THREE PHASE TRANSFORMER Work Order No.:
TEST REPORT
Sales Order No.:
TRANSFORMER DATA
Capacity: :
Standard :
H.V. Rating :
L.V. Rating :
Impedance % :
Manufacturer :
Year of Manufacture :
Serial No. :
Vector Group
Type of Oil
ACCEPTANCE CRITERIA The tolerance of the voltage ratio should be within 0.5% of the specified nameplate voltage for all windings and winding taps.
The resistances between phases should be within 2% of each other. Agreement to within 5% for any of the above comparison is usually
ACCEPTANCE CRITERIA
considered satisfactory.
Primary - Ground
Primary - Secondary
Secondary - Ground
Remarks
ACCEPTANCE CRITERIA Insulation Resistance >1 Mega-Ohm/kV + 1Mega-Ohm for safe energization of electrical equipment.
REFERENCE Electrical Power Equipment Maintenance and testing, 2nd Edition by Paul Gill
TEST INSTRUMENT DATA
Test Instrument Type Brand Model No. Serial Number
Turns Ratio Tester
Winding Resistance Tester
Insulation Resistance Tester
Recommendation:
FERDINAND V. ABSALON
DPSI Test Engineer Client's Representative Operation's Manager
P.O. No.:
THREE PHASE TRANSFORMER Work Order No.:
TEST REPORT
Sales Order No.:
L.V. SIDE Current Capacitance As Found Oil Temp. Correction Adjusted Power
Test Voltage (kV) Watts (mW)
(mA) (nF) Power Factor (°C) Factor Factor (20°C)
Test Mode
UST (CLH)
GSTg (CL)
GST (CL + CLH)
REMARKS
Insulating Liquid kV Rating Nominal / new Power Serviceability Aged Power Factor
ACCEPTANCE CRITERIA Factor Limit Limit
(All PF's are corrected to 20°C Mineral Oil < 230 kV 0.5% 1.0%
except for Natural Ester) Mineral Oil > / = 230 kV 0.4% 1.0%
Natural Ester All 1.0% 1.0%
REFERENCE IEEE Std C57.152-2013 Table 18 - Nominal and serviceabiity service-aged limit: power transformer insulation power factor.
PHYSICAL QUANTITIES
BEFORE REPAIR AFTER REPAIR
Tap Position Tap Position
Oil Temperature (W/R) Oil Temperature (W/R)
Oil Quantity Level Oil Quantity Level
Nitrogen Pressure Level Nitrogen Pressure Level
Dehydrating Breather Color Dehydrating Breather Color
REMARKS
TEST INSTRUMENT DATA
Test Instrument Type Brand Model No. Serial Number
Dielectric Breakdown Voltage Tester
Insulation Power Factor Tester
Exciting Current Tester
Recommendation:
FERDINAND V. ABSALON
DPSI Test Engineer Client's Representative DPSI Operation's Manager