d= 0 to 80
Outside Inside (0 to 20) (0 to 20)
III d=100 to 200 d=90 to 190 d=80 to 180
(20 to 100) (20 to 80)
(Outside) (Inside) IV d=200or more d=190or more d=180or more
(100or more) (80or more)
Normal concrete d (mm)
Styrene foam board l (mm)
Air layer: semi-enclosed,
gypsum 9 mm,
rock wool sound-absorbing board 12 mm
With heat With heat Left (steel board) Left (aluminum board)
insulation insulation I d=0 to 30 d=0 to 20
Metallic Metallic
board board II d=30 to 60 d=20 to 50
Multi-layer wall Multi-layer wall
III d=60 to 90 d=50 to 80
Steel board 1.5 mm Aluminum board 3.0 mm
Sprayed-on rock wool Air layer: Semi-helmetic
IV d=90 or more d=80 or more
l (mm) Sprayed-on rock wool
l (mm)
Gypsum board 12 mm
For dimensions with an asterisk (*), obtained effective temperature difference values are used as the representative
values of those materials.
HKGSG includes wall type S. For this wall type, no effective temperature difference is set.
This wall type is used for materials that have no heat storing capacity, such as slate roofs.
IZE-04002 Page 44
[Shading Factors and Heat Transfer Coefficients of Different Glass Types]
Heat absorbing glass 3 mm + Clear glass 3 mm 0.81 0.48 0.56 3.50 3.05
Heat absorbing glass 5 mm + Clear glass 5 mm 0.72 0.45 0.51 3.43 2.99
Heat absorbing glass 6 mm + Clear glass 6 mm 0.69 0.43 0.49 3.40 2.97
Heat absorbing glass 8 mm + Clear glass 8 mm 0.62 0.39 0.44 3.34 2.92
In HKGSG, when "Others" is selected for the window glass type, the shading factor and heat transfer
coefficient can be set to any value.
IZE-04002 Page 45
Heat Load Calculation Software
DACCS-HKGSG
Operation Manual
Third Edition
IZE-04002 Page 46