Operation
Maintenance
CG-SVX06F-GB
Original instructions
Contents
General information 3
Model Number Description 5
General data 7
Installation 10
Location Requirements 10
Evaporator piping 11
Minimal installation water content 13
Parameters which influence the water temperature stability 13
Minimum water volume for a comfort application 13
Water connections 14
Refrigerant line connections 15
Winter freeze protection 20
Electrical connections 21
Interconnection between CCUN and Remote Condenser 25
Preparation for start-up 27
General Start-up 28
Start-up 28
Operation 37
Installation checklist 37
Control and unit operation 38
Weekly start up 38
Weekend shutdown 38
Seasonal shutdown 38
Seasonal start-up 39
Maintenance 40
Maintenance Instructions 40
Troubleshooting guide 42
CG-SVX06B-GB 3
General information
Warranty Training
Warranty is based on the general To assist you in obtaining the best
terms and conditions of the use of it and maintaining it in perfect
manufacturer. The warranty is operating condition over a long
void if the equipment is repaired period of time, the manufacturer
or modified without the written has at your disposal a refrigeration
approval of the manufacturer, if the and air conditioning service school.
operating limits are exceeded or if The principal aim of this is to give
the control system or the electrical operators and technicians a better
wiring is modified. Damage due knowledge of the equipment they
to misuse, lack of maintenance are using, or that is under their
or failure to comply with the charge. Emphasis is particularly
manufacturer’s instructions or given to the importance of periodic
recommendations is not covered by checks on the unit operating
the warranty obligation. If the user parameters as well as on preventive
does not conform to the rules of this maintenance, which reduces the
manual, it may entail cancellation cost of owning the unit by avoiding
of warranty and liabilities by the serious and costly breakdown.
manufacturer.
Maintenance contract
It is strongly recommended that
you sign a maintenance contract
with your local Service Agency.
This contract provides regular
maintenance of your installation
by a specialist in our equipment.
Regular maintenance ensures
that any malfunction is detected
and corrected in good time and
minimizes the possibility that serious
damage will occur. Finally, regular
maintenance ensures the maximum
operating life of your equipment.
We would remind you that failure
to respect these installation and
maintenance instructions may result
in immediate cancellation of the
warranty.
4 CG-SVX06B-GB
Model Number Description
CG-SVX06B-GB 5
Model Number Description
Digit 45 – 46 – 47 – 48 – Factory
assigned
6 CG-SVX06B-GB
General Data
CG-SVX06F-GB 7
General Data
Unit size 205 206 207 208 209 210 211 212 213 214 215
Evaporator
Number 1 1 1 1 1 1 1 1 1 1 1
Brazed Brazed Brazed Brazed Brazed Brazed Brazed Brazed Brazed Brazed Brazed
Type
plate plate plate plate plate plate plate plate plate plate plate
DP400- DP400- DP400- DP400- DP400- DP400- DP400- ACH502DQ- ACH502DQ- ACH502DQ- ACH502DQ-
Standard Efficiency Model
74 90 114 162 186 186 206 138 150 162 174
Water volume (total) (L) 15.6 18.9 24.0 34.1 39.2 39.2 43.4 35.9 39.0 42.1 45.2
DP400- DP400- DP400-
High Efficiency Model - - - - - - - -
154 154 162
Water volume (total) (L) 32.4 32.4 34.1 - - - - - - - -
Antifreeze Heater (W) no no no no no no no no no no no
Condenser (CGWN)
Number 1 1 1 1 1 1 1 2 2 2 2
Brazed Brazed Brazed Brazed Brazed Brazed Brazed Brazed Brazed Brazed Brazed
Type
plate plate plate plate plate plate plate plate plate plate plate
DP400- DP400- DP400- DP400- DP400- DP400- DP400- B400T- B400T- B400T- B400T-
Standard Efficiency Model
90 114 134 186 206 206 222 114 114 130 130
Water volume (total) (L) 19 24 28 39 43 43 47 23 23 26 26
DP400- DP400- DP400-
High Efficiency Model - - - - - - - -
162 162 186
Water volume (total) (L) 34.1 34.1 39.2 - - - - - - - -
Antifreeze Heater (W) no no no no no no no no no no no
Condenserless Unit (CCUN)
Discharge line diameter circuit 1 & 2 1”3/8 1”3/8 1”3/8 1”5/8 1”5/8 1”5/8 1”5/8 1”5/8 1”5/8 1”5/8 1”5/8
Liquid line diameter circuit 1 & 2 7/8 7/8 7/8 7/8 7/8 1”1/8 1”1/8 1”3/8 1”3/8 1”3/8 1”3/8
Hydraulic Module / Evaporator Side (Option high head)
Pump Type (Single) LRL LRL LRN LRN LRN LRN LRN SIL SIL SIL SIL
205 - 205 - 206 - 206 - 206 - 206 - 206 - 208 - 208 - 208 - 208 -
Model
15 / 4 15 / 4 13 / 5.5 13 / 5.5 13 / 5.5 14 / 7.5 14 / 7.5 16 / 11 16 / 11 16 / 11 16 / 11
Pump Type (Dual) JRL JRL JRN JRN JRN JRN JRN DIL DIL DIL DIL
205 - 205 - 206 - 206 - 206 - 206 - 206 - 208 - 208 - 208 - 208 -
Model
15 / 4 15 / 4 13 / 5.5 13 / 5.5 13 / 5.5 14 / 7.5 14 / 7.5 16 / 11 16 / 11 16 / 11 16 / 11
Number of Pump sets 1 1 1 1 1 1 1 1 1 1 1
Motor (6) (kW) 4.0 4.0 5.5 5.5 5.5 7.5 7.5 11.0 11.0 11.0 11.0
Rated Amps (6) (A) 7.5 7.5 10.5 10.5 10.5 14.3 14.3 20.0 20.0 20.0 20.0
Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900
Water strainer Ø 3” 3” 4” 4” 4” 4” 4” 4” 4” 4” 4”
Expansion tank volume (L) 25 25 25 25 25 25 25 35 35 35 35
User volume expansion capacity (6) (L) 3600 3600 3600 3600 3600 3600 3600 5100 5100 5100 5100
Max. water-side operating pressure,
without hydraulic module (kPa) 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000 1000
with hydraulic module (kPa) 400 400 400 400 400 400 400 400 400 400 400
Antifreeze heater (W) no no no no no no no no no no no
Piping Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel
Hydraulic Module / Evaporator Side (Option low head)
Pump Type (Single) LRL LRL SIL SIL SIL LRN LRN LRN LRN LRN LRN
205 - 205 - 206 - 206 - 206 - 206 - 206 - 206 - 206 - 206 - 206 -
Model
13 / 2.2 13 / 2.2 12 / 4.0 12 / 4.0 12 / 4.0 13 / 5.5 13 / 5.5 13 / 5.5 13 / 5.5 14 / 7.5 14 / 7.5
Pump Type (Dual) JRL JRL DIL DIL DIL JRN JRN JRN JRN JRN JRN
205 - 205 - 206 - 206 - 206 - 206 - 206 - 206 - 206 - 206 - 206 -
Model
13 / 2.2 13 / 2.2 12 / 4.0 12 / 4.0 12 / 4.0 13 / 5.5 13 / 5.5 13 / 5.5 13 / 5.5 14 / 7.5 14 / 7.5
Number of Pump sets 1 1 1 1 1 1 1 1 1 1 1
Motor (6) (kW) 2.2 2.2 4.0 4.0 4.0 5.5 5.5 4.0 4.0 5.5 5.5
Rated Amps (6) (A) 4.9 4.9 7.8 7.8 7.8 10.5 10.5 7.8 7.8 10.3 10.3
Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900
Hydraulic Module / Conderser Side (Option high head)
Pump Type SHC SHC SHC SHC SHC SHC SHC JRN JRN JRN JRN
35 - 35 - 50 - 50 - 50 - 50 - 50 - 206 - 206 - 206 - 206 -
Model high head
135 / 3 135 / 3 135 / 4 135 / 4 135 / 4 135 / 4 135 / 4 14 / 7.5 14 / 7.5 14 / 7.5 14 / 7.5
2 (in 2 (in 3 (in 4 (in 5 (in 6 (in 7 (in 2 (in 2 (in 2 (in 2 (in
Number of Pump sets
parallel) parallel) parallel) parallel) parallel) parallel) parallel) parallel) parallel) parallel) parallel)
Motor (6) (kW) 3.0 3.0 4.0 4.0 4.0 4.0 4.0 7.5 (x2) 7.5 (x2) 7.5 (x2) 7.5 (x2)
Rated Amps (6) (A) 6.2 6.2 7.4 7.4 7.4 7.4 7.4 13.8 13.8 13.8 13.8
Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900
Water strainer Ø 4” 4” 4” 4” 4” 4” 4” 4” 4” 4” 4”
Expansion tank volume (L) No No No No No No No No No No No
Max. water-side operating pressure,
without hydraulic module (kPa) 1000 1000 1001 1002 1003 1004 1005 1000 1000 1000 1000
with hydraulic module
(kPa) 400/640 400/640 400/641 400/642 400/643 400/644 400/645 1000 1000 1000 1000
suction/discharge
Antifreeze heater (W) no no no no no no no no no no no
Piping Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel Steel
8 CG-SVX06F-GB
General Data
Unit size 205 206 207 208 209 210 211 212 213 214 215
Hydraulic Module / Conderser Side (Option low head)
Pump Type SHC SHC SHC SHC SHC SHC SHC DIL DIL JRN JRN
20 20 35 - 35 - 35 - 35 - 35 - 206 - 206 - 206 - 206 -
Model high head
-134 / 2.2 -134 / 2.2 135 / 3 135 / 3 135 / 3 135 / 3 135 / 3 12 / 4.0 12 / 4.0 13 / 5.5 13 / 5.5
2 (in 2 (in 3 (in 4 (in 5 (in 6 (in 7 (in 8 (in 9 (in 10 (in 11 (in
Number of Pump sets
parallel) parallel) parallel) parallel) parallel) parallel) parallel) parallel) parallel) parallel) parallel)
Motor (6) (kW) 2.2 2.2 3.0 3.0 3.0 3.0 3.0 4.0 4.0 5.5 5.5
Rated Amps (6) (A) 5.0 5.0 6.2 6.2 6.2 6.2 6.2 7.8 7.8 10.3 10.3
Motor RPM (rpm) 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900 2900
Unit water connection
(Inch/
Chilled water 3” (80) 3” (80) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100)
mm)
Type Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic
(Inch/
Hot water High Head 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 5” (125) 5” (125) 5” (125) 5” (125)
mm)
Type Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic
(Inch/
Hot water Low Head 3” (80) 3” (80) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 5” (125) 5” (125) 5” (125) 5” (125)
mm)
Type Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic
Unit water connection without pumps
(Inch/
Chilled water 3” (80) 3” (80) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100)
mm)
Type Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic
(Inch/
Hot water 3” (80) 3” (80) 4” (100) 4” (100) 4” (100) 4” (100) 4” (100) 5” (125) 5” (125) 5” (125) 5” (125)
mm)
Type Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic Victaulic
Dimensions
Height (mm) 1842 1842 1842 1842 1842 1842 1842 1950 1950 1950 1950
Length (without pumps) (mm) 2545 2545 2545 2545 2545 2545 2545 2808 2808 2808 2808
Length (with pumps) (mm) 2545 2545 2545 2545 2545 2545 2545 3498 3498 3498 3498
Width (mm) 880 880 880 880 880 880 880 878 878 878 878
Standard Efficiency Operating Weight (CGWN/CCUN)
1360 / 1300 / 1420 / 1500 / 1650 / 1710 / 1790 / 2232 / 2442 / 2525 / 2640 /
Base Unit (without pumps) (kg)
1260 1170 1270 1280 1420 1480 1550 1879 2070 2120 2180
1360 / 1300 / 1420 / 1500 / 1650 / 1710 / 1790 / 2128 / 2337 / 2420 / 2500 /
Base Unit (with pumps) (kg)
1260 1170 1270 1280 1420 1480 1550 1880 2071 2122 2182
1450 / 1390 / 1590 / 1670 / 1820 / 1880 / 1960 / 2618 / 2827 / 2910 / 2990 /
Evap Hyd Kit (kg)
1350 1260 1440 1450 1590 1650 1720 2370 2561 2612 2672
Evap + Cds Hyd Kit (kg) 1520 / NA 1460 / NA 1690 / NA 1770 / NA 1920 / NA 1980 / NA 2060 / NA 2992 / NA 3201 / NA 3284 / NA 3364 / NA
Shipping Weight (CGWN/CCUN)
1290 / 1220 / 1320 / 1370 / 1510 / 1570 / 1650 / 2109 / 2315 / 2387 / 2492 /
Base Unit (without pumps) (kg)
1210 1120 1200 1190 1320 1380 1450 1832 2023 2070 2130
1380 / 1310 / 1490 / 1540 / 1680 / 1740 / 1820 / 2480 / 2685 / 2758 / 2840 /
Evap Hyd Kit (kg)
1300 1210 1370 1360 1490 1550 1620 2274 2465 2512 2568
Evap + Cds Hyd Kit (kg) 1450 / NA 1380 / NA 1590 / NA 1640 / NA 1780 / NA 1840 / NA 1920 / NA 2797 / NA 3002 / NA 3075 / NA 3157 / NA
High Efficiency Operating Weight (CGWN/CCUN)
Base Unit (without pumps) (kg) 1460/13301450/12401470/1250 - - - - - - - -
Evap Hyd Kit (kg) 1550/14201540/13301640/1420 - - - - - - - -
Evap + Cds Hyd Kit (kg) 1620/NA 1610/NA 1740/NA - - - - - - - -
Shipping Weight (CGWN/CCUN)
Base Unit (without pumps) (kg) 1360/12701350/11701340/1160 - - - - - - - -
Evap Hyd Kit (kg) 1450/13601440/12601510/1330 - - - - - - - -
Evap + Cds Hyd Kit (kg) 1520/NA 1510/NA 1610/NA - - - - - - - -
Refrigerant Charge (4) (5)
CGWN Standard Efficiency Circuit 1 & 2 (kg) 10 11 13 17 18 18 19 22 23 24 25
CGWN High Efficiency Circuit 1 & 2 (kg) 15 15 17 - - - - - - - -
CCUN Nitrogen Charge
Oil Charge per circuit
Circuit 1 & 2 (l) 13.4 13.4 13.4 13.4 13.4 13.9 14.4 21.2 21.7 22.2 22.7
(1) Indicative performance at Evaporator water temperature: 12°C / 7°C - Condenser 30°C/35°C or 40°C/45°C (heating) - for detailed performances consult Order Write Up.
(2) Under 400V/3/50Hz.
(3) Max Rated Condition without Pump Package.
(4) Electrical & system data are indicative and subject to change without notice. Please refer to unit nameplate data.
(5) per circuit
(6) Dual Pump Option
CG-SVX06F-GB 9
Installation - Mechanical
10 CG-SVX06F-GB
Installation
CG-SVX06F-GB 11
Installation
Figure 1 - Connection of units with hydraulic module - Evaporator and condenser sides
5
4
2
7
3 6
5
4
8
12 CG-SVX06F-GB
Installation
Notes
(1) Minimum water loop volume in order to obtain maximum +/- 1°C chilled water temperature fluctuation vs. Chilled
water set-point
(2) Minimum water loop volume in order to obtain maximum +/- 1.5°C chilled water temperature fluctuation vs.
Chilled water set-point
(3) Minimum water loop volume in order to obtain maximum +/- 2°C chilled water temperature fluctuation vs. Chilled
water set-point
CG-SVX06F-GB 13
Installation
14 CG-SVX06F-GB
Installation
Figure 3 - Installation configuration - CCUN and remote condenser at the same level
50 m
1: Discharge line
2: Liquid line
CG-SVX06F-GB 15
Installation
16 CG-SVX06F-GB
Installation
Table 5 - Recommended liquid line diameters for vertical or horizontal risers (Circuit 1)
Table 6 - Recommended liquid line diameters for vertical or horizontal risers (Circuit 2)
CG-SVX06F-GB 17
Installation
18 CG-SVX06F-GB
Installation
High pressure The party in charge of the supply of Pressure relief valve - CCUN
The remote condenser must have a the condenser and of its refrigerant Above the maximum system
service pressure equal to or higher piping is responsible of implementing refrigerant charge, it is recommended
than the high service pressure. all the required protections to to install a pressure relief valve.
comply with the PED requirements See figures below for installation.
Note: CCUN is only one component for the design pressure of the
of a complete installation. It includes Depending upon the liquid
condenser installed. line diameter selected in the
its own high pressure protection set
at 44.5 bar for R410A units. Please refer to the document PROD- “Recommended liquid line diameters”
SVX01_-xx delivered with this table, find the predicted maximum
chiller to check all the mandatory liquid line length of installation
conformity requirements of the without pressure relief valve installed.
Pressure Equipment and Machinery The recommended pressure relief
directives for this installation. valve setting is 29 bar and shall be
installed on the low pressure side of
the refrigerant circuit.
Table 7 - Recommended liquid line diameters with pressure relief valve - CCUN
Figure 5 - Installing pressure relief valve (205-211) Figure 6 - Installing pressure relief valve (212-215)
2 1
2
1 = Connection for pressure relief valve circuit 1 1 = Connection for pressure relief valve circuit 1
2 = Connection for pressure relief valve circuit 2 2 = Connection for pressure relief valve circuit 2
CG-SVX06F-GB 19
Installation
-1 0
Brine temperature (°C)
1
-2 0
2
-3 0
-4 0
-5 0
0 10 20 30 40 50 60
% Ethylene glycol
1. Liquid
2. Freezing without burst effect
3. Freezing with burst effect
20 CG-SVX06F-GB
Installation
Figure 8 - CGWN and CCUN main power supply connection (1) (205-211)
CG-SVX06F-GB 21
Installation
Figure 9 - CGWN and CCUN main power supply connection (1) (212-215)
22 CG-SVX06F-GB
Installation
When ordered, the outdoor air operation of the chiller. The wiring of
temperature sensor and associated the sensor has to be performed with
electronics are factory-mounted a 2 wires cable of 0.75 to 1.5 mm²
and wired in the control panel of type H05WWF or equivalent. The
the chiller. This sensor has to be maximum length of this cable is 305
installed outdoors to allow for proper m. (see Figure 10). The IPC bus is
factory-wired.
Self-thread screw
L1
L2
L3
1Q10
CG-SVX06F-GB 23
Installation
L1 L1
L2 L2
1Q10 L3 L3
Note: Check phase rotation prior to start compressor and make sure phase order is
correct. Failure to do so may result on compressor damage.
24 CG-SVX06F-GB
Installation
Table 10 - Fan staging - Example : 4 fans per circuit with first fan 2-speed
CG-SVX06F-GB 25
Installation
70 80
+4/+67
Compressor saturated condensing
60 70
-12/+50
-12/+45 60
temperature
50
50
40
temperature
40
30
30
+18/+30
+18/+23
20 -12/+25 20
+14/+25
-12/+20 10 +14/+20 10
0 0
Note: CGWN 205 to 211 have a maximum condenser leaving water temperature of 60°C.
26 CG-SVX06F-GB
Installation
CG-SVX06F-GB 27
General Start-up
28 CG-SVX06F-GB
General Start-up
CG-SVX06F-GB 29
General Start-up
30 CG-SVX06F-GB
General Start-up
1000
A=205
B=206
A C E G C=207
100
D=208-27HE
E=209-210
10 F=211
B H D F G=212-213-214-
215
H=205HE-206HE
1
1.00 10.00 100.00
1000
A = CGWN 205
B = CGWN 206
C=CGWN 207
A C E G I D=CGWN 208
100
E=CGWN 209
F=CGWN 210
G=CGWN 211
10
B D F H=CGWN 212-213
L I=CGWN 214-215
M H
L=CGWN 205HE-
206HE
M=CGWN 207HE
1
1.00 10.00 100.00
CG-SVX06F-GB 31
General Start-up
Figure 18 - Chiller available pressure - Evaporator side - Standard and High Efficiency
units - Low head pressure - Single pump
K I=213
J=214
100
K=215
L=205 HE
D M=206 HE
M N=207 HE
50 B I
C E
G
0
0.00 5.00 10.00 15.00 20.00 25.00 30.00
Figure 19 - Chiller available pressure - Evaporator side - Standard and High Efficiency
units - Low head pressure - Dual pump
I=213
J=214
100 D K=215
L=205 HE
M=206 HE
I
M N=207 HE
50
C N G
B
0
0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00
32 CG-SVX06F-GB
General Start-up
Figure 20 - Chiller available pressure - evaporator side - Standard and High Efficiency
units - High head pressure - Single pump
I=213
150 I J=214
J K=215
L=205 HE
100
N M=206 HE
M K N=207 HE
50 B
B D E
G
0
0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00
Figure 21 - Chiller available pressure - evaporator side - Standard and High Efficiency
units - High head pressure - Dual pump
I=213
150
J=214
K=215
I
L=205 HE
100
N J M=206 HE
K N=207 HE
50
M
D
B C E
G
0
0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00
CG-SVX06F-GB 33
General Start-up
Figure 22 - Chiller available pressure - condenser side - Standard and High Efficiency
units - Low head pressure
I H=212
100
I=213
J=214
50 E K=215
M
C F L=205 HE
0
B
M=206 HE
0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00
N=207 HE
Water flow (L/s)
Figure 23 - Chiller available pressure - condenser side - Standard and High Efficiency
units - High head pressure
250
A=205
L N B=206
A F
200
G C=207
D=208
E=209
150 K
F=210
kPa
I
G=211
100 H=212
I=213
J=214
50
D K=215
B
M C J L=205 HE
E H
0 M=206 HE
0.00 5.00 10.00 15.00 20.00 25.00 30.00 35.00 40.00
N=207 HE
Water flow (L/s)
34 CG-SVX06F-GB
General Start-up
When ethylene glycol is added in the chilled water circuit the following glycol
concentration has to be taken in account.
Figure 24 - Ethylene Glycol recommended concentration
40
35
30
(%)
(%)
25
Concentration
Concentration
20
15
10
0
-12 -10 -8 -6 -4 -2 0 2 4
LWT (°C)
45
40
35
Concentration (%)(%)
30
Concentration
25
20
15
10
0
-10 -8 -6 -4 -2 0 2 4
LWT (°C)
CG-SVX06F-GB 35
General Start-up
36 CG-SVX06F-GB
Operation
Installation checklist
This list must be checked off by the installer to ensure correct installation before the unit start up.
UNIT POSITION
Check clearance around condenser
Check clearance required for maintenance access
Check type and position of rubbers pads
Check unit is level
ELECTRICAL EQUIPMENT
Check installation and rating of mains power switch/fuses
Check electrical connections complied with specification
Check that electrical connections are in accordance with information on manufacturer’s identification plate
Check direction of rotation using phasemeter
Comments
…………………………………………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………………………………
…………………………………………………………………………………………………………………………………………………
Signature:…………………………………………………………………….Name:…………………………………...…………………
Order N°: ……………………………………………………………………………………………………………………………………
Work site: ……………………………………………………………………………………………………………………………………
CG-SVX06F-GB 37
Operation
38 CG-SVX06F-GB
Operation
Seasonal start-up
• Check water flows and interlocks.
• Check Ethylene glycol
concentration in the chilled
water circuit if glycol presence is
required
• Check operational set points and
performance
• Calibrate controls
• Check operation of all safety
devices
• Inspect contacts and tighten
terminals
• Megger the motor compressor
windings
• Record operating pressures,
temperatures, amperages and
voltage
• Carry out leak test
• Check configuration of unit control
module
• Change the oil as required based
upon results of the oil analysis
made during seasonal shutdown.
CG-SVX06F-GB 39
Maintenance
40 CG-SVX06F-GB
Maintenance
CG-SVX06F-GB 41
Maintenance
B) Compressor stops
High pressure switch tripped.
Over current thermal relay tripped. Discharge pressure too high. See instructions for “discharge pressure high”.
a) Voltage too low. a) Contact Power Supply Utility.
Motor temperature thermostat tripped. b) Cooling demand too high, or condensing temperature b) See instruction “discharge pressure too high”.
too high.
Anti-freeze security tripped. Not enough cooling fluid. Repair leak. Add refrigerant.
Water flow to evaporator too low. Check water flow rate, and flow switch contact in water
42 CG-SVX06F-GB
Maintenance
F) Compressor noisy
Compressor knocks. Components broken in compressor. Change compressor.
a) Check superheat setting and fixing of expansion valve
a) Uneven liquid flow.
Suction duct abnormally cold. bulb.
b) Expansion valve locked in open position.
b) Repair or replace.
G) Insufficient cooling capacity
Thermostatic expansion valve “whistles”. Not enough refrigerant. Check refrigerant circuit tightness and add refrigerant.
Excess pressure drops through filter drier Drier filter clogged. Replace.
Check adjustment of superheat and adjust thermostatic
Excessive superheat. Superheat not properly adjusted.
expansion valve.
Insufficient water flow. Chilled water pipes obstructed. Clean pipes and strainer.
H) Discharge pressure too high
Presence of uncondensable liquids in system, or excess Purge uncondensable fluids and drain off excess
Condenser abnormally hot.
refrigerant. refrigerant.
Reduce load on system.
Chilled water leaving temperature too high. Overload on cooling system.
Reduce water flow if necessary.
Reduced air flow. Air intake temperature higher than Clean or replace air filters. Clean coil. Check operation
Condenser air output too hot.
specified for unit of fan motors.
I) Suction pressure too high
CG-SVX06F-GB 43
Trane optimizes the performance of homes and buildings around the world. A business of Ingersoll Rand, the leader
in creating and sustaining safe, comfortable and energy efficient environments, Trane offers a broad portfolio
of advanced controls and HVAC systems, comprehensive building services and parts. For more information visit
www.Trane.com
Trane has a policy of continuous product and product data improvement and reserves the right to change design and specifications without notice.